Conrad RM 100-2 Uni-S, 75 06 66 Operating Instructions Manual

Version 12/06
OPERATING INSTRUCTIONS
Radio smoke detector „RM 100-2 Uni-S“
Item no. 75 06 66
Table of contents
Page
1. Introduction ................................................................................................................. 4
2. Prescribed use ............................................................................................................ 5
3. Scope of delivery ........................................................................................................ 6
4. Explanation of icons .................................................................................................. 6
5. Safety instructions ..................................................................................................... 7
6. Notes on batteries and rechargeable batteries ..................................................... 8
7. Features and functions .............................................................................................. 9
8. Selecting the installation location ......................................................................... 10
9. Installation ................................................................................................................. 13
10. Initial operation ......................................................................................................... 14
a) Setting the house code for the smoke detector### ........................................... 14
b) Setting the house code for the ‘FHZ 1000’ ......................................................... 15
c) Switching the ‘HMS 100’ function on and off ...................................................... 16
d) Starting the sensor search on the ‘HMS 100 Z’ ................................................. 17
e) Inserting the batteries into the smoke detector .................................................. 18
f) Starting the sensor search on the ‘HMS 100 Z’ ................................................. 19
g) Locking the smoke detector into its socket ........................................................ 19
11. Function control and operation ............................................................................. 20
a) Control panel & function test ............................................................................... 20
b) Alarm indicator on the ‘HMS 100 Z’ .................................................................... 21
c) Alarm indicator on the ‘FHZ 1000’ ...................................................................... 21
d) Periodic monitoring and error display ................................................................. 21
12. Wired connection of several smoke detectors .................................................... 23
13. Replacing the batteries ............................................................................................ 26
a) General information ............................................................................................. 26
b) Setting the ‘HMS 100 Z’ to the maintenance mode ........................................... 27
c) Replacing the batteries ....................................................................................... 28
d) Quitting the maintenance mode of the ‘HMS 100 Z’ .......................................... 29
Page
14. Escape plan ................................................................................................................30
15. Information on the radio range ............................................................................... 32
16. Maintenance and cleaning ....................................................................................... 33
17. Disposal ...................................................................................................................... 33
a) General information .............................................................................................. 33
b) Batteries and rechargeable batteries .................................................................. 33
18. The smoke detector’s signal output ....................................................................... 34
19. Declaration of conformity (DOC) ............................................................................. 34
20. Technical specifications ........................................................................................... 35
1. Introduction
Dear customer, Thank you for purchasing this product.
This product meets the requirements of both current European and national guidelines.
In order to preserve this condition and ensure the safe operation of the product we kindly ask you to carefully follow these operating instructions!
Please read the operating instructions completely and observe the safety and operation notes before using the product!
All company names and product names contained herein are trademarks of the respective owners. All rights reserved.
Should you have any further questions, please contact our technical advisory service: Germany: Tel. no.: +49 9604 / 40 88 80
Fax. no.: +49 9604 / 40 88 48 e-mail: tkb@conrad.de Mon. to Thur. 8.00am to 4.30pm Fri. 8.00am to 2.00pm
2. Prescribed use
The ‘RM 100-2 Uni-S’ smoke detector registers smoke emissions (smouldering fire and open fires with smoke emissions) and sets off an alarm when the smoke concentration reaches a certain level.
The alarm is carried out via the integrated signal transmitter and a red warning LED. A bright, white LED is also activated as an emergency light.
The smoke alarm is simultaneously radio-transmitted to the
‘HMS 100 Z’ central unit of the
‘HMS 100’ hazard detection system or the ‘FHZ 1000’ home radio central unit. This ensures that a fire, which is some distance away (on another floor of the house, for example), can be responded to in good time.
A smoke alarm can also be relayed by cable when several smoke detectors of this type are connected by cable.
This allows rooms to be monitored whose current conditions make radio
monitoring technically difficult.
For further information please see section 7.
The radio smoke detector should not be used in environments such as hospitals with life­support systems or other similar environments in which the transmission of radio signals may cause devices to malfunction.
Batteries must be used to power the smoke detector. The product should only be installed and operated in dry indoor locations. Make sure it does
not get damp or wet. No part of the device may be modified or adapted. Doing so invalidates the licence (CE) and
the guarantee/warrantee. The manufacturer does not assume liability for damages caused by the improper use of the
device. All guarantees and guarantee claims will be invalidated in such cases. The device may only be operated when its casing is fully closed.
