CONTREX ML-TRIM User Manual

ML–Trim
User Manual
0001-0127 Revision C
i
T echnical Assistance
If you have comments or questions concerning the operation of the ML–Trim, please call us. A member of our Technical Support Staff will be happy to assist you. Ask for Technical Support: (763) 424-7800 or 1-800-342-4411
Copyright © 1998 Contrex
ii
Contrex
®
8900 Zachary Lane North
Maple Grove, Minnesota 55369
DANGER
Improper installation can cause severe injury, death or damage to your system.
Integrate this motion control unit into your system with caution.
Operate this motion control unit only under the conditions prescribed in this manual. Any other use shall be deemed inappropriate.
Comply with the National Electrical Code and all applicable local and national codes.
iii
iv

Table of Contents

Introduction ...................................................................... 1-1
Introducing the ML–Trim................................................................................ 1-3
Examples of ML–Trim Applications............................................................... 1-4
Installation / Setup ......................................................... 2-1
Mounting ........................................................................................................ 2-3
Wiring............................................................................................................ 2-5
Inputs.................................................................................................... 2-7
Outputs............................................................................................... 2-13
Serial Communications ...................................................................... 2-15
Calibration.................................................................................................... 2-17
Motor Drive Set Up............................................................................. 2-18
ML–Trim Calibration........................................................................... 2-19
Operation.......................................................................... 3-1
Keypad Operation.......................................................................................... 3-3
Keypad Lockout ............................................................................................. 3-5
Control Parameters........................................................................................ 3-7
Direct Mode.......................................................................................... 3-8
Master Mode ........................................................................................ 3-9
Follower Mode.................................................................................... 3-13
Inverse Master Mode ......................................................................... 3-22
Inverse Follower Mode....................................................................... 3-24
Acceleration/Deceleration .................................................................. 3-26
Tuning ................................................................................................. 3-27
Alarms ................................................................................................ 3-29
Jog...................................................................................................... 3-31
Logic Control................................................................................................ 3-33
Logic Inputs........................................................................................ 3-34
Logic Output....................................................................................... 3-37
Monitor Parameters ..................................................................................... 3-39
Input Monitoring ................................................................................. 3-40
Output Monitoring............................................................................... 3-42
v
Performance Monitoring..................................................................... 3-43
Status Monitoring ............................................................................... 3-45
Serial Communications................................................................................ 3-49
Using Serial Communications............................................................ 3-50
Communications Software Design..................................................... 3-52
Troubleshooting.............................................................. 4-1
Diagnostics .................................................................................................... 4-3
Troubleshooting ........................................................................................... 4-11
PROM chip Replacement ............................................................................ 4-16
Glossary..............................................................Glossary-1
Glossary.............................................................................................Glossary-3
Appendices ......................................................................A-1
Appendix A: ML–Trim Specifications ............................................................ A-1
Appendix B: Formulas ..................................................................................B-1
Appendix C: Parameter Summary - numeric quick reference......................C-1
Appendix D: Control Parameter Reference..................................................D-1
Appendix E: Monitor Parameter Reference..................................................E-1
Appendix F: ML–Trim Fax Cover Sheet ....................................................... F-1
Appendix G: Wiring Diagram Examples ...................................................... G-1
Appendix H: Revision Log ............................................................................H-1
Warranty ..............................................................Warranty-1
Service Policy ....................................................................................Warranty-3
Warranty.............................................................................................Warranty-4
