INSTALLATION AND OPERATING INSTRUCTIONS
Adiabatic Humidifiers
2529324 EN 1112
Condair SH2
Page 2
Page 3
3
Contents
3.3.2
System overview model “flow” 11
3.6.2
System overview model “REflow” 17
4.1 Important notes on the mounting and installation work 23
6.4.1 Dismantle and install the mist eliminator and humidification boxes 53
Page 4
4
Limitation
The subject of these installation and operating instructions is the adiabatic air humidifier Condair SH2. The various accessories are only described insofar as this is necessary for proper
operation of the equipment. Further information on accessories can be obtained in the respective instructions.
These installation and operating instructions are restricted to the installation, commissioning, op- eration, servicing, and trouble-shooting of the adiabatic air humidifier Condair SH2 and is meant for well trained personnel being sufficiently qualified for their respective work.
The installation and operating instructions are supplemented by various separate items of documenta­tion (spare parts list, manuals for accessories, etc.). Where necessary, appropriate cross-references are made to these publications in the installation and operating instructions.
1 Introduction
We thank you for having purchased the Adiabatic Air Humidifier Condair SH2.
The adiabatic air humidifier Condair SH2 incorporates the latest technical ad van ces and meets all recognized safety standards. Nevertheless, improper use of the adiabatic air humidifier Condair SH2 may result in danger to the user or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the adiabatic air humidifier Condair SH2, please observe and comply with all information and safety instructions contained in the present installation and operating instructions as well as in the separate documentations of the components installed in the humidification system.
If you have questions, which are not or insufficiently answered in this documentation, please contact your Condair supplier. They will be glad to assist you.
1.2 Notes on the installation and operating instructions
1.1 To the very beginning
Page 5
5
Symbols used in this manual
CAUTION!
The catchword “CAUTION” designates notes in this installation and operating instructions that, if neglected, may cause damage and/or malfunction of the unit or other material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this installation and operating instructions that, if neglected, may cause to
injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol designates safety and danger notes in this installation and operating instructions that, if neglected, may lead to severe
injury or even death of persons.
Safekeeping
Please safeguard these installation and operating instructions in a safe place, where they can be immediately accessed. If the equipment changes hands, the documentation must be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair supplier.
Language versions
These installation and operating instructions are available in various languages. Please contact your Condair supplier for information.
Copyright protection
The present installation and operating instructions is protected under the Copyright Act. Passing-on and reproduction of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnification.
The manufacturer reserves the right to fully exploit commercial patent rights.
Page 6
6
2 For your safety
General
Every person working with the Condair SH2 must have read and understood the installation and operating instructions before carrying out any work. Knowing and understanding the contents of the installation and operating instructions is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All ideograms, signs and markings applied to the unit must be observed and kept in readable state.
Qualification of personnel
All work (installation, operating, servicing , etc.) described in these installation and operating instruc­tions may only be carried out by specialist who are well trained and adequately qualified and are authorized by the customer. For safety and warranty reasons any action beyond the scope of this manual must be carried out only by qualified personnel authorised by the manufacturer.
It is assumed that all persons working with the Condair SH2 are familiar and comply with the ap­propriate regulations on work safety and the prevention of accidents.
Intended use
The adiabatic air humidifier/cooler Condair SH2 are intended exclusively for air humidification/air cooling in air ducts or monoblocs within the specified operating conditions (see chapter 9 “Prod-
uct specifications”. Any other type of application, without the written consent of your Condair sup­plier, is considered as not conforming with the intended purpose and may lead to the Condair SH2 becoming dangerous. Operation of the equipment in the intended manner requires that all the information in these instructions are observed (in particular the safety instructions).
Page 7
7
Danger that may arise from the unit
DANGER! Danger of electric shock!
Some components of the Condair SH2 are mains powered. One may get in touch with live parts when the control unit or the distribution boxes are open. Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work set the Condair SH2 out of operation as described in
chapter 5.4 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
WARNING!
The UV lamp used in the water treatment unit (option) emits harmful UV-C rays. If the UV lamp is operated outside the housing, the emitted UV-C rays may damage the eyes and the skin lasting.
Prevention: Never operate the UV lamp outside the housing.
WARNING!
Badly maintained humidifiers can endanger the health. If the unit is insufficient maintained ill-making germs may grow in the water tub and the humidification boxes (and the mist eliminator) of the Condair SH2 and may can affect the air passing through the humidifier.
Prevention: The Condair SH2 must be cleaned in the prescribed intervals according to the infor-
mation given in chapter 6 “Maintenance". The cleaning works must be carried out correctly and the humidification boxes and the mist eliminator boxes must be replaced after their prescribed lifetime has elapsed.
.
