Contemporary Control Systems BMT-AO4 User Manual

Analog Output Module BMT-AO4
1108851302
1. Description
The BACnet MS/ TP module with 4 analog outputs was develo­ped for decentralized switching tasks. It is suit able as encoder for control variables, for example for elec trical vent and mixing valves, valve positions, etc.
The outputs can be output by means of standard objects via a BACnet client. T he module is addressed and the baud rate is set by means of t wo addre ss switches on the front.
Suitable for decentralized mounting in serial sub- distributor.
2. Declaration of Conformity
The device was tested according to the applic able st andards. Con­formit y was proofed. The declaration of conformit y is available at the manufacturer METZ CONNECT GmbH.
Notes Regarding Device Description
The indicated installation dire ctions or rules are applicable to the Federal Republic of Germany. If the device is used in other countries it applies to the equipment installer or the user to meet the national directions.
Safety Instructions
Keep the applicable dire ctions for industrial safety and prevention of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to elec trically discharge themselves as prescribed before installation or maintenance of the devices.
Only qualified personnel shall do mounting and installation work with the device s, see section “qualified personnel”.
The information of these instruc tions have to be read and under­stood by every person using this device.
7628/899299-07
Symbols
Warning of dangerous electrical voltage
Danger
means that non-obser vance may cause risk of life, grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personne l in the sense of these instructions are per sons who are well versed in the use and installation of such devices and whose professional qualification meets the requirements of their work.
This includes for example:
• Qualification to connect the device according to the VDE specifications and the local regulations and a qualification to put this device into operation, to power it down or to activate it by respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the equipment sys tem etc.
3. Technical Data
BACnet Interface
Protocoll BACnet MS/TP Transmission rate 9600 to 115200 Bd (factory set ting 9600 Bd) Cabling RS485 two wire bus with voltage equalizing cable in bus / line topology; terminate with 120 Ohms
Supply
Operating volt age range 20 to 28 V AC/ DC (SELV) Current consumption 50 mA (AC ) / 20 mA (DC) Relative duty cycle 100 %
Output
Output voltage 4 x 0 to 10 V DC Output current 5 mA at 10 V DC Resolution 10 mV / Digit
Housing
Dimensions WxHxD 1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm) Weight 72 g Mounting position any Mounting standard rail TH35 per IEC 60715 Mounting in series the maximum quantity of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per connection to the power supply. For any similar block of additional modules a sepa ­ rate connection to the power supply is mandatory. Material Housing Polyamide 6.6 V0 Terminal blocks Polyamide 6.6 V0 Cover plate Polycarbonate Type of protection (IEC 60529) Housing IP4 0 Terminal blocks IP20
Terminal blocks
Supply and bus 4 pole ter minal block max. AWG 16 (1.5 mm²) solid wire max. AWG 18 (1.0 mm²) stranded wire Wire diameter min. 0.3 mm up to max . 1.4 mm (terminal block and jumper plug are included to each packing unit) Module connection Outputs max. AWG 12 (4.0 mm²) solid wire max. AWG 14 (2.5 mm²) stranded wire Wire diameter min. 0.3 mm up to max 2.7 mm Protective circuitr y polarity reversal protection of operating voltage polarity reversal protection of supply and bus
Temperature range
Operation -5 °C to +55 °C Storage -20 °C to +70 °C
Display
Operating / bus ac tivity green L ED Error indication red LED
4. Wiring Diagram
A1/+24 V
A2 /GND
BUS B+
BUS A-
24 V
BACnet MS/TP on RS-485
Output: Voltage 0-10V
5. Connection Diagram
C2 4 C2 3
24 V AC/DC
A1
A2
BUS B+
B+
BUS A-
A-
C21 C22
GND
D
RISC - CPU
A
A1
A2
B+
A-
1
C2
2
C2
3 C2
4
C2
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany Phone +49 7702 533-0 | Fax +49 7702 533-433 Mounting instruction see www.metz-connect.com
6. Mounting
Power down the equipment
Mount the module on standard rail (TH35 per IEC 60715 in junction boxes and/or on distribution panels).
Installation Electric installation and device termination shall be done by qua­lifie d persons only, by re spec ting all ap plicab le specifications and regulations.
