CONTROLMATIK M 4510 C SERIES Instruction Manual

INSTRUCTION MANUAL FOR
Chlorine gas leak detector
with battery back up
series M 4510 C
2007 © Controlmatik ABW d.o.o.
NAV00196
CONTROLMATIK ABW d.o.o. Fajfarjeva 15, 1230 Domž ale, Slovenija, Evr opa Tel.: 01 721 35 52, Fax.: 01 721 93 60 http://www.contolmatik-abw.si, Email: info@controlmatik-abw.si
1
NAV00196
CONTROLMATIK ABW d.o.o. Fajfarjeva 15, 1230 Domž ale, Slovenija, Evr opa Tel.: 01 721 35 52, Fax.: 01 721 93 60 http://www.contolmatik-abw.si, Email: info@controlmatik-abw.si
2
CONTENT
1.0 General description: .................................................................................................... 3
2.0 The Unit ......................................................................................................................... 4
3.0 Controls and Displays ................................................................................................. 6
3.1 Start up ................................................................................................................................... 9
4.0 Set the limits for alarms ............................................................................................ 10
5.0 Test functions ............................................................................................................ 11
6.0 During operation ........................................................................................................ 12
7.0 Reset the alarm relay outputs ................................................................................... 13
8.0 The Sensor ................................................................................................................. 14
9.0 Connection scheme ................................................................................................... 16
10.0 Technical data .......................................................................................................... 18
NAV00196
CONTROLMATIK ABW d.o.o. Fajfarjeva 15, 1230 Domž ale, Slovenija, Evr opa Tel.: 01 721 35 52, Fax.: 01 721 93 60 http://www.contolmatik-abw.si, Email: info@controlmatik-abw.si
3
1.0 General description:
The M 4510 C series Controlmatik ABW leek detector is assembled as unit with display, two adjustable alarms and unit fault alarm, power supply module, battery back up and separate detection cell - probe. The detection cell is mounted in IP 65 housing and features 4- 20 mA output which is connected to the signal evaluation unit. Two adjustable alarms can be set and following units can be activated in case of chlorine gas leak:
- Alarm horn
- Flashing light
- Ventilation system
- Neutralisation system For detection cell see product information for Chlorine Gas measuring sensor M 2103 C.
Typical use of chlorine gas leek detector
NAV00196
CONTROLMATIK ABW d.o.o. Fajfarjeva 15, 1230 Domž ale, Slovenija, Evr opa Tel.: 01 721 35 52, Fax.: 01 721 93 60 http://www.contolmatik-abw.si, Email: info@controlmatik-abw.si
4
2.0 The Unit
The unit consists of:
POWER SUPPLY MODULE SIGNAL EVALUATION MODULE IP 65 HOUSING
The signal gas measuring sensor probe M 2103 C (2) is connected to the signal evaluation unit with display (1). The signal evaluation unit evaluates the signal and displays the value in PPM.
NAV00196
CONTROLMATIK ABW d.o.o. Fajfarjeva 15, 1230 Domž ale, Slovenija, Evr opa Tel.: 01 721 35 52, Fax.: 01 721 93 60 http://www.contolmatik-abw.si, Email: info@controlmatik-abw.si
5
2.1 Principle of the system
¾ The unit amplifies the current input signal from gas measuring sensor M 2103 C
proportional to the gas concentration in the room air.
¾ Chlorine gas leak detection unit M 4510:
Amplifies the current from gas measuring sensor M 2103 Actuate the warning system when the set limit is exceeded Outputs the measured concentration of both sensors as a signal of 4-20 mA
via two current outputs
¾ Display mode:
When unit is switch ON it automatically starts with display mode in this mode you can:
Indicate the actual measured values Indicate error messages
¾ Set mode
Set the parameters for two adjustable set point alarms Check all test functions
¾ Menu mode(Only for certificated Controlmatik ABW service)
Set all parameters which are important for the normal operation of the
device