Behaviour in case of danger
If it is suspected that safe operation is no longer possible, then the Condair SH2 should immedi- ately be shut down and secured against accidental power-up according to chapter 5.4. This can be the case under the following circumstances:
– if the Condair SH2 is damaged – if the Condair SH2 is no longer operating correctly – if connections and/or piping are not sealed – if electrical cables are defective
All persons working with the Condair SH2 must report any alterations to the unit that may affect safety to the owner without delay.
Prohibited modifications to the unit
No modifications must be undertaken on the Condair SH2 without the express written consent
of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts available from your Condair supplier.
Page 8
8
Condair AG, CH-8808 Pfäffikon
Made in Switzerland
SH2 REflow SC
Befeuchtungsleistung = 150.0 kg/h Fliessdruck 2...10 bar max. 45°C
REflow SC 300 1800 2000 1 150
230V 1~ / 50Hz 393 VA
XXXXXXX
03.07
3 Product overview
3.1 Model overview
The Condair SH2 is available in the two base versions “flow” with direct water system and “REflow” with circulating water system. The following base models are available:
Condair SH2 flow
Condair SH2 flow C (with control unit RC and On/Off control)
Condair SH2 flow SC (with control unit SH2 and step control)
Condair SH2 REflow
Condair SH2 REflow C (with control unit SH2 and On/Off control)
Condair SH2 REflow SC (with control unit SH2 and step control)
All base models can be extended in their functions by different options. In addition there are different accessories available for all models.
The product designation and the most important unit data are found on the rating plate:
Type designation Serial number Month/Year
Supply voltage
Humidification capacity
Admissible water supply pressure
Certificates
3.2 Product designation
Type key
Power consumption
Page 9
9
Example:
Condair SH2 REflow SC 300 1800 2000 0 150
Model:
flow flow C flow SC REflow REflow C REflow SC
Depth of humidification box:
200 mm 300 mm
Order code width W
Order code height H
Mist eliminator: No mist eliminator (can be retrofitted): 0 Mist eliminator 100 mm: 1 Mist eliminator 200 mm: 2
No mist eliminator (can not be retrofitted): 3
Humidification capacity in kg/h according layout
Type key
Page 10
10
3
1
2
4
5
6
7
8
3.3 Model “flow”
3.3.1 Construction model “flow”
1 Water connection on unit R 3/4" (outside thread) 2 Volume controlling valves (adjustable manually) 3 Water tub 4 Open drain (ø 40/34 mm) 5 Water hoses 6 Trickling hoods with distribution pipes 7 Humidification boxes 8 Mist eliminator (for air speed above humidification boxes >3.8 m/s)
Page 11
11
3.3.2 System overview model “flow”
Functional description
In case of a humidification/cooling request the supply valve (building side) opens and the water flows via the pressure reducing valve (accessory), the water filter (accessory) and the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub and then directly to the drain.
Shut-off valve
Pressure reducing valve
Water filter
Volume controlling valves (adjustable manually)
Water tub
Open drain
Siphon (building side)
Humidification boxes
Water supply
2...10 bar
Control: via humidistat that actuates the supply valve depending on the humidification requests
Water connection unit (accessory)
Drain funnel (building side)
Supply valve (building side)
Page 12
12
3
1
2
4
5
6
7
8
9
3.4 Model “flow C”
3.4.1 Construction model “flow C”
1 Water connection on unit R 3/4" (outside thread) 2 Volume controlling valves (adjustable manually) 3 Water tub 4 Open drain (ø 40/34 mm) 5 Water hoses 6 Trickling hoods with distribution pipes 7 Humidification boxes 8 Mist eliminator (for air speed above humidification boxes >3.8 m/s) 9 Control unit RC
Page 13
13
L1 N S S
NL1PE
%rH
3.4.2 System overview model “flow C”
Functional description
The “flow C” model provides On/Off control by means of the RC control unit and an external On/Off humidistat. In case of a humidification/cooling request the supply valve opens and the water flows via the pressure reducing valve (accessory), the water filter (accessory) and the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub and then directly to the drain.
Shut-off valve
Pressure reducing valve
Water filter
Volume controlling valves (adjustable manually)
Water tub
Open drain
Siphon (building side)
Humidification boxes
Water supply
2...10 bar
Control unit RC
Water connection unit (accessory)
Input: Potential free contact 230 V
Output: Supply valve
Humidistat 230V/2A
Drain funnel (building side)
Supply valve
Page 14
14
4
1
2
5
6
7
8
9
3
10
11
3.5 Model “flow SC”
3.5.1 Construction Model “flow SC”
1 Water connection on unit R 3/4" (outside thread) 2 Volume controlling valves (adjustable manually) 3 Step valves (1 to 3) 4 Water tub 5 Open drain (ø 40/34 mm) 6 Water hoses 7 Trickling hoods with distribution pipes 8 Humidification boxes 9 Mist eliminator (for air speed above humidification boxes >3.8 m/s) 10 UV water treatment (option) 11 Control unit SH2
Page 15
15
3.5.2 System overview model “flow SC”
Shut-off valve
Functional description
The “flow SC” model provides multistep control by means of the SH2 control unit and the step valves (1, 2 or 3 step valves depending on the humidifier capacity). The SH2 control unit (for wall mounting) processes analog sensor/control signals and uses them to control the step valves. This allows multistep control (1 to 3 steps depending on the humidifier capacity) which improves control accuracy compared to the “flow” model.
