Continental USAC-40, CAD-20, USA-20, CDX-20, USAC-8 User Manual

...
Technical Guide Form UTG-0204
Continental Chillers LLC
Phone: 317-337-9813 Fax: 317-337-9816
www.continentalchillers.com
UniPac
Air Cooled Chillers
Water Cooled Chillers
Split System Chillers
3 through 60 HP
Shown, model USAC-8
Packaged Air Cooled Chiller with
Factory Mounted Chiller Pump
Typical Scroll
Compressor
Continental Single Phase Chillers
Introducing UniPac™ Chiller Systems
All over the world, Continental has successfully developed and marketed various packaged and split chillers to serve many needs. For several years discerning Engineers, Contractors, and Owners have expressed a desire to specify, install and own Unique Single Phase quality chillers in sizes ranging from 3 to 60 HP.
This need is being fulfilled by Continental’s line of UniPac™ Chillers.
To order Packaged Air Cooled Chiller:
Use model USAC
To order Packaged Water Cooled Chiller:
Use model USWC
*For 4, 8, 12 Ton Ratings, Contact Factory Ordering Examples: 40 ton packaged Single Phase Air Cooled Chiller, model USAC-40
Packaged Air Cooled and
Water Cooled Systems
To order Split (A)
Compressor, Chiller, Control Panel – model USC with matching Outdoor Air Cooled Condenser – model CAD To order Split (B)
Compressor/Condenser (Condensing Unit) Outdoor – model USA with matching Indoor Chiller – model CDX
UNIPAC™ NOMENCLATURE
Packaged Air Cooled and Water Cooled Chiller Systems
U S AC or WC – X
U Unique S Scroll
AC Condenser – Air Cooled
WC Condenser – Water Cooled
X
30 ton packaged Single Phase Water Cooled Chiller, model USWC-30 20 ton split Single Phase Air Cooled Chiller, option A, models USC-20 (indoor compressor/chiller) and CAD-20 (outdoor A/C condenser) 20 ton split Single Phase Air Cooled Chiller, option B, models USA-20 (outdoor condensing unit) and CDX-20 (indoor chiller)
3, 4*, 5, 8*,10,12*,15, 20, 25, 30, 40, 50, 60
Nominal Horse Power -
2
UniPac™
UniPac™ chillers have a full compliment of factory installed and wired optional accessories. These accessories can save several hundreds of dollars in field labor and material, resulting in cost effective installation.
Packaged UniPac™ chillers are factory tested and shipped with a vapor charge of R-22.
Split UniPac™ chillers are “dry run” tested for functional tests and shipped with dry air or nitrogen for field piping evacuating and refrigerant charging.
Split Air Cooled Systems
Phone: 317-337-9813 www.continentalchillers.com
Fax: 317-337-9816
Continental Single Phase Chillers
UniPac™
Standard Unit Specifications of UniPac™ Single Phase Chillers
General Description
Continental’s Single Phase Air and Water Cooled Chillers
are packaged systems complete with scroll compressor(s), air cooled or water cooled condenser(s), individual cooler/evaporator(s), independent refrigerant circuit(s) and a control center all mounted on a heavy duty structural steel frame.
Scroll Compressor(s)
Compressors are well proven state-of-the-art scrolls with fewer moving parts, less rotating mass, and less internal friction than traditional reciprocating compressors.
Motor is suction gas-cooled, hermetically sealed, two pole, squirrel cage induction type and is directly driven at 3600 rpm.
All compressor(s) are mounted on resilient pads to minimize vibration.
Air Cooled Condenser for Air Cooled Models
Condenser Coil-industrial quality, seamless copper tube Fins-all aluminum, die formed with full self–spacing collars that
completely cover the copper tube; fins are mechanically bonded to the copper tubes Propeller Fans-large surface, low speed, low sound level propeller fans for vertical airflow; fans are statically and dynamically balanced and operate at low tip speeds for low vibration and sound levels
Fan Guards- PVC coated for long life Fan Venturi- high collar fully spun venturi design for high efficiency
and low outlet noise Fan Motors-special “enclosed air over” motor design with built-in overload protection; single phase motors operate at a low speed of 1075 rpm
Water Cooled Condenser for Water Cooled Models
Each water cooled condenser is of shell/coil design. The condenser water flows through special heat transfer copper tube. Refrigerant flows through the steel shell and a built in receiver.
