Continental CDIZC - P, CDIZC - N User Manual

Page 1
INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS
GAS-FIRED DIRECT VENT INSERT
1
INSTALLATION AND OPERATION INSTRUCTIONS FOR:
VENTED GAS FIREPLACE HEATER
PROP ANE GAS MODELS CDIZC - P
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS
CDIZC - N
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
R-2000
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.continentalfireplaces.com • ask@continentalfire.com
W415-0224 / D / 01.15.04
Page 2
2
TABLE of CONTENTS
Pg 2-4 INTRODUCTION
Warranty General Instructions General Information Care of Glass & Plated Parts
5-7 INSTALLATION
Insert Vent Connection Chimney Connection Wall Switch / Thermostat Gas Pipe Installation
7-8 FINISHING
Trim Extrusion Installation Log Placement Door Installation Mantle Clearances Logo Placement
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
Pg 9 OPERATION / MAINTENANCE
Operating Instructions Maintenance
10 REPLACEMENT BLOWER
11 ADJUSTMENTS
Pilot Burner Adjustment Vent Restrictions Venturi Adjustments
12-13 REPLACEMENTS
Ordering Replacement Parts Replacement Parts Terminal Kits Accessories
14-15 TROUBLE SHOOTING GUIDE
16 SERVICE HISTORY
WARNING
• The fireplace insert is a vented gas-fired heater . Do not burn wood or other materials in this fireplace insert.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the fireplace insert.
• Due to high temperatures, the fireplace insert should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the fireplace insert.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace insert.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the fireplace insert and venting system are kept clean. The fireplace insert and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The fireplace insert area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace insert be modified.
• This fireplace insert must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace insert if any part has been under water . Immediately call a qualified service technician to inspect the fireplace insert and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace insert with the glass door opened, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.
• Do not strike or slam shut the fireplace insert glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Lt d.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0224 / D / 01.15.04
Page 3
CONTINENTAL gas fireplaces are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate. CONTINENTAL products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. Once assembled the complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from WOLF STEEL Ltd..
CONTINENTAL GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
CONTINENTALCONTINENTAL
CONTINENTALCONTINENTAL
CONTINENTAL
gas fireplace are gas fireplace are
gas fireplace are gas fireplace are
gas fireplace are
warranted against defects for as long as you own the fireplace. This covers: combustion cham-warranted against defects for as long as you own the fireplace. This covers: combustion cham-
warranted against defects for as long as you own the fireplace. This covers: combustion cham-warranted against defects for as long as you own the fireplace. This covers: combustion cham-
warranted against defects for as long as you own the fireplace. This covers: combustion cham­ber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermalber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal
ber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermalber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal
ber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components andbreakage only), gold plated parts against tarnishing, porcelainized enamelled components and
breakage only), gold plated parts against tarnishing, porcelainized enamelled components andbreakage only), gold plated parts against tarnishing, porcelainized enamelled components and
breakage only), gold plated parts against tarnishing, porcelainized enamelled components and aluminium extrusion trims.aluminium extrusion trims.
aluminium extrusion trims.aluminium extrusion trims.
aluminium extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
thermal switch, switches, wiring, remote controls, igniter, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, igniter, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, igniter, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, igniter, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, igniter, gasketing, and pilot assembly are covered and covered and
covered and covered and
covered and
WOLF STEEL WOLF STEEL
WOLF STEEL WOLF STEEL
WOLF STEEL
LTD. LTD.
LTD. LTD.
LTD.
will provide replacement parts free of charge during the firstwill provide replacement parts free of charge during the first
will provide replacement parts free of charge during the firstwill provide replacement parts free of charge during the first
will provide replacement parts free of charge during the first
year of the limited warranty.year of the limited warranty.
year of the limited warranty.year of the limited warranty.
year of the limited warranty.
Any labour related to warranty repair is not covered.Any labour related to warranty repair is not covered.
Any labour related to warranty repair is not covered.Any labour related to warranty repair is not covered.
Any labour related to warranty repair is not covered.
CONDITIONS AND LIMITATIONS
WOLF STEEL LTD. warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the warranty registration card filed with WOLF STEEL Ltd. -- provided that the purchase was made through an authorized CONTINENTAL dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
WOLF STEEL Ltd. warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years WOLF STEEL Ltd. will replace or repair the defective parts at our option free of charge. From 10 years to life, WOLF STEEL LTD. will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated in accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty, WOLF STEEL LTD. may, at its discretion, fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale price of any warranted but defective part(s).