All the safety instructions and installation notes in this manual must be observed without fail.
3. Scope of delivery
‘RM 100-2 Uni-S’ smoke detector
Spacers for mounting
User manual
4. Explanation of icons
The icon with a lightning flash in a triangle is used to alert you to potential
personal injury hazards such as electric shock.
The icon with an exclamation mark in a triangle points to important instructions
in this user manual that must be observed.
The ‘hand’ symbol provides special information and advice on operating the
device.
5. Safety instructions
The product’s guarantee becomes invalid, if the product is damaged as a result of the failure to observe these operating instructions! We do not assume any liability for any resulting damages!
Nor do we assume liability for damage to property or personal injury caused by improper use or failure to observe the safety instructions. In such cases the product’s guarantee becomes invalid.
Do not use this product in hospitals or medical institutions. Although the product emits only relatively weak radio signals, these may cause life-support systems to malfunction. This may also be the case in other areas.
If, during mounting, connection or installation you are not sure or have doubts about how to proceed, contact a skilled technician.
For safety and licensing (CE) reasons any unauthorised alterations to and/or modification of the product are not permitted.
The product is only approved for installation and operation in dry and closed indoor rooms. Make sure that the product does not get damp or wet. Do not expose the device to direct sunlight and avoid using it in dusty environments.
The smoke detector must not be painted or pasted over with wall paper.
This product is not a toy and should be kept out of the reach of children. The product should not be stored or used within the reach of children.
Do not leave packaging material lying around. This may become a dangerous plaything in the hands of children.
You should carry out a function test once a month by pressing the test button.
6. Notes on batteries and rechargeable batteries
For safety reasons, the smoke detector should not be operated using recharge­able batteries.
Due to the its low voltage (rechargeable battery = 1.2V, battery = 1.5V) the smoke alarm may perceive that the rechargeable battery is low even though it is fully charged. It then emits a soft signal tone every 48 seconds and the red LED blinks three times every 48 seconds.
Therefore, please make sure that you only use high-quality alkaline batteries (Conrad item no. 650117, for example. Order 3 batteries).
Keep batteries (and rechargeable batteries) out of the reach of children.
Make sure that the polarity is correct when inserting the batteries.
Do not leave batteries/rechargeable batteries lying around as they could be swallowed by children or pets. In such case seek immediate medical care.
Leaking or damaged batteries/rechargeable batteries may cause acid burns, if they come into contact with skin. Therefore, please make sure you use suitable protective gloves.
Make sure that batteries/rechargeable batteries are not short-circuited, taken apart or thrown into fire. They might explode!
Conventional batteries must not be recharged. They might explode!
If the device is not used for a longer period of time (when stored, for example), remove the inserted batteries. This way, you can prevent the aging batteries from leaking and causing damage.
For safety reasons, the device’s casing cannot be locked, if no batteries have been inserted!
7. Features and functions
The ‘RM 100-2 Uni-S’ smoke detector registers smoke emissions (smouldering fires and open fires with smoke emissions) optically using the scattered light principle.
When the smoke concentration reaches a specific level, the smoke detector activates the integrated signal transmitter. A red warning LED is also activated as well as a white LED, which serves as an emergency light.
A smoke alarm is simultaneously transmitted to an existing ‘HMS 100 Z’ central unit belonging to the ‘HMS 100’ hazard detection system or the ‘FHZ 1000’ home radio central unit.
This ensures that a fire, which is some distance away (on another floor of the house, for example), can be responded to in good time.
Furthermore, several smoke detectors in the ‘RM 100’ series can be connected by cable, allowing the smoke alarm to be relayed by cable.
This allows rooms to be monitored whose current conditions make radio monitoring technically difficult.
In order to avoid crossovers with other radio services operating on the 868 MHz frequency band, the system can be coded using a house code. This protects the system from false alarms caused by other radio transmitters operating in the same frequency range.
10
1m
8. Selecting the installation location
We generally recommend that several smoke detectors be installed in a building or an apartment. One smoke detector should defi­nitely be installed on each floor of a multi­storey building. This is the only way to en­sure that an effective warning is issued in time when a fire starts.
Smoke detectors should be installed in such a way that they safeguard a route to the bedroom (entrance area, hall or stairway). And, when an alarm sounds, they must also be audible through a closed bedroom door.
The smoke detector should always be mounted to the centre of a room’s ceiling.