Cooler/Evaporator for All Models
Each cooler/evaporator is of shell/coil design. The water to be chilled flows through special heat transfer copper tube. Refrigerant flows through the steel shell/receiver.
Refrigerant Piping
Each Refrigerant circuit includes:
Liquid line with charging connection
Filter drier
Liquid solenoid valve with 115 V coil (220 V or 24 V, optional)
Sight glass/ moisture indicator
Suction line fully insulated, designed for proper oil return at
minimum friction loss
Discharge line formed of clean ACR type tubing and pre-formed radius fitting
Control Center
All power, starting, safety and operating controls are mounted in
a built in fully enclosed, weather proof control panel for air cooled models and NEMA-1 enclosures for indoor water cooled or condenserless models.
Power controls include:
Single point electrical terminal block for 230/1/60 power input
Compressor-motor contactor(s)
Compressor run capacitor(s)
Fan motor contactor(s) (air cooled units only)
Control circuit fuse
Control circuit terminal block
Safety/Operating controls include:
Two position switch indicating off/system on – per circuit
High Pressure control with manual reset –per circuit
Low pressure control with auto reset – per circuit
Adjustable chilled water temperature controller
Adjustable freezestat
Adjustable compressor anti-recycle timer(s)
Relay(s)
Built-in compressor-motor overload
Testing, Evacuation and Refrigerant Charging
Each completed system is pressure tested with nitrogen,
evacuated with a high capacity vacuum pump, vapor charged with R-22 and fully tested for all operating and safety controls. Field charge of R-22 required.
Split chiller systems are “dry run” tested for operating and
safety controls.
Assembly
All above components are assembled on a heavy-duty
structural steel frame, formed of channels and angles as a rugged pre-engineered package. Each steel frame has mounting holes and “lifting eyes” on four sides for “spreader bar” lifting and rigging.
The cabinet of air cooled units is made of heavy gauge
galvanized steel.
3
Phone: 317-337-9813 www.continentalchillers.com
Fax: 317-337-9816
Continental Single Phase Chillers
UniPac™ Options and Selection Procedures
UniPac™
1. Control Transformer - For applications where a separate 115-volt power
source is not available, a transformer can be installed and wired between the line voltage power terminal block and the 115-volt control circuit. Transformer primary fuses are included.
2. Factory mounted and wired flow switch - This accessory is mandatory for
Continental warranty to be effective. Provides protection from chiller freezing due to “no flow” through chiller-evaporator.
3. Factory Mounted and Wired Chiller Water Pump/Valve - Includes chilled
water circulating pump, pump starter, and isolation valve. Provides system pump for chilled water circulation- saves field labor and material. This pump is interlocked with the flow switch and “phased in” at the factory for proper rotation.
4. Non-fused Disconnect - Factory mounted non-fused disconnect sized for
model and voltage. This saves field labor and material.
5. Low Evaporator Pressure Freezestat - Senses low evaporator pressure and
shuts down system after sixty second time delay. Extra safety protection against low pressure due to gas shortage or freeze conditions.
6. Pressure Gauges - Two-inch diameter gauges are factory installed and piped
to compressor. High and low pressure for each refrigerant circuit.
7. Indicator Lights - Three indicating lights show Power On, High Pressure Fail,
and No Flow/Freeze for each refrigerant circuit.
8. Vibration Isolators - Level adjusting spring type for one-inch deflection for
field mounting-reduces vibration transmission.
9. Low Ambient Controls - Standard units have fan cycling and are good for
45°F ambient. a) For Low Ambient of 0°F. Includes a modulating solid state fan speed controller and a single phase condenser motor(s) as well as fan cycling. b) For Low Ambient of –20°F. Includes head pressure control valve in conjunction with oversized heated and insulated receiver(s) and fan cycling. Receiver includes pressure relief valve.
10. Micro-Processor Controller
11. Water Regulating Valve - Provides head pressure control for water cooled
models USWC.
12. 90/10 Cu-Ni Condenser - For water cooled models, USWC.
13. Blygold or Heresite Coated Condenser - Coil is coated with Blygold or
Heresite for protection against elements. Minimal effect on heat transfer.
14. Copper Tube/Copper Fin Condenser Coil - Seamless copper tube with die
formed copper fins, mechanically bonded to the tube. Provides maximum protection from salt-water environment due to the elimination of dissimilar metals.