WOLF STEEL Ltd. will not be responsible for installation, labour, or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, WOLF STEEL’S responsibility under this warranty is defined as above and it shall not in any event extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of WOLF STEEL Ltd. with respect to the CONTINENTAL gas fireplace and any other warranties expressed or implied with respect to this product, its components or accessories are excluded.
WOLF STEEL Ltd. neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. WOLF STEEL Ltd. will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of WOLF STEEL Ltd.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
WOLF STEEL Ltd. reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. CONTINENTAL® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.
3
W415-0224 / D / 01.15.04
Page 4
4
GENERAL INSTRUCTIONS
THIS GAS FIREPLACE INSERT SHOULD BE INST ALLED AND SERVICED BY A QUALIFIED INSTALLER to con-
form with local codes. Installation practices vary from re­gion to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install to the current CAN1­B149 Installation Code in Canada or to the National Fuel Gas Code, ANSI Z223.1, and NFPA 54 in the United States. Mobile home installation must conform with local codes. In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the Fire Safety Criteria for manufactured home installa­tions, Sites and Community Standard ANSI/NFPA 501A in the United States.
Purge all gas lines with the glass door of the fireplace insert opened. Assure that a continuous gas flow is at the burner before closing the door.
Under extreme vent configurations, allow several min­utes (5-15) for the flame to stabilize after ignition.
The fireplace insert and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace insert must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure test­ing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). A 1/8 inch NPT plug, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the fireplace insert. The fireplace insert must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70-1990 NATIONAL ELECTRICAL CODE in the United States. The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not be removed from the cord plug.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE INSERT HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. Manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane. When the fireplace is installed at el­evations above 4,500ft, and in the absence of specific rec­ommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft. Expansion / contraction noises during heating up and cool­ing down cycles are normal and to be expected.
Maximum input is 24,000 BTU/hr for natural gas and pro­pane. Maximum output for natural gas and propane is 20,400 BTU/hr at an efficiency of 85% with the fan on. Maxi­mum A.F.U.E. (annual fuel utilization efficiency) rating is 79 % for natural gas and propane. This fireplace insert is not approved for closet or recessed installations. It is ap­proved for bathroom, bedroom and bed-sitting room in­stallations and is suitable for mobile homes. The natural gas model is suitable for installation in a mobile home that is permanently positioned on its site and fuelled with natu-
ral gas. This insert must be recessed into a vented noncombus­tible wood-burning fireplace (prefabricated or masonry) only. The minimum fireplace opening size in which the heater is to be installed is:
HEIGHT 14½ inches WIDTH 25 inches DEPTH 11 inches
The minimum allowable chimney flue size is 6" round.
The minimum distance, from the bottom of a combustible mantle projecting 3" maximum from the wall to the top of the aluminium trim, is 3".
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly with a clean dry cloth. The glass is 3/16" ceramic glass available from your Continental / Wolf S teel Ltd. dealer. DO NOT SUBSTITUTE MATERIALS. Clean the glass after the first 10 hours of op­eration with a recommended gas fireplace glass cleaner. Thereafter clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and / or blemishes may result.
W415-0224 / D / 01.15.04
Page 5
INSTALLATION
Provide adequate ventilation air.
Provide adequate accessibility clearance for servicing and operating the fireplace insert.
Never obstruct the front opening of the fire­place insert.
Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.
5
Clean out ashes from the inside of the wood-burning fire­place. Make sure that the chimney and wood-burning fire­place are in a clean and sound condition and constructed of non-combustible materials. If necessary have any re­pair work done by a qualified person before installing the insert. Remove the existing fireplace damper or lock into an open position. Using screws, attach the fireplace warning tag (W385-0199) to the inside of the firebox of the fireplace into which the insert is being installed.
FIGURES 1a-c
3 SIDED BACKER PLA TE - FRONT VIEW
WARNING: THIS FIREPLACE HAS BEEN CONVERTED FOR USE WITH A GAS
FIREPLACE INSERT ONLY AND CANNOT BE USED FOR BURNING WOOD OR SOLID FUELS UNLESS ALL ORIGINAL PARTS HAVE BEEN REPLACED AND THE FIREPLACE IS RE-APPROVED BY THE AUTHORITY HAVING JURISDICTION.
ATTENTION: CE FOYER A ETE CONVERTI AFIN D'ETRE UTILISE SEULEMENT COMME FOYER ENCASTRE AU GAZ ET NE PEUT ETRE UTILSE POUR BRULER DU BOIS OU TOUT AUTRE COMBUSTIBLE SOLIDE, SANS QUE TOUTES LES PIECES ORIGINALES AIENT ETE REMPLACEES ET QUE LE FOYER SOIT APPROUVE DE NOUVEAU PAR LES AUTORITES AYANT JURIDICTION.
