This closed loop PID amplifier, drives a single solenoid proportional pressure or flow
control valve coil up to 2.6A. It is suitable to provide precise closed loop control in
pressure, force, or velocity systems. This module uses traditional PID error correction to
provide stable control in dynamic systems.
A wide range of analog signals are accepted. User may select either voltage or current
input mode. These inputs are easily scaled to match system requirements. Input
command can be ramped. PID variables are adjustable over a wide range. The
Amplifier is easily switched from open loop to closed loop control.
Min and Max output current are adjustable. Output characteristics can be independently
customized. The module is disabled if the coil outputs are shorted or open. If command
current signal is outside of the proper range, the module is disabled. PWM and Dither
are user adjustable.
This module is easily adapted to a variety of system requirements. All variables are user
adjusted with easy to use software on your Microsoft Windows laptop. Control variables
are stored in non-volatile memory internal to the module. All variables can be read by
the laptop, and reproduced exactly on other modules.
Page 1 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Table of Contents
Information Description Page #
Technical Data ………………………………………………………………….. 3
Steps to install and configure a new application ……………………………. 4-5
Module Mounting Location …………………………………………………….. 5
Power Supply …………………………………………………………………… 5 Wiring to Valve ………………………………………………………………….. 5
Circuit Diagram …………………………………………………………………. 6
LED Definitions …………………………………………………………………. 7
Terminal Identification ………………………………………………………….. 7
Parameter List …………………………………………………………………… 8
4. Connect to laptop via USB to USB Type B communication cable.
5. Select com port in upper left hand corner of the GUI program.
6. Open the Options Tab and verify that the correct com port, full Duplex and 57.6K Baud
rates are selected.
7. Connect with the CEM by selecting the connect button.
8. Click on the ID Button.
9. Adjust CURRENT parameter to match the nominal solenoid current.
10. Adjust dither amplitude, DAMPL, and dither frequency, DFREQ, to optimize performance
of valve.
11. Set the SIGNAL type to voltage (0-10V) or current (4-20ma). See ANIMODE if the
signals are other than standard. Some scaling may be required.
12. Set the MIN, MAX, and TRIGGER, for the desired system output.
13. Adjust the SYS_RANGE to the pressure output of the valve at rated current. For
example, the Continental model VER03M-210-A-K1-24D is rated for 210 bar. Set the
SYS_RANGE X to 210. The units on this parameter is bar.
Page 4 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
14. Set the N_RANGE:X to the maximum pressure rating of the pressure sensor. For a 0210 bar pressure transducer, set N_RANGE:X to 210 bar. This setting should be the
same or greater than the SYS_RANGE value.
15. Use the OFFSET:X to compensate for the pressure transducer reading at actual 0bar
pressure.
16. Adjust RAMP as required.
17. Set internal monitor function, SENS, as required.
18. Adjust PID error correction parameters, (C:P, C:I, C:D, C:D_TI, C:FF), to tune the
system performance.
Module Mounting Location:
This module is to be mounted in a cabinet for protection from the local environment.
Ensure there is adequate free space around the module to allow for cooling air flow.
This module is designed to snap onto an industry standard 35mm DIN rail.
Do not mount near other modules that emit high power electrical interference, such as
motor controllers and high power contactors.
Power Supply:
This module is designed to operate on DC power from a regulated power supply ranging
from 12 to 30 volts. Match valve solenoid voltage rating to power supply, typically 12 or
24 volts. A 3 amp medium action fuse is recommended in the “+” power supply line.
Wiring to Valve:
Two conductors are required for each solenoid. There is no need for shielding on these
power conductors.
Wire size is chosen to provide an acceptable voltage drop between the module and the
valve solenoid. The following chart is based on 5% drop for 12v and 24v applications.
The listed cable length is distance from module to valve, and includes the voltage drop
of the return conductor.
Wire size 2.6A 12v 1.6A 24v 0.86A 24v
12 gauge 66 ft. max 215 ft. max 400 ft. max
14 gauge 49 ft. max 159 ft. max 295 ft. max
16 gauge 31 ft. max 100 ft. max 186 ft. max
18 gauge 19 ft. max 63 ft. max 117 ft. max
20 gauge 13 ft. max 39 ft. max 73 ft. max
22 gauge 8 ft. max 25 ft. max 46 ft. max
All analog input signal cables must be shielded!
