Continental Refrigerator C8IA41, C0EA21K Operation Manual

OPERATIONS MANUAL
easy Electronic Control
FOR REFRIGERATORS, FREEZERS AND WARMERS
IMPORTANT NOTE: Any unauthorized changes to Tech Service Parameters may damage equipment and void warranty.
SCAN this code
to download manual
1-800-523-7138
Continental Refrigerator
A Division of National Refrigeration & Air Conditioning Products, Inc.
539 Dunksferry Road Bensalem, PA 19020-5908 P 215-244-1400 F 215-244-9579
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
Page
Electronic Control Display and Button Description 4
Initial Sequence of Operation 4
Electronic Control User Level Parameters 5
How to Change the Set-Point 6
How to Initiate a Manual Defrost 7
How to Change the Defrost Interval 8
How to Turn the AUX (Anti-Condensate) Heaters ON/OFF 9
How to Calibrate the Temperature Display 10
How to Change the High and Low Temperature Alarm Set Points 11
How to Silence the Alarm Beeper 12
How to Switch the Controller OFF/ON 13
How to Lock/Unlock the Controller Keypad 14
How to Access the Tech Service Parameters 15
How to See the Evaporator Probe Temperature 16
How to Activate EZY Set Parameters/Restore Factory Settings 17
Control Troubleshooting 18
Electronic Control Error Codes 20
Probe Resistance Values 20
How to Remove the Electronic Control 21
Split Control Parameters 22
Self-Contained Control Parameters 24
Warmer Control Parameters 26
OPERATIONS MANUAL
ELECTRONIC CONTROL DISPLAY AND BUTTON DESCRIPTION
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
The control icons shown above will be illuminated when the associated function is active. If the icons are flashing, it means the function will be activated after the controller delays are finished.
The easy control has a “3” button interface.
The “AUX HTRS/UP” button is used for activation or deactivation of the auxiliary anti-condensate heaters or for increasing values.
The “SET/MUTE” button is used to lock in a new value or to silence the alarm beeper.
The “POWER/DOWN” button is used to turn the unit on/off or for decreasing values.
Press the UP and DOWN buttons simultaneously to put into a manual defrost.
INITIAL SEQUENCE OF OPERATION
1. Cabinet is plugged in.
a. Display will show “F’ and the firmware version, then will show “P” and the parameter version. b. Display will then show current cabinet temperature. c. The compressor icon and the auxiliary heater icon may flash for a period of time,
indicating normal delayed start-up. d. After the start-up delay, the compressor and evaporator fan(s) will start if the control is calling for cooling. The fans may pulse on and off when the compressor is off to conserve energy.
2. The control will cycle the compressor on and off determined by the Set-Point and Differential Temperatures. (If the Set-Point needs to be changed, please see instructions on Page 6).
a. The Set-Point is the preprogrammed temperature which shuts off the compressor. b. The Differential is the preprogrammed temperature that is added to the Set-Point
temperature that will start the compressor.
EXAMPLE: Set-Point is 36°F and the Differential is 4°F The compressor and condenser fan(s) will cycle off at 36°F and back on at 40°F.
3. The control may be preprogrammed to initiate a defrost by time interval. (If additional defrost cycles are needed or a manual defrost is required due to conditions, please see the instructions on Pages 7 & 8).
a. During defrost, the defrost icon will appear in the display and the compressor will turn
off until a preprogrammed temperature or time is reached. During this time for freezers only, evaporator fan(s) will also turn off and the defrost heater will be energized.
b. After a preprogrammed evaporator temperature or time has been reached, there may
be a short delay for both the compressor and evaporator fan(s) to restart.
c. After the defrost cycle is completed, the control will resume normal operation.
If you have any questions, please contact the Technical Service Department.
Phone: (800) 523-7138 • Email: service@continentalrefrigerator.com
4
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
ELECTRONIC CONTROL USER LEVEL PARAMETERS
User level parameters give the end user the option to customize their control.
TO ACCESS AND CHANGE USER LEVEL PARAMETERS
Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button. You now have access to the User Parameters.
Use the “UP” or “DOWN” button to go to the parameter.
Press and RELEASE the “SET” button to access the parameter settings.
Use the “UP” or “DOWN” button to change the
parameter value.
Press and HOLD the “SET” button for 5 seconds to lock in the new value.
When the display returns back to cabinet temperature, RELEASE the “SET” button.
Parameter Description
PS
/C1
dl
AL
AH
H4
Password used to access tech service parameters
Display probe offset value
Defrost interval
Low temperature alarm setting
High temperature alarm setting
Alarm beeper
Used by service personnel to access tech service parameters
Used to calibrate the temperature display
Hours between defrost. The lower the value, the more defrosts per day.