Index .......................................................................... Index-1
Index ....................................................................................................... Index-3
vi
List of Illustrations
Figure 1-1 ML–Trim Master Mode ............................................................. 1-4
Figure 1-2 ML–Trim Follower Mode ........................................................... 1-5
Figure 2-1 ML–Trim Cutout Dimensions and Mounting Guide .................. 2-2
Figure 2-2 ML–Trim General Wiring Guide ............................................... 2-4
Figure 2-3 I/O Power (Isolated).................................................................. 2-7
Figure 2-4 I/O Power (Non-Isolated) .......................................................... 2-7
Figure 2-5 AC Power.................................................................................. 2-8
Figure 2-6 Lead Frequency ....................................................................... 2-8
Figure 2-7 Feedback Frequency ............................................................... 2-9
Figure 2-8 Run ........................................................................................... 2-9
Figure 2-9 Jog .......................................................................................... 2-10
Figure 2-10 R–Stop .................................................................................... 2-10
Figure 2-11 F–Stop .................................................................................... 2-11
Figure 2-12 Master or Follower .................................................................. 2-11
Figure 2-13 Setpoint Select........................................................................ 2-12
Figure 2-14 Speed Command Out ............................................................. 2-13
Figure 2-15 Drive Enable and Alarms Outputs .......................................... 2-14
Figure 2-16 ML–Trim Multidrop Installation................................................ 2-15
Figure 2-17 ML–Trim Serial Communications Connections .................... 2-16
Figure 3-1 ML–Trim Front Panel ............................................................... 3-4
Figure 3-2 ML–Trim Internal Structure .................................................... 3-43
Figure 4-1 Motor Does Not Stop Flowchart ............................................ 4-12
Figure 4-2 Motor Does Not Run Flowchart ............................................. 4-13
Figure 4-3 Motor Runs at Wrong Speed Flowchart ................................ 4-14
Figure 4-4 Motor Runs Unstable Flowchart ............................................ 4-15
Figure 4-5 PROM Location ...................................................................... 4-17
Figure G-1 ML–Trim Wiring Connections without Relays ........................ G-1
Figure G-2 Relay Start/Stop Wiring Connections .................................... G-2
Figure G-3 Start/Stop for Regen with Armature Contactor ...................... G-3
Figure G-4 Start/Stop for Non-Regen with Armature Contactor .............. G-4
Figure G-5 Two Channel Start/Stop - Lead/Follower Logic ..................... G-5
vii
List of Tables
Table 3-1 Basic Keypad Entry ................................................................. 3-4
Table 3-2 Default Direct Mode Control Parameters ................................. 3-8
Table 3-3 Entering Direct Mode Control Parameters ............................... 3-8
Table 3-4 Default Master Scaling Control Parameters .......................... 3-10
Table 3-5 Entering Master Scaling Control Parameters ........................ 3-10
Table 3-6 Entering Master Setpoint Control Parameters ....................... 3-11
Table 3-7 Master Mode Control Parameters Example .......................... 3-12
Table 3-8 Default Follower Scaling Control Parameters ....................... 3-14
Table 3-9 Entering Follower Scaling Control Parameters ..................... 3-14
Table 3-10 Entering Follower Setpoint Control Parameters .................... 3-15
Table 3-11 Follower Mode Control Parameters Example A .................... 3-18
Table 3-12 Follower Mode Control Parameters Example B .................... 3-21
Table 3-13 Default Inverse Master Control Parameters........................... 3-22
Table 3-14 Entering Inverse Master Control Parameters......................... 3-22
Table 3-15 Inverse Master Mode Control Parameters Example .............. 3-23
Table 3-16 Default Inverse Follower Control Parameters ........................ 3-24
Table 3-17 Entering Inverse Follower Control Parameters ...................... 3-24
Table 3-18 Inverse Follower Mode Control Parameters Example............ 3-25
Table 3-19 Default Master or Follower Accel/Decel Control Parameters 3-26 Table 3-20 Entering Master or Follower Accel/Decel Control Parameters 3-26
Table 3-21 Default Master or Follower Tuning Control Parameters ........ 3-27
Table 3-22 Entering Master or Follower Tuning Control Parameters ...... 3-28
Table 3-23 Default Alarm Control Parameters ......................................... 3-29
Table 3-24 Entering Alarm Control Parameters ....................................... 3-30
Table 3-25 Default Jog Control Parameters ............................................ 3-31
Table 3-26 Entering Jog Control Parameters .......................................... 3-31
Table 3-27 Default Drive Enable Logic Control Parameters ....................3-37
Table 3-28 Entering Drive Enable Logic Control Parameters .................. 3-37
Table 3-29 Parameter Send - Host Transmission.....................................3-53
Table 3-30 Parameter Send - ML–Trim Response .................................. 3-56
Table 3-31 Control Command Send - Host Transmission ....................... 3-58
Table 3-32 Control Command Send - ML–Trim Response ...................... 3-60
Table 3-33 Data Inquiry - Host Transmission ........................................... 3-62
Table 3-34 Data Inquiry - ML–Trim Response ......................................... 3-64
Table 3-35 ASCII to Binary ...................................................................... 3-66
Table 3-36 Binary to Monitor Parameters ................................................ 3-67
viii