W385-0199
The sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, must not be cut.
If the wood-burning factory-built fireplace has no gas access hole(s) provided, an access hole of 1½ inch or less may be drilled through the lower sides or bottom of the fireplace in a proper workman like manner. This access hole must be plugged with non-combustible in­sulation after the gas supply line has been installed.
Ensure that existing chimney cleanouts fit properly. The refractory, glass doors, screen rails, screen mesh
and log grates may be removed from the fireplace be­fore installing the gas fireplace insert.
Smoke shelves, shields and baffles may be removed if attached by mechanical fasteners.
The ventilation openings in the fireplace may be ob­structed by the backer plates, aluminium trim etc. but these parts are not to be applied so as to have an air­tight seal.
3 & 4 SIDED BACKER PLA TES - SIDE VIEWS
TOP VIEW
4 SIDED BACKER PLA TE - FRONT VIEW
W415-0224 / D / 01.15.04
Page 6
6
INSERT VENT CONNECTION
Move the insert close to its final position inside the wood­burning fireplace. This unit is equipped with 6 levelling screws located as follows: two are on either side of the circulation blower on the rear panel; four are located front and back on either side beneath the log support. Level using four of the levelling screws. See Figure 1a. Levelling the unit will eliminate rocking or excessive noise when the fan is in operation. Once the unit is level, move it partially into place within the fireplace to allow for all connections to be made. It is not practical to level the insert once the it has
been installed. Determine the required depth prior to in­stalling the unit and adjust the four levelling screws accord­ingly.
CHIMNEY CONNECTION
Chimney installation must conform to both national and local code requirements. The chimney must be lined with one 2" or 3" diameter liner for intake and one 3" diameter liner for exhaust. The minimum and maximum vent lengths are 10 and 35 feet respectively. Recommended Continent al kits come in 3 lengths: While the liners must be continuous from the fireplace to the terminal, to achieve the needed length, they may be coupled, using an aluminium coupler, provided installation is sealed & secured.
1-2" & 1-3" DOUBLE PL Y ALUMINUM LINER-INLET AND EXHAUST & 2-3" TO 2" REDUCER:
GDI-2320K T VENT KIT 20FT GDI-2325K T VENT KIT 25FT GDI-2335K T VENT KIT 35FT
2-3" DOUBLE PL Y ALUMINUM LINER-INLET AND EXHAUST:
GDI-320KT VENT KIT 20FT GDI-325KT VENT KIT 25 FT GDI-335KT VENT KIT 35 FT
We recommend that exhaust vents that pass through unheated spaces, such as a garage or attic, be wrapped in a protective sleeve to minimize condensa­tion and reverse flow symptoms. See Trouble Shooting for details. This unit is approved for use with a 2" liner for air intake and a 3" liner for exhaust. For best performance, however, it is recommended to use two 3" liners. If a 2" liner is used for the intake, it is necessary to adjust the primary air shutter. See "Air Shutter Settings" on page 11.
1. OUTSIDE: Slip one end of a liner a minimum of 2" over one of the collars of the terminal. Se­cure using 3 screws. Then seal the joint and screw heads with high tempera­ture sealant. Repeat with the other liner.
NOTE: We recommend that the other end of the exhaust liner be marked to eliminate the exhaust liner being con­nected to the intake collar at the unit.
FIGURE 2
2. Gently stretch the liners to the required lengths and in­sert into the chimney . Place the terminal onto the top of the chimney cap and fit the flashing plate to suit. Make weather tight by sealing with caulking (not supplied) and fasten to the chimney with screws and plugs (not supplied)
3. INSIDE: Attach and secure the flex liners to the vent connection assembly using the same procedure as be­fore, ensuring that the marked exhaust liner is attached
to the exhaust collar.
FIGURE 3
FIGURE 4
4. Detach the two screws from the back of the firebox and remove the panel, as illustrated.
STUDS
VENT CONNECTOR
EXTENSION
RESTRICTOR PLATE
FIGURE5a-b
5. Reaching in through the insert, manoeuvre the vent con­nection assembly through the openings in the firebox top, taking care not to damage the gasket. In case of a low ceiling fireplace, the extension should be removed and reinstalled after the vent connection is secured to the fire­box. Attach the restrictor plate to the centre stud and se­cure the assembly using the three studs and ¼-20 hex nuts.
W415-0224 / D / 01.15.04
Page 7
WALL SWITCH / THERMOSTAT GAS INSTALLATION
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient location. Route 2-strand solid core millivolt wire from the gas fireplace insert to the wall switch / millivolt ther­mostat. The recommended maximum lead length de­pends on the wire size:
WIRE SIZE MAX. LENGTH
14gauge 100 feet 16gauge 60 feet 18gauge 40 feet
Do not connect either the wall switch, thermo­stat or gas valve to electricity (110 VOLTS).
