20.0 WIRE DIAGRAM FOR TWO STAGE FURNACE WITH ECM 2.3 54
IOM
21.0 WARRANTY 56
22.0 REPLACEMENT PARTS LIST 57
23.0 SERVICE HISTORY 58
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
IMPORTANT:
PLEASE READ THIS MANUAL CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE
BY A SERVICE TECHNICIAN.
ATTENTION:
TO REMOVE OUTER STAINLESS STEEL DOOR, FIRMLY GRAB DOOR SIDES AND PULL OFF.
TO REPLACE OUTER STAINLESS STEEL DOOR, ALIGN AND PUSH DOOR ON INTO PLACE.
1.0 INTRODUCTION
This high effi cient gas fi red two stage condensing furnace is an upfl ow warm air furnace suitable for residential
and light commercial heating applications with inputs from 60,000 to 120,000 Btu/hr.
This high effi cient furnace series is CSA certifi ed as a Category IV indirect or direct vent central forced air fur-
nace. When installed as a direct vent furnace, all combustion air is supplied to the furnace burners through the air
intake system. (See Section 7, “Ventilation and Combustion Piping.”)
The furnace is shipped completely assembled except for the condensate drain trap assembly. Please inspect
for damage when the furnace is unpacked.
W415-1080 / B / 08.28.13
IOM
IOM
4
2.0 SAFETY SYMBOLS AND WARNINGS
Understand and pay particular attention to the words DANGER, WARNING, and CAUTION and the following
defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
! !
DANGER
INDICATES AN IMMINENTLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, WILL
RESULT IN DEATH OR SERIOUS INJURY.
!
WARNING
INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, COULD
RESULT IN DEATH OR SERIOUS INJURY.
!
CAUTION
INDICATES A POTENTIAL HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY
RESULT IN MINOR OR MODERATE INJURY. IT MAY ALSO BE USED TO ALERT AGAINST
UNSAFE PRACTICES.
IMPORTANT:
READ THE FOLLOWING INSTRUCTIONS COMPLETELY BEFORE INSTALLING!
!
WARNING
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR
LOSS OF LIFE.
FOR YOUR SAFETY
!
!
!
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS, OR
OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR
BUILDING.
• IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE, OR A CELLULAR PHONE FROM A LOCATION WELL AWAY FROM THE BUILDING. FOLLOW THE
GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
• DO NOT RE-ENTER THE BUILDING UNTIL AUTHORIZED TO DO SO BY THE GAS
SUPPLIER OR THE FIRE DEPARTMENT.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO THIS MANUAL.
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER,
W415-1080 / A / 08.28.13
WHAT TO DO IF YOU SMELL GAS
SERVICE AGENCY OR THE GAS SUPPLIER.
5
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE
PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF
THIS FURNACE. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING
INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE,
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE
POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
2.1 SAFETY RULES
1. Use this furnace only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in dry indoor locations (protected from weather).
3. Provide adequate combustion and ventilation air to the furnace space as specifi ed in Section 7 of this
manual, “Ventilation and Combustion Piping.”
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only,
as specifi ed in Section 7 of this manual, “Venting and Combustion Piping.”
5. Never test for gas leaks with an open fl ame. Use a commercially available soap solution made specifi cally
for the detection of leaks to check all connections as specifi ed in Section 12 of this manual, “Gas Supply
and Piping.”
6. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system,
which has an external static pressure within the allowable range, listed on the furnace rating plate, and as
specifi ed in Sections 3, 6, and 18 of this manual, “Furnace Sizing,”“Ductwork,” and “Airfl ow.”
7. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the
space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace. (Furnace for heating the home located in the attached
garage, for example).
8. A gas-fi red furnace for installation in a residential garage must be installed so that the burners and ignitor are
no less than 18” (457 mm) above the fl oor. The furnace must be located, or protected to avoid physical dam-
age by vehicles. (See safety warning).
9. This furnace may be used for heating of buildings or structures under construction provided that:
• The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed per
these installation instructions.
• A room thermostat must control the furnace. The use of fi xed jumpers that will provide continuous
heating is not allowed.
• The return air duct must be provided and sealed to the furnace casing, and terminate outside the
space containing the furnace.
• Return air temperature range between 55°F (13°C) and 80°F (27°C) must be maintained.
• Air fi lters must be installed in the system and must be maintained during construction.
• Air fi lters used to clean the circulating air during the construction process must be either replaced or
thoroughly cleaned prior to occupancy.
• The input rate and temperature rise must be set per the furnace rating plate.
• One hundred percent (100%) outdoor air must be provided for combustion air requirements during
construction. This is to minimize the corrosive effects of adhesives, sealers and entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
• The furnace heat exchanger, components, duct system, and evaporator coils must be thoroughly
cleaned following fi nal construction clean-up.
• All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be
verifi ed according to these installation instructions.
!
WARNING
!
IOM
W415-1080 / B / 08.28.13
IOM
IOM
6
2.2 CODES
1. This furnace must be installed:
a. In accordance with all local codes, by-laws and regulations by those authorities having jurisdiction.
b. In Canada, this furnace must be installed in accordance with the current CAN/CGA -B149.1 and .2
Natural Gas and Propane, and the National Electric Code (NEC) NFPA 70.
c. In the United States, this furnace must be installed in accordance with the current ANSI Z223.1 (NFPA
54) National Fuel Gas Code.
2. Electrical connections must be made in accordance with:
a. Any applicable local codes, by-laws and regulations.
b. Canada: current edition of CAN/CSA C22.1 and C22.2, Canadian Electrical Code (Part 1 and 2).
c. United States: current edition of ANSI/NFPA 70, National Electrical Code.
Codes and additional information may be obtained from:
Canadian Standards Association American Gas Association
5060 Spectrum Way 400 North Capitol Street, NW, Suite 450
Mississauga, Ontario, L4W 5N6 Washington DC, 20001
Phone: (416) 747-4000 Phone: (202) 824-7000
website: www.csa.ca website: www.aga.org
National Fire Protection Association
1 Batterymarch Park
Quincy, MA, 02169-7471
Phone: (617) 770-3000
website: www.nfpa.org
!
