CONTREX M-Drive User Manual

M-DRIVE INSTALLATION/START-UP GUIDE
CAUTION
Hazardous Voltages. Can cause severe injury, death or damage to equipment. The M-Drive should only be installed by a qualified electrician.
Proper earth grounding of all electronic equipment is required for successful operation. Connect a low impedance earth ground to terminal 7 of connector J2.
Shield all logic and signal wiring (J1, J3 and J4) and terminate to earth ground at one point only.
REQUIRED WIRING
CC
ONTREX, INC.ONTREX, INC.
C
ONTREX, INC.
ONTREX, INC.ONTREX, INC.
CC
SK1416 Rev 3SK1416 Rev 3
SK1416 Rev 3
SK1416 Rev 3SK1416 Rev 3
Page 1
SCALING
After completing the required wiring of the M-Drive, follow the procedure below to scale the M-Drive for Master format RPM operation. Complete this procedure before scaling the M-Drive for engineering units.
1. While pressing the “CLEAR” and “7” keys on the keypad, apply AC power to the M-Drive (loads factory default parameters).
2. Enter the pulses-per-revolution of the feedback sensor into CP-31. The keypad sequence for a 60 tooth gear sensor is “Code Select”, “3”, “1”, “Enter”, “6”, “0”, “Enter”.
3. Enter the maximum system operating RPM into CP-20, CP-22, CP-34 and CP-37. If the feedback sensor is not directly connected to the motor shaft, enter the maximum feedback sensor shaft RPM.
4. Press the “SETSPEED” key and enter ½ of the RPM entered in Step 3.
5. Press the RUN pushbutton.
6. Verify the motor direction is forward (exchange A1 and A2 if not forward).
7. Press the “TACH” key. Verify an RPM reading appropriate to the motor setpoint speed.
8. Press the R-Stop pushbutton.
The M-Drive is now properly scaled in RPMs. If engineering unit setpoints and/or displays other than RPMs are desired, refer to Chapter 5 of the “M-Drive User Manual” .
TUNING
If the drive system acts unstable or sluggish in response to setpoint or load changes, it may be necessary to tune the M-Drive. Follow the procedure below to improve system performance:
1. Set CP-66 (Integral) and CP-67 (Derivative) to zero.
2. Reduce CP-65 (Gain) until the system goes unstable (erratic). Stability can be tested by moving between two wide spread setpoint values. When instability is reached, increase the CP-65 number slightly until the system stabilizes (larger values reduce the system gain).
3. Using only Gain, the system setpoint value may never be reached due to system losses. Reduce CP-66 (Integral) until the system becomes unstable, then increase the Integral number slightly until the system stabilizes and the desired setpoint value is reached.
4. Derivative (CP-67) is only required if the system is too sluggish after setting the Gain and Integral terms. The Derivative value, like Gain, should be reduced to the point of instability, then increased slightly until the system regains stability.
CC
ONTREX, INC.ONTREX, INC.
C
ONTREX, INC.
ONTREX, INC.ONTREX, INC.
CC
SK1416 Rev 3SK1416 Rev 3
SK1416 Rev 3
SK1416 Rev 3SK1416 Rev 3
Page 2
Loading...
+ 2 hidden pages