Introduction

Introducing the ML–Trim Examples of ML–Trim Applications
1 - 1
1 - 2

INTRODUCING THE ML–TRIM

The ML–Trim is a highly accurate, digital, motor controller. It has advanced embedded software that is capable of solving a great variety of speed control tasks. It operates as either a stand-alone control of a single motor (Master mode) or as a part of a complex multi-drive system (Follower mode).
The ML–Trim is ideal for motor control applications where your present open loop or rudimentary closed loop operations are inaccurate or where there is inadequate load regulation. The ML–Trim adds accurate digital control to virtually any AC, DC, Servo, Flux Vector or Clutch drives. The ML–Trim is also at the forefront in digitally accurate Follower applications. See Figure 1-1 and Figure 1-2 for examples of Master and Follower applications.
The ML–Trim is unique among its competition because the ML–Trim has preprogramed software that integrates with your system with little effort from you. The ML–Trim will also allow you to enter data that is unique to your system's specific needs (e.g., maximum RPMs, setpoints, acceleration/deceleration ramp rates). Using Control Parameters (CPs), this data is entered through either the ML–Trim's integrated keypad or though a host computer via the RS485 Serial Communications port. In addition to the Control Parameters that allow you to customize for your systems specific needs, the ML–Trim's Monitor Parameters (MPs) allow you to monitor your system's performance.
The ML–Trim's multiple scaling formats allow you to enter the setpoints and monitor speed in the Engineering Units (e.g., RPMs, gallons per hour, feet per minute) that are unique to your system. Among the ML–Trim's advanced capabilities is the flexibility to preset up to four setpoint entries.
Integrating the ML–Trim's applied intelligence with your system puts precise speeds and perfect synchronization at your fingertips, quickly, easily and cost effectively.
1 - 3
EXAMPLES OF ML–TRIM
APPLICATIONS
Figure 1-1 is an example of a Master mode of operation for a pump application. The scaling format allows the operator to enter a setpoint in Engineering Units of gallons per minute. The ML–Trim compares the sensor shaft feedback to the scaled setpoint and calculates any speed error. When the ML–Trim finds speed error, the control algorithm adjusts the Speed Command Out to the motor drive and reduces the error to zero.
Speed Command Out
ontrex
C
Motor Drive ML–Trim
Contrex
CODE
SELECT
POINT
TACH
SET
89
7
456
23
1
0
ENTER
CLEAR
.
1 - 4
Motor
Sensor
Pump
Feedback Frequency
Figure 1-1 ML–Trim Master Mode
Figure 1-2 is an example of the Follower mode of operation in a pump application. The scaling format allows the operator to enter the setpoint as a ratio of ingredient B to ingredient A. The ML–Trim compares the setpoint ratio to the Follower sensor shaft feedback and Lead sensor shaft feedback to calculate any speed error. When the ML–Trim finds speed error, the control algorithm adjusts the Speed Command Out to the motor drive and reduces the error to zero.
Lead
Speed
Lead Motor
Command Out
ontrex
C
Motor Drive ML–Trim
Sensor
Pump
Contrex
8 9
7
CODE SELECT
4 5 6
SET POINT
2 3
1
TACH
.
0
ENTER
CLEAR
Feedback Frequency
Ingredient A
Final Product
Follower
Follower Motor
Lead Frequency
Contrex
8 9
7
CODE SELECT
4 5 6
SET POINT
2 3
1
TACH
.
0
ENTER
CLEAR
C
ontrex
Speed Command Out
Motor Drive ML–Trim
Feedback Frequency
Sensor
Pump
Ingredient B
Figure 1-2 ML–Trim Follower Mode
1 - 5
—NOTES—
1 - 6

