Contemporary Control Systems MR-AI8 User Manual

Analog Input Module MR-AI8
11083213
1. Description
The Modbus module with 8 individually configurable resistance or voltage inputs is designed for local switching operations. It is suitable to record resistance or voltage values of for example passive and active temperature sensors electrical ventilation or mixing valves, valve positions etc. The inputs are universally configurable and can be scanned via a Modbus-Master. Setting of the slave address, bit rate and parity is done with the two address switches (x1 / x10) on the front. Possible settings are addresses 00 to 99 and baud rates 1200, 2400, 4800, 9600, 19200, 38400, 57600 und 115200 Bd.
The device does not participate in bus communication if the address is 00 (reserved for broadcast commands).
2. Declaration of Conformity
The device was tested according to the applicable standards. Conformity was proofed. The declaration of conformity is available at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the device. In case of questions that cannot be answered with these instructions please consult supplier or manufacturer.
Safety Instructions
Keep the applicable directions for industrial safety and preventi­on of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to electrically discharge themselves as prescribed before installati­on or maintenance of the devices.
Only qualified personnel shall do mounting and installation work with the devices, se e section “qualified personnel”.
The information of these instruc tions have to be read and un­derstood by every person using this device.
7170/899289
Symbols
Warning of dangerous electrical voltage
Dange r
means that non- obser vance may cause risk of life, grievous bodily harm or he avy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons who are well versed in the use and installation of such devices and whose professional qualification meets the require­ments of their work.
This includes for example:
• Qualification to conne ct the device according to the VDE specifications and the local regulations and a qualific ation to put this device into operation, to power it down or to activate it by respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the equipment system etc.
Modbus Interface
Protocoll Modbus RTU Transmission rate 1200 ... 115200 Bd (factory set ting 19200 Bd Even) Cabling RS485 two wire bus with voltage equalizing cable in bus / line topology
Supply
Operating volt age range 20 ... 28 V AC/DC (SELV) Current consumption 65 mA (AC) / 25 mA (DC) Relative duty cycle 100 %
Input
Resistance range 40 W to 4 MW Voltage input 0 ... 10 V DC Resolution 1 mV Error Voltage input about ±10 mV Resistance input < 12 kW = 0,1 % / > 12 kW = 1 %
Housing
Dimensions Wx HxD 2.0 x 2.8 x 2.6 in. (50 x 70 x 65 mm) Weight 104 g Mounting position any Mounting standard rail TH35 per IEC 60715 Mounting in series the maximum quantit y of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per conne ction to the power supply. For any similar block of additional modules a separate connection to the power supply is mandatory. Material Housing Polyamide 6.6 V0 Terminal blocks Polyamide 6.6 V0 Cover plate Polycarbonate Type of protection (IEC 60529) Housing IP40 Terminal blocks IP20
Terminal blocks
Supply and bus 4 pole ter minal block max. AWG 16 (1,5 mm²) solid wire max. AWG 18 (1,0 mm²) stranded wire Wire diameter min. 0.3 mm up to max. 1.4 mm (terminal block and jumper plug are included to each packing unit) Module connection Input/Output max. AWG 12 (4.0 mm²) solid wire max. AWG 14 (2.5 mm²) stranded wire Wire diameter min. 0.3 mm up to max 2.7 mm
Temperature range
Operation -5 °C ... +55 °C Storage -20 °C ... +70 °C Protective circuitr y polarity reversal protection of operating voltage polarity reversal protection of supply and bus
Display
Operating and bus activity green LED Error indication red LED
4. Wiring Diagram3. Technical Data
5. Connection Diagram
METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433 Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH Mounting instruction see www.metz-connect.com
6. Mounting
Power down the equipment
Mount the module on standard rail (TH35 per IEC 60715 in junction boxes and/or on distribution panels).
Installation Electric ins tallat ion and device te rminat ion shal l be done by
qualified persons only, by respecting all applicable specifications and regulations.
Plug in th e terminal bloc k for bus co nnection
21
Conne ct the ca ble for bus supply
5 mm
43
Mounting in series
65
The module can be aligned w ithout interspace. Use the jumper plug to connect bus and supply voltage when the modules are mounted in series.
The max imum quantity o f modules conne cted in l ine is lim i­ted to 15 or to a ma ximum power consumption of 2 Amps (AC or DC ) per connecti on to the power supply. For any simila r block of additi onal mod ules a se parate co nnection to the power suppl y is manda tory.