Install suitable supply piping connection to the 3/8" flex
connector supplied (as per local gas codes).
FIGURE 6
The insert may now be pushed into its final posi­tion inside the wood-burn­ing fireplace. Secure the in­sert to the fireplace using perforated strapping at­tached to the two securing holes on either side of the unit as shown. We recom-
mend that the trim be in­stalled before the unit is placed into its final position.
FIGURE 7
7
SECURING
HOLES
FINISHING
In order to close off the fireplace opening or if the opening is larger than the 3- or 4-sided aluminium extrusion trim kits, it is recommended to reduce the opening using a non­combustible material such as ceramic tile, marble, etc or the GIZBP6-3 or GIZBP6-4 backer plate kits. The outside edge of the backer plate is finished off with gold trim in­cluded in each kit. A deluxe flashing kit complete with mar­quis trim may also be used to complete the installation. These flashing and trim combinations are available in 6 and 9 inch widths as well as many finishes to accent any room decor. Mounting brackets, GIZBRKT, are required to install the deluxe flashing. Detailed installation instructions are included with each kit. If this unit is being installed into an existing wood burning, zero clearance fireplace, then be aware of this precaution:
Any circulation air opening may be covered (with non­combustible material) but not sealed!
ALUMINIUM EXTRUSION TRIM KIT
INSTALLATION
The insert can be equipped with either a 3- or 4-sided trim kit to finish off the fire­place opening. Slide the trim assembly over the keyholes (2 per side) and drop into place. If installing the op-
tional 3- or 4-sided backer plate (GIZBP6-3 or GIZBP6-
4), it must be hung prior to the trim kit installation us­ing the same keyholes.
FIGURE 9
FIRE VIEWING DOOR
VAL VE CONTROL DOOR
FIGURE 8
FIGURE 10
To adjust the trim: If the mitre is out of alignment, open each side and loosen the two screws at either side trim hinge. Slide the trim up or down to adjust and re-tighten screws. There is also a very slight in/out adjustment that
can be made.
Note: Since the side panels open and close, to access the controls, a gap is necessary at the mitre joint.
The top trim piece has an adjustable securing bracket which enables the trim to be secured to the firebox shell.
SLIDE TO ADJUST
LOOSEN SCREWS
FIGURE 11
W415-0224 / D / 01.15.04
Page 8
8
LOG PLACEMENT DOOR INSTALLATION
Positioning the logs improperly will cause flame im­pingement and carboning.
PHAZERTM logs and glowing embers, exclusive to Continental
Fireplaces, glow when exposed to direct flame and provide a unique and realistic glowing effect that is different in every installation. Take the time to carefully position the glowing embers for a maximum glowing effect. Use only certified
PHAZERTM logs available from your Continental / Wolf S teel
Ltd. dealer.
1. Place the rear log (#1) onto the two log supports and against the air intake pipe.
FIGURE 12
#1
Place the door into the two lower door brackets, and se­cure at the top of the unit with two #10-24 machine screws.
FIGURE 16
LOWER DOOR BRACKET
2. Position logs #2 and #3 against the grate posts and line up the studs located on the burner with the holes on the bottom of the logs. Keep slightly back of the front row of ports.
FIGURE 13
#2
#3
3. Fit the centre log (#4) into place behind log #3 and into the pocket provided on the back log.
FIGURE 14
#4
FIGURE 15
GLOWING EMBERS
MANTLE CLEARANCE
This can vary according to the mantle depth. Use the graph to help evaluate the clearance needed.
FIGURE 17
H
M
E
A
I
N
G
T
H
L
T
E
MANTLE WIDTH
LOGO PLACEMENT
Remove the backing of the logo supplied and place on the glass viewing door, as indicated.
4. Tear the glowing embers into pieces and place along the front row of ports covering all of the burner area in front of the logs. Care should be taken to shred the embers into thin, small irregular pieces as only the exposed edges of the fibre hairs will glow. The ember material will only glow
when exposed to direct flame; however, care should be taken to not block the burner ports. Blocked burner ports
can cause an incorrect flame pattern, carbon deposits and delayed ignition. Log colours may vary . During the initial use of the fireplace, the colours will become more uniform as colour pigments burn in during the heat activated curing process.
W415-0224 / D / 01.15.04
½”
LOGO
½”
FIGURE 18
Page 9
OPERATION / MAINTENANCE
OPERATING INSTRUCTIONS
The on-off switch is located behind the left side control door.
