22
845.778.5566 ● Fax: 845.778.7123 ●
www.nicholsonsteamtrap.com
Thermal actuator is filled at its free length with a
liquid having a lower boiling point than water.
On start-up, valve is normally open. When
steam enters trap, thermal actuator fill vaporizes
to a pressure higher than line pressure. This
forces valve into seat orifice to prevent any
further flow. As condensate collects, it takes heat from
thermal actuator, lowering internal pressure. Line
pressure will then compress thermal actuator to open
valve and discharge condensate. Valve opening automatically adjusts to load conditions from minimum on
very light loads to full lift at maximum load.
ACHIEVER “A” SERIES
THERMOSTATIC
STEAM TRAPS
Pressures To 200 PSIG (13.8 barg)
Temperatures to 400°F (204°C)
Temperature Sensitive Actuator — One moving part
stainless steel welded actuator for maximum corrosion,
thermal and hydraulic shock resistance.
Improved Energy Savings — Maximum elimination of air
and non-condensibles–trap closes at saturated steam
temperature.
Compact — Requires minimum space and provides
condensate capacities equal to larger mechanical traps.
Freeze Proof — Type A with horizontal inlet and vertical
outlet. Type AHV when installed vertically (outlet down) or
horizontally on side (cover perpendicular to ground).
Renewable In-line — With factory packaged, precision
matched internal parts kits.
Superior Performance — Fast response to changing
pressure and condensate loads. Maximum air handling
capability.
Guaranteed — Guaranteed against defects in materials
or workmanship for 3 years.
MODELS
●
A33–1/2" right angle trap
●A43–3/4" right angle trap
●A53–1" right angle trap
●AHV33–1/2" straight thru trap
●AHV43–3/4" straight thru trap
●AHV53–1" straight thru trap
*Add (-HC) to end of model number for high capacity.
APPLICA TIONS
●
Unit Heaters
●Sterilizers
●Air Vents
●Autoclaves
●Dry Kilns
●Dryers
●Flash Tanks
●Small Heat Exchangers
●Plating Tanks
●Cookers
●Kettles
●Other Process Equipment
OPTIONS
●
ST - Sterilizer Trim
●SLR - SLR Orifice
●HC - High capacity orifice
Canadian Registration # 0E0591.9
See page 9
Shown in AHV Configuration
OPERA TION