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME! THIS FURNACE IS NOT
APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE,
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
THE FURNACE CONTAINS FOIL COVERED FIBERGLASS INSULATION. INHALATION OF
FIBERGLASS PARTICLES IS ASSOCIATED WITH RESPIRATORY DISEASE INCLUDING
CANCER.
NATURAL GAS AND PROPANE ARE NORMALLY ODORIZED BY THE FUEL SUPPLIER. IN
SOME CASES, THE ODORANT MAY NOT BE PERCEIVABLE. INSTALLATION OF UL AND
ULC RECOGNIZED FUEL GAS DETECTORS INSTALLED IN ACCORDANCE WITH THEIR
MANUFACTURER’S INSTRUCTIONS IS RECOMMENDED AS AN ADDITIONAL MARGIN OF
SAFETY.
THE EXHAUST GASES FROM THIS FURNACE CONTAIN CHEMICALS WHICH ON
SOME OCCASIONS MAY INCLUDE CARBON MONOXIDE. CARBON MONOXIDE IS AN
ODORLESS, TASTELESS, CLEAR COLORLESS GAS WHICH IS HIGHLY TOXIC. EVEN
LOW CONCENTRATIONS ARE SUSPECTED OF CAUSING BIRTH DEFECTS AND OTHER
REPRODUCTIVE HARM.
UL AND ULC RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS
EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS SHOULD
BE INSTALLED IN ACCORDANCE WITH THEIR MANUFACTURER’S INSTRUCTIONS AND
APPLICABLE LOCAL BUILDING CODES.
FAILURE TO REPLACE WITH PROPER CONTROL COULD RESULT IN FIRE, EXPLOSION
REPLACE GAS VALVE ONLY WITH THE SAME MODEL NUMBER OR AS SPECIFIED BY THE
W415-1080 / A / 08.28.13
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD!
OR CARBON MONOXIDE POISONING.
MANUFACTURER.
!
WARNING
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE
INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN
18” (457 mm) ABOVE THE FLOOR TO PREVENT THE RISK OF IGNITING FLAMMABLE
VAPORS WHICH MAY BE PRESENT IN THE GARAGE.
THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY
VEHICLES.
FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING
IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
!
7
IOM
FIGURE 1 - FURNACE DIMENSIONS AND CLEARANCE TO COMBUSTIBLES
0.625”
(15.875 MM)
31.000” (787.4 MM)
19.625” (498.475 MM)
ALTERNATE VENT OUTLET
ALTERNATE AIR IN
SIDE CUTOUT
HIGH VOLTAGE IN
23.0” (584.200 MM)
LOW VOLTAGE IN
AIR
INLET
0.625”
(15.875 MM)
7.82”
(198.628 MM)
STD. GAS SUPPLY
CONDENSATE
DRAIN TRAP WITH
1/2” CPVC DISCHARGE
LEFT & RIGHT SIDE
UPFLOW DRAIN HOLE
A
B
C
D
2” PVC VENT OUTLET
32.875”
(835.025 MM)
TABLE 1 - RANGE OF TEMPERATURE RISE
Furnace ModelsTemperature Rise
High Fire (HF) 35 - 65°F (20 - 36°C)
ALL
Low Fire (LF) 20 - 50°F (11 - 28°C)
H12.15.4
6.572”
(166.929 MM)
ALT. GAS LINE IN
ALT. AIR INLET
ALT. VENT OUTLET
ALT. UPFLOW DRAIN HOLE
ALT. HIGH
VOLTAGE IN
ALT. LOW
VOLTAGE IN
WITNESS MARKS
FOR SIDE CUTOUTS
SIDE CUTOUT
TABLE B - MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
UPFLOW
TOP0
PLENUM TOP1/2ʺ (13mm)
FRONT 0*
BACK0
SIDES0
BOTTOM 0***
FLUE PIPE0
ENCLOSURECLOSET
*24ʺ (610mm) REQUIRED FOR SERVICE
*** CERTIFIED FOR CLOSET INSTALLATION ON COMBUSTIBLE FLOORING.
H12.11.4b
0"
0"
NOTES:
S - Service clearance 24 inches (610mm) or more.
C - Combustible oor (but not carpet or non-ceramic tile).
All models approved for closet installation.
0"
Top
W415-1080 / B / 08.28.13
Plenum
1/2" (13mm)
on all sides
0"
0"
IOM
IOM
8
FIGURE 2 - FURNACE COMPONENTS
15
7
22
1
5
18
10
9
20
14
8
21
19
6
13
12
2
3
17
*16
4
11
LEGEND
1. Combustion Air Intake Fitting 13. Two Speed Exhauster
3. Flame Sensor - located underneath 15. Front Manifold Cover Pressure Tap (3)
4. Two Stage Gas Valve *16. PFC “Choke Coil” (used on ¾ and 1 Hp units only)
5. Air High Temperature Limit - supply air 17. Door Switch and Junction Box
6. Vent and Drain (Assembly) Coupling 18. Blower Motor (not shown, located on right side of
7. Drain for Recovery Coil (3) blower)
8. Condensate Trap 19. Circulating Air Blower
9. Two Stage Integrated Furnace Control (IFC) 20. UV Light Ballast (Optional)
10. Transformer for 24 VAC / 40 VA 21. UV Light Bulb (Optional)
11. Burner Assembly 22. LED Trouble Light (2)
12. Hot Surface Igniter (HSI)(located underneath)
W415-1080 / A / 08.28.13
3.0 FURNACE SIZING
9
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures
described in the manuals of the Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or by
any other method which is suitable for local conditions, provided the results obtained are in substantial agreement with, and not less than those obtained using the procedure described in their manuals.
In the United States, “Manual J - Load Calculation,” published by the Air Conditioning Contractors of America,
describes a suitable procedure for calculating the maximum hourly heat loss.