Purge all gas lines with the glass door open. Assure that a continuous gas flow is at the burner before clos­ing the door. Allow several minutes (5-15) for the flame to stabilize after ignition.
Do not operate the main burner of the in­sert with the door removed.
9
When lit for the first time, the fireplace will emit a slight odour for a few hours. This is a normal temporary con­dition caused by the "burn-in" of paints and lubricants used in the manufacturing process and will not occur again. Simply open a window to sufficiently ventilate the room. After extended periods of non-operation such as following a vacation or a warm weather season, the fireplace may emit a slight odour for a few hours. This is caused by dust particles in the heat exchanger burning off. Open a window to sufficiently ventilate the room.
PURGE THE GAS LINE WITH THE GLASS DOOR OPEN.
FOR YOUR SAFETY READ BEFORE LIGHTING:
A. This fireplace is equipped with a pilot which must be lit
by hand. While following these instructions exactly.
B. Before operating smell all around the fireplace area for
gas and next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to turn the gas control knob. Never
use tools. If the knob will not turn by hand, do not try to repair it. Call a qualified service technician. Force or at­tempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under water .
Immediately call a qualified service technician to inspect the fireplace and replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
When lighting and re-lighting, the gas knob cannot be turned from pilot to off unless the knob is depressed slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the fireplace.
3. Turn the gas knob clockwise
4. Wait five (5) minutes to clear out any gas. If you smell gas
including near the floor. Stop! Follow "B" in the above safety information on this label. If you don't smell gas go the next step.
5. If fireplace is equipped with flame adjustment valve turn clockwise to off.
6. Find pilot located in front of back log.
TO TURN OFF GAS
1. Turn off all electrical power to the unit if service is to be performed.
to off.
WHAT TO DO IF YOU SMELL GAS:
• Turn off all gas to the fireplace.
• Open windows.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire dep art­ment.
FIGURE 19
7. Turn gas knob counter-clockwise
8. Depress slightly and hold gas knob while lighting the pilot
with the push button ignitor. Keep knob depressed for one minute, then release. If pilot does not continue to burn, re­peat steps 3 through 7.
9. With pilot lit, depress and turn gas knob counter-clock-
wise to on.
10. If equipped with flame adjustment valve, push and turn
knob to high.
11. If equipped with remote on-off switch/thermostat, main
burner may not come on when you turn valve to on. Remote switch must be in the on position to ignite burner.
12. Turn on all electric power to the fireplace.
2. Push in gas control knob slightly and turn clockwise
to off. Do not force.
FLAME ADJUSTMENT
KNOB
to pilot.
ON/OFF KNOB
FIGURE 20
MAINTENANCE
TURN OFF THE GTURN OFF THE G
TURN OFF THE G
TURN OFF THE GTURN OFF THE G
BEFORE SERBEFORE SER
BEFORE SER
BEFORE SERBEFORE SER
CAUTION: Label all wires prior to disconnection when serv­icing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after servicing. This insert and its venting system should be inspected before use and at least annually by a qualified service per­son. The fireplace area must be kept clear and free of combustible materials, gasoline or other flammable va­pours and liquids. The flow of combustion and ventilation air must not be obstructed.
1. In order to properly clean the burner and pilot assembly, remove the logs exposing both assemblies.
AS AND UNPLAS AND UNPL
AS AND UNPL
AS AND UNPLAS AND UNPL
VICING THE FIREPLVICING THE FIREPL
VICING THE FIREPL
VICING THE FIREPLVICING THE FIREPL
UG ELECTRICAL POUG ELECTRICAL PO
UG ELECTRICAL PO
UG ELECTRICAL POUG ELECTRICAL PO
AA
CE INSERCE INSER
A
CE INSER
AA
CE INSERCE INSER
T!T!
T!
T!T!
WERWER
WER
WERWER
2. Keep the control compartment, logs, burner , air shutter open­ing and the area surrounding the logs clean by vacuuming or brushing, at least once a year.
3. Check to see that all burner ports are burning. Clean out any of the ports which may not be burning or are not burning properly.
4. Check to see that the pilot flame is large enough to engulf the thermocouple on one leg and reaches toward the burner on the other leg.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely on all
openings when the gas knob for the burner is turned on. A 5-10 second total light-up period is satisfactory. If ignition takes longer, consult your Continental dealer/distributor.