Bedroom Hallway
Study Living
room
Children’s room
Entrance area Kitchen
Minimal protection Recommended protection
When installed in an attic room with a pointed roof, the smoke detector should not be attached to the highest point of the room as here there is hardly any movement of air. An ideal installation location would be a roof beam or an overhang beam.
Smoke
Air pockets that keep the rising smoke away collect close to the walls, and also in the corners of rooms and where there are sharp-angled ceilings. This makes the smoke detector take a lot longer to detect smoke and trigger its alarm.
11
In normal rooms, the smoke detec­tor should be installed at least 60 cm away from the corners of the room.
Radiators, window sills, windows and even furniture affect the circu­lation of air.
Ideally you should mount it to the ceiling in the centre of the room.
60cm60cm
60cm
Smoke
If you select an unsuitable installation location the smoke detector will remain more or less useless when a fire starts; only triggering an alarm when the smoke concentration reaches a very high level.
This will significantly reduce the amount of time available for saving yourself and others from danger or for extinguishing the fire.
Window sills, curtains or furniture strongly influence the circulation of air, and thus, the movement of smoke. They create a zone of dormant air. This means that rising smoke does not reach the smoke detector or it reaches it too late!
We generally recommend that the smoke detector be mounted to the ceiling in the centre of a room. However, you should make sure that you do not install the device directly under any lights (halogen lamps, for example).
You can check whether the alarm is sufficiently loud enough to wake someone up from its installation location by setting off a test alarm (see ‘Installation’) while someone is asleep in the bedroom.
The smoke detector should be loud enough to wake people up! It should not just be audible!
You should also carry out extensive checks to make sure that the radio signals sent by each of the smoke detectors from their installation locations will reach the ‘HMS 100 Z’ or ‘FHZ 1000’ central unit.
In general, reception problems are not experienced in most single family houses. As you can see in section 15 (‘Information on the radio range’), however, many things can restrict the radio reception.
12
For example, reinforced concrete ceilings or electric floor-heating systems can hinder reception between several floors.
Electric cables, electric devices or metal objects can also reduce the range.
It can be difficult to install the smoke detector in the following rooms and locations:
Kitchen/bathroom: False alarms due to kitchen steam or high levels of humidity
Garages: False alarms due to exhaust gases from cars, motorcycles or other combustion engines
Living rooms with an open fireplace: False alarms due to escaping smoke
Dusty and dirty rooms: Dirt on the measurement chamber causes the smoke detector to become less sensitive so that the alarm is activated later or not at all
Places with a strong movement of air: Late smoke detection and alarm due to the proximity of windows, fans, lamps, lamp tubes, halogen transformers, radiators, fireplaces
Proximity to metal/electric devices: Deterioration of the radio range due to steel beams, large metal surfaces, metal doors, televisions, power cables and so on
Smoke from tobacco: False alarms as the smoke detector cannot differentiate between ‘harmless’ tobacco smoke and a real fire
Some smoke detectors have a sensitivity setting. The disadvantage of this, however, is that the alarm is triggered late when a ‘real’ fire occurs, and this shortens the response time considerably. The time that is available for extinguishing the fire, for saving people or for escaping is considerably reduced!
13
9. Installation
Please make sure you read the information on selecting an installation location provided in section 8.
Remove the smoke detector’s upper plate by carefully twisting the upper plate and the lower plate against each other (anticlockwise).
The upper and lower plates can only be locked firmly, once the batteries have been inserted.
A
B
C
A Mounting holes for installation using an
installation box B Holder for cable ties C Alternative installation using spacers
You can use the two mounting holes to screw the lower plate securely to a wall or a ceiling, for example.
Depending on the type of surface, you may have to first drill two mounting holes and insert suitable dowels.
When drilling or screwing be careful not to accidentally damage any power supply lines, gas or water pipes. Life-threatening danger!
Alternatively, the lower plate can be mounted using the two spacers (if cables run under the smoke detector, for example) or via the screws of an installation box.
14
0 000
1 001
2 002
3
003
4
004
5
005
6
006
7
007
8
008
9
009
10
010
11
011
12
012
13
013
14
014
15
015
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
1
2345
ON DIP
10. Initial operation
Initial operation varies for the two ‘HMS 100’ and ‘FHZ 1000’ systems. Please make sure you read the following subsections.
a) Setting the house code for the smoke detector
You only need to set this house code, if the smoke detector is operated as part of the ‘FHZ 1000’ system!
