Contemporary Control Systems BMT-AI8 User Manual

Analog Input Module BMT-AI8
11088213
1. Description
The BACnet MS/TP module with 8 individually configurable resistance or voltage input s is designed for local s witching operations. It is suitable to record resistance or voltage values of for example passive and active temperature sensors electric al ventilation or mixing valves, valve positions etc. The inputs are univer sally configurable by standard object via a BACnet-Client. Addressing of the module and baud rate set ting are done with the two address switches (x1 / x10) on the front. Possible settings are addresses 00 to F9 and baud rates 9600 Bd, 19200 Bd, 384 00 Bd, 57600, 7680 0 Bd and 115200 Bd.
2. Declaration of Conformity
The device was te sted according to the applicable standards. Con­formit y was proofed. The declaration of conformity is available at the manufacturer METZ CONNECT GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the device. In case of questions that cannot be answered with these instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the Federal Republic of Germany. If the device is used in other countries it applies to the equipment installer or the user to meet the national directions.
Safety Instructions
Keep the applic able directions for industrial safety and prevention of accidents as well as the VDE rule s.
Technicians and/or installers are informed that they have to elec trically discharge themselves as prescribed before installation or maintenance of the devices.
Only qualified pers onnel shall do mounting and installation work with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under­stood by ever y person using this device.
7603/899299-03
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life, grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are per sons who are well versed in the use and installation of such devices and whose professional qualification meets the requirements of their work.
This includes for example:
• Qualification to connect the device according to the VDE specifications and the local regulations and a qualification to put this device into operation, to power it down or to activate it by respecting the internal directions.
• Knowledge of safet y rules.
• Knowledge about application and use of the device within the equipment system etc.
3. Technical Data
BACnet Interface
Protocoll BACnet MS/ TP Transmission rate 9600 ... 115200 Bd (factory setting 9600 Bd) Cabling RS485 two wire bus with voltage equalizing cable in bus / line topology; terminate with 120 Ohms
Supply
Operating voltage range 20 ... 28 V AC/DC (SELV) Current consumption 65 mA (AC) / 25 mA (DC) Relative duty cycle 100 %
Input
Resistance range 40 Ohms to 4 MOhms Voltage input 0 ... 10 V DC Resolution 10 mV Error about ±100 mV
Housing
Dimensions Wx HxD 2.0 x 2.8 x 2.6 in. (50 x 70 x 65 mm) Weight 104 g Mounting position any Mounting standard rail TH35 per IEC 60715 Mounting in series the maximum quantity of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per connection to the power supply. For any similar block of additional modules a separate connection to the power supply is mandatory. Material Housing Polyamide 6.6 V0 Terminal blocks Polyamide 6.6 V0 Cover plate Polycarbonate Type of protection (IEC 60529) Housing IP4 0 Terminal blocks IP20
Terminal blocks
Supply and bus 4 pole te rminal block max. AWG 16 (1.5 mm²) solid wire max. AWG 18 (1.0 mm²) stranded wire Wire diameter min. 0.3 mm up to max. 1.4 mm (terminal block and jumper plug are included to each packing unit) Module connection Inp ut/Output max. AWG 12 (4.0 mm²) solid wire max. AWG 14 (2.5 mm²) stranded wire Wire diameter min. 0.3 mm up to max 2.7 mm Protective circuitry polarity reversal prote ction of operating voltage polarity reversal prote ction of supply and bus
Temperature range
Operation -5 °C ... +55 °C Storage -20 °C ... +70 °C
Display
Operating and bus activity green L ED Error indication red LED
4. Wiring Diagram
A1/+24 V
A2 /GND
BUS B+
BUS A-
24 V
BACnet MS/TP on RS-485
Outputs:
S
Voltage 15 V DC
S
or 24 V AC/DC
Inputs: Voltage: 0-10 V Resistance: 40 Ohm - 4MOhm
5. Connection Diagram
8 C2 7 C2 6 C2 5 C2 S
24 V AC/DC
A1
A2
B+
A-
1 C2 2 C2 3 C2 4 C2 S
GND
BUS B+
BUS A-
RISC - CPU
A1
A2
B+
A-
8 C2 7 C2 6 C2 5 C2 4 C2 3 C2 2 C2
1 C2
METZ CONNECT GmbH
Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433 Mounting instruction see ww w.metz-connect.com
6. Mounting
Power down the equipment
Mount the module on standard rail ( TH35 per IEC 60715 in junction boxes and/or on distribution panels).
Installation Electric installation and device termination shall be done by qua­lifie d pers ons only, by respe cting all applicable specifications and regulations.
Plug in the terminal block for bus connection
1
2
Connect the cable for bus supply
5 mm
43
Mounting in series
5 6
The module can be aligned without inter space. Use the jumper plug to connect bus and supply voltage when the modules are mounted in series.
The max imum qua ntity of modules connecte d in line is limited to 15 or to a maximum powe r consumption of 2 A mps (AC o r DC) pe r conne ction to the power suppl y. For any similar block of additional mo dules a s eparate conne ction to the pow er supply is mandatory.
7. Network adress and Bit rate setting
Configuration Switches Hexadecimal Switches x10, x1 define the Network Address (00 - F9; e.g. F9h = 15x16+9 = 249d) and Baud rate (FA – FF).
• Turn Switch x10 to E (Device is temporaryly configured as Slave)
• Turn Switch x1 to A – F to select Baud rate
• Turn Switch x10 to F, wait 1 second
• Red and green LEDs are blinking when Baud rate ist stored in EEPROM
• Turn Switch x10 to select Network Address
• Turn Switch x1 to select Network Address
MS/ TP Master if using Network Address 0 x00 … Max_Master, MS/ TP Slave if using Network Address Max_Master + 1 … 0xF9.
Adress switch x10 F F F F F F
Adress switch x1 A B C D E F
Bit rate (Bit/s) 9600 19200 38400 57600 76800 115200
Factor y set ting: 9600 Bit/s
8. Jumper positions for voltage feeding of active sensors
8 C2 7 C2 6 C2 5 C2 S
24V
+24 V GND B+ A-
BMT-AI8
1 C2 2 C2 3 C2 4 C2 S
8 C2 7 C2 6 C2 5 C2 S
24V
+24 V GND B+ A-
BMT-AI8
1 C2 2 C2 3 C2 4 C2 S
X10
ERROR
BACnet MS/TP
X10
ERROR
BACnet MS/TP
24V
+24 V GND
BUSY
BUSY
B+ A-
1
2
3
4
24V
+24 V GND B+ A-
1
2
3
4
Jumper unter der Blende Jumper below the faceplate
Jumper unten: Klemmen S = 15 V DC (Werkseinstellung)
Jumper in bottom position: Contacts S = 15 V DC (Facotry setting)
Jumper unter der Blende Jumper below the faceplate
Jumper oben: Klemmen S = 24 V AC/DC
Jumper in top position: Contacts S = 24 V AC/DC
X1
X1
9. Connection examples
Passiver Fühler Passive sensor
8 C2 7 C2 6 C2 5 C2 S
24V
+24 V GND B+ A-
BMT-AI8
1 C2 2 C2 3 C2 4 C2 S
Halbleiter Sensor
Semiconductor sensor
ERROR
Pullup Widerstand
Pullup resistor
BACnet MS/TP
X10
X1
BUSY
Aktiver Fühler Active sensor
24V
+24 V GND B+ A-
1
24 V
2
J
3
15 V
4
METZ CONNECT GmbH
Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433 Mounting instruction see ww w.metz-connect.com
Loading...
+ 2 hidden pages