7. Check that the door gasketing is not broken or missing. Replace if necessary.
W415-0224 / D / 01.15.04
Page 10
10
REPLACEMENT BLOWER INSTALLATION
The Napoleon gas fireplace insert comes standard with a blower, a heat sensor, variable on/off speed control and a power cord. Because the blower is thermally activated, when turned on, it will automatically start approximately 15 minutes after lighting the fireplace and will run for approxi­mately 30 minutes after the fireplace has been turned off. Use of the fan increases the output of heat. Air, drawn in through the lower slot, is driven up the back of the firebox, and exhausted as hot air through the upper slot.
black
white
FIGURE 21
red
THERMODISC BRACKET ASSEMBLY
FIGURE 24
4. Disconnect the two blower wires. Remove the blower bracket secured with one wing nut and lock washer. For thermodisc replacement: Remove the "Z" shaped mounting bracket secured to the firebox wall to the left of the blower. Remove the thermodisc from the bracket and replace.
BLOWER WIRES
B C
1. Turn off the electrical power and the gas supply to the fireplace insert.
2. Remove the fire viewing door. Remove the logs.
FIGURE 22
3. Detach the two screws from the back of the firebox and remove the panel, as illustrated.
BLOWER ACCESS DOOR
A
FIGURE 25
5. Replace the blower using the existing bracket. Slide the vibration reducing pad (A) into the clip (C) and up against the threaded stud (B) at the other end. The blower must be able to be positioned entirely onto the pad.
Slide the blower into the clip (C). Secure to the threaded stud using the existing lock washer and wing nut. Ensure that the blower does not touch the fireplace base or the firebox.
6. Reconnect the two wires. Holding the replacement gas­ket in place, reattach the blower access door and panel. Replace the logs. Re-install the fire viewing door.
7. Turn the gas supply and electricity back on.
Drywall dust will penetrate into the blower bearings caus­ing irreparable damage and must be prevented from coming into contact with the blower or its compartment. Any damage resulting from this condition is not cov­ered by the warranty policy.
FIGURE 26
FIGURE 23
4. Remove the blower access door held on with the re­maining 8 screws. Replace the blower access door gas­ket when changing the blower.
W415-0224 / D / 01.15.04
Page 11
ADJUSTMENTS
11
PILOT BURNER ADJUSTMENT
Remove the pilot screw cap. Adjust the pilot screw to pro­vide properly sized flame. Turn in a clockwise direction to reduce the gas flow. Replace the pilot screw cap.
FIGURE 27
VENTURI ADJUSTMENT
This unit is approved for use with a 2" liner for air intake and a 3" liner for exhaust. For best performance, however, it is recommended to use two 3" liners. Air shutter settings will differ depending on the liner sys­tem used. Use the charts below to determine the correct air shutter setting:
3"/ 3" LINER SYSTEM
NG 1
LP 3
AIR SHUTTER SETTING
2"/ 3" LINER SYSTEM
NG 1
LP 5
AIR SHUTTER SETTING
Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be estab­lished.
Air shutter adjustment must only be done by a qualified gas installer!
/ /
/
16 16
/
8
16
"
"
"
"
FIGURE 28
VENT RESTRICTION
Some vent configurations may display a very active flame. If this appearance is not desirable, the vent exit may be re­stricted using the restrictor plate shown in FIGURE 6b. Bend the flap up as shown to reduce the velocity of the exhaust gases, slowing down the flame pattern and creating a more traditional appearance.
FIGURE 29
FIGURE 30
HELPFUL HINT :
A mirror will let you see the opening of the air shutter without removing the burner. Scribe a line along the venturi tube and air shutter cap. Open or close according to the original opening by using the scribed line as your datum.
W415-0224 / D / 01.15.04
Page 12
12
REPLACEMENTS
Contact your dealer for questions concerning prices and availability of replacement parts. Normally all parts can be ordered through your Continental dealer or distributor.
When ordering replacement parts always give the follow­ing information:
1. MODEL & SERIAL NUMBER OF FIREPLACE
2. INSTALLA TION DATE OF FIREPLACE
* IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED. FOR
FURTHER INFORMATION, CONTACT YOUR CONTINENTAL
DEALER.
FOR WARRANTY REPLACEMENT PARTS , A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM.