If the installation is a retrofi t application, do not rely on the capacity of the existing heating equipment as a
method to size the new furnace. Many of the heat transfer multiples listed in earlier versions of load calculation
manuals were much higher than those listed in more recent editions. It is possible that energy saving measures have been completed since the installation of the existing furnace. This might include additional insulation in the attic or walls, the application of sprayed foam insulation, the addition of storm windows and doors,
weather-stripping, caulking, etc.
Many of the older furnaces were equipped with large belt drive blower systems, operating at low RPM’s. If replacing an existing furnace, be sure that the existing ductwork can handle the amount of airfl ow necessary for
a reasonable temperature rise. Most older gas furnaces operated with a system temperature rise of 70 - 100°F
(39 - 56°C). This furnace is designed to be operated with a system temperature rise (∆T) of High Fire 35 - 65°F
(20 - 36°C), Low Fire 20 - 50°F (11 - 28°C). If the furnace
selected has an identical output capacity as the original
furnace, a substantial increase in system air fl ow will be
necessary. See Table 1 and the airfl ow characteristics in
Section 18 of this manual, “Airfl ow”.
Existing ductwork should be assessed for its air handling
TABLE 1 - RANGE OF TEMPERATURE RISE
Furnace ModelsTemperature Rise
High Fire (HF) 35 - 65°F (20 - 36°C)
ALL
Low Fire (LF) 20 - 50°F (11 - 28°C)
H12.15.4
capabilities.
The “Equal Friction Chart,” as published by ASHRAE and HRAI, is the basis for the various air duct calculators available through heating supply companies. Following the air velocity guide lines, according to the “Equal Friction Chart,” or a slide rule air duct calculator, a typical 6” (152 mm) round duct has a capacity of approxi-
mately 100 cfm.
IOM
NOTE:
The return air system is equally as important as the supply air system. An under-sized return
air system will prevent suffi cient quantities of air from reaching the supply air system and will
consequently reduce the service life of the furnace and its components.
W415-1080 / B / 08.28.13
IOM
IOM
10
4.0 LOCATION OF UNIT
4.1 GENERAL GUIDELINES
1. Select a location where the exhaust and combustion air piping can be routed between the furnace and
their terminations with a minimum of lengths and fi ttings. Be sure to check that the proposed termination
location will meet code requirements with respect to location and minimum clearances. (See venting sec-
tion for minimum and maximum limits.)
2. Select a location as near as possible to the existing or proposed duct system.
3. The furnace location must have provisions for condensate drainage. If a suitable drain is unavailable near
the furnace, a condensate pump must be used. The condensate pump drain tubing must not terminate
outdoors; similar to some air conditioning condensate installations. Be sure to select a condensate pump
that has been approved for furnace condensate applications.
4. The furnace location must permit access for servicing and be within the clearance to combustibles guidelines as marked on the appliance rating plate.
5. The furnace must be installed on a level surface. It is recommended that the rear of the furnace be elevated 1/4” (6 mm) higher than the front to facilitate proper condensate drainage.
6. If the furnace is being installed so that the return air will enter through the bottom, the perimeter of the
furnace must be properly supported.
7. In right venting confi guration, furnace must drain on the left side.
4.2 OTHER CONSIDERATIONS
1. If the furnace is to be located in an area where the combustion air is laden with chemical compounds such
as bromine, chlorine or fl uorine, as may be found in swimming pool chemicals, laundry detergents, etc., use outdoor air for combustion. These compounds when exposed to fl ame, form acids which attack the
heat exchanger and other components.
Exposure to the following substances in the combustion air supply (but not limited to the following) will also
require OUTDOOR AIR for combustion:
• Aerosols, particularly CFC based or propelled aerosols
• Air fresheners
• “Airplane Glue” and similar adhesives and cements
• Ammonia, as commonly found in permanent wave solutions used in hair dressing salons
• Anti-static fabric softeners used in clothes dryers
• Carbon tetrachloride
• Chlorinated cleaners and waxes
• Chlorine and bromine based swimming pool chemicals
• De-icing salts or chemicals (rock salt, etc.)
• Dry cleaning fl uids such as perchloroethylene
• Fumes from curing polyurethane and similar substances
• Halogen based refrigerants including R-12 and R-22
• Hydrochloric acid, muriatic acid and other acid based masonry washing and curing materials
• Printer’s inks, paint removers, varnishes, varsol, toluene, etc.
• Water softener salt and chemicals
2. If this furnace is to be installed in an area over a fi nished ceiling or living area, install a fi eld fabricated
auxiliary drain pan under the furnace to protect that area from accidental condensate spills. The auxiliary
pan should be large enough to collect accidentally spilled condensate from the air conditioning evaporator
coil assembly if applicable.
3. If the furnace is installed in an area where freezing may occur, a garage, an attic, a crawl space or any
unconditioned space, steps must be taken to protect the condensate trap and drain line from freezing.
One possible measure could be to use a self-regulating 5 or 6 watt per foot heat tape covered with a jacket
of insulation. Heat tapes are available in plumbing supply houses.
W415-1080 / A / 08.28.13
4.3 INSTALLATION IN UPFLOW POSITION
11
UPFLOW INSTALLATION: Vent positioning, pressure switch location and drain locations shall be performed in accordance with instructions in the appropriate sections of this manual.
NON-SUSPENDED INSTALLATION: Maintain clearances to combustibles as outlined in Figure 1, Table B. The
furnace must be supported in such a way as to not allow twisting or sagging of the cabinet.
IMPORTANT:
• THE FURNACE MUST BE INSTALLED ON A LEVEL SURFACE. IT IS RECOMMENDED
THAT THE REAR OF THE FURNACE BE ELEVATED 1/4” (6 mm) HIGHER THAN THE
FRONT TO FACILITATE PROPER CONDENSATE DRAINAGE.
• IF THE FURNACE AND AIR CONDITIONER IS LOCATED ABOVE A FINISHED SPACE,
INSTALL A DRAIN PAN UNDERNEATH THE UNIT.