House code RM100-2 Uni-S FHZ1000
Code on the display
Use the DIP switches 1 to 4 to set a house code (freely selectable between 0 and 15).
The same code must also be set for the ‘FHZ 1000’.
This code stops neighbouring radio smoke detectors from triggering unin­tentional alarms on the ‘FHZ 1000’.
15
b) Setting the house code for the ‘FHZ 1000’
You only need to set this house code, if the smoke detector is operated as part of the ‘FHZ 1000’ system!
Proceed as follows:
Press the ‘x’ button on the ‘FHZ 1000’.
Turn the scroller on the ‘FHZ 1000’ until ‘
Sonderfkt.Sonderfkt.
Sonderfkt.Sonderfkt.
Sonderfkt.’ appears on the display.
Keep the ‘PROG’ button pressed until ‘
Ext. AlarmExt. Alarm
Ext. AlarmExt. Alarm
Ext. Alarm’ appears on the display of the ‘FHZ
1000’.
Use the scroller to set the house code that you previously set for the ‘RM 100-2 Uni-S’ smoke detectors.
Press the ‘PROG’ button. The setting is applied and the menu closes.
It is not necessary to separately register the smoke detector to the ‘FHZ 1000’. Only the alarm priority may still need to be set up according to the FHZ 1000’s user manual.
16
c) Switching the ‘HMS 100’ function on and off
The ‘RM 100-2 Uni-S’ radio smoke detectors transmit a status signal every 30 minutes (including, amongst other things, the battery level) to the ‘HMS 100 Z’ central unit.
DIP switch 5 must be in the ‘ON’ position for this function to work.
1
2345
ON DIP
‘HMS 100’ function on
If you do not intend to operate the smoke detector as part of the ‘HMS 100’ system, you can use DIP switch 5 to switch off the ‘HMS 100’ radio protocol.
This extends the battery life.
1
2345
ON DIP
‘HMS 100’ function off
Alarms are still transmitted to the ‘FHZ 1000’ home radio central unit irrespec- tive of this setting, provided that the house code matches.
17
d) Starting the sensor search on the ‘HMS 100 Z’
You only need to set this, if the smoke detector is operated as part of the ‘HMS 100’ system!
Proceed as follows:
When the ‘HMS 100 Z’ is in normal operation, press the ‘MENU’ button. ‘
StörungenStörungen
StörungenStörungen
Störungen
bearbeitenbearbeiten
bearbeitenbearbeiten
bearbeiten’ appears on the display.
Use the scroller or the ‘x’ and ‘w’ buttons to select the ‘
Sensor einstellenSensor einstellen
Sensor einstellenSensor einstellen
Sensor einstellen” menu
item.
Press the ‘OK’ button. ‘
Sensor hinzufügenSensor hinzufügen
Sensor hinzufügenSensor hinzufügen
Sensor hinzufügen’ appears on the HMS 100 Z’s display.
Press the ‘OK’ button again. ‘
SensorsucheSensorsuche
SensorsucheSensorsuche
Sensorsuche’ appears on the display.
Now insert the batteries into the smoke detector, as described in section 10 e).
Then complete the registration. See section 10 f).
18
e) Inserting the batteries into the smoke detector
Have you already set the ‘HMS 100 Z’ to the sensor search mode?
If you have not done so already, remove the batteries and first follow the instructions provided on the previous page in section 10 d).
Insert three new AA batteries (LR06, Conrad item no. 650117, for example) into the three battery holders, making sure that the polarity is correct. Useful figures are located in the battery compartments.
As described in chapter 6, we recommend that you use high-quality alkaline batteries.
Once the batteries have been inserted, the red control indicator blinks approx. every 48 seconds to signal that the smoke detector is ready to be used.
+
+
+
-
-
-
+
-
+
+
-
-
19
f) Completing the sensor search on the ‘HMS 100 Z’
You only need to set this, if the smoke detector is operated as part of the ‘HMS 100’ system!
Once the central unit has received the signal from the radio smoke detector, ‘
Sensor xxSensor xx
Sensor xxSensor xx
Sensor xx
(xx = 01-30) appears on the display. The smoke alarm symbol is also displayed. A cursor appears on the lower display line (entry bar). Here you can enter a name for the
smoke detector in plain text that is up 11 positions long.