Used to set the low temperature alarm value.
Used to set the high temperature alarm value.
0: Beeper active 1: Beeper not active
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
For a more detailed description on how to access and change these parameter values, there are individual pages in this manual with detailed instructions.
OPERATIONS MANUAL
5
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO CHANGE THE SET-POINT
The set-point is the temperature at which the compressor will shut off. Please note the set-point is not the cabinet holding temperature. Please refer to Page 4 for an explanation of set-point and differential.
1. Press and HOLD the “SET” button until the current set-point begins flashing. RELEASE the “SET” button.
2. Press the “UP” or “DOWN” button to adjust to the new set-point value. Here the “UP” button was pressed to change the set-point from 36°F to 37°F.
3. Press and RELEASE the “SET” button to lock in the new set-point. The control will now resume normal operation with the new set-point.
6
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO INITIATE A MANUAL DEFROST
A one-time additional defrost may be necessary to clear accumulated ice from the evaporator coil.
1. Press and HOLD the “UP” and “DOWN” buttons simultaneously.
2. After 5 seconds, the defrost icon will illuminate.
RELEASE the defrost buttons.
Defrost will terminate when the pre programmed temperature or time duration has been reached. The manual defrost can also be manually terminated by pressing and holding the “Up” and “Down” button for 5 seconds.
OPERATIONS MANUAL
7
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO CHANGE THE DEFROST INTERVAL
This is used to increase or decrease the frequency of defrosts. If the interval is set at “8”, a defrost will occur every 8 hours. If you need more defrosts, lower this value.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press the “UP” button until “dI” appears (defrost interval). RELEASE the “UP” button.
3. Press and RELEASE the “SET” button. The current defrost interval will appear in the display.
4. Press the “UP” or “DOWN” button to adjust to the new defrost interval. Here the “DOWN” button was pressed to change the interval from every 8 hours to every 6 hours.
5. Press and HOLD the “SET” button to lock in this new value. When the display returns back to cabinet temperature, RELEASE the “SET” button.
8
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO TURN THE AUX (ANTI-CONDENSATE) HEATERS ON/OFF
Anti-condensate heaters are located around the door to eliminate condensation. In order to save energy these heaters can be turned off.
1. To see the current state of the AUX (anti-condensate) heaters, press and HOLD the AUX HTR button for 1 second. RELEASE the AUX HTR button. The display will show the current state of the heater when the button is pressed. In this case the heaters are currently ON.
2. To change the current state of the AUX Heaters, press and HOLD the AUX HTR button. The display will show the current state of heater operation. After 5 seconds, the heater will switch to the opposite state and the display will return to displaying the cabinet temperature.
RELEASE the button.
The control has a built in energy saving feature for the aux (anti-condensate heaters). When in the ON position, the “AUX” icon may not illuminate indicating the AUX heaters are not currently energized. The control will automatically energize the AUX heaters when the conditions require these heaters to be activated.
OPERATIONS MANUAL
9
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO CALIBRATE THE TEMPERATURE DISPLAY
The controller temperature display can be calibrated if required. Before attempting to calibrate the tem­perature display, check display by placing a pre-calibrated temperature sensing device in center of the refrigerated compartment and keep doors closed for at least 15 minutes. Temperature display should read same temperature as sensing device, within +/-2°F. If not, follow these instructions to calibrate.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press the “UP” button until “/C1” appears in the display. RELEASE the “UP” button.
3. Press and RELEASE the “SET” button. The current value of the offset will appear in the display. In this case, the offset is set at 0.0
4. Press the “UP” button to increase or the “DOWN” button to decrease the offset value. In this case the “UP” button was pressed to increase the offset to 1.0
5. Press and HOLD the “SET” button for 5 seconds to confirm and save the new value. When complete, the current temperature will be displayed. RELEASE the “SET” button
For example: If a sensing device in the cabinet reads 38° and control display shows 41°, follow steps above and decrease current offset value by 3 (if current offset value was 0, change to: -3.0 and save.)
10
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO CHANGE THE HIGH AND LOW TEMPERATURE ALARM SET POINTS
The controller has a high and low alarm set point. These values can be modified per the end user requirements. There is a pre programmed time delay for the alarm to activate to eliminate nuisance alarms.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press the “UP” button until “AL” (Low Alarm Setting) or “AH” (High Alarm Setting) appears in the display. RELEASE the “UP” button.
3. Press and RELEASE the “SET” button. The current alarm setting will be shown.
4. Press the “UP” or “DOWN” to get to the new alarm set-point. Release the button. In this case the “UP” button was pressed until the new set point of 55.0°F was reached.