NOTE
THIS FURNACE IS CERTIFIED FOR UPFLOW INSTALLATION ONLY.
This furnace is approved for installation in attics, alcoves, utility rooms, closets and crawl spaces.
If this furnace is to be installed in a utility room, be sure that it is located in such a way as to allow
access for servicing or the removal of other appliances installed in the room (hot water heater, for
example). It is not permissible to use a rear return on this appliance. Use only side and bottom
returns.
IOM
4.4 AIR CONDITIONING
This furnace may be used as part of an air conditioning system. The furnace wiring and control system is “air
conditioning ready.” There are the following factors to consider:
• The air conditioning evaporator coil must be downstream of the heat exchanger. The cooled air passing
over the warmer heat exchanger tubes can cause condensation inside the tubes, resulting in corrosion and
premature failure.
• A parallel duct system can be installed to direct the air from the furnace through the evaporator coil only.
Use dampers or other means to bypass the heat exchanger. If (summer/winter) dampers are used, they
should be interlocked to prevent system operation unless the dampers are in the full open or full closed
position.
NOTE
If installing a two stage air conditioning system, clip the JW38 jumper wire between Y (low cool) and Y2
(high cool) on the furnace control board.
Control defaults to Y2 (high cool) if JW38 jumper wire is NOT cut.
W415-1080 / B / 08.28.13
IOM
IOM
12
5.0 COMBUSTIBLE CLEARANCES
Table B provides the certifi ed clearances to combustibles and dimensional information. Also see the appliance
rating plate affi xed to the furnace for specifi c model number, serial number and clearance to combustibles
information.
IMPORTANT:
THIS FURNACE REQUIRES A MINIMUM OF 24” (610 mm) OF FRONT CLEARANCE FOR
SERVICE PURPOSES. FOR THIS PURPOSE, SERVICE CLEARANCE TAKES PRECEDENCE OVER CLEARANCE TO COMBUSTIBLES.
WARNING
THIS FURNACE IS CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. THIS
SHALL BE INTERPRETED AS A WOOD FLOOR ONLY.
THE FURNACE MUST NOT BE INSTALLED DIRECTLY ON CARPETING, OR OTHER
COMBUSTIBLE MATERIAL EXCEPT WOOD.
INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS
AND LIQUIDS.
THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE
USED AS A CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
! !
W415-1080 / A / 08.28.13
6.0 DUCTWORK
13
Proper airfl ow is required for the correct operation of this furnace. Insuffi cient airfl ow may cause erratic opera-
tion, could cause the furnace to cycle on the high temperature limit, and may damage the heat exchanger.
Excessive airfl ow may result in an excessively noisy duct system and may result in undesirable consequences
such as creating uncomfortable drafts.
If air conditioning is to be used with the furnace, the duct system must be capable of delivering the correct
amount of airfl ow for each system.
The ductwork should be sized and constructed in accordance with accepted industry standards. Duct sizing
and construction information may be obtained from:
• A.C.C.A. (Air Conditioning Contractors of America)
• A.S.H.R.A.E. (American Society of Heating, Refrigeration and Air Conditioning Engineers
• H.R.A.I. (Heating, Refrigerating and Air Conditioning Institute (Canada)
• S.M.A.C.N.A. (Sheet Metal and Air Conditioning Contractors’ National Association (United States)
All of the above professional organizations have duct sizing manuals available.
The total static pressure drop of the air distribution system (including fi lters) should not exceed 1.0” w.c.
!
WARNING
DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH JOIST SPACES THAT ARE
USED FOR RETURN AIR PURPOSES. DO NOT USE JOIST SPACES FOR RETURN AIR
PURPOSES IF THE JOIST SPACE ALREADY CONTAINS PLUMBING STACKS, CHIMNEY
COMPONENTS, ETC. UNLESS THE PORTION USED FOR RETURN AIR PURPOSES CAN
BE COMPLETELY ISOLATED FROM PORTIONS WITH OTHER USAGES.
!
IOM
NEVER ALLOW THE PRODUCTS OF COMBUSTION FROM THE FLUE TO ENTER THE
RETURN AIR OR SUPPLY AIR DUCTWORK.
ALL RETURN AIR DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO
THE FURNACE WITH SHEET METAL SCREWS. TAPE THE SHEET METAL SEAMS IN THE
VICINITY OF THE FURNACE WITH DUCT TAPE OR SIMILAR MATERIAL.
WHEN THE FURNACE IS MOUNTED ON A PLATFORM WITH RETURN AIR THROUGH THE
BOTTOM, IT MUST BE SEALED AIR TIGHT BETWEEN THE FURNACE AND THE RETURN
AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT
OF THE FURNACE WITHOUT SAGGING, OR GAPS AROUND THE BASE. IT MUST ALSO
BE SEALED BETWEEN THE SUPPORT AND THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCULATED INTO
THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING
CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
W415-1080 / B / 08.28.13
IOM
IOM
14
6.1 DUCTWORK STEPS
1. Position the furnace to minimize ductwork length and fi ttings.
2. Cut open a return air inlet. The choices are furnace bottom, either side, or any combination thereof (i.e.,
two sides or a side and the bottom).In all cases, cut the return air opening the full width of the return air
markers on the side panel.
!
WARNING
!
DO NOT USE THE REAR PANEL AS A RETURN AIR INLET. THERE IS INSUFFICIENT
ROOM TO PERMIT ADEQUATE AIRFLOW.
DAMAGES, DEFECTS OR FAILURES CAUSED BY CONDITIONED AIR (RETURN AIR)
SUPPLIED TO THE FURNACE BEING GREATER THAN 20% FROM OUTDOORS (55°F/13°C
MIN. RETURN AIR TEMPERATURE).
SOME HEATING AIR FLOW VALUES MAY BE HIGHER THAN THOSE REQUIRED FOR
COOLING. BE SURE TO SIZE DUCT SYSTEM FOR HIGHEST POSSIBLE VALUES.