Use the ‘x’ and ‘w’ buttons to select the desired entry position (this also allows you to enter space characters) and use the scroller to set the character you require (alphabet, umlauts, digits, space characters) at the cursor position.
Then select the next position using the ‘x’ and ‘w’ buttons and repeat the procedure until you have entered the complete name.
You can also use the ‘x’ and ‘w’ buttons and the scroller to subsequently modify the text you have entered.
You can also delete characters that have been entered using the space character (after ‘9’ or before ‘A’). You can delete the whole name all at once using the ‘Löschen’ button (= ‘Delete’).
Once you have entered the name, press ‘OK’.
g) Locking the smoke detector into its socket
Insert the smoke detector into the mounted lower plate by turning it clockwise. The red triangles
fitted in the lower plate and in the smoke detector help you to position it correctly.
Please note: For safety reasons, the two parts of the casing (lower plate/smoke
detector) cannot be locked, if no batteries have been inserted!
20
11. Function control and operation
a) Control panel & function test
After mounting the smoke detector you should carry out a function test.
A
B
C
A Opening for acoustic signal trans-
mitter B Test button with LED indicator C Optical signal transmitter (emer-
gency light) lights up together with
the acoustic signal transmitter
Blow tobacco smoke, for example, onto the smoke detector. Once the smoke has penetrated the smoke chamber inside the smoke detector, the alarm is activated, so long as smoke is still located in the smoke detector’s smoke chamber.
A triggered alarm is signalised by an acoustic and an optical signal (about every second).
The alarm is automatically terminated after 48 seconds once the smoke alarm’s electronics in the smoke chamber no longer detect any smoke.
The red control indicator of the triggering smoke alarm continues to blink for about ten minutes after the alarm has terminated. This makes it easier to find the triggering alarm when there is a false alarm, for example.
Pressing the test button for approx. 2 seconds (press the button up to the pressure point) causes the acoustic alarm to stop for approx. 10 minutes.
If there is still smoke in the smoke chamber, the LED continues to blink. Otherwise the alarm stops completely.
21
b) Alarm indicator on the ‘HMS 100 Z’
When an alarm is triggered the ‘ ’ symbol should appear on the central unit’s display (select display type ‘Aktuell’).
The smoke detector transmits a status signal to the control centre every 30 minutes, which serves to control the connection and also includes the battery level.
c) Alarm indicator on the ‘FHZ 1000’
An acoustic signal is used to audibly indicate that an alarm has been triggered, while an exclamation mark appears on the lower left of the display to optically indicate that an alarm has been triggered.
d) Periodic monitoring and error display
You can find an overview of the smoke detector’s optical and acoustic output in section 18.
You should check that the smoke detector is working once a month. To do this, press the test button for approx. 2 seconds (press the button to the pressure point).
If the acoustic signal sounds once and the LED blinks 10 times, then the smoke detector is working properly.
If, after pressing the button, only the LED starts to blink, then the smoke detector is faulty and must be replaced.
If no signals are emitted, then the batteries are flat. Replace the old batteries with a complete set of new batteries.
22
To replace the batteries make sure you follow the instructions provided in section 13.
For safety reasons, a particular procedure must be followed when replacing the batteries,
if the smoke detector is part of a ‘HMS 100’ radio system (the central
unit stores the battery level as a ‘fault’ (= ‘Störung’)).
Note that the ‘HMS 100 Z’ should first be set to the maintenance mode before its batteries can be replaced!
If the batteries are in good condition, then the smoke detector is likely to be faulty and must be replaced.
23
12. Wired connection of several smoke detectors
Many installation locations allow no radio reception or only poor reception. This may be due to how the building is constructed, for example, (reinforced concrete, metal-dampened insulation glass windows, metal doors and so on). Also see section 15 ‘Information on the radio range’.
To ensure that an alarm is still triggered when a fire with smoke emissions starts, the smoke alarms can be connected to each other by cable.
This also allows a smoke detector to relay an alarm over long distances (from neighbouring buildings, garages and so on). You can also connect any existing ‘RM 100’ smoke detectors without radio at any time.
A twisted, two-core connecting cable should be used (of the type ‘J-Y(ST)Y2 x 2 x 0.6mm’, for example, or a similar rigid installation cable). A total cable length of up to 400m is feasible in the ideal case.
You can connect up to 40 smoke detectors of the type ‘RM 100’ with one another via cable (in the case of a radio connection you can connect any number of smoke detectors).