5. Press and HOLD the “SET” button for 5 seconds to confirm and save the new value. When complete, the current temperature will be displayed. RELEASE the “SET” button.
OPERATIONS MANUAL
11
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO SILENCE THE ALARM BEEPER
When a high or low temperature alarm is activated AL (low) or AH (high) will flash in the display alternating with the current cabinet temperature. At the same time, a beeper will sound. To silence the beeper for the active alarm just press and release the “SET/MUTE” button. To silence the beeper for all future alarms follow this procedure.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press the “UP” button until “H4” appears in the display. RELEASE the “UP” button.
3. Press and RELEASE the “SET” button. “0” will appear in the display. 0: alarm beeper active.
4. Press and RELEASE the “UP” button. 1 will appear in the display. 1: alarm beeper silenced.
5. Press and HOLD the “SET” button for 5 seconds to confirm and save the new value. When complete, the current temperature will be displayed. RELEASE the “SET” button.
To turn the alarm beeper ON, follow the same instructions but change H4 from “1” back to “0”.
12
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO SWITCH THE CONTROLLER OFF/ON
IMPORTANT: The controller can be switched OFF. This just switches OFF the controller. If servicing, the appliance must be unplugged.
1. To turn OFF controller, press and HOLD the “POWER/DOWN” button. When “On” appears, hold the “POWER/DOWN” button for another 5 seconds.
2. To turn controller back ON, press and HOLD the “POWER/DOWN” button for 5 seconds. Controller will resume normal operation.
When the control is powered “OFF”, OFF will alternate in the display with the current appliance temperature.
OPERATIONS MANUAL
13
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO LOCK/UNLOCK THE CONTROLLER KEYPAD
The controller keypad can be locked to eliminate any unwanted changes to the controller functions.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press and RELEASE the “SET” button. “0” will be in the display.
3. Press the “UP” button until “22” appears. This is the password. RELEASE the “UP” button.
4. Press and RELEASE the “SET” button. “PS” will appear in the display.
5. Press the “UP” or “DOWN” button until “H2” appears. RELEASE the button.
6. Press and RELEASE the “SET” button. “1” will appear in the display.
7. Press the “UP” or “DOWN” button until “0” appears. Release the “UP” or “DOWN” button.
8. Press and HOLD the “SET” button for 5 seconds until the display returns back to cabinet temperature. The keypad will now be locked.
To unlock the keypad, follow the same instructions but change H2 from “0” back to “1”.
14
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO ACCESS THE TECH SERVICE PARAMETERS
The controller has a tech service level of parameters. Please consult with Continental’s service depart­ment before accessing these parameters. Adjusting these parameters in the field will affect the appli­ance’s performance and could void the warranty.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press and RELEASE the “SET” button. “0” will be in the display.
3. Press the “UP” button until “22” appears. This is the password. RELEASE the “UP” button.
4. Press and RELEASE the “SET” button. “PS” will appear in the display. You now have access to the tech service level parameters. Use the “UP” or “DOWN” button to navigate to the required parameter.
5. When you get to the parameter you want to change press and RELEASE the “SET” button. The current setting will be shown in the display. Use the “UP” or “DOWN” button to change the value. Press and HOLD the “SET” button for 5 seconds to confirm and save the new value. When com­plete, the current temperature will be displayed. RELEASE the “SET” button.
OPERATIONS MANUAL
15
COMPRESSOR
EVAP FAN
DEFROST
AUX HTRS
ALARM
DEFROST
2 BUTTONS
AUX HTRS (UP)
SET (MUTE)
POWER (DOWN)
HOW TO SEE THE EVAPORATOR PROBE TEMPERATURE
It may be useful for tech service personnel to see the temperature of the evaporator probe.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press and RELEASE the “SET” button. “0” will be in the display.
3. Press the “UP” button until “22” appears. This is the password. RELEASE the “UP” button.
4. Press and RELEASE the “SET” button. “PS” will appear in the display.
5. Press the “UP” or “DOWN” button until “d/” appears. RELEASE the button.
6. Press and RELEASE the “SET” button. The evaporator temperature will be in the display. After 30 seconds, the control will be back to displaying the cabinet air temperature.
16
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
HOW TO ACTIVATE EZY SET PARAMETERS/RESTORE FACTORY SETTINGS
This is used to activate other preprogrammed parameter settings.