Good analog system design requires that all analog signals in an electrically noisy
environment be shielded. Long wires act like antennas that pick up analog noise. The
wire connecting the analog command source to command this module must be shielded!
Shielding a noise sensitive wire is accomplished by wrapping a noise blocking foil or
braided shield around the signal wire. This shield must be grounded at only one end,
usually the end that sends the signal. A control cable may have many individual
conductors. The conductors may be shielded individually, or may be shielded as a
group. Short signal wires in electrically quiet environments may not need to be shielded.
The CEM family of modules all have an internal ground connection to the DIN rail. For
this module ground to be effective, please insure the DIN rail is properly grounded.
Page 5 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
Circuit Diagram
Page 6 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
LED Definitions
LEDsDescription of the LED function
Identical to the READY output.
OFF: No power supply or ENABLE is not activated
ON: System is ready for peration
Flashing: Error discovered
Only active when SENS = ON
YELLOW A
Intensity of the solenoid current
1. Chasing light (over all LEDs): The bootloader is active. No
normal functions are possible.
2. All LEDs flash shortly every 6 s: An internal data error was
detected and corrected automatically! The module still works
regularly. To acknowledge the error the module has to be cycle
powered.
YELLOW A +
YELLOW B
Both yellow LEDs flash oppositely every 1 s: The nonvolatile stored
parameters are inconsistent! To acknowledge the error, data has to
be saved with the SAVE command or the corresponding button in the
CHI-PC.
GREEN
GREEN + YELLOW A
Terminal Identification - Input and output signals
Connection Supply
PIN 7Power supply (see technical data)
PIN 80 V (GND) connection.
ConnectionAnalogue signals
PIN 9 / 10
Pressure com m and value (WA), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL W)
PIN 13 /14
Pressure feedback value (X), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL X)
PIN 110 V (GND) connection for analogue signals
PIN 128V reference voltage output
PIN 3 / 4PWM output to the solenoid
ConnectionDigital inputs and outputs
Enable input:
Generally enabling of the application.
RUN (Start) Input:
ON: The controller is active.
OFF: The controller is not active.
READY output:
ON: The module is enabled; there are no discernable errors.
OFF: ENABLE (PIN 15) is not active or an error has been detected.
PIN 15
PIN 6
PIN 5
Page 7 of 24 CEM-PA-B CHI 1020688 01/2016
Continental Hydraulics Installation Manual
CEM-PA-B Function Parameter layout
Ref Page Command Parameter Help / Description STDEXP
9LGEN EN EnglishXX
9MODEEXP Standard / Expert modeXX
9SENSAUTO Malfunction monitoring [ON / OFF /AUTO]XX
10EOUT0 Output signal if not ready [0.01%]X
10SYS_RANGE100 System pressure [bar]XX
10SIGNAL:XU0-10 Type of InputXX
13N_RANGE:X100 Sensor nominal pressure [bar]XX
13OFFSET:X0 Sensor offset [mbar]XX
10SIGNAL:WU0-10 Type of InputXX
14RA:UP100 Command signal ramp time [ms]XX
14RA:DOWN100 Command signal ramp time [ms]XX
15C:P50 P gain [x 0.01]xX
15C:I4000 I gain [0.01ms]XX
15C:D0 D gain [0.1ms]XX
15C:D_T1500 D gain filter [0.1ms]xX
15C:FF8000 Feed forward [0.01%]XX
16C:I_LIM2500 Integrator limitation [0.01%]XX
16C:I_ACT2500 Integrator activation threshold [0.01%]XX
17MIN0 Deadband compensation [0.01%]XX
17MAX10000 Output Scaling [0.01%]XX
17TRIGGER200 Trigger point of the MIN function in 0.01%XX
18SIGNAL:U + Output polarityXX
18CURRENT1000 Rated solenoid current [mA]XX
18DFREQ121 Dither frequency [Hz]XX
18DAMPL500 Dither amplitude [0.01%]XX
19PWM2604 PWM frequency [Hz]XX
19ACCON Auto Adjustment of the current loop [OFF / ON]X
20PPWM7 P-Gain of the current loopX
20IPWM40 I-Gain of the current loopX
MODE
Page 8 of 24 CEM-PA-B CHI 1020688 01/2016
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.