Installation / Setup

Mounting Wiring
Inputs Outputs Serial Communications
Calibration
Motor Drive Setup ML–Trim Calibration
2 - 1
Contrex
,
,
CUTOUT
(
3.65" .03"
6.00"
(
DOOR PANEL
Contrex
8 9
7
CODE
SELECT
4 5 6
SET
POINT
TACH
1
CLEAR
2 3
0
ENTER
.
)
3.60"
CUTOUT
(
3.65" .03"
3.60"
*
4.00"
*
From the rear of the door panel to the back of the connectors
4.00"
2 - 2
Figure 2-1 ML–Trim Cutout Dimensions and Mounting Guide

MOUNTING

This section contains instructions for mounting the ML–Trim in the door panel of a NEMA Industrial Electrical enclosure. The ML–Trim is packaged in a compact 1/4 DIN Vertical Instrument Enclosure that mounts easily in the door of your Industrial Electrical Enclosure. The Electrical Enclosure must have an IP54 rating or higher to comply with CE installations.
To mount the ML–Trim:
1) The NEMA Industrial Electrical Enclosure that will house the ML–Trim must conform to the following environmental conditions:
Temperature: 0 - 55 degrees C
(Internal NEMA enclosure temperature) Humidity: 0 - 95% RH non-condensing Environment: Pollution degree 2 macro - environment Altitude: To 3300 feet (1000 meters)
NOTE: Allow adequate spacing between the ML–Trim and other equipment to provide for proper heat convection. Placing the ML–Trim too close to adjacent equipment could cause the interior ambient temperature to exceed 55 degrees C. Spacing requirements depend on air flow and enclosure construction.
2) The dimensions for the door panel cutout are 3.65"+ .03" x 3.65 +.03" (see Figure 2-1). Allow two inches of clearance on all sides of the cutout for mounting clamp attachments, wire routing and heat convection.
3) Insert the ML–Trim through the door panel cutout until the gasket and bezel are flush with the door panel (see Figure 2-1).
4) Slide the mounting clamps into the slots that are located on the top and bottom of the ML–Trim. Tighten the mounting screws until the ML–Trim is mounted securely in the NEMA Electrical Enclosure. Do not overtighten.
2 - 3
*
Use 115 VAC with ML-Trim model # 3200-1931
Use 230 VAC with ML-Trim model # 3200-1932
L1
*
Neut or L2
GND/PE
RS485 Serial
Communications
5V_DI
COM
LEAD_FQ
FDBK_FQ
COM
RUN
JOG
COM
R–STOP
F–STOP
COM
MST / FOL
SETPT
COM
V_DO
DRV_EN
ALARM
COM
USE COPPER WIRE ONLY. SELECT WIRE SIZE ACCORDING TO AMPACITY FOR 60/75 C WIRE ONLY. TIGHTEN J3 TERMINALS TO 5 LB-INS.
J1 J4
J3
T / R +
T / R –
COM_AUX
RS485 COMM
AUX
PWR
L1
NEUT
GND
PE
AC
POWER
INC
MAX_SPD
SPD
CMD
DRV_SIG
DRV_COM
AC POWER
115 VAC
0.1 AMPS
50 / 60 HZ
I / O
PWR
FREQ
INPUTS
DIGITAL
INPUTS
J5
DIGITAL
OUTPUTS
5V
COM_AUX
J2
Run
Jog
R-Stop
F-Stop
Master/
Follower
Setpoint
Select
Lead
Frequency
Sensor
Feedback
Frequency
Sensor
+5VDC External
DC Power
Supply
+5V COM
+5V
SIG
COM
+5V
SIG
COM
50V
MAX
+V
COM
R1
R2
External
DC Power
Supply
TD/RD+
TD/RD–
COM
Motor Drive
SIG
COM
1
2
3
1
2
1
2
3
1
2
123456789
101112131415161718
Fuses
1A
250V
2 - 4
Figure 2-2 ML–Trim General Wiring