Proceed as follows to connect the cables:
First of all, remove any batteries that may be inserted in the smoke alarms.
When the cables are wall-mounted (in a garage or in a neighbouring building, for example) the smoke detector’s lower plate should be mounted using the supplied spacers so that you can lay the cables under the smoke detector and then lead them inside the casing. Otherwise, the cables will get damaged/pinched.
Guide the cables through the lower plate’s opening and use a cable tie to fix them, at the length you require, to the lower plate’s holder. Allow for enough additional cable length so that you have no difficulty in replacing the batteries later.
Strip the cable ends at a length of approx. 6mm.
24
+
-
+
-
-
-
-
+
+
+
+
-
-
-
-
+
+
+
-
-
-
+
+
+
-
-
-
+
+
+
+
-
Observe the correct polarity!
Cable terminal
Installation of cable in the de­vice when using radio modules
Avoid contacting the cable with the antenna loop on the circuit board!
25
Pull the cable terminal out slightly and insert the stripped cable ends into the terminals.
When doing so, make sure you observe the correct wiring, see the figure above! Always connect the positive terminals with one another and then the negative terminals. Connecting these incorrectly will destroy all the smoke detectors! Markings illustrating the polarity (+/-) are embossed next to the cable terminal.
Reinsert the cable terminal and check once again that the polarity of the wiring is correct.
Connect the smoke detectors as shown in the figure on the previous page. Always observe the correct wiring/polarity. Guide the cable from the first smoke detector to the second one then to the third one and so on.
Insert batteries into each of the smoke detectors, making sure that the polarity is correct.
Place the smoke detector onto the lower plate and lock it.
Guide the cables through the opening of the module cover plate and then outwards. When placing the smoke detector on the lower plate, make sure that the cables are not clamped while sealing.
Any additional cable length (which is required to help you replace the batteries easily!) can be stored in the shaft in front of the cable terminal.
Too many cables above the module cover plate can impair the radio range.
Carry out a function test for each of the mounted smoke detectors as described in section
11.
When carrying out a normal (periodic) function test by pressing the test button up to the pressure point for approx. 2 seconds only the one smoke detector, which is being operated/tested, is activated.
Only when a genuine smoke alarm occurs (triggered by tobacco smoke, for example) are all the cable-connected smoke detectors set off.
However, the red LED only blinks on the smoke detector that set off the alarm.
If, in the case of a ‘genuine’ smoke alarm, one or several smoke detectors do not trigger an alarm, please check the wiring (make sure that the polarity is correct!)
26
13. Replacing the batteries
a) General information
Stop a moment! Please read the following pages before you replace the batteries.
When high-quality alkaline batteries are used, the batteries in the smoke detector can last for longer than 3 years (if no alarm is set off).
When using conventional devices you normally only notice that their batteries are flat when the devices no longer work (in the case of a radio or a remote control, for example).
When using an important device such as a smoke detector, however, this could have fatal consequences!
For this reason, the smoke detector emits a short alarm signal (approx. every 48 seconds) when the capacity of the battery reaches a specific level. In addition, the red LED blinks three times every 48 seconds.
The smoke detector’s battery level is evaluated, displayed and stored as a fault by the ‘HMS 100 Z’.
For this reason, a particular procedure must be followed when replacing the batteries.
To proceed, please follow the instructions provided on the following pages.
27
b) Setting the ‘HMS 100 Z’ to the maintenance mode
You only need to set this, if the smoke detector is operated as part of the ‘HMS 100’ system!
In normal operation press the ‘MENU’ button. ‘
Störungen bearbeitenStörungen bearbeiten
Störungen bearbeitenStörungen bearbeiten
Störungen bearbeiten’ appears
on the display.
Use the scroller or the ‘x’ or ‘w’ buttons to select the ‘
Sensor einstellenSensor einstellen
Sensor einstellenSensor einstellen
Sensor einstellen’ menu
item.
Press the ‘OK’ button.
Use the scroller or the ‘x’ or ‘w’ buttons to select the ‘
Sensor wartenSensor warten
Sensor wartenSensor warten
Sensor warten’ menu item.
Press the ‘OK’ button.
Now you can use the ‘x’ or ‘w’ buttons to limit the sensor selection to the ‘Rauchmelder’ (smoke detector) sensor type. The other sensors are then removed from the symbol line.
Then use the scroller to select the desired sensor/smoke detector.