REPLACEMENT PARTS
1 W725-0039 RBT SHAW VALVE - NG 1 W725-0040 RBT SHAW VALVE - LP 2 W100-0068 BURNER 3 W455-0017 #42 BURNER ORIFICE - NG 3 W455-0059 #53 BURNER ORIFICE - LP 4 W010-0800 PILOT ASSEMBL Y - LP 4 W010-0801 PILOT ASSEMBL Y - NG 5 W455-0069 PILOT INJECTOR - NG 5 W455-0067 PILOT INJECTOR - LP 6 W680-0005 THERMOCOUPLE 7 W680-0004 THERMOPILE 8* W573-0008 HIGH TEMPERATURE SEALANT 9* W357-0001 PIEZO IGNITOR 10 GL-631 LOG SET 11 W135-0136 REAR LOG 12 W135-0138 RIGHT LOG 13 W135-0137 LEFT LOG 14 W135-0139 CENTER LOG 15* W361-0016 GLOWING EMBERS 16 GZ552 BLOWER 17* W385-0131 CONTINENTAL LOGO 18* W010-0804 DOOR GLASS C/W GASKET 19* W225-0095 DOOR FRAME 20 W010-0802 DOOR C/W GLASS 21* W290-0063 BLOWER ACCESS GASKET 22* W430-0013 MAGNETIC CLOSURE 23* W660-0009 ON/OFF SWITCH 24* W690-0002 THERMODISC 25* W380-0002 VARIABLE SPEED SWITCH KNOB 26* KB35 VARIABLE SPEED SWITCH 27 W080-0451 RESTRICTOR BRACKET
TERMINAL KITS
28 GDI-223 TERMINAL KIT
VENT KITS
1-2" & 1-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST & 2-3" TO 2" REDUCER:
31* W690-0001 MILLIVOLT THERMOSTAT 32* W660-0010 REMOTE CONTROL - ADVANTAGE 32* W660-0011 REMOTE CONTROL - ADVANTAGE PLUS 33* GD660 REMOTE WALL SWITCH C/W 20FT WIRE 34 GI-790KT DECORATIVE BRICK PANELS 35* W175-0162 CONVERSION KIT - NG-LP 35* W175-0192 CONVERSION KIT - LP-NG 36* GIZBP6-3 3 SIDED BACKER PLATE C/W ACCENT TRIM 37* GIZBP6-4 4 SIDED BACKER PLATE C/W ACCENT TRIM 38* GIZTRM3 ALUMINIUM EXTRUSION - MATTE BLACK 38* GIZTRM3-K ALUMINIUM EXTRUSION - POLISHED BLACK 38* GIZTRM3-B ALUMINIUM EXTRUSION - POLISHED BRASS 39 GIZTRM4 ALUMINIUM EXTRUSION - MATTE BLACK 39 GIZTRM4-K ALUMINIUM EXTRUSION - POLISHED BLACK 39 GIZTRM4-B ALUMINIUM EXTRUSION - POLISHED BRASS 40 GIZUT-B UPPER DOOR TRIM - BRASS 40 GIZUT-G UPPER DOOR TRIM - GOLD 41 GI-900K6 6" DELUXE FLASHING W MARQUIS TRIM - BLACK 41 GI-900B6 6" DELUXE FLASHING W MARQUIS TRIM - POLISHED BRASS 41 GI-900AB6 6" DELUXE FLASHING W MARQUIS TRIM - ANTIQUE BRASS 41 GI-900SS6 6" DELUXE FLASHING W MARQUIS TRIM - BRUSHED STAINLESS STEEL 41 GI-909S6 6" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN ALMOND 41 GI-909K6 6" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN BLACK 41 GI-909F6 6" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN GREEN 41 GI-900K9 9" DELUXE FLASHING W MARQUIS TRIM - BLACK 41 GI-900B9 9" DELUXE FLASHING W MARQUIS TRIM - POLISHED BRASS 41 GI-900AB9 9" DELUXE FLASHING W MARQUIS TRIM - ANTIQUE BRASS 41 GI-900SS9 9" DELUXE FLASHING W MARQUIS TRIM - BRUSHED STAINLESS STEEL 41 GI-909S9 9" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN ALMOND 41 GI-909K9 9" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN BLACK 41 GI-909F9 9" DELUXE FLASHING W MARQUIS TRIM - PORCELAIN GREEN 42* GIZBRKT MOUNTING BRACKETS (REQUIRED FOR THE 900 SERIES FLASHING KITS) 43 CISK-A CAST IRON SURROUND KIT - PAINTED BLACK 43 CISKK-A CAST IRON SURROUND KIT - PORCELAIN ENAMEL BLACK 43 CISKN-A CAST IRON SURROUND KIT - PORCELAIN ENAMEL MAJOLICA BROWN 43 CISKF-A CAST IRON SURROUND KIT - PORCELAIN ENAMEL MAJOLICA GREEN 44* AK-4 ADAPTOR KIT FOR CAST IRON SURROUND 45 ANI-K ANDIRON - PAINTED BLACK 45 ANI-G ANDIRON - GOLD PLATED
3. PART NUMBER
4. DESCRIPTION OF P ART
5. FINISH
ACCESSORIES:
29* GDI-2320KT VENT KIT 20FT 29* GDI-2325KT VENT KIT 25FT 29* GDI-2335KT VENT KIT 35FT
2-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST:
30* GDI-320KT VENT KIT 20FT 30* GDI-325KT VENT KIT 25 FT 30* GDI-335KT VENT KIT 35 FT
W415-0224 / D / 01.15.04
Page 13
13
* WARNING: This is a fast acting thermocouple. It is an integral safety component. Replace only
with a fast acting thermocouple supplied by Wolf Steel Ltd.