3. Connect the return air duct or fi lter fi tting to the furnace. The connection should be sealed air tight to prevent
entraining combustion gases from an adjacent fuel burning appliance, or entraining combustion air for this
furnace or adjacent fuel burning appliances.
4. Ensure that there is adequate space and accessibility for air fi lter removal.
5. If an air conditioning evaporator coil is required, position it on the supply air side of the furnace. Ensure
that no air can bypass the evaporator coil.
6. Connect the supply air plenum to the supply air outlet.
FLEXIBLE DUCT CONNECTORS are an effective device to prevent the telegraphing of mechanical noise from
the furnace to other parts of the home via the ductwork. If using fl exible connectors, ensure that the adjoining
duct is independently supported.
NOTE: For upfl ow 5 ton airfl ow models where the airfl ow requirements exceed 1800 cfm, models
will require air openings and fi lters on: • both sides, OR
• one side and the bottom, OR
• just the bottom
W415-1080 / A / 08.28.13
7.0 VENTING AND COMBUSTION PIPING
15
IOM
!
WARNING
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO
PROPERLY VENT OR SUPPLY COMBUSTION AIR TO THIS FURNACE CAN CAUSE CAR-
BON MONOXIDE POISONING, OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
!
7.1 ACCEPTABLE MATERIALS IN CANADA
Effective August 1, 2007, all vent piping materials and fi ttings for fl ue gas venting must be ULC S636 listed
and identifi ed as such on the material. The fi rst 3ft. (900mm) of venting must be readily available for visual
inspection. Specifi ed primers and glues of the certifi ed vent system must be from a single system manufacture,
and not intermixed with other system manufacture’s vent system parts. The components of the certifi ed vent
system must not be interchanged with other vent systems, or unlisted pipe, and or fi ttings. Follow the venting
manufacturers instructions on installation, cutting, de-burring, cementing, curing and supporting of the venting
system.
This furnace must be vented with ULC S636 certifi ed:
• PVC (Polyvinyl Chloride), OR
• PPE (Polypropylene) material
with a minimum rating of 149°F (65º C) or more.
The combustion air piping does not have fl ue gases traveling through it and may be installed with common
ABS, PVC or CPVC piping or fi ttings. This piping, fi ttings, primer and cement will need to be installed as per
the manufacturers instructions including cementing, cutting, curing and supporting the piping.
7.2 ACCEPTABLE MATERIALS IN UNITED STATES
For United States installations, the combustion air and vent piping and fi ttings may be comprised of:
• Schedule 40 PVC, ASTM D1785 or CSA B137.3
• PVC-DWV, ASTM D2665 or CSA B181.2
• Schedule 40 CPVC, ASTM F441 or CSA B137.6
• PVC PRIMER AND SOLVENT CEMENT: ASTM D2564
• PPE ULC S636
Follow piping manufacturers instructions on proper installation of piping and fi ttings including cutting, deburr-
ing, priming, cementing, curing and supporting.
W415-1080 / B / 08.28.13
16
8.0 NON-DIRECT VENT FURNACE INSTALLATIONS
IOM
IOM
USING INDOOR COMBUSTION AIR (ONE PIPE
SYSTEM)
The furnace, although designed as a direct vent type appliance, may be installed with the intake vent inside the
structure.
!
WARNING
THIS FURNACE AND ANY OTHER FUEL BURNING APPLIANCE MUST BE PROVIDED
WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE
FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE BROUGHT TO
THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE PERSONAL INJURY, OR DEATH
FROM CARBON MONOXIDE POISONING.
Adequate provisions for combustion and ventilation air must be in accordance with CAN/CGA-B149 in Canada,
and ANSI Z223.1 - 1992, section 5.3, “Air for Combustion and Ventilation,” in the United States. Check with lo-
cal authorities for any additional building codes bylaws or regulations.
!
CAUTION
AIR FOR COMBUSTION AND VENTILATION PURPOSES MUST NOT ORIGINATE FROM A COR-
ROSIVE ATMOSPHERE. ANY FURNACE FAILURE CAUSED BY CORROSIVE ELEMENTS IS
EXCLUDED FROM WARRANTY COVERAGE.
!
!
The following types of installation sites (but not limited to the following) will REQUIRE OUTDOOR AIR for combustion because of chemical exposures:
• Commercial buildings
• Buildings with indoor swimming pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air supply (but not limited to the following) will also
require OUTDOOR AIR for combustion:
• Aerosols, particularly CFC based or propelled aerosols
• Air fresheners
• “Airplane Glue” and similar adhesives and cements
• Ammonia, as commonly found in permanent wave solutions used in hair dressing salons
• Anti-static fabric softeners used in clothes dryers
• Carbon tetrachloride
• Chlorinated cleaners and waxes
• Chlorine and bromine based swimming pool chemicals
• De-icing salts or chemicals (rock salt, etc.)
• Dry cleaning fl uids such as perchloroethylene
• Fumes from curing polyurethane and similar substances
• Halogen based refrigerants including R-12 and R-22
• Hydrochloric acid, muriatic acid and other acid based masonry washing and curing materials
• Printer’s inks, paint removers, varnishes, varsol, toluene, etc.
• Water softener salt and chemicals
Combustion air must be free of acid forming chemicals such as sulphur, fl uorine and chlorine. These elements
are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish remov-
W415-1080 / A / 08.28.13
ers, refrigerants, and many other commercial and household products. When burned in a gas fl ame, vapors
from these products form acid compounds. Acid compounds increase the dew point temperature of the fl ue
products and are highly corrosive after they condense.
8.1 DETERMINING COMBUSTION AIR
8.1.1 CASE 1: FURNACE LOCATED IN A UNCONFINED SPACE
Unconfi ned space does not necessarily mean that ventilation will not have to be introduced from the outdoors,
particularly in airtight homes. The minimum requirement for unconfi ned space is a volume of 50 cubic feet (1.42
m³) for each 1000 Btu/hr for all fuel burning appliances located within the unconfi ned area.