TABLE OF PREPROGRAMMED PARAMETER SETTINGS
MEDIUM TEMP: COEA21K
SELF CONTAINED CONTROL
SET 1 RESTORE FACTORY SETTINGS RESTORE FACTORY SETTINGS
SET 2 3.4°C MEDIUM TEMP FAN PULSING -17.8°C LOW TEMP FAN PULSING
SET 3 55°F WINE REFRIG FAN PULSING -15°F LOW TEMP FAN PULSING
SET 4 38°F FAN CONSTANT 0°F FAN CONSTANT
NOTE: PULSING MEANS FANS ON FOR 1 MIN. AND OFF FOR 3 MIN. THIS CYCLE CONTINUES FOR THE WHOLE OFF CYCLE.
1. Press and HOLD the “SET” button until “PS” appears flashing in the display. RELEASE the “SET” button.
2. Press and RELEASE the “SET” button. “0” will be in the display.
3. Press the “UP” button until “22” appears. This is the password. RELEASE the “UP” button.
LOW TEMP: C8IA41
SPLIT CONTROL
4. Press and RELEASE the “SET” button. “PS” will appear in the display.
5. Press and RELEASE the “DOWN” button. “EZY” will appear in the display.
6. Press and RELEASE the “SET” button. The current EZY set will appear in the display.
7. Press the “UP” button until EZY SET required is in the display (see table above). Here “2” was chosen: this is the Celsius setting for the low and medium temperature controller.
8. Press and HOLD the “SET” button for 5 seconds. RELEASE the “SET” button. The control will now operate with the new parameter settings. In this case, the controller will now operate in degrees Celsius.
NOTE: EZY SET 1 WILL RESTORE THE ORIGINAL FACTORY SETTINGS IN ALL CONTROLLERS.
OPERATIONS MANUAL
17
CONTROL TROUBLESHOOTING
Problem Cause Checks
The compressor does not start (signalled by the compressor
LED ashing)
Compressor or Fan Icon Illuminated in Display and the Compressor or Fan is not Operating
Condensing unit running but compressor icon is not illuminated on the display.
Blank Display Split Control
Blank Display Self Contained Control
1. Compressor safety delay in progress or defrost post dripping in progress
1. Improper wiring
2. Faulty control
1. Condensing unit plugged into the wrong outlet.
2. Bad compressor relay on control.
1. No power to appliance or control
2. Connection cable not fully seated at control board or display
3. Bent pins where connection cable attaches to board or display
4. Moisture damage
5. Firmware error
1. No power to appliance or control
2. Moisture damage
3. Firmware error
1. Wait for compressor safety delays
or defrost dripping time to nish.
Parameters: c0, c1, c2, c3, and dd. The maximum delay should not exceed 3 minutes.
1. Check wiring and make sure getting voltage to the relay.
2. If the dispay icon is iluminated and getting voltage to the relay but not across the contacts, the relay is bad.
1. Check to make sure condensing unit plugged into outlet labeled for condensing unit.
2. If voltage is going across the compressor relay and the compressor icon is off, it is a bad relay.
1. Check power at outlet. Make sure power switch on control box is ON. Check power to L & N at control board.
2. Remove display and check to make sure white connectors are fully seated and correct orientation. Check display cable at control board to make sure white connectors are fully seated and correct orientation.
3. Remove display cable at display and board and check to make sure pins are not bent.
4. Check for signs of moisture damage at or behind the control board. Remove the display and check for signs of moisture damage on the display board
5. Check to see if display is blank except for compressor icon.
1. Check power at outlet. Make sure power switch on control box is ON. Check power to terminals 6 & 7 at control. Check terminal(s) that plug into control and look for burn marks or loose connections.
2. Check for signs of moisture damage on the board of the control.
3. Check to see if display is blank except for compressor icon.
18
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
CONTROL TROUBLESHOOTING (Continued)
Problem Cause Checks
1. Make sure probes are installed in proper terminals. See parameter section of manual for wiring locations. Make sure the green terminal block on the self­contained control is fully seated. Make sure there are not any loose strands of wire. Make sure screw terminals are
Error Codes: E0 - Regulation Probe Error (Black) E1 - Evaporator Probe Error (Red) E2 - Ambient Probe Error (White)
Error Codes: L0 - Low Temperature HI - High Temperature
Display High Temperature
Evaporator Coil Icing
After modifying a parameter, controller continues working with old values
1. Loose probe wire/ connections
2. Bad probe
3. Bad control
1. Cabinet temperature exceeds alarm set point for 60 minutes.
1. Something wrong with refrigeration system.
2. Door was just opened for a long duration, excessive door openings, loading warm product, missing pans in rail.
3. Set point too high
1. Something wrong with refrigeration system.
2. Insufcient defrost time
3. Parameters incorrect
1. The control has not updated the old value or the parameter setting procedure has not been ended correctly by pressing the SET button for 3 s
not clamping down on wire sheathing instead of the probe wire.