In case of a humidification/cooling request one, two or all three step valves open (depending on the request). The water flows via the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub and then directly to the drain.
If the “flow SC” model is equipped with the optional UV water treatment (installed in the water supply) the water is continuously degerminated during the humidification process.
Pressure reducing valve
Water filter
UV water treatment (option)
Step valves 1..3
Minimum
pressure switch
Volume controlling valves (adjustable manually)
Water tub
Open drain
Siphon (building side)
Humidification boxes
Inputs
Minimum pressure
Outputs
Control unit SH2
Display
Error
Humidification
Control/sensor signal analog
0...5 VDC, 1...5 VDC, 0...10 VDC
2...10 VDC, 0..16 VDC, 3.2...16 VDC,
0..20 mA, 4..20 mA
Step valves 1...3
UV water treatment
Remote indication (On, Error, Maintenance and Humidification)
Water supply
2...10 bar
Water connection unit (standard delivery **)
** installation mandatory
Drain funnel (building side)
Rinsing valve
Page 16
16
3.6 Model “REflow”
3.6.1 Construction model “REflow”
1 Water connection on unit R 3/4" (outside thread) 2 Level-controlled supply valve 3 Circulation pump 4 Volume controlling valves (adjustable manually) 5 Overflow 6 Drain (ø 40/34 mm) 7 Shut-off valve 8 Water tub 9 Drain line 10 Water hoses 11 Trickling hoods with distribution pipes 12 Humidification boxes 13 Mist eliminator (for air speed above humidification boxes >3.8 m/s)
CAUTION!
The circulation pump must be protected against dry operation by taking appropriate measures (by the customer).
8
3
1
10
11
12
13
5
7
2
4
9
6
Page 17
17
3.6.2 System overview model “REflow”
Functional description
The water tub is filled up to a preset upper level via the level-controlled supply valve. When the water level in the tub drops below a certain limit, the level-controlled supply valve opens until the upper limit is reached again.
In case of a humidification/cooling request the circulation pump starts and supplies the water via the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub and is fed back to the circulation pump.
To prevent accumulation of mineral residues in the water tub, a limited amount of water is continu­ously drained via a manually adjustable volume controlling valve and replaced with fresh water.
Water supply
2...10 bar
Shut-off valve
Pressure reducing valve
Water filter
Level-controlled supply valve
Volume controlling valves (adjustable manually)
Circulation pump
Overflow
Water tub
Water level
Shut-off valve
Siphon (building side)
Humidification boxes
Control: Via humidistat switching the circulation pump on or off depending on humidification request
Draining: Draining is done continuously via the volume controlling valve (to the very right).
Water connection unit (accessory)
Drain funnel (building side)
Page 18
18
8
3
1
6
9
10
11
12
2
4
7
13
3.7 Model “REflow C”
3.7.1 Construction model “REflow C”
1 Water connection on unit R 3/4" (outside thread) 2 Level-controlled supply valve 3 Circulation pump 4 Overflow 5 Drain (ø 40/34 mm) 6 Drain valve 7 Volume controlling valves (adjustable manually) 8 Water tub 9 Water hoses 10 Trickling hoods with distribution pipes 11 Humidification boxes 12 Mist eliminator (for air speed above humidification boxes >3.8 m/s) 13 Control unit SH2
5
Page 19
19
3.7.2 System overview model “REflow C”
Water supply
2...10 bar
Stop valve
Pressure reducing valve
Water filter
Level-controlled supply valve
Level switch
Functional description
The water tub is filled up to a preset upper level via the level-controlled supply valve. When the water level in the tub drops below a certain limit, the level-controlled supply valve opens until the upper limit is reached again.
The “REflow C” model provides On/Off control by means of the SH2 control unit and an external On/Off humidistat. In case of a humidification/cooling request one, two or all three step valves open (depending on the request). The water flows via the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub.
To prevent accumulation of mineral residues and the formation of germs in the water tub, the tub is completely drained periodically (interval or time controlled). Additionally further hygiene functions can be activated: Operation-dependent draining of the water tub (conductivity or fill cycle controlled) as well as cleaning and drying of the humidification boxes.