W415-0224 / D / 01.15.04
Page 14
14
TROUBLE SHOOTING GUIDE
B
EFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED
SYMPTOM PROBLEM TEST SOLUTION
.
Pilot will not light.
Pilot goes out when the gas knob is re­leased.
No spark at pilot burner
Spark gap is incorrect
No gas at the pilot burner
Out of propane gas.
System is not correctly purged. Out of propane gas Pilot flame is not large enough Pilot flame is not engulfing the
thermocouple. Thermocouple shorting.
Faultly thermocouple. Faulty valve.
- check if pilot can be lit by a match
- check that the wire is connected to the push button ignitor.
- check if the push button ignitor needs tightening.
- replace the push button ignitor.
- spark gap should be 0.150" to 0.175" (5/32" to 1 1/64" approx.) from the electrode tip and the pilot burner.
- check that the manual valve is turned on.
- check the pilot orifice for blockage.
- replace the valve.
- call the gas distributor.
- fill the tank.
- purge the gas line with the glass door open.
- fill the tank.
- turn up the pilot flame.
- turn up pilot flame.
- replace pilot assembly.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- replace.
Pilot burning; no gas to main burner; gas knob is on 'HI'; wall switch / thermostat is on.
Pilot goes out while standing; Main burner is in 'OFF' position.
Main burner goes out; pilot stays on.
Main burner orifice is plugged.
Faulty thermopile. Faulty themostat or switch.
Faulty valve.
Gas piping is undersized.
Pilot flame is not large enough or not engulfing the thermopile.
Thermopile shorting
Remote wall switch wire is too long, too much resistance in the system
Faulty thermostat or switch
- remove stoppage in orifice.
- replace.
- connect a jumper wire across the wall switch terminals; if main burner lights, replace thermostat.
- disconnect the switch wires & connect a jumper wire across terminals 1 & 3; if the main burner lights, check the wires for defects and / or replace wires.
- replace.
- turn on all gas appliances and see if pilot flame flutters, diminishes or extinguishes, especially when main burner ig­nites. Monitor supply pressure.
- check if supply piping size is to code. Correct all undersized piping.
- turn up pilot flame.
- replace pilot assembly.
- clean thermopile and thermopile connection to valve.
- shorten wire to correct length or wire gauge.
- replace
W415-0224 / D / 01.15.04
Page 15
SYMPTOM PROBLEM TEST SOLUTION
15
Main burner goes out; pilot goes out.
Exhaust fumes smelled in room, headaches.
Carbon is being de­posited on glass, logs or combustion chamber surfaces.
REFER TO "MAIN BURNER GOES OUT ; PILOT ST A YS ON"
Vent re-circulating
Thermocouple shorting or faulty.
Vent is reversing
Fireplace is spilling.
Air shutter has become blocked
Flame is impinging on the logs or combustion chamber.
- check joint seals and installation.
- loosen and tighten thermocouple
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- check all venting and insert seals.
- check that door is properly sealed. If the insert is allowed to burn with the door off when purging the unit, exhaust products may escape through the air intake pipe and reverse the venting action. Let the unit cool down to correct the reversed venting action.
- check all seals.
- ensure air shutter opening is free of lint or other obstruc­tions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is tight.
- check that both vent liners are free of holes and well sealed at all joints.
Main burner flame is a blue, lazy , transpar­ent flame.
White / grey film forms.
Air shutter is not set to specifi­cations.
Blockage in vent. - remove blockage. In really cold conditions, ice buildup may
Incorrect installation.
Sulphur from fuel is being de­posited on glass, logs or com­bustion chamber surfaces.
- check and adjust air shutter to correspond with the fuel type and air intake size.
occur on the terminal and should be removed as required.
- vent liners are reversed. Refer to Figure 2.
- check all venting and insert seals.
- clean the glass with a recommended gas fireplace glass cleaner. DO NOT CLEAN GLASS WHEN HOT. If deposits are not cleaned off regularly, the glass may be­come permanently marked.
W415-0224 / D / 01.15.04
Page 16
16
Service Performed Special ConcernsDealer Name
Name
Service Technician
Wolf Steel Fireplace Service History
This fireplace must be serviced annually depending on usage.
W415-0224 / D / 01.15.04
Date