2. Ohm out probe. See Probe Resistance Value Chart. For self contained control can remove the green terminal block of probe wires from control and then take resistance values on the screw terminals. For split control, must remove probe to take resistance.
3. Remove probes from the control. With control powered, should get 5VDC between probe common and other terminal probe screws into.
1. Check alarm parameters: AL, AH, Ad.
1. Do standard refrigeration system checks.
2. Keep door closed and see if tempera­ture pulls down. NOTE: Display reads
cabinet air, not product temperature.
3. Check set point and adjust if necessary. Can also increase the display delay parameters to slow down display response. Increase the /3 parameter on the split by 1. Increase the /2 parameter on the self contained by 5.
1. Do standard refrigeration system checks.
2. Check the DI and Dt parameters. Adjust if necessary.
3. Check parameters to parameter list in this manual.
1. Temporarily disconnect and reconnect power to the control. Go back in to parameter to see if the change worked.
OPERATIONS MANUAL
19
ELECTRONIC CONTROL ERROR CODES
Alarm Code Alarm Description Notes
E0 Regulation Probe Error Located in return air stream (black)
E1 Evaporator Prope Error Located in evaporator coil (red)
E2 Ambient Probe Error Located by condensing unit (white)
LO Low Temperature Alarm Reference “AL” & “Ad” alarm parameter
HI High Temperature Alarm Reference “AH” & “Ad” alarm parameter
Note: If there is a probe error, first check connection to electronic control. Then check resistance value. See troubleshooting section of manual.
PROBE RESISTANCE VALUES
Temp. Resistance Temp. Resistance Temp. Resistance
°F °C Typ K °F °C Typ K °F °C Typ K
-15 -26 90.84 34 1 26.13 82 28 8.94
-13 -25 86.43 36 2 25.03 84 29 8.62
-11 -24 82.26 37 3 23.99 86 30 8.31
-9 -23 78.33 39 4 23.00 88 31 8.01
-8 -22 74.61 41 5 22.05 90 32 7.73
-6 -21 71.10 43 6 21.15 91 33 7.45
-4 -20 67.77 45 7 20.30 93 34 7.19
-2 -19 64.57 46 8 19.48 95 35 6.94
0 -18 61.54 48 9 18.70 97 36 6.70
1 -17 58.68 50 10 17.96 99 37 6.47
3 -16 55.97 52 11 17.24 100 38 6.28
5 -15 53.41 54 12 16.56 102 39 6.03
7 -14 50.98 55 13 15.90 104 40 5.83
9 -13 48.68 57 14 15.28 106 41 5.63
10 -12 46.50 59 15 14.69 108 42 5.44
12 -11 44.43 61 16 14.12 109 43 5.26
14 -10 42.47 63 17 13.58 111 44 5.08
16 -9 40.57 64 18 13.06 113 45 4.91
18 -8 38.77 66 19 12.56 115 46 4.75
19 -7 37.06 68 20 12.09 117 47 4.59
21 -6 35.44 70 21 11.63 118 48 4.44
23 -5 33.90 72 22 11.20 120 49 4.30
25 -4 32.44 73 23 10.78 122 50 4.16
27 -3 31.05 75 24 10.38 124 51 4.03
28 -2 29.73 77 25 10.00 126 52 3.90
30 -1 28.48 79 26 9.63 157 53 3.77
32 0 27.28 81 27 9.28 129 54 3.65
20
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
HOW TO REMOVE THE ELECTRONIC CONTROL
1. Turn off power to the unit.
2. Place tip of small flat head screw driver under plastic bezel and gently pry up on bezel to remove.
3. Use a PZ1 screw driver (#1 Phillips will also work) and turn both screws ¼ turn counter clockwise. This will rotate the plastic keeper behind the sheet metal to be able to pull out the electronic control.
Plastic Keeper. When turning screw counter clockwise, this will rotate this keeper.
When the screw is turned ¼ turn CCW, the plastic keeper will be in a position to remove the control.
4. To re-install the control, push the control back into the rectangular cutout. Turn the (2) screws clockwise to rotate the keeper back in place and secure the control. Snap back on the plastic bezel.