Press the ‘OK’ button.
•‘
SensorsucheSensorsuche
SensorsucheSensorsuche
Sensorsuche’ appears with the name of the sensor concerned below it.
Now replace the batteries in the smoke detector as described in section 13 c).
Then quit the maintenance mode. See section 13 d).
28
d) Replacing the batteries
If you have registered the smoke detector with a ‘HMS 100 Z’, you should first set the central unit to the maintenance mode. Do not remove the batteries yet! To do this, please read the instructions provided on the previous page in section 13 c).
Turn the smoke detector anticlockwise and remove it from the socket.
Remove the used batteries from the battery compartments.
Do not throw the used batteries into the household rubbish! Dispose of the batteries according to the applicable environmental regulations. See the ‘Disposal’ section.
You may be able to use any remaining capacity of the batteries in noncritical devices such as radios, clocks and so on.
Insert three new AA batteries (LR06), making sure that the polarity is correct (plus/+ and minus/-). Useful diagrams are located in the battery compartment. See section 10 e).
For safety reasons, the use of rechargeable batteries is not authorised. See section 6.
Once the batteries have been inserted, the red control indicator blinks approx. every 48 seconds to signal that the smoke detector is ready to be used.
Lock the smoke detector into the socket by turning it clockwise. The red triangles fitted in the socket and in the smoke detector should help you to position it correctly
.
For safety reasons, the smoke detector cannot be locked to the socket, if no batteries have been inserted.
29
d) Quitting the maintenance mode of the ‘HMS 100 Z’
You only need to set this, if the smoke detector is operated as part of the ‘HMS 100’ system!
Once the central unit has received the sensor’s new address, it transmits the following notification ‘
Sensor x, xxSensor x, xx
Sensor x, xxSensor x, xx
Sensor x, xx” (x = old address, for example, ‘01’, xx = old name, for
example, ‘TF’).
The sensor is now registered again with its available data.
Now press the ‘MENU’ button. The display returns to normal operation.
30
14. Escape plan
Even if, at first glance, you think this seems overcautious: Establish an escape plan for each room of your house or apartment.
The plan should include the following:
The fastest and safest way out of the building
The place where keys are kept so that locked cellar doors, terrace doors, windows and so on can be opened in case of an emergency
Location of fire extinguishers or rescue blankets
Emergency telephone numbers of the fire brigade and emergency doctor
Telephone numbers of neighbours, other tenants, caretaker and so on so that these can also be alerted
If there is a fire, do not waste time looking for important documents, papers or IDs, which could be destroyed by the fire. By doing this you waste the few seconds or minutes that could save lives.
Simply make copies of important documents (personal ID, driver’s licence and so on). You can use a conventional copier, digital camera or scanner. Store the copies in a safe-deposit box, for example.
Consider the following points for each room:
What are the possible sources of fire? Electrical equipment, for example?
How can dangers be avoided?
Is the escape route cut off? How can one still get out?
How can I get to the keys I need?
How far is it to the next fire extinguisher?
It is too late to think about these things once a fire has already started. Although fires in apartments are relatively rare in Europe, there are many
causes for such fires, such as faulty electrical equipment, amateurish electrical installations, as well as children playing with fire or candles that have been forgotten about.
31
Prefabricated buildings that have a lot of wooden elements are more susceptible to fire than conventional buildings, which are made of stone. However, the dangers posed by carpets, wooden ceilings, wooden floors, furniture, curtains and so on are the same for both types of buildings.
Flames are less dangerous than the toxic smoke that is generated by a fire.
Even the best escape plan is of little use, if other family members are not familiar with it or they do not know what they should do when a fire alarm sounds.
Organise a family meeting in order to discuss the escape plan.
Explain to each person what they should do in the event of a fire or a smoke alarm.
Choose a location outside your house where you can meet after you have managed to get out of the building. This way, you can easily check to see, if anyone is missing.
Acquaint all family members with the smoke detector’s acoustic signal.
Every 6 months go over what should be done in the event of a smoke alarm or a fire. Practise using fire extinguishers or rescue blankets
32
15. Information on the radio range
Ranges and interference
The smoke detector works in the 868 MHz range, which is also used by other radio services.
Therefore devices that operate on the same or neighbouring frequencies may restrict both its operation and its range.
The specified range of up to 100m is the so-called free-field range, which means the range within visual contact between the transmitter and receiver. In practice however, there are ceilings, walls, garages or adjoining buildings between the transmitter and the receiver that affect and reduce the range accordingly.