WIRING

This section contains the input, output and serial communications wiring information for the ML–Trim. Please read this section prior to wiring the ML–Trim to ensure that you make the appropriate wiring decisions.
NOTE: The installation of this motor control must conform to area and local electrical
codes. See National Fire Protection Association, or Use local codes as applicable.
Use a minimum wire gauge of 18 AWG. Use shielded cable to minimize equipment malfunctions from electrical noise. Keep the AC power wiring (J3) physically separated from all other wiring on the
ML–Trim. Failure to do so could result in additional electrical noise and cause the ML–Trim to malfunction.
A hand operated supply disconnect device must be installed in the final applica­tion. The primary disconnect device must meet EN requirements.
Inductive coils on relay, contactors, solenoids that are on the same AC power line or housed in the same enclosure should be suppressed with an RC net­work across the coil. For the best results, use resistance (r) values of 50 ohms and capacitance (c) values of 0.1 microfarads.
The National Electrical Code
The Canadian Electrical Code
(NEC,) Article 430 published by the
(CEC).
Install an AC line filter or isolation transformer to reduce excessive EMI noise, such as line notches or spikes, on the AC power line.
DANGER
Hazardous voltages. Can cause severe injury, death or damage to the equipment. The ML–Trim should only be installed by a qualified electrician.
2 - 5
–NOTES—
2 - 6
INPUTS
NOTE: The installation of this motor control must conform to area and local electrical
codes. See National Fire Protection Association, or Use local codes as applicable.
I/O Power (J5 pins 1, 2)
The National Electrical Code
The Canadian Electrical Code
(NEC,) Article 430 published by the
(CEC).
For isolated operations, the Frequency Inputs (J5 pins 3, 4, 5), the Digital Inputs (J5 pins 6-14 ) and the Digital Outputs (J5 pins 15-18) require an external source of +5VDC power.
CAUTION: The ML-Trim is shipped from the factory non­isolated with J4 and J5 jumpers. You must remove the J4 and J5 jumpers before you connect the External Power supply or you can damage the equipment. Do not exceed +5VDC on the I/O Power Input.
Use the Auxiliary Power Output (J4 pins 1, 2) to supply power to non-isolated operations. The ML-Trim is shipped from the factory with the wiring defaulted to the non­isolated operation.
+5VDC MAXIMUM
1
2
J5
* Do not connect the External Power Supply
Common to Earth Ground.
+5V
COM
+5VDC External Power Supply
Figure 2-3 I/O Power / Isolated
1
2
J4
+5V
COM_AUX
*
1
2
J5
Figure 2-4 I/O Power / Non-Isolated
2 - 7
AC Power (J3 pins 1, 2, 3)
The ML–Trim model #3200-1931 operates on 115 VAC + 15%, 0.1 Amp., 50/60 Hz. The ML–Trim model #3200-1932 operates on 230 VAC + 15%, 0.1 Amp., 50/60 Hz.
* Fuse L1 for 115VAC applica­tions. Fuse L1 and L2 for 230VAC applications. Use 1 Amp 250V normal blow fuses.
L1
Neutral or L2
GND/PE
*
*
Figure 2-5 Input Power
1
2
3
J3
Lead Frequency (J5 pins 3, 5)
The Lead Frequency is a pulse train input that the ML–Trim uses to determine the speed of the lead motor. For signal level specifications, refer to
ML–Trim Specifications,
2 - 8
References: Appendix A
page A-1
3
,
5
J5
Signal
Common
Figure 2-6 Lead Frequency
Feedback Frequency
(J5 pins 4, 5)
The Feedback Frequency is a pulse train input that the ML–Trim uses to determine the speed of the follower motor. For signal level specifications refer to
ML–Trim Specifications,
References: Appendix A
page A-1.
If the Feedback Frequency is lost, the ML-Trim will command a 100% Speed Out and the motor will run at 100% capacity. This can cause severe injury, death or equipment damage.