OPERATIONS MANUAL
21
SPLIT CONTROL PARAMETERS
1.215/.216 REV. 5/21/2019
C8IA41>-10D
UPRIGHT FRZR -10F
C8IA41>-15D
UPRIGHT FRZR -15F
C8IA41>28D
UPRIGHT FRZR 28F
C8IA41>CEL
UPRIGHT FRZR CELSIUS
C8IA41>38D
SW SOLID TOPS
C8IA41>38DOT
SW OPEN TOPS
C8IA41>28DNH
SW SOLID TOP 28F
C8IA41
UPRIGHT FRZR, SWF
Par. Description Level Unit Set Set Set Set Set Set Set Set Set Set
/2 measurement stability: lower quicker resp PW - 4 4 4 4 4 4 4 4 4 4
/3 probe display response: lower quicker resp PW - 1 1 1 1 1 1 1 1 1 1
/4 probe display select 1: box 2: evap 3: amb PW - 1 1 1 1 1 1 1 1 1 1
/5 units in °C (0) or °F (1) PW - 1 1 1 1 0 1 1 1 1 1
/6 decimal display (0) or not (1) PW - 1 1 1 1 0 1 1 1 1 1
/C1 probe 1 offset (display) User °F 2.5 2.5 2.5 1.2 1.4 1.2 0 1.2 2.5 10.0
/C2 probe 2 offset (evap) PW °F 1 1 1 1 0.6 1.2 0 1 1 1
/C3 probe 3 offset (ambient) PW °F 0 0 0 0 0 0 0 0 0 0
St set point (cutout) User °F -2 -10 -15 26 -18.9 36 36 26 -3 -2
rd differential (positive dif) PW °F 5 5 5 4 2.8 4 3 4 6 5
r1 minimum set point allowed PW °F -10 -18 -18 20 -23.3 32 32 20 -10 -10
r2 maximum set point allowed PW °F 15 15 15 40 -9.4 40 40 40 15 15
FH FH enabled PW - 1 1 1 1 1 2 2 2 1 1
FHt fascia heater threshold: temp heaters turn on PW °F 80 80 80 80 26.7 80 80 80 80 80
FHd fascia heater differential PW °F 1 1 1 1 1 1 1 1 1 1
c0 comp and fan start delay power up PW min 1 1 1 1 1 1 1 1 1 1
c1 min time between starts PW min 2 2 2 2 2 3 3 2 2 2
c2 min comp off time PW min 1 1 1 1 1 1 1 1 1 1
c3 min comp on time PW min 1 1 1 1 1 2 2 1 1 1
c4 compressor on time with duty cycle PW min 14 15 15 8 14 6 6 8 14 14
d0 type of defrost PW - 0 0 0 0 0 0 0 0 0 0
dl interval between defrosts User hr 6 8 8 8 8 6 6 8 8 8
dt end defrost temperature PW °F 50 50 50 44 10 40 44 44 50 50
dP max defrost duration PW min 30 30 30 20 30 40 40 20 30 30
d6 display during defrost (1: temp 2: DF) PW - 1 1 1 1 1 1 1 1 1 1
dd dripping time PW min 3 3 3 3 3 0 0 3 3 3
d8 alarm bypass after defrost PW hr 2 2 2 2 2 2 2 2 2 2
d/ display defrost probe (displays def temp) PW °F - - - - - - - - - -
A0 alarm and fan differential PW °F -10 -10 -10 -10 -5.6 -2 -2 -10 -10 -10
AL low temp alarm F °F -20 -20 -25 15 -28.9 30 30 15 -20 -20
AH high temp alarm F °F 40 40 40 50 4.4 50 50 50 40 40
Ad temp alarm delay PW min 60 60 60 60 60 60 60 60 60 60
A4 third input config (0: not used 13: amb probe) PW - 13 13 13 13 13 0 0 0 13 13
C8IA41>EFC
1FS, 1FSE, DL1FS, DL1FSE
C8IA41>CFA
CFA MODELS
22
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
If control number not listed here, please consult factory. Celsius Temps in °C.