Volume controlling valves (adjustable manually)
Circulation pump
Water tub
Operating level = pump immediately on / delayed off
Overflow
Drain valve
Siphon (building side)
Humidification boxes
Inputs
Control unit SH2
Display
Error
Humidification
Outputs
Operating level
Signal On/Off humidistat
Supply valve
Drain valve
Circulation pump
Remote indication (On, Error, Maintenance and Humidification)
Water connection unit (accessory)
Drain funnel (building side)
Conductivity monitoring (option)
Conductivity (option)
Page 20
20
9
3
1
10
11
12
13
2
4
8
7
14
15
3.8 Model “REflow SC”
3.8.1 Construction model “REflow SC”
1 Water connection on unit R 3/4" (outside thread) 2 Level-controlled supply valve 3 Circulation pump 4 Overflow 5 Drain (ø 40/34 mm) 6 Drain valve 7 Step valves (1 to 3) 8 Volume controlling valves (adjustable manually) 9 Water tub 10 Water hoses 11 Trickling hoods with distribution pipes 12 Humidification boxes 13 Mist eliminator (for air speed above humidification boxes >3.8 m/s) 14 UV water treatment (option) 15 Control unit SH2
6
5
Page 21
21
3.8.2 System overview model “REflow SC”
Water supply
2...10 bar
Stop valve
Pressure reducing valve
Water filter
Level-controlled supply valve
Level switch
Functional description
The water tub is filled up to a preset upper level via the level-controlled supply valve. When the water level in the tub drops below a certain limit, the level-controlled supply valve opens until the upper limit is reached again.
The “REflow SC” model provides multistep control by means of the SH2 control unit and the step valves (1, 2 or 3 step valves depending on the humidifier capacity). The SH2 control unit (for wall mounting) processes analog sensor/control signals and uses them to control the step valves. This allows multistep control (1 to 3 steps depending on the humidifier capacity) which improves control accuracy compared to the “REflow” model.
In case of a humidification/cooling request the circulation pump starts and one, two or all three step valves open (depending on the request). The water flows via the manually adjustable volume controlling valves to the distribution pipes above the humidification boxes.
The distribution pipes evenly supply the water to the entire surface of the humidification boxes where it flows down and humidifies the air flowing through the humidification boxes. The excess water not used for humidification flows to the water tub.
Step valves 1..3
Volume controlling valves (adjustable manually)
UV water treatment (option)
Circulation pump
Water tub
Operating level = pump immediately on / delayed off
Overflow
Drain valve
Siphon (building side)
Humidification boxes
Inputs
Control unit SH2
Display
Error
Humidification
Outputs
Operating level
Control/sensor signal analog
0...5 VDC, 1...5 VDC, 0...10 VDC,
2...10 VDC, 0..16 VDC, 3.2...16 VDC,
0..20 mA, 4..20 mA
Step valves 1...3
UV water treatment
Supply valve
Drain valve
Circulation pump
Remote indication (On, Error, Maintenance and Humidification)
Water connection unit (accessory)
Drain funnel (building side)
Conductivity monitor­ing (option)
Conductivity (option)
Page 22
22
To prevent accumulation of mineral residues and the formation of germs in the water tub, the tub is completely drained periodically (Interval or time controlled). Additionally further hygiene functions can be activated: Operation-dependent draining of the water tub (conductivity or fill cycle controlled) as well as cleaning and drying of the humidification boxes.
If the “REflow SC” model is equipped with the optional UV water treatment, a particular amount of water is led to the UV water treatment unit where it is degerminated.
3.9 Standard delivery
The standard delivery includes:
– Adiabatic air humidifier Condair SH2 according type designation (delivered apart) equipped with
options according delivery note.
– Ordered accessories with operating instructions, packed separately.
– Installation and operating instructions (this document)
– Operating instructions control unit SH2 (models with control unit SH2 only)
– Spare parts list
3.10 Storing/Transport/Packaging
Storing
Store the unit and unit components in a protected area meeting the following requirements:
– room temperature: 1 ... 40 °C – room humidity: 10 ... 75 %rh
Transport
For optimum protection always transport the unit and the unit components in the original packag­ing.
The weight of the unit components depends on the unit model. To transport bigger unit components always ask a second person for assistance.
Packaging
Keep the original packaging of the Condair SH2 for later use.
In case you wish to dispose of the packaging, observe the local regulations on waste disposal. Never dispose of the packaging to the environment.
Page 23
23
4 Installation
4.1 Important notes on the mounting and installation work
Qualification of personnel
All mounting and installation work must be carried out only by well qualified personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.
General note
Strictly observe and comply with all information given in the present installation and operat­ing instructions regarding the mounting of the unit and the installation of water and electricity.
Observe and comply with all local regulations dealing with water and electrical installations.
Safety
The electrical installation for the unit models flow C, flow SC, REflow C and REflow SC requires the removal of the control unit cover. Please note the following:
DANGER! Danger of electric shock!