If the amount of combustion and ventilation air is insuffi cient to properly operate the furnace and other fuel
burning appliances within the unconfi ned area, it will be necessary to supply it from the outdoors based on the
criteria used when calculating the air supply for a confi ned space.
NOTE
If planning to use the inside air in an unconfi ned space, remember to test for proper furnace operation (as well
as other fuel burning appliances located within the unconfi ned space) with respect to adequate combustion and
ventilation air with fi replace dampers open, clothes dryer running, bathroom exhaust fans on, kitchen range hood
on, etc.
17
IOM
8.1.2 CASE 2: FURNACE LOCATED IN A CONFINED SPACE
A confi ned space, (any space smaller than the minimums discussed in Case 1), must have two air openings;
one within 12” (305 mm) of the ceiling and the other within 12” (305 mm) of the fl oor. The air openings must be
sized based on whether the combustion and ventilation air is being taken from indoors or outdoors, the method
outdoor air (if used) is introduced, and taking into account any other fuel burning appliances in the confi ned
space.
If suffi cient indoor combustion and ventilation air is available for the furnace and all other fuel burning
appliances, size each opening on the basis of one square inch (645 mm²) of free area per 1000 Btu/hr.
(Figure 4)
NOTE
Be sure to consider all clothes dryers, bathroom fans, range hoods, etc., when making this calculation.
The minimum requirement for these openings is
100 square inches (645 mm²), even for the furnace
models under 100,000 Btu/hr.
NOTE
If using grills to cover the two openings, factor
in the free area of the grill. Typically, a sidewall
grill will have a free area approximately 50% of
its nominal size. Consequently, if the required
opening is 10 x 10 (254 mm x 254 mm), it will
have to be doubled if using a sidewall grill
with 50% free area.
FIGURE 4 - COMBUSTION/DILUTION AIR FROM
HEATED INSIDE SOURCES (CASE 2)
W415-1080 / B / 08.28.13
IOM
IOM
18
IMPORTANT:
IF AN EXHAUST FAN, FIREPLACE, CLOTHES DRYER OR ANY SIMILAR DEVICE IS PRESENT IN THE
INDOOR AREA FROM WHICH THE COMBUSTION AND VENTILATION AIR WILL BE DRAWN, NEGATIVE
PRESSURE COULD BE A PROBLEM IF NATURAL INFILTRATION FROM THE OUTDOORS DOES NOT
MATCH THE RATE AT WHICH AIR IS EXHAUSTED.
8.1.3 CASE 3: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR
FROM ATTIC OR CRAWL SPACE
In this circumstance, the free area of each of the two combustion and ventilation air openings is based on a
minimum of 1 square inch (645 mm²) per 4000 Btu/hr. In this confi guration, one opening can originate from
the fl oor drawing combustion and ventilation air from the ventilated crawl space.
The other opening may communicate freely with a ventilated the attic. If using the attic air, ensure that the
opening is ducted from the ceiling high enough to be above the insulation. The attic must be adequately
vented with soffi t vents or gable vents (Figure 5).
As an alternative to creating an opening in the fl oor to draw air from a crawl space, a duct may be dropped from
the attic terminating 12” (305 mm) above the fl oor.
The following table shows minimum free areas and
round pipe sizes when drawing combustion air vertically from the attic or crawl space for the furnace
only. If other fuel burning appliances are present,
their combustion air and ventilation air requirements
must be added to those of the furnace.
FIGURE 5 - OUTSIDE AIR FOR COMBUSTION, ATTIC OR
CRAWL SPACE (CASE 3)
TABLE 2 - VERTICAL AIR SUPPLY (CASE 3)
InputFree Area
K/Btu/hrEa. Opening
6015 in.² (97 cm²)5 in. (127 mm)
8020 in.² (129 cm²)
10025 in.² (161 cm²)
12030 in.² (194 cm²)7 in. (178 mm)
IMPORTANT:
Round Pipe Size
6 in. (152 mm)
H12.16.2
IF THE ATTIC HAS AN EXHAUST FAN (POWER VENT), IT MAY CREATE A NEGATIVE
PRESSURE SUFFICIENTLY LARGE ENOUGH TO PREVENT THE ATTIC FROM BEING
AN EFFECTIVE SOURCE OF COMBUSTION AND VENTILATION AIR. POWERED ATTIC
FANS DO NOT CUSTOMARILY RUN DURING THE HEATING SEASON; HOWEVER,
SOME ARE CONTROLLED BY A HUMIDISTAT AS WELL AS A THERMOSTAT, WHICH MAY
ALLOW SOME OPERATION DURING THE HEATING SEASON. THE CHOICES ARE (A)
USE THE DIRECT VENT OPTION; (B) OBTAIN OUTDOOR AIR FROM ELSEWHERE; OR
(C) INTERLOCK THE ATTIC EXHAUST FAN WITH THE FURNACE SUCH THAT THE TWO
CANNOT OPERATE SIMULTANEOUSLY.
W415-1080 / A / 08.28.13
8.1.4 CASE 4: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR
DUCTED HORIZONTALLY
Similar to Case 3, outdoor air for combustion and ventilation may be drawn through horizontal ducting. The
free area for each opening is calculated on the basis of a minimum of 1 square inch (645 mm²) per 2000 Btu/hr
input.
The following table shows minimum free areas and round pipe sizes when drawing combustion air horizontally
from the outdoors for the furnace only. If other fuel burning appliances are present, their combustion air and
ventilation air requirements must be added to those of the furnace.
TABLE 3 - HORIZONTAL AIR
SUPPLY (CASE 4)
19
IOM
Combustion Air
Duct Terminates
12” (305mm)
above oor.
Input
K/Btu/hr
100
120
60
80
Free Area
Ea. Opening
2
30 in
(194 cm2)
2
40 in
(258 cm2)
2
50 in
(323 cm2)
2
60 in
(387 cm2)
Round Pipe
Size
7 in
(178 mm)
8 in
(203 mm)
9 in
(229 mm)
H12.9.2
IMPORTANT:
THE OUTDOOR GRILLS MUST BE INSTALLED IN A LOCATION WHERE THEY WILL NOT
BE OBSTRUCTED IN ANY MANNER.
