Continental Hydraulics CEM-PA-B Installation Manual

Continental Hydraulics Installation Manual
CEM-PA-B
Product Description:
This closed loop PID amplifier, drives a single solenoid proportional pressure or flow control valve coil up to 2.6A. It is suitable to provide precise closed loop control in pressure, force, or velocity systems. This module uses traditional PID error correction to provide stable control in dynamic systems.
A wide range of analog signals are accepted. User may select either voltage or current input mode. These inputs are easily scaled to match system requirements. Input command can be ramped. PID variables are adjustable over a wide range. The Amplifier is easily switched from open loop to closed loop control.
Min and Max output current are adjustable. Output characteristics can be independently customized. The module is disabled if the coil outputs are shorted or open. If command current signal is outside of the proper range, the module is disabled. PWM and Dither are user adjustable.
This module is easily adapted to a variety of system requirements. All variables are user adjusted with easy to use software on your Microsoft Windows laptop. Control variables are stored in non-volatile memory internal to the module. All variables can be read by the laptop, and reproduced exactly on other modules.
Page 1 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Table of Contents
Information Description Page #
Technical Data ………………………………………………………………….. 3 Steps to install and configure a new application ……………………………. 4-5 Module Mounting Location …………………………………………………….. 5 Power Supply …………………………………………………………………… 5 Wiring to Valve ………………………………………………………………….. 5 Circuit Diagram …………………………………………………………………. 6 LED Definitions …………………………………………………………………. 7 Terminal Identification ………………………………………………………….. 7 Parameter List …………………………………………………………………… 8
Command Parameter Descriptions
LG (Language) ………………………………………………………….. 9  MODE ……………………………………………………………………. 9  SENS …………………………………………………………………….. 9  EOUT …………………………………………………………………….. 10  SYS_RANGE ……………………………………………………………. 10  SIGNAL:X / SIGNAL:W ………………………………………………… 10  AINMODE (Signal Scaling mode)……………………………………… 11-12  N_RANGE:X …………………………………………………………….. 13  OFFSET:X ……………………………………………………………….. 13  RA:UP / RA:DOWN (Ramp times) …………………………………….. 14  C:P, C:I, C:D, C:D_TI, C:D_FF ………………………………………… 15  C:I_LIM / C:I_ACT ………………………………………………………. 16  MIN ………………………………………………………………………... 17  MAX ………………………………………………………………………. 17  TRIGGER ………………………………………………………………… 17  SIGNAL:U ………………………………………………………………… 18  CURRENT ……………………………………………………………….. 18  DFREQ / DAMPL ………………………………………………………... 18  PWM ……………………………………………………………………… 19  ACC ………………………………………………………………………. 19  PPWM / IPWM …………………………………………………………… 20
Process Data (Monitoring) ……………………………………………………… 20 Failure Monitoring ……………………………………………………………….. 21 Troubleshooting …………………………………………………………………. 22-24
Page 2 of 24 CEM-PA-B CHI 1020688 01/2016
Technical data
Supply voltage [VDC] 12… 30 (incl. ripple)
Current requirement [mA] 60 + solenoid current
External protection [A] 3 medium time lag
Reference voltage [V] 8 (max. 25 mA load)
Digital inputs [V] logic 0: < 2
[V] logic 1: > 10
Input resistance [kOhm] 25
[V] logic 0: < 2
[V] logic 1: > 12 (50 mA)
Analogue inputs:
Command value [V] 0… 10; 150 kOhm
[mA] 4… 20; 390 Ohm
Signal resolution [%] 0.006 incl. Oversampling
Sensor value [V] 0… 10; 90 kOhm
[mA] 4… 20; 390 Ohm
Signal resolution [%] 0.006 incl. Oversampling
PWM output [A]
0.5, to 2.6 Amp; broken wire and short circuit monitored
PWM frequency [Hz] 61… 2604
Sample time (pressure control) [ms] 1
Sample time (solenoid current control)
[ms] 0.125
USB type B
Virtual COM port driver (CHI-PC):
9600… 57600 Baud (Default = 57600),
1 Stop bit, No parity, No handshake
Snap-on module to EN 50022
PA 6.6 polyamide
Flammability class V0 (UL94)
Weight [kg] 0,190
Protection class IP20
Temperature range [°C] -20… 60
Storage temperature [°C] -20… 70
Humidity [%] < 95 (non-condensing)
USB Typ B
4 x 4-pole terminal blocks
PE: via the DIN mounting rail
EN 61000-6-2: 8/2005
EN 61000-6-4: 6/2007 + A1:2011
EMC
Digital outputs
Serial interface Housing
Connections
Continental Hydraulics Installation Manual
Page 3 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Steps to install and configure a new application:
All parameters are adjusted using VEA-BUSB-A programming cable and CHI-PC Microsoft Windows application.