C8IA41>28D
C8IA41>-10D
UPRIGHT FRZR -10F
C8IA41
UPRIGHT FRZR, SWF
Par. Description Level Unit Set Set Set Set Set Set Set Set Set Set Set
evap fan operation
F0
(0: on, 1: based on set pt. see F1)
PW - 1 1 1 1 1 0 0 1 1 1 0
F1 evap fan control set point PW °F 30 30 30 42 -1.1 40 40 42 20 30 40
stop evap fans if comp stops (0: per F0
F2
1: off w/comp 2: cyclical see F4 & F5
evap fan status during defrost
F3
(0: on 1: off)
PW - 2 2 2 2 2 2 0 2 1 2 2
PW - 1 1 1 1 1 0 0 1 1 1 0
Fd post-dripping time PW min 0 0 0 0 0 0 0 0 0 0 0
F4 fan duty on time (when F2=2) PW min 1 1 1 1 1 1 100 1 1 1 1
F5 fan duty off time (when F2=2) PW min 3 3 3 3 3 3 0 3 3 3 3
Pw password User - 22 22 22 22 22 22 22 22 22 22 22
serial address (if connecting to
H0
monitoring)
AUX output config (0: inactive 8: fac
H1
htr)
PW - 1 1 1 1 1 1 1 1 1 1 1
PW - 8 8 8 8 8 0 0 0 8 8 0
H2 key enabled PW - 1 1 1 1 1 1 1 1 1 1 1
H4 disable buzzer User - 0 0 0 0 0 0 0 0 0 0 0
H5 detect changed parameters PW - 0 0 0 0 0 0 0 0 0 0 0
H7 management of 4th relay/serial comm PW - 1 1 1 1 1 1 1 1 1 1 1
H99 parameter level PW - 66 51 52 53 54 56 63 55 58 62 59
EZY sets (1: reset 2: Celsius 3: -15F
EZY
4: fan constant
Display Interface
up to 5m
SERIAL CONV
PW - 0 0 0 0 0 0 0 0 0 0 0
PROG
KEY
UPRIGHT FRZR 28F
C8IA41>-15D
UPRIGHT FRZR -15F
C8IA41>CEL
UPRIGHT FRZR CELSIUS
C8IA41>38D
SW SOLID TOPS
C8IA41>38DOT
REGULATION PROBE: BLACK DEFROST PROBE: RED AMBIENT PROBE: WHITE
SW OPEN TOPS
C8IA41>28DNH
SW SOLID TOP 28F
C8IA41>EFC
1FS, 1FSE, DL1FS, DL1FSE
C8IA41>CFA
CFA MODELS
C8IA41>48D
SW SOLID TOP 48F
Use copper conductors only
Ambient probe not installed on: *C8IA41>38DNH *C8IA41>38DOT
Power Supply
115/230/Vac
(depending on the model)
24A max (*)
OPERATIONS MANUAL
23
SELF-CONTAINED CONTROL PARAMETERS
2.015/.016 PARAMETERS Rev. 10/29/2019
C0EA21K
LINE1 UPRIGHT REF
C0EA21K>NH
CRA SOLID TOP, BBC, KC,
CBC
C0EA21K>38DOT
CRA OPEN TOP, CPA,
GRIDDLE REF
C0EA21K>32DNH
BBC DEEP CHILL
C0EA21K>55D
LINE 1 UPRIGHT 55 DEG
C0EA21K>CEL
LINE 1 UPRIGHT REF
CELSIUS
C0EA21K>MCCW
MILK COOLER COLD WALL
Par. Description Level Unit Set Set Set Set Set Set Set Set
/2 measurement stability: lower quicker response PW - 4 5 4 4 4 4 2 4
/4 probe display selection 1: box 2: evap 3: amb PW - 1 1 1 1 1 1 1 1
/5 units in °C (0) or °F (1) PW - 1 1 1 1 1 0 1 1
/6 decimal display (0) or not (1) PW - 1 1 1 1 1 0 1 1
/C1 probe 1 offset (display) User °F 1.2 1.2 1.2 1.2 1.0 0.7 1.0 1.2
/C2 probe 2 offset (evap) PW °F 1.2 1.2 1.2 1.2 1.0 0.7 0.0 1.2
/C3 probe 3 offset (ambient) PW °F 0 0 0 0 0 0 0 0
St set point (cutout) User °F 36 36 36 25 51 2.2 38 35
rd differential (positive dif) PW °F 4 3 3 5.0 4 2.2 3 5
r1 minimum set point allowed PW °F 32 32 33 20 34 0 32 33
r2 maximum set point allowed PW °F 40 40 40 38 55 4.4 40 40
FH FH enabled PW - 1 2 2 2 1 1 2 2
FHt fascia heater threshold: 0 inactive PW °F 80 0 0 0 80 26.7 0 0
FHd fascia heater differential PW °F 1 1 1 1 1 1 1 1
Pr power User - 1 1 1 1 1 1 1 1
c0 comp and fan start delay power up PW min 1 1 1 1 1 1 1 1
c1 min time between starts PW min 3 2 2 3 3 3 3 2
c2 min comp off time PW min 1 1 1 1 1 1 1 1
c3 min comp on time PW min 2 1 1 2 2 2 2 1
c4 compressor on time with duty cycle PW min 6 6 6 8 5 6 3 6
d0 type of defrost: 1 time init., time or temp term. PW - 1 1 1 1 1 1 0 1
dl interval between defrosts User hr 6 6 6 8 6 6 0 6
dt end defrost temperature PW °F 44 44 45 50 44 6.7 37 45
dP max defrost duration PW min 40 40 40 30 40 40 60 40
d6 display during defrost (1: temp 2: DF) PW - 1 1 1 1 1 1 0 1
dd dripping time PW min 0 0 0 3 0 0 0 0
d8 alarm bypass after defrost PW hr 2 2 2 2 2 2 2 2
d/ display defrost probe (displays def temp) PW °F - - - - - - - -
C0EA21K>MC
MILK COOLER AIR
24
OPERATIONS MANUAL
easy ELECTRONIC CONTROL FOR REFRIGERATORS, FREEZERS AND WARMERS
If control number not listed here, please consult factory. Celsius Temps in °C.