The actual attainable distance between the transmitter and receiver in normal operation depends very much on the installation location and the environment.
As a rule – when mounted in a family home, for example – the smoke detector should work properly and there should be no radio reception problems.
Other causes of reduced ranges:
All types of high-frequency interference
Any buildings or vegetation
Conductive metal parts that are located near the devices or within or near their transmission path, for example, radiators, metallised insulation glass windows, reinforced concrete ceilings, etc.
Influence on the radiation pattern of antennas due to the distance from the transmitter or receiver to conductive surfaces or objects (also to human bodies or the ground)
Broadband interference in urban areas that reduces the signal-to-noise ratio; the signal is no longer recognised due to this ‘noise’
Interference radiation resulting from insufficiently shielded electronic devices, for example, operating computers or similar
33
16. Maintenance and cleaning
The product requires no servicing except for battery replacement. Any repairs should be carried out by a skilled technician or professional workshop. Clean the product with a soft, clean, dry and lint-free cloth. To remove heavier dirt, use a cloth which is slightly moistened with lukewarm water. Do not use any solvent-based cleaning agents as these may damage the plastic casing. Dust can be removed using a longhair brush and a vacuum cleaner.
17. Disposal
a) General information
When the product is no longer usable, dispose of it in accordance with the applicable statutory regulations.
b) Batteries and rechargeable batteries
As the consumer, you are legally obliged to return all your used batteries and rechargeable batteries. Do not dispose of your used batteries via the household rubbish!
Batteries/rechargeable batteries containing harmful substances are marked with the following icons, which alert you to the fact that disposal via the household rubbish is prohibited. The identifiers for the respective heavy metals are: Cd=cadmium, Hg=mercury, Pb=lead (identifier is on the battery/recharge­able battery, for example, under the rubbish bin icons on the left).
You can return your used batteries/rechargeable batteries free of charge to any authorised disposal station in your area, in our stores or in any other store where batteries/rechargeable batteries are sold.
By doing so you comply with your legal obligations and also make a contribution to environ­mental protection.
34
18. The smoke detector’s signal output
Operating state
Normal operation
Function test OK
Function test faulty
Local smoke alarm
Smoke alarm from another detector
Weak battery
optical/red LED
blinks every 48 sec.
blinks 10 times
blinks every second
blinks every second
blinks every 48 seconds
blinks 3 times every 48 seconds
acoustic/signal tone/ white LED indicator
-
short signal tone
-
3 short tones every 4 seconds, white LED indicator is activated
3 short tones every 4 seconds, white LED indicator is activated
short signal tone every 48 seconds
19. Declaration of conformity (DOC)
We, Conrad Electronic, Klaus-Conrad-Straße 1, D-92240 Hirschau (Germany), hereby declare that this product complies with the fundamental requirements and other relevant regulations of directive 1999/5/EG.
You can find the declaration of conformity for this product at www.conrad.com.
35
20. Technical specifications
Frequency: ............................................................... 868MHz
Range: ...................................................................... up to 100m (in free-field)
Power supply: .......................................................... 3 x AA batteries (LR06)
Protection class: ...................................................... IP30
Ambient temperature: .............................................. 0°C to 50°C
Storage temperature: ............................................... -25°C to +70°C
Relative humidity: .................................................... 5% to 93% (non-condensing)
Internal signal transmitter: ....................................... >85dB(A)/3m
Dimensions (dia. x H): ............................................. 120mm x 44mm
Max. cable length for cable connection: ................. 400m (J-Y(St)Y2 x 2 x 0.6mm)
Max. no. of devices for cable connection: .............. 40
You can choose to operate the smoke detector as part of the ‘HMS 100 Z’ system or the ‘FHZ 1000’ system.
For the ‘FHZ 1000’, the house code set for the smoke detectors must also be used.
CONRAD IM INTERNET http://www.conrad.com
http://www.conrad.com
Imprint
These operating instructions are published by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau/Germany.
No reproduction (including translation) is permitted in whole or part e.g. photocopy, microfilming or storage in electronic data processing equipment, without the express written consent of the publisher.
The operating instructions reflect the current technical specifications at time of print.We reserve the right to change the technical or physical specifications.
© Copyright 2006 by Conrad Electronic SE. Printed in Germany.
100% recycling paper.
Bleached without chlorine.
Loading...