,
Figure 2-7 Feedback Frequency
DANGER
4
5
J5
Signal
Common
Run (J5 pins 6, 8)
When the Run input (J5 pin 6) is momentarily shorted to common, the ML–Trim enters Run. As a momentary input, Run is internally latched and does not need to be maintained by an operator device.
NOTE: Close the R–Stop and F–Stop
inputs prior to entering Run. If you are only using one of the Stop inputs, wire short the other Stop input to common or the ML–Trim will not enter “Run”.
RUN
6
8
J5
Figure 2-8 Run
2 - 9
Jog (J5 pins 7, 8)
Jog is a maintained input. When Jog is closed, the ML–Trim sends a Speed Command Out signal to the drive at the selected jog speed. As a maintained input, Jog is only active when the operator device is closed.
JOG
7
8
NOTE: Close the R–Stop and
F–Stop inputs and open the Run input, prior to entering Jog. If you are only using one of the Stop inputs, wire short the other Stop input to common or the ML–Trim will not enter Jog.
R–Stop (J5 pins 9, 11)
R–Stop is a momentary input. When it is opened, the ML–Trim ramps to a zero Speed Command Out at the specified deceleration rate. As a momentary input, R–Stop is internally latched and does not need to be maintained by an operator device.
J5
Figure 2-9 Jog
9
11
R-STOP
J5
2 - 10
Figure 2-10 R–Stop
F-Stop (J5 pins 10, 11)
F-Stop is a momentary input. When it is open, the ML–Trim stops immediately (zero RPM) and ignores the specified deceleration rate. As a momentary input, F-Stop is internally latched and does not need to be maintained by an operator device.
F-STOP
10
11
J5
Figure 2-11 F–Stop
Master or Follower
(J5 pins 12, 14)
This input determines the ML–Trim's mode of operation and resulting scaling formula that the control algorithm uses. The ML–Trim is in Master mode when the circuit is open, and Follower mode if the circuit is shorted to the common.
12
14
J5
MASTER
FOLLOWER
Figure 2-12 Master / Follower
2 - 11
Setpoint Select (J5 pins 13, 14)
The Master and Follower setpoints are determined by the Setpoint Select input combined with the Master/ Follower Input. For access to Master Control Parameters 1 and 2 and Follower Control Parameters 3 and 4, refer to the chart below.
CONTROL
13
14
J5
PARAMETER 1 OR 3
CONTROL PARAMETER 2 OR 4
Figure 2-13 Setpoint Select
Setpoint Select / Closed Setpoint Select / Open
Master/Follower Input Open
Master/Follower Input Closed
Master Control Parameter 1 Master Control Parameter 2
Follower Control Parameter 3
Follower Control Parameter 4
2 - 12
OUTPUTS
NOTE: The installation of this motor control must conform to area and local electrical
codes. See National Fire Protection Association, or Use local codes as applicable.
Speed Command Out (J2 pins 1, 2)
The National Electrical Code
The Canadian Electrical Code
(NEC,) Article 430 published by the
(CEC).
Speed Command Out is an isolated analog output signal that is sent to the motor drive to control the speed of the motor. Wire the Speed
SIGNAL INPUT
*
DRIVE COMMON
Speed Command Out
Isolated Common
1
2
Command Out into the Speed Signal Input of the drive. If the motor drive has a potentiometer speed control, remove the potentiometer connections and wire the Speed Command Output to the
MOTOR DRIVE
Do not connect the Drive Isolated Common to other
*
Logic Commons
J2
potentiometer wiper input. The ML–Trim's isolated common should
Figure 2-14 Speed Command Out
always be connected to the drive common.
Drive Enable (J5 pin 16)
The Drive Enable output is activated (driven low) when the ML–Trim is signaling a nonzero speed command to the motor drive, as defined by Drive Enable Logic (CP-74) The Drive Enable output is driven high (relay deactivated) after Power Up and during R–Stop and F–Stop. See Figure 2-15. Refer to