You may get in touch with live parts when the control unit is open. The control unit must be connected to the mains only after all mounting and installation work has been completed and the control unit cover has been relocated properly.
CAUTION!
The electronic components inside the control unit are very sensitive to electrostatic discharge. When the unit is open for installation work, appropriate measures must be taken to protect these components against damage caused by electrostatic dis­charge (ESD protection).
4.2 Unit mounting
4.2.1 Note on locating the unit
Usually, the design and dimensioning of the ventilation duct/monobloc as well as the location of the Condair SH2 inside the duct are determined, recorded and set compulsory when planning the entire system. Prior to installation, however, make sure the following criteria have been taken into consideration:
– For operation with fully demineralised water: Fully demineralised water is aggressive! For this
reason, all components located close to the humidification unit (duct/monobloc, fastening mate­rial, drain pipe, etc.) must be made of corrosion-proof steel (minimum requirements according to DIN 1.4301) or plastic.
– For installation and maintenance of the humidification unit a viewing window and a sufficiently
large maintenance door (min. width= installation depth Condair SH2, see chapter 9.2) must be available in the duct/monobloc.
– In the area of the humidification unit the ventilation duct/monobloc must be waterproof.
– In the area of the humidification unit the duct floor must offer a plane support (plane duct floor or
profile construction), which is lengthwise and crosswise horizontal aligned and has a sufficient load-bearing capacity to support the humidifier unit.
Page 24
24
– We recommend to install air filter (quality standard F7 (EU7) or better) before the humidification
unit. The operation without air filter or with a filter of lower quality is possible, this can however, depending on the air quality, lead to an increased contamination of the humidifier boxes and thus to a reduction of the performance/lifetime.
– In case of low ambient temperature the duct must be insulated to prevent the moist air from
condensing inside the duct.
– If the system is equipped with a heater, make sure it is at least 0.5 m away from the humidifica-
tion unit.
– If silencers are mounted in the airconditioning units make sure to locate the humidification unit
at a minimum distance of 3 m before or after the silencers.
– In order to avoid drops seeping over the humidification boxes, an even air flow over the full cross
section of the humidification unit must be guaranteed. If necessary, rectifiers or perforated plates must be installed on the building side before the humidifier. If the air velocity above the humidification boxes exceeds 3.8 m/s, mist eliminator must be in­stalled.
– The effective height of the siphon in the drain line depends on the duct pressure. Correct dimen-
sioning of the siphon is the customer’s responsibility.
Page 25
25
4.2.2 Mounting process
1. Fix the two mounting brackets “A” to the water tub using one nut M6 and washer for each
bracket. Align the water tub to the centre of the duct, then use the spirit level to adjust the water tub to the duct lengthwise and crosswise. When adjusted, fix the mounting brackets to the duct wall using two self-tapping screws 5.5x19.
Note: Alternatively the water tub can be fixed directly to the duct floor/support construction with four self-tapping screws 5.5x19 on each side.
2. Fix the cross beam “B” to the water tub using four hexagon socket screws M6x12 and washers.
A
A
BB
Page 26
26
Hint: With close space conditions we recommend to install the EPDM sealing profile to the vertical supports before installing the supports. Please refer to step 7 for more information.
3. Carefully mount the left “D” and the right vertical support “E” onto the threaded bolts of the
water tub, then fix each support with four nuts M6 and washers (do not overtighten the nuts).
Important! Before tightening the nuts make sure the holes of the vertical supports seat solidly on the sheet metal of the water tub and do not stuck on the collar of the threaded bolt!
D
E
Page 27
27
4. Carefully mount the vertical intermediate support(s) “F” (number depending on the unit size)
onto the threaded bolts of the water tub, then fix each support with two nuts M6 and washers to the water tub (do not overtighten the nuts) and with a hexagon socket screw M6x12 and a washer to the cross beam.
Important! Before tightening the nuts make sure the holes of the intermediate support seat solidly on the sheet metal of the water tub and do not stuck on the collar of the threaded bolt!
F
Page 28
28
5. Fix the front bracket “G” to each vertical support using two hexagon socket screws M6x12 and
washers.
Important! Before tightening the screws make sure all supports are vertically exactly aligned!
G
Page 29
29
H
H
H
6. Fix one mounting bracket “H” to each vertical support and intermediate support using a hexagon socket screw M6x12, a nut M6 and a washer (see figure above). Important: With multiple inter­mediate supports all mounting brackets must be mounted to the supports on the same side. The mounting brackets fixed to the outermost supports must be mounted always outside (between duct wall and support) and point inward. Finally align the supports, then fix the mounting brackets to the duct ceiling using two self-tapping screws 5.5x19 each.