Plug in the terminal block for bus connection
21
Connect the cable for bus supply
5 mm
43
Mounting in series
5 6
The module can be aligned without interspace. Use the jumper plug to connect bus and supply voltage when the modules are mounted in series.
The max imum quan tity of m odules connec ted in line is limite d to 15 or to a maximum power c onsumpt ion of 2 Amp s (AC or DC) pe r connec tion to the power supply. For any similar b lock of additional modules a se parate connect ion to the p ower supply is mandatory.
7. Network adress and Bit rate setting
Configuration Switches Hexadecimal Switches x10, x1 define the Network Address (00 - F9; e.g. F9h = 15x16+9 = 249d) and Baud rate (FA – FF).
• Turn Switch x10 to E (Device is temporaryly configured as Slave)
• Turn Switch x1 to A – F to select Baud rate
• Turn Switch x10 to F, wait 1 second
• Red and green LEDs are blinking when Baud rate ist stored in EEPROM
• Turn Switch x10 to select Network Address
• Turn Switch x1 to select Network Address
MS/ TP Master if using Network Address 0x00 … Max_Master, MS/ TP Slave if using Network Address Max_Master + 1 … 0xF9.
Adress switch x10 F F F F F F
Adress switch x1 A B C D E F
Bit rate (Bit/s) 9600 19200 38400 57600 76800 115200
Factor y setting: 9600 Bit /s
8. Software Description
Device Object
Property Remark / Value RW Object_Identifier device, default instance: 421000 + Network-Address RW-E
Object_Name
Obj ec t_Ty pe DEVICE (8) R System_Status OPERATIONAL (0) R Vendor_Name “BTR Netcom GmbH” R Vendor_Identifier 421 R Model_Name “BMT-AO4” R Description max. 127 Bytes, default “” RW-E Location max. 63 By tes, default “” RW-E Firmware_Revision “1.2” R Application_Software_Version “1. 0” R Protocol_Version 1 R Protocol_Revision 12 R
Protocol_Services_Supported
Protocol_Object_Types_Supported DEVICE, ANALOG_OUTPUT, ANALOG_VALUE R Object_ List [6] device, analog-output 1…4, analog-value 1 R Max_APDU_Length_Accepted 480 R Segmentation_Supported NO_SEGMENTATION (3) R APDU_Time out 10000 R Number_Of_APDU_Retries 3 R Device_Address_Binding - R Database_Revision 0 R Max_Master 0…127, de faul t 127 RW-E Max_Info_Frames 1…255, default 1 RW-E
Active_COV_Subscriptions
R: Read Proper ty, W: Write Proper ty, -E: Storage in EEPROM / Flash
Analog Output Object 1…4
Property Remark / Value RW Object_Identifier analog-output, instance 1 … 4 R Obj ec t_Ty pe ANALOG_OUTPUT (1) R Object_Name max. 42 Bytes, default “Output 1” … “Output 4” RW-E Description max. 84 Byte s, default “” RW-E Pre sent_Va lue 0.0 … 102.4 (0V … 10.24V) RW
Status_Flags
Event_State NORMA L (0) R Out_Of_Service FALSE (0) / TRUE (1) RW Units Percent (98) R Priority_Array [16] NULL / 0.0 … 102.4 (0V … 10.24V) R Relinquish_Default 0.0 … 102.4 (0V … 10.24V) RW-E
COV_Increment
Notification_Class
Resolution 0.00625 (0.625 mV) ­R: Read Proper ty, W: Write Proper ty, -E: Storage in EEPROM / Flash
max. 63 B ytes, default “BMT-AO4_” + Network-Address (Hexadecimal)
read-property, write-property, subscribe-cov, who-has, who-is, device-communication­control, reinitialize-device
max. 6 Subscriptions, for analog- output 1…4, Confirmed / Unconfirme d, Lifetime = 0…65535 sec.
IN_ALARM: 0 FAULT: 0 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 / 1
Minimum change of Present_Value for COV notification, default 1.0
Unsubscribed UnconfirmedCOVNotification 0: no COV notification, default, 1: local broadcast, 2: global broadcast
RW-E
R
R
R
RW-E
RW-E
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany Phone +49 7702 533-0 | Fax +49 7702 533-433 Mounting instruction see www.metz-connect.com
Loading...
+ 1 hidden pages