1. Mount the module in suitable location. See page 5.
2. Connect the power supply, valve connections and enable.
3. Download and open the GUI program (www.continentalhydraulics.com/wp-
content/uploads/2015/01/setup-CEWMPC-10-v3.5.0.zip)
4. Connect to laptop via USB to USB Type B communication cable.
5. Select com port in upper left hand corner of the GUI program.
6. Open the Options Tab and verify that the correct com port, full Duplex and 57.6K Baud rates are selected.
7. Connect with the CEM by selecting the connect button.
8. Click on the ID Button.
9. Adjust CURRENT parameter to match the nominal solenoid current.
10. Adjust dither amplitude, DAMPL, and dither frequency, DFREQ, to optimize performance of valve.
11. Set the SIGNAL type to voltage (0-10V) or current (4-20ma). See ANIMODE if the signals are other than standard. Some scaling may be required.
12. Set the MIN, MAX, and TRIGGER, for the desired system output.
13. Adjust the SYS_RANGE to the pressure output of the valve at rated current. For example, the Continental model VER03M-210-A-K1-24D is rated for 210 bar. Set the SYS_RANGE X to 210. The units on this parameter is bar.
Page 4 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
14. Set the N_RANGE:X to the maximum pressure rating of the pressure sensor. For a 0­210 bar pressure transducer, set N_RANGE:X to 210 bar. This setting should be the same or greater than the SYS_RANGE value.
15. Use the OFFSET:X to compensate for the pressure transducer reading at actual 0bar pressure.
16. Adjust RAMP as required.
17. Set internal monitor function, SENS, as required.
18. Adjust PID error correction parameters, (C:P, C:I, C:D, C:D_TI, C:FF), to tune the system performance.
Module Mounting Location:
This module is to be mounted in a cabinet for protection from the local environment. Ensure there is adequate free space around the module to allow for cooling air flow. This module is designed to snap onto an industry standard 35mm DIN rail. Do not mount near other modules that emit high power electrical interference, such as motor controllers and high power contactors.
Power Supply:
This module is designed to operate on DC power from a regulated power supply ranging from 12 to 30 volts. Match valve solenoid voltage rating to power supply, typically 12 or 24 volts. A 3 amp medium action fuse is recommended in the “+” power supply line.
Wiring to Valve:
Two conductors are required for each solenoid. There is no need for shielding on these power conductors. Wire size is chosen to provide an acceptable voltage drop between the module and the valve solenoid. The following chart is based on 5% drop for 12v and 24v applications. The listed cable length is distance from module to valve, and includes the voltage drop of the return conductor.
Wire size 2.6A 12v 1.6A 24v 0.86A 24v 12 gauge 66 ft. max 215 ft. max 400 ft. max 14 gauge 49 ft. max 159 ft. max 295 ft. max 16 gauge 31 ft. max 100 ft. max 186 ft. max 18 gauge 19 ft. max 63 ft. max 117 ft. max 20 gauge 13 ft. max 39 ft. max 73 ft. max 22 gauge 8 ft. max 25 ft. max 46 ft. max
All analog input signal cables must be shielded!