IMPORTANT:
IF GRILLS ARE USED ON THE OUTSIDE WALL, THEY MUST BE SIZED PROPERLY.
MOST SIDEWALL GRILLS HAVE ONLY 50% FREE AREA. IN THE CASE OF A UNIT WITH
100,000 BTU/HR INPUT, WHICH REQUIRES A PAIR OF 8” (203 mm) ROUND PIPES TO
OBTAIN SUFFICIENT COMBUSTION AND VENTILATION AIR, THE DUCT COULD BE AN
EQUIVALENT RECTANGULAR DUCT; 8” X 7” (203 mm X 178 mm) FOR EXAMPLE. BASED
ON 50% FREE AREA FOR THE INLET GRILLS, THE ACTUAL GRILL SIZE WOULD HAVE
TO BE 14” X 8” (356 mm X 203 mm) OR ITS EQUIVALENT. A TRANSITION MAY BE USED
TO REDUCE TO THE SMALLER DUCT SIZE IF NECESSARY.
8.1.5 CONNECTION TO FURNACE NON-DIRECT VENT
IMPORTANT:
WHEN USING INDOOR AIR OR THE NON-DIRECT VENT
CONFIGURATION, THE COMBUSTION AIR INLET TO THE
FURNACE MUST BE PROTECTED FROM BLOCKAGE. USE
A DOUBLE ELBOW ARRANGEMENT IF SUPPLYING COMBUSTION AIR THROUGH THE TOP, OR A DOWNWARD
POINTING SINGLE ELBOW IF SUPPLYING COMBUSTION
AIR THROUGH THE SIDE. (FIGURE 7)
FIGURE 7 - NON-DIRECT
COMBUSTION AIR INLET
W415-1080 / B / 08.28.13
IOM
IOM
20
9.0 VENTING GUIDELINES
!
CAUTION
FAILURE TO FOLLOW ALL VENTING GUIDELINES MAY RESULT IN ERRATIC FURNACE
OPERATION, FREEZE-UP OF THE EXHAUST AIR PIPING.
!
!
WARNING
READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS
FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE RESULTING
IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
NOTE
• Combustion air intake and exhaust termination should be inspected periodically to ensure they are clear of
obstructions. i.e. vegetation, debris, snow, etc.
• Accumulation of snow around the combustion air intake and exhaust termination may have
negative effects on appliance operation and/or performance. Snow accumulation should be
considered when locating combustion air intake and exhaust terminations.
ATTENTION:
UPFLOW VENTING RIGHT, MUST DRAIN ON LEFT SIDE.
IMPORTANT:
• CLEAN AND DE-BURR ALL PIPE CUTS. THE SHAVINGS MUST NOT BE ALLOWED TO
BLOCK THE EXHAUST, COMBUSTION AIR INLET OR CONDENSATE DRAIN LINES.
• EVEN UNCUT FULL LENGTH SECTIONS PRODUCE SHAVINGS DURING ASSEMBLY
THAT COULD BLOCK CONDENSES TO DRAINAGE.
• THE EXHAUST VENT MUST BE SUPPORTED APPROPRIATELY PRIOR TO IT BEING
FITTED TO THE EXHAUSTER. UNDER NO CIRCUMSTANCES SHALL THE EXHAUSTER
BEAR ANY WEIGHT OF THE VENTING SYSTEM.
• IF THE PIPE AND FITTINGS ARE TO BE OTHER THAN PVC, USE THE PROPER
CLEANER, PRIMER AND CEMENT FOR THE DISSIMILAR MATERIALS.
!
• Venting may be vertical or horizontal.
• Minimum vent length - 15 total equivalent feet. (See Venting Table)
• Horizontal piping must slope back towards the furnace at a minimum rate of ¼” (6.4 mm) to the foot (305
mm), so that condensate drains towards the furnace.
• Horizontal runs must be supported at least every 3 feet (914 mm). Horizontal sections must not dip or sag.
• All vent runs through unconditioned space where freezing might occur should be insulated with 1” (25 mm) thick,
medium density, foil-faced Fiberglass insulation. An equivalent “arm-a-fl ex” or “rub-a-tex” may also be used as
long as there is no heat tape applied to the vent pipe. For horizontal runs where water may collect, wrap the vent
pipe with self regulating 3 or 5 watt heat tape. The heat tape must be CSA, UL, or ULC listed and installed per the
manufacturer’s instructions. This includes travel through unconditioned attic space.
• DO NOT COMMON VENT WITH ANY OTHER APPLIANCE.
• If venting vertically, do not vent up a chimney serving another appliance or install in a chase with a metal or
high temperature plastic pipe from another gas or fuel burning appliance unless the required clearances to
combustibles can be maintained between the furnace venting system and other pipes.
All exhaust piping must be installed in accordance with CAN/CGA-B149.in Canada; the latest edition of National Fuel Gas Code, NFPA 54 / ANSI Z223.1 in the United States, as well as in accordance with local codes.
Size the combustion air and exhaust piping in accordance with Table 4. When calculating allowable vent
W415-1080 / A / 08.28.13
21
lengths, be sure to count all termination fi ttings
in addition to counting the concentric vent as a
straight pipe.
Take the building orientation and the presence
of other buildings or other nearby structures into
consideration when planning the venting system
location. Certain external structures could create
FIGURE 8 - STANDARD (STRAIGHT) HORIZONTAL
VENT DETAIL
*3"
(76mm)
MIN.
EXHAUST
air turbulence around the vent termination leading to downdrafts and similar venting problems. In
windy and hill locations, roof venting may improve
operations. Maximum venting length is based on 30
mph (48 km) winds, areas where higher gusts are
dominant it is suggest to shorten the horizontal vent
length.
The vent and combustion air intake shall be installed so that both are located in the same wind
pressure zone.
