KVD is a group name for detectors in the Salwico gas alarm
programme for detection of explosive, toxic or inflammable
fluids and gases. KVD detectors are intended for use in
heavy-duty industrial environments and can be adapted for
detection of different gases depending on which semiconductor sensor it is equipped with.
The KVD detector consists of an aluminium junction box and
a sintered housing around the sensor. The KVD is connected
to the central unit via a screened 3-core cable.
KVD(COD) is intended for detection of carbon monoxide
(CO). The KVD(COD) also includes a dust filter to minimise
interference from other gases.
Dimensions (mm)
75
Technical data
Cable connection to See connection diagram
gas alarm central for gas detector
Enclosure protectionIP-54
Cable entry6 - 11 mm
Temperature range-40° - +85°C
Relative humidity0 - 95%
Material connection boxVarnished aluminium
Weight350 g
ColourGrey box with nickel-
plated sintered housing
86
53
111
Connection
Specifications may be subject to change for improvement without prior notice Data sheet no: 3242.01.1.E
The BUTOX ST400EC gas detector to measure oxygen,
toxic or flammable gases consists of a chrome plated
ABS-housing with transmitter print, sensor and sensor
holder in stainless steel.
The transmitter print is based on the “one man
calibration” technology. This means that one person can
make all the necessary calibrations inside the detector
head, without the necessity of a second calibration
procedure on the measurement module.
Data
Weight ~470 g
Material housing Chrome plated ABS
Sensor housing SS 316
Power supply 12-30 VDC
Signal 4-20mA (2-wire)
Sensor 2- or 3-electrode
Measuring principle Electrochemical cells
Temperature range -40°C to +60°C
Protection class IP65 (excl. sensor)
Cable entry Od Ø 8-13.5 mm
Optional certificate class* EEx ia IIC T6,
Measuring Range
CO 0-250 ppm
H
S 0-30 ppm
2
0-25 %
O
2
Sensors for other toxic gases are available upon request.
*If used with a specified safety barrier.
Dimensions (mm) Connection
T
-40°C to +60°C
amb
120
172
Mounting holes
110
122
145
55
90
43
Specifications may be subject to change for improvement without prior notice Data sheet no: 4461 04 1 E
The BUCOM ST600EX gas detector for combustible
gases is assembled with an EExd sensor, housing and
cable gland.
The transmitter is based on the so-called “one man
calibration” principle, which means that the calibration
takes place at the detector head only.
The sensor is a replaceable catalytic oxidation sensor and
consists of detection and reference elements that are
provided in a wheatstone bridge. When exposed to gas,
the bridge will be unbalanced and an electric signal
proportional to the gas-concentration will be converted to
a 4-20mA output signal.
Sensors for other explosive gases are available upon
request.
When installing BUCOM ST600EX in ventilation ducts,
the air duct mounting kit part. no. 4490 shall be used, see
separate drawing.
Data
Weight 2.8 kg
Material housing Steel coated
Sensor housing SS 316
Power supply 18-35 VDC
Power consumption 1.7 W
Output signal 4-20mA (3-wire)
Response time t90 < 15sec.
Sensor lifetime Min. 3 years in air
Measuring principle Catalytic
Measuring range 0-100% LEL
Temperature range -20°C to +60°C
Protection class IP65 (excl. sensor)
Cable entry Od Ø 10-16 mm
Ex class EEx-d IIC T6
Certificate KEMA No. Ex.99.E.1378
Cable spec. Shielded, min. 3x0.75mm
Cable resistance Max 100Ω at 24VDC
Dimensions (mm) Connection
194
2
Max 200Ω at 30VDC
Mounting holes
183
76
Specifications may be subject to change for improvement without prior notice Data sheet no: 4460 04 1 E
KVD-Ex är en detektor ingående i Salwico
gaslarmsprogram för detektering av
explosiva, giftiga och brännbara vätskor
och gaser. KVD-Ex är avsedd för tuff inomeller utomhusmiljö och den är godkänd för
installation i Ex-klassade områden, zon 1
eller motsvarande. KVD-Ex anpassas för
detektering av olika
çConsilium
gaser genom att den kan bestyckas med
olika halvledarsensorer.
KVD-Ex består av en kopplingsdosa av
polyester och ett sensorhus av rostfritt stål.
KVD-Ex är typgodkänd av Nemko.
u9090303.DOC 1(2)
Dimensioner (mm)
Anslutningar
Data
Kabelförbindning med
gaslarmscentral
Kapslingsgrad
kopplingsdosa
Kabelgenomföring10 – 15 mmEx-skyddsklassEEx de IIC T6
Temperaturområde-40 - +85Vikt900 g
Relativ fuktighet0 – 95%Färg kopplingsdosaSvart
Material kopplingsdosaPolyesterFärg sensorhusBlank metall
*) Hela detektorn håller IP-65 om den förses med speciellt stänkskydd för sensorhus. Se separat ritning.
Se separat
inkopplingsschema
Material sensorhusRostfritt stål
(SIS2343)
IP-65MätprincipHalvledare
(Figaro TGS)
Artikelnummer3122
u9090303.DOC 2(2)
çConsilium
CONSILIUM SECURITY SYSTEMS AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Besöksadress:
Salsmästaregatan 21
Ringön
GÖTEBORG
Telefon:
Nat 031-710 79 00
Int +46 31 710 79 00
Telex:
20660 consmar s
Telefax:
Nat 031-710 79 99
Int +46 31 710 79 99
Gas Detector
Salwico KVD-Ex
KVD-Ex is a detector type included in the
Salwico gas alarm program for detection of
explosive, toxic and inflammable fluids and
gases. KVD-Ex is intended for heavy
environments, both indoors and outdoors
and is approved for installation in Ex
classified areas.
çConsilium
KVD-Ex can be adapted to detect different
gases when equipped with semiconductor
sensors.
KVD-Ex consists of a junction box of
polyester type and a sensor housing of
stainless steel type.
KVD-Ex is type approved.
u9090302.DOC 1(2)
Loading...
+ 13 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.