Good analog system design requires that all analog signals in an electrically noisy environment be shielded. Long wires act like antennas that pick up analog noise. The wire connecting the analog command source to command this module must be shielded! Shielding a noise sensitive wire is accomplished by wrapping a noise blocking foil or braided shield around the signal wire. This shield must be grounded at only one end, usually the end that sends the signal. A control cable may have many individual conductors. The conductors may be shielded individually, or may be shielded as a group. Short signal wires in electrically quiet environments may not need to be shielded. The CEM family of modules all have an internal ground connection to the DIN rail. For this module ground to be effective, please insure the DIN rail is properly grounded.
Page 5 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Circuit Diagram
Page 6 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
LED Definitions
LEDs Description of the LED function
Identical to the READY output.
OFF: No power supply or ENABLE is not activated
ON: System is ready for peration
Flashing: Error discovered
Only active when SENS = ON
YELLOW A
Intensity of the solenoid current
1. Chasing light (over all LEDs): The bootloader is active. No normal functions are possible.
2. All LEDs flash shortly every 6 s: An internal data error was detected and corrected automatically! The module still works regularly. To acknowledge the error the module has to be cycle powered.
YELLOW A + YELLOW B
Both yellow LEDs flash oppositely every 1 s: The nonvolatile stored parameters are inconsistent! To acknowledge the error, data has to be saved with the SAVE command or the corresponding button in the CHI-PC.
GREEN
GREEN + YELLOW A
Terminal Identification - Input and output signals
Connection Supply
PIN 7 Power supply (see technical data)
PIN 8 0 V (GND) connection.
Connection Analogue signals
PIN 9 / 10
Pressure com m and value (WA), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL W)
PIN 13 /14
Pressure feedback value (X), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL X)
PIN 11 0 V (GND) connection for analogue signals
PIN 12 8V reference voltage output
PIN 3 / 4 PWM output to the solenoid
Connection Digital inputs and outputs
Enable input:
Generally enabling of the application.
RUN (Start) Input:
ON: The controller is active.
OFF: The controller is not active.
READY output:
ON: The module is enabled; there are no discernable errors.
OFF: ENABLE (PIN 15) is not active or an error has been detected.
PIN 15
PIN 6
PIN 5
Page 7 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
CEM-PA-B Function Parameter layout
Ref Page Command Parameter Help / Description STD EXP
9 LG EN EN English X X 9 MODE EXP Standard / Expert mode X X
9 SENS AUTO Malfunction monitoring [ON / OFF /AUTO] X X 10 EOUT 0 Output signal if not ready [0.01%] X 10 SYS_RANGE 100 System pressure [bar] X X 10 SIGNAL:X U0-10 Type of Input X X 13 N_RANGE:X 100 Sensor nominal pressure [bar] X X 13 OFFSET:X 0 Sensor offset [mbar] X X 10 SIGNAL:W U0-10 Type of Input X X 14 RA:UP 100 Command signal ramp time [ms] X X 14 RA:DOWN 100 Command signal ramp time [ms] X X 15 C:P 50 P gain [x 0.01] x X 15 C:I 4000 I gain [0.01ms] X X 15 C:D 0 D gain [0.1ms] X X 15 C:D_T1 500 D gain filter [0.1ms] x X 15 C:FF 8000 Feed forward [0.01%] X X 16 C:I_LIM 2500 Integrator limitation [0.01%] X X 16 C:I_ACT 2500 Integrator activation threshold [0.01%] X X 17 MIN 0 Deadband compensation [0.01%] X X 17 MAX 10000 Output Scaling [0.01%] X X 17 TRIGGER 200 Trigger point of the MIN function in 0.01% X X 18 SIGNAL:U + Output polarity X X 18 CURRENT 1000 Rated solenoid current [mA] X X 18 DFREQ 121 Dither frequency [Hz] X X 18 DAMPL 500 Dither amplitude [0.01%] X X 19 PWM 2604 PWM frequency [Hz] X X 19 ACC ON Auto Adjustment of the current loop [OFF / ON] X 20 PPWM 7 P-Gain of the current loop X 20 IPWM 40 I-Gain of the current loop X
MODE
Page 8 of 24 CEM-PA-B CHI 1020688 01/2016
Loading...
+ 16 hidden pages