Page 30
30
7. The air gap between the outermost vertical supports and the duct walls as well as between the front bracket and the duct ceiling must be sealed using EPDM sealing profile (accessory). Cut the EPDM sealing profiles to the desired length (channel height and channel width plus 5 cm allowance). Fix the EPDM sealing profiles to the outermost vertical supports and to the front bracket using the clamping brackets and self-tapping screws 5.5x19 supplied. Tailor the EPDM sealing profiles to the duct height and the duct width, then fix them to the duct walls and the duct ceiling using the clamping brackets and self-tapping screws 5.5x19 supplied (number of self-tapping screws to be used as required). Note: In place of the EPDM sealing profiles also sheet metal angles of stainless steel (not included in the delivery) may be used for the sealing.
Page 31
31
8. Fix hydraulic unit to the water tub and the cross beam using four hexagon socket screws M6x12 and washers. Important: Remove the closing plug “H” from the circulation pump inlet before mounting the hydraulic units REflow, REflow C or REflow SC.
H
Page 32
32
flow flow C flow SC
REflow
REflow C REflow SC
9. Assemble the drains according to the corresponding figure above (the drains can be assembled for draining to the right or to the left) and fix it to the connector(s) of the water tub. Fasten all
threaded connections and hose clamps and fix the drain pipe to the water tub with the pipe sup­port supplied.
remains open
Important: Insert the hose at least 20–30 mm into the opening!
Page 33
33
10. Starting from the bottom, install the humidification boxes in each row: Hook the mounting clips of the boxes into the corresponding openings of the supports, then push the humidification box downwards until it comes to a stop (arrangement of the humidification boxes according to the
installation drawing included in the delivery). Note: in ventilation systems with an air speed >4.7 m/s the cover sheet “K” must be mounted to all topmost humidification boxes before installing them.
K
Page 34
34
11. Only for units with mist eliminator: Hook the mounting brackets into corresponding openings of the vertical supports, then push the brackets downwards until it comes to a stop (if necessary use a rubber mallet). Note: arrangement of the mounting brackets according to the detail figures above and the instal­lation drawing included in the delivery.
Page 35
35
12. Only for units with mist eliminator: Starting from the bottom, install the mist eliminator in each row: Hook the mounting clips of the mist eliminator into the corresponding openings of the mounting brackets, then push the mist eliminator downwards until it comes to a stop. Note: arrangement of the mist eliminator according to the installation drawing included in the delivery.
Page 36
36
13. Mounting the trickling hoods: Push the two tongues on the back side of the trickling hood under­neath the frame sheet of the humidification box (see detail above), then flap the trickling hood downwards. The two brackets on the front side of the trickling hood must engage in the frame (see detail above) of the humidification box. Note: arrangement of the trickling hoods according to the installation drawing included in the delivery.
Page 37
37
14. Remove the closing plugs from the connections of the hydraulic unit. Cut the water hoses to the
required length. Connect water hoses to the connectors on the trickling hoods and the volume
controlling valves and fix them with the hose clamps. Note: arrangement of the water hoses according to the installation drawing included in the de­livery.
Page 38
38
4.3 Water installation
4.3.1 Overviews water installation
Water supply
2...10 bar
5...45 °C
Shut-off valve
Pressure reducing valve
Water filter
Water connection unit (accessory)
Siphon (building side, height
adjusted to the duct pressure)
Model “flow C”
Water supply
2...10 bar
5...45 °C
Shut-off valve
Pressure reducing valve
Water filter
Water connection unit (accessory)
Model “flow”
Open funnel (building side)
Siphon (building side, height
adjusted to the duct pressure)
Open funnel (building side)
Drain line with constant down-slope
ø 40/34 mm
R 3/4"
R 3/4"
ø 40/34 mm
Drain line with constant down-slope
Supply valve (building side)
Page 39
39
Siphon (building side, height
adjusted to the duct pressure)
Model “flow SC”
Water supply
2...10 bar
5...45 °C
Shut-off valve
Pressure reducing valve
Water filter
Water connection unit **
(standard delivery)
Open funnel (building side)
Model “REflow”
Water supply
2...10 bar
5...45 °C
Shut-off valve
Pressure reducing valve
Water filter
Water connection unit (accessory)
Siphon (building side, height
adjusted to the duct pressure)
Open funnel (building side)
R 3/4"
ø 40/34 mm
Drain line with constant down-slope
R 3/4"
ø 40/34 mm
Drain line with constant down-slope
Insert drain hose at least
20–30 mm into the opening
** installation mandatory
Page 40
40
Models “REflow C” and “REflow SC”
Water supply
2...10 bar
5...45 °C
Shut-off valve
Pressure reducing valve
Water filter
Water connection unit (accessory)
Siphon (building side, height
adjusted to the duct pressure)
Open funnel (building side)
R 3/4"
ø 40/34 mm
Drain line with constant down-slope
Page 41
41
Water supply
The water supply is to be carried out according to the figure found in chapter 4.3.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.