Output,
page 3-37 for details.
Operations: Logic Control, Logic
NOTE: This is an open-collector relay driver. For specification details, see
Appendix A
-
ML–Trim Specifications,
page A-1. Use an external DC power supply to power the relays. Free-wheeling diodes are incorporated internally in the ML–Trim and do not need to be added externally.
References:
2 - 13
Alarm (J5 pin 17)
By entering alarm Control Parameters, you can establish circumstances under which the ML–Trim will alert you to potential operating problems. The alarm can be wired to activate a warning light, a warning sound, or to shut down the system under specified conditions. Alarm Format (CP-10) determines which alarm conditions will activate the Alarm output, using the values that are entered in Low Alarm (CP-12), High Alarm (CP-13), Ramped Error (CP-14) and Scaled Error (CP-15). See Figure 2-15. Refer to
Operations: Logic Control, Logic Output,
NOTE: This is an open-collector relay driver. Use an external DC power supply to
power the relays. Free-wheeling diodes are incorporated internally in the ML–Trim and do not need to be added externally.
page 3-37 for details.
+V_DO
Drive Enable
Alarm
Common
15
16
17
18
J5
R1
R2
+
EXTERNAL DC POWER SUPPLY
(50V Max)
Figure 2-15 Drive Enable and Alarm Outputs
Auxiliary DC Power (J4 pin 1, 2)
The 5 volt output (J4 pin 1) is a DC regulated output that can be used to power encoders or other auxiliary equipment that is used in conjunction with the ML–Trim. If this output is used, it will nullify optical isolation.
WARNING
Do not exceed the maximum current output of 150 mA for +5 VDC.
2 - 14
Exceeding the maximum current output can damage the ML–Trim.
SERIAL COMMUNICATIONS
NOTE: The installation of this motor control must conform to area and local electrical
codes. See National Fire Protection Association, or Use local codes as applicable.
The Serial Communications interface on the ML–Trim complies with EIA Standard RS–485-A for balanced line transmissions. This interface allows the host computer to perform remote computer parameter entry, status or performance monitoring, and remote control of the ML–Trim. See information on using Serial Communications. The ML-Trim is designed to use with an isolated RS232 to RS485 converter.
Figure 2-16 illustrates a multidrop installation of the Serial Communications link and Figure 2-17 illustrates the Serial Communications connections.
The National Electrical Code
The Canadian Electrical Code
Operations: Serial Communications,
(NEC,) Article 430 published by the
(CEC).
page 3-49 for
Contrex
8 9
7
CODE SELECT
4 5 6
SET
POINT
2 3
1
TACH
.
0
ENTER
CLEAR
Isolated
RS232 to RS485
Converter
Contrex
8 9
7
CODE
SELECT
4 5 6
SET
POINT
2 3
1
TACH
.
0
ENTER
CLEAR
Figure 2-16 ML–Trim Multidrop Installation
Contrex
CODE
SELECT
SET
POINT
TACH
7
4 5 6
1
CLEAR
Contrex
8 9
2 3
0
ENTER
Contrex
8 9
7
CODE
SELECT
4 5 6
SET
POINT
2 3
1
TACH
.
0
ENTER
CLEAR
Contrex
.
8 9
7
CODE SELECT
4 5 6
SET POINT
2 3
1
TACH
.
0
ENTER
CLEAR
8 9
7
CODE SELECT
4 5 6
SET POINT
2 3
1
TACH
.
0
ENTER
CLEAR
2 - 15
Isolated
RS232 to RS485
Converter
TXD/ TXD/ COM RXD RXD — +
1. Shield only at one end of the cable.
2. If you need to terminate the communication line, then terminate it at the unit which is the furthest away from the converter. A 100 ohm, 1/2 Watt resistor will usually terminate successfully. Refer to EIA Standard RS485A, for more information.
J1
1
2
3
J1
2
1
2
3
1
ML–Trim #1
T/R+ T/R– COM
ML–Trim #2
T/R+ T/R– COM
2 - 16
Figure 2-17 ML–Trim Serial Communications Connections
Loading...
+ 150 hidden pages