7. Bit rate and Parity setting
The bit rate and parity can be set in the programming mode when ajumper is plugged behind the front cover of the module. This jumper is removed in normal mode. A connection to the bus is not require d during bit rate setting.
The bit rate of the modules can be set in the following way:
1. remove the front cover of the module;
2. plug a jumper to the two middle pins of the 4 pole header between the red and green LED ( Á);
3. set the desired parity and bit rate with the address s witches (Â) in accordance to the chart below.
7
C2C2C2
24V 24V
+24V
GND
B+
A -
ERROR
MODBus RTU
MR-AI8
182
C2
4. switch on the supply voltage of the module; it is now per­manently saving the bit rate in an EEPROM;
5. switch off the supply voltage of the module;
6. remove the jumper from the header and place the front cover.
Switch
1 2 3
x10
C26
x10
x1
Jumper below the faceplate
3C2
BUSY
5
S
+24V
GND
B+
A -
1
2
24V
J
3
15V
4
4
C2C2S
Parity even odd none
Switch
1 2 3 4 5 6 7 8
x1
Bitrate
1200 2400 4800 9600 19200 38400 57600 115200
(Bit/s)
If the settings differ from the settings specified in the chart the factory setting applies.
Factor y setting: 19200 Bd Even
8. Jumper Positions for Voltage feeding of Ac­tive Sensors
7
C2C2C2
24V 24V
+24V
GND
B+
A -
ERROR
MODBus RTU
MR-AI8
182
C2
7
C2C2C2
24V 24V
+24V
GND
B+
A -
ERROR
MODBus RTU
MR-AI8
182
C2
5
S
C26
+24V
GND
x10
B+
x1
BUSY
4
3C2
5
C26
x10
x1
BUSY
4
3C2
1
2
3
4
C2C2S
1
2
3
4
C2C2S
+24V
GND
A -
S
B+
A -
Jumper below the faceplate
Jumper in bottom position contacts S =15VDC (factory setting)
Jumper below the faceplate
Jumper in top position contacts S =24VAC/DC
9. Connection examples
active
passive sensor
7
C2C2C2
24V 24V
+24V
GND
B+
A -
ERROR
Pullup resistance
MODBus RTU
MR-AI8
182
C2
Semiconductor
sensor
D
sensor
Ub
0..10V
GN
5
S
C26
+24V
GND
x10
B+
x1
A -
1
BUSY
2
24V
J
3
15V
4
4
C2C2S
3C2
10. Software Description
10.1 I/O Commands
„04 (0x04) Read Input Registers“
Request:
Valid Starting Address 0 .. 15 Valid Quantity of Registers 1 .. 16 (1 to 8 inputs)
Response:
Byte Count 2 x Quantity o. R. Registers Values Quantity o. R x 2 Bytes
Input
Register
Information
1 0-1
2 2-3
3 4-5
4 6-7
5 8-9
6 10-11
7 12-13
8 14-15
Figure 1
Sign
Byte 1 Bit 7 Byte 1 Bit 6..0 Byte 2 Bit 7 Byte 2 Bit 6..0 Byte 3 Byte 4
Configuration Registers Input circuit and measuring range, data type and value unit and
the sensor characteristic for usual temperature sensors are set for the 8 inputs with the 8 configuration registers.
Register contents is stored in an EEPROM. Modbus functions:
“03 (0x03) Read Holding Registers” (max. 20 at once) “06 (0x06) Write Single Register” “16 (0x10) Write Multiple Registers” (max. 20 at once)
Holding Register 0-15 Offset Register is added to the measured value in 2 succeeding registers, (Input 1 = Register 0 - 1) Float in both or Signed Integer 16 in the first one, same as for measured value
Holding Register 16-23 Configuration register (EEPROM) used to set measuring range, data type of the measure d value (Float / Integer 16),
unit of the measured value and the sensor characteristic
(Input 1 = Register 16) Holding Register 24-63 Register for interpolation charts
(EEPROM), alternately temperature and resistance,
Float in two succeeding registers
Configuration Register for voltage or resistance measurement:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Values are supplied in 2 registers (4 Bytes).
Data type in registers can be configured (see Registers 16 to 23):
Float value needs 2 registers (fig. 1)
signed int value is in 1st register
signed int 0 fills 2nd register
Value remains 0 until a measurement takes place
Data types composed from 2 registers start at an even address
Exponent Exponent Mantisse Mantisse Mantisse
0 0 range number
METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH Mounting instruction see www.metz-connect.com
Loading...
+ 2 hidden pages