– The installation of the shut-off valve, pressure reducing valve and a water filter should be
made as close as possible to the unit.
Notes on water quality:
– For the water supply of the Condair SH2, use exclusively untreated drinking water, fully dem-
ineralised water, fully softened water or partly softened water with a max of 100 cfu/ml.
– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since
these additives may endanger health and affect proper operation.
– The connection material must be pressure-proof and certified for use in drinking water supply systems.
Important! Before connecting the water line to the unit, the line must be flushed thoroughly.
CAUTION!
The thread at the humidifier connection is made of plastic. To avoid overtightening, the union nut of the water pipe must be tightened by hand only.
Water drain
The water drain is to be carried out according to the figure found in chapter 4.3.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.
– Make sure the drain line is installed with a constant down-slope to the siphon of the building.
– Make sure the drain pipe is correctly fixed and easily accessible for inspections and cleaning pur-
poses.
– The minimum inside diameter of the drain pipe of 34 mm must be maintained throughout the
entire length!
When operating the Condair SH2 with fully demineralised water: Fully demineralised water is aggressive! For this reason, use exclusively plastic or stainless steel installation materials (min. DIN 1.4301).
4.3.2 Notes on water installation
Page 42
42
4.4 Electric installation
Note: the electric installation of the unit models Condair SH2 “flow” and “REflow” is by the clients responsibility.
4.4.1 Leading the electric cables out of the duct
Lead the cable(s) of the connecting boxe(s) via cable gland(s) out of the duct.
Page 43
43
1.
2.
3.
236 mm
280 mm
220 mm
306 mm
4.4.2 Mounting the control unit SH2
1. Unlock and swivel up the transparent cover, then unlock the two hinges (see detail “A”) and re­move the cover.
2. Undo the 6 screws, then carefully lift the control unit cover and disconnect the cables on the electronic.
3. Break out the 4 oblong holes in the bottom of the unit housing and fix the control unit to the wall using 4 screws.
4. Connect the cables from the connecting box(es), the voltage supply, etc. to the corresponding terminals in the control unit according the appropriate wiring diagram (see chapter 4.4.3, 4.4.4,
4.4.5 and 4.4.6).
Important: all cables must be lead into the control unit via the cable glands in the housing.
CAUTION!
The electronic components inside the control unit are very sensitive to electrostatic discharge. When the unit is open for installation work, appropriate measures must be taken to protect these components against damage caused by electrostatic dis­charge (ESD protection).
Detail “A”
Detail “B”
Page 44
44
Q
F8
B1 B2
Y1
L1 N S S
NL1PE
%rH %rH
4.4.3 Wiring diagram Condair SH2 flow C
cross section 1.5 mm
2
B1 Humidistat or thermostat (230V/2A)
B2 Safety humidistat (Safety chain) F8 External fuse 2 A, slow acting (voltage supply)
Y1 Inlet valve Q Service switch (min. contact opening 3 mm) or plug connection (installation mandatory)
Control unit RC
Connecting box
Page 45
45
6.3AT
F1
4
1
5
2
B2
J
F2
1AT
F3
630mAT
F4
200mAF
F5
200mAF
Reserve
Output
B1
Y
+-
P
L1 N L1 N
N
L1NSCSCPT1
PT2
P1
+24V
24V
0-10V
GND
GND
Input+
5V/24V
5V
Res1
Res2
Level max
level min / PS
+24V
S2
Stage 1
Inlet Valve
Drain Valve
UV Lamp
N
N
Stage 2
Stage 3
N
Pump
N
Connector
to CPU
Front panel
PS
white
brown
white
brown
Unit On
Error
Service
Humidification
H
Y1
Y2
blue
blue
2
3
4
1
6
7
5
230 V
brown
brown
green/yellow
PE
N
10-wire cable
Y5
blue
brown
Y4
blue
brown
blue
brown
V
bluebrown
NL1PE
Q
F8
L1 NL1 N
4.4.4 Wiring diagram Condair SH2 flow SC