15. Complete Unit Coating - Your choice of paint, Blygold, Imron, polyester or
Heresite coating for compete unit.
16. Stainless Steel Hardware - For extra protection against corrosion.
17. Low Speed Condenser Fan Motors - For lower noise levels
18. Centrifugal Condenser Fans - For ducted applications
19. Acoustical Enclosure - Compressor is located in an acoustical enclosure
providing dampening of sound levels.
20. Dual Unit Kit - Allows operation of two or more units
21. Alarm Bell Contacts - Allows alarm bell connection to pressure controls for
signaling if unit fails on manual reset safety controls. (alarm bell is not included but can be provided)
22. Water Flange Kit - Factory or field mounted consists of 150lb raised face
flanges to convert male pipe thread to flanged cooler connections.
23. High Return Water Thermostat - Factory mounted thermostat senses high
return water temperature at start-up. Allows unit to run un-loaded instead of shutting down due to high head pressure
24. Brine Chilling - Modified cooler and controls for various
brines/glycols/alcohols.
25. High entering Water Process Cooling - Secondary plate heat exchanger
with pump, factory mounted and wired to protect compressor against burnouts due to high water temperatures.
26. Potable/Ingredient Water at 34°F - For bakeries/produce or other
applications.
27. Cooler Heater with Thermostat - For freeze protection.
28. Desuperheaters - Provides “free hot water” by recovering heat from super
heated gas.
29. Compressor Circuit Breaker - Both fused and non-fused short circuit
protection for each compressor, further reducing chance of motor burnout.
30. Digital Temperature Readout
31. Compressor Cycle Counter/Hour Meters
32. Non-Ozone Depleting, Environmentally-Friendly Refrigerant
Ratings and Selection Procedures
1. Ratings: are in accordance with ARI standard for chillers. These ratings
may be interpolated for any published chilled water temperatures between 40°F and 50°F but must not be extrapolated.
2. Chilled Water Flow: based on 2.4 GPM per Ton and 10°F chilled water
range. Limit 6°F minimum to 14°F maximum.
3. Cooler Fouling Factor: 0.00025 fouling is standard
For 0.0005 fouling capacity correction factor = 0.982 x TR, 0.994 x kW For 0.00075 fouling capacity correction factor = 0.964 x TR, 0.989 x kW
4. Water cooled condenser fouling factor : ratings are based on 0.00025 for
condenser. For 0.00075 Condenser tons x 0.97 –kW x 1.045
5. Copper Fin Ratings: TR x 1.01 – kW x 0.99
6. Ethylene Glycol Correction Factors: Following factors are to be applied
to the standard ratings for ethylene glycol. For other glycols consult factory.
% Wt.
Ethylene
Glycol
10 .995 1.000 1.02 24.1 26 20 .990 0.995 1.05 24.8 16 30 .980 .990 1.10 26.0 5 40 .975 0.985 1.13 27.3 -10 50 .960 0.980 1.18 29.0 -32
Tons kW
Correction Factors
VP
GPM/
°F /Ton
Freeze
Point
(°F)
Phone: 317-337-9813 www.continentalchillers.com
Fax: 317-337-9816
Altitude: Ratings are based on altitude of sea level. For other ratings use the following correction factors
Alt. Above
Sea Level
Sea Level 1.0 4000 .971
1000 1.0 5000 .962 2000 .995 6000 .951 3000 .980 7000 .949
Capacity
Multiplier
Alt. Above
Sea Level
Capacity
Multiplier
7. For ratings outside this catalog range consult Continental for assistance
Tel:(317)337-9813 Fax:(317)337-9816 E-mail: sales@continentalchillers.com
Selection Procedures
All units are rated in accordance with ARI Standard and cover a wide range of leaving chilled water temperatures and ambients from 85°F to 120°F. To select any chiller it is necessary to know:
1. Capacity: ______ Tons
2. Entering and leaving chilled water temperature: ______ °F
3. Water Flow: ______ GPM
4. Design ambient temperature: ______ °F or
5. Entering/leaving cond. water temperature, for water cooled units: ______ °F
Knowing any two of items 1,2 or 3, the third can be calculated as follows: GPM = Tons x 24 Temp. Rise(Vt)
4