C0EA21K
LINE1 UPRIGHT REF
C0EA21K>NH
CRA SOLID TOP, BBC, KC,
CBC
C0EA21K>38DOT
CRA OPEN TOP, CPA,
GRIDDLE REF
C0EA21K>32DNH
BBC DEEP CHILL
C0EA21K>55D
LINE 1 UPRIGHT 55 DEG
C0EA21K>CEL
LINE 1 UPRIGHT REF
CELSIUS
C0EA21K>MCCW
MILK COOLER COLD WALL
Par. Description Level Unit Set Set Set Set Set Set Set Set
A0 alarm and fan temp differential PW °F -2 -2 -2 -5 -2 -1.2 -2 -2
AL low temp alarm F °F 30 30 25 18 30 -1.1 30 25
AH high temp alarm F °F 50 50 50 50 65 10 50 50
Ad temp alarm delay PW min 60 60 60 60 60 60 60 60
Fd0 fan duty on time PW min 1 1 100 100 1 1 0 100
FdF fan duty off time PW min 3 3 0 0 3 3 3 0
Pw password User - 22 22 22 22 22 22 22 22
H0 serial address (if connecting to monitoring) PW - 1 1 1 1 1 1 1 1
H2 key enabled PW - 1 1 1 1 1 1 1 1
H4 disable buzzer User - 0 0 0 0 0 0 0 0
H5 detect changed parameters PW - 0 0 0 0 0 0 0 0
H99 parameter level PW - 0 10 11 3 5 4 6 13
EZY sets (1: reset 2: Celsius 3: wine
EZY
4: fan constant
PW - 0 0 0 0 0 0 0 0
C0EA21K>MC
MILK COOLER AIR
REGULATION PROBE: BLACK DEFROST PROBE: RED AMBIENT PROBE: WHITE
REG DEF AMB
C0EA21K: RELAY 5 FOR FASCIA HEATERS C0EA21K>NH: RELAY 5 NOT USED. AMBIENT (WHITE) PROBE NOT USED C0EA21K>38DOT: RELAY 5 NOT USED. AMBIENT (WHITE) PROBE NOT USED C0EA21K>32DNH: RELAY 5 FOR DEF HEATER. AMBIENT (WHITE) PROBE NOT USED C0EA21K>CEL: RELAY 5 FOR FASCIA HEATERS C0EA21K>MCCW: RELAY 5 NOT USED. RELAY 2 NOT USED. AMBIENT (WHITE) NOT USED. DEF (RED) NOT USED. COEA21K>MC: RELAY 5 NOT USED. AMBIENT (WHITE) NOT USED.
OPERATIONS MANUAL
25
WARMER CONTROL PARAMETERS
If control number is not listed here, please consult factory.
Par. Description Level Unit Set
/2 Measurement Stability: Lower quicker response PW - 2
/5 Units in °C (0) or °F (1) PW - 1
/6 decimal display (0) or not (1) PW - 1
/C1 probe 1 offset (display) User °F 4.0
St set point (cutout) User °F 182
rd differential (negative dif) PW °F 2
r1 minimum set point allowed PW °F 90
r2 maximum set point allowed PW °F 195
c1 min time between starts PW min 0
c2 min heater off time PW min 0
c3 min heater on time PW min 0
c4 heater on time with duty cycle PW min 9
A0 alarm and fan temp differential PW °F -2
AL low temp alarm F °F 60
AH high temp alarm F °F 220
Ad temp alarm delay PW min 60
Pw password User - 22
H0 serial address (if connecting to monitoring) PW - 1
H2 keypad enabled PW - 1
H4 disable buzzer User - 0
H5 detect changed parameters PW - 1
EZY EZY Sets (1: Reset, 2: Celsius) PW - 0
S2L000>W (220V)
S2L100>W (115V)
26
WARMER
OPERATIONS MANUAL
A Division of National Refrigeration & Air Conditioning Products, Inc.
539 Dunksferry Road • Bensalem, PA 19020-5908 Phone: 215-244-1400 • Toll Free: 800-523-7138
IM-EC-50154-20191120
Loading...