!
WARNING
12"
(305mm)
MIN.
GRADE
*18" (457mm) MIN. FOR COLD
CLIMATES (SUSTAINED 0°F (-18°C)
FOR 24 OR MORE CONSECUTIVE
HOURS
!
INTAKE
DO NOT CONNECT FURNACE TO A CHIMNEY OR FLUE SERVING OTHER APPLIANCES OR A
SOLID FUEL BURNING APPLIANCE.
IOM
9.1 VENT TERMINATION
Horizontal vents should pass through the exterior wall. Figure 8 shows a standard horizontal vent detail. Terminate the vent approximately 8” (203 mm) or more from the wall.
Exterior vent pipe greater than 24” (610 mm) should be insulated with ½” (13 mm) insulation to prevent moisture from freezing within the pipe and accumulating.
Size the exhaust pipe as specifi ed in
Table 4 - Direct and Non-Direct Vent
Lengths. This table lists the maximum
allowable length of pipe with respect to
the number of 90° elbows used. For the
purposes of this calculation, one 90°
elbow is equivalent to two 45° elbows.
Avoid locating the terminal in locations
where dripping condensate may cause
problems such as sidewalks, patios,
above planters, near windows where
exhaust gases may cause fogging, etc.
Avoid locating the termination too close
to shrubs and other vegetation. The
condensate may stunt or kill them.
EQUIVALENTS
Short Radius Elbow = 7’ (2.13 m)
Medium Radius Elbow = 2.5’ (.76 m)
Long Radius Elbow = 5’ (1.52 m)
Vent lengths that require more than
6-90° elbows, add listed equivalents for
every elbow up to the maximum allowable vent length.
TABLE 4 - DIRECT AND NON-DIRECT VENT LENGTHS
Maximum Allowable Length Of Exhaust Or Intake. Minimum Vent Length 15 ft.
(4.6 m) or equivalent.
INPUT
K/Btu/hr
100
1203100*95908580 75 70
NOTE * Maximum allowable vent (intake and exhaust) length.
When 1½” or 3” pipe is used, exit the cabinet with 2” pipe. Reduce or increase immediately after exiting the cabinet on both intake and exhaust.
60
80
PIPE
SIZE
1½60*55504540 35 30
275*70656055 50 45
3100*95908580 75 70
250*45403530 25 20
3100*95908580 75 70
250*45403530 25 20
3100*95908580 75 70
NUMBER OF 90° ELBOWS
0123456
1. Count concentric vent
2. Use medium or long
3. One 90° elbow is
4. For direct vent, the
5. For non-direct vent,
H12.4.3
NOTES
fi tting as straight pipe.
sweep elbows where
possible.
equivalent to two 45°
elbows.
listed lengths are
allowed for each vent
(intake and exhaust).
the listed lengths are allowed for exhaust. The
intake should have a
1½” or 2” snorkel intake
fi tting. (Figure 7)
W415-1080 / B / 08.28.13
22
INTAKE
EXHAUST
GRADE
*3"
(76mm)
MIN.
12"
(305mm)
MIN.
12"
(305mm)
MIN.
*18" (457mm) MIN. FOR COLD
CLIMATES (SUSTAINED 0°F (-18°C)
FOR 24 OR MORE CONSECUTIVE
HOURS
IOM
IOM
FIGURE 9 - PERISCOPED VENT DETAIL
!
CAUTION
FIGURE 10 - VERTICAL VENTING
ROOF TERMINATION
EXHAUST
18" (457mm) MIN.
!
MOISTURE IN THE FLUE GASES CONDENSES AS IT LEAVES THE TERMINAL. THIS MOISTURE
CAN FREEZE ON EXTERIOR WALLS, ON SOFFITS, AND OTHER NEARBY OBJECTS. SOME
DISCOLORATION IS TO BE EXPECTED; HOWEVER, IMPROPER LOCATION OR INSTALLATION CAN
CAUSE STRUCTURAL OR EXTERIOR FINISH DAMAGE TO THE BUILDING.
Caulk all cracks, seams or joints within a 6 foot radius of the termination.
Do not terminate under a deck unless there is adequate clearance to prevent damage from the fl ue gases. A
termination may be located at the end of a patio deck. Piping running beneath the deck must be suitably insulated and suspended in a manner to prevent condensate from collecting and freezing.
Do not locate the terminal on the side of the building facing the prevailing winter winds.
9.2 IN CANADA
In addition to the general guidelines, in Canada, the vent exhaust shall not terminate:
• Directly above a paved sidewalk or paved driveway which is located between two single-family dwellings and
serves both dwellings;
• Less than 7 feet (2.1 m) above a paved sidewalk or paved driveway located on public property;
• Within 6 feet (1.8 m) of a mechanical air supply inlet to any building;
• Above a meter/regulator assembly within 3 feet (.91 m) horizontally of the center line of the regulator;
• Within 6 feet (1.8 m) of any service regulator vent outlet;
• Less than 12” (305 mm) above grade level or anticipated snow level;
• Within 12” (305 mm) of any door, window, or non-mechanical air supply inlet to any building;
• Within 12” (305 mm) of the combustion air inlet of any other appliance;
• Underneath a veranda, porch or deck, unless (a) the veranda, porch or deck is fully open on a minimum of
two sides beneath the fl oor, and (b) the distance between the top of the vent termination and the underside
of the veranda, porch or deck is greater than 12” (305 mm).
9.3 IN UNITED STATES
In addition to the general guidelines, in the United States, the vent exhaust shall be installed in accordance
with the following:
• The clearance from the bottom of the terminal to grade shall be 12” (305 mm).
• The vent shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard.
• The vent terminal shall be installed 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from, or 1 foot (305
mm) above any door, window, soffi t, under eave vent or gravity air inlet to the building.
• The vent terminal shall have a minimum horizontal clearance of 4 feet (1.2 m) from electric meters, gas meters, regulators and relief equipment.
W415-1080 / A / 08.28.13
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.