B1 Active controller or humidity sensor (set jumper to 5 V) B2 Ventilator interlock (safety chain) F1 Fuse 6.3 A, slow acting (Voltage supply control unit) F2 Fuse 1 A, slow acting (Relay 230 V) F3 Fuse 630 mA, slow acting (Step valves) F4 Fuse 200 mA, fast acting (Analog entry)
F8 External fuse 10 A, slow acting (Voltage supply)
H Remote operating and fault indication (Option) J Cable bridge (must be removed, if “B2” is connected) PS Pressure switch
S2 Unit switch
Y2 Rinsing valve Y3-Y5 Step valves Q Service switch (min. contact opening 3 mm) or
plug connection (installation mandatory)
V UV lamp for water sterilisation (Option)
cross section 1.5 mm
2
Connecting box
Page 46
46
GND
GND
Input+
5V/24V
white
brown
6.3AT
F 1
4
1
5
NL1PE
Q
F8
L1 NL1 N
2
B2
J
K
F2
1AT
A1
A2
F6
Y1
Y2
M
F3
630mAT
S1
white
green
F4
200mAF
Reserve
Output
brown
F5
200mAF
P
L1 N L1 N
N
L1NSCSCPT1
PT2
P1
+24V
24V
0-10V
5V
Res1
Res2
Level max
Level min / PS
+24V
S2
Stage 1
Inlet Valve
Drain Valve
UV Lamp
N
N
Stage 2
Stage 3
N
Pump
N
Connector
to CPU
Front panel
1 3 5 13
14
97
498 2 6
95
96
blue
blue
blue
8
9
2
3
4
1
6
7
5
1
2
24 V
230 V
brown
brown
brown
green/yellow
black
black
F7
Unit On
Error
Service
Humidification
H
B4
B1
PE
N
10-wire cable 230 V
B3
Cond. signal
Temp. signal
Electrode
green
blue black
brown
white white
brown
1 2 + –
3
4 5 6
7 8 + –
4.4.5 Wiring diagram Condair SH2 REflow C
cross section 1.5 mm
2
B1 Humidistat or thermostat (set jumper to 24 V) B2 Ventilator interlock (safety chain) B3 Conductivity measuring (option) B4 Potential free contact to trigger a box rinsing cycle F1 Fuse 6.3 A, slow acting (Voltage supply control unit) F2 Fuse 1 A, slow acting (Relay 230 V) F3 Fuse 630 mA, slow acting (Step valves) F4 Fuse 200 mA, fast acting (Analog entry)
F5 Fuse 200 mA, fast acting (Control voltage 24 V) F6 Fuse 6.3 A, slow acting (Pump) F7 Thermo relay motor F8 External fuse 10 A, slow acting (Voltage supply)
H Remote operating and fault indication (Option) J Cable bridge (must be removed, if “B2” is connected)
K Main contactor with manually resettable protective motor
switch “F7”
M Pump
S1 Level switch (operating level) S2 Unit switch
Y1 Inlet valve Y2 Drain valve Q Service switch (min. contact opening 3 mm) or
plug connection (installation mandatory)
Connecting
box
Page 47
47
GND
GND
Input+
5V/24V
6.3AT
F 1
4
1
5
NL1PE
Q
F8
L1 NL1 N
2
B2
J
K
F2
1AT
A1
A2
F6
Y1
Y2
M
F3
630mAT
S1
white
green
F4
200mAF
Reserve
Output
brown
F5
200mAF
P
L1 N L1 N
N
L1NSCSCPT1
PT2
P1
+24V
24V
0-10V
5V
Res1
Res2
Level max
Level min / PS
+24V
S2
Stage 1
Inlet Valve
Drain Valve
UV Lamp
N
N
Stage 2
Stage 3
N
Pump
N
Connector
to CPU
Front panel
1 3 5 13
14
97
498 2 6
95
96
blue
blue
blue
8
9
2
3
4
1
6
7
5
2
24 V
230 V
1
brown
brown
brown
green/yellow
black
black
F7
Unit On
Error
Service
Humidification
H
B4
B1
PE
N
10-wire cable 230 V
Y5
blue
brown
Y4
blue
brown
Y3
blue
brown
V
bluebrown
B3
Cond. signal
Temp. signal
Electrode
green
blue black
brown
white white
brown
1 2 + –
3
4 5 6
7 8 + –
white
brown
Y
– +
4.4.6 Wiring diagram Condair SH2 REflow SC
B1 Active controller or humidity sensor (set jumper to 5 V) B2 Ventilator interlock (safety chain) B3 Conductivity measuring (option) B4 Potential free contact to trigger a box rinsing cycle F1 Fuse 6.3 A, slow acting (Voltage supply control unit) F2 Fuse 1 A, slow acting (Relay 230 V) F3 Fuse 630 mA, slow acting (Step valves) F4 Fuse 200 mA, fast acting (Analog entry)
F5 Fuse 200 mA, fast acting (Control voltage 24 V) F6 Fuse 6.3 A, slow acting (Pump) F7 Thermo relay motor F8 External fuse 10 A, slow acting (Voltage supply)
H Remote operating and fault indication (Option) J Cable bridge (must be removed, if “B2” is connected) K Main contactor with manually resettable protective motor
switch “F7” M Pump
S1 Level switch (operating level) S2 Unit switch
Y1 Inlet valve Y2 Drain valve Y3-Y5 Step valves Q Service switch (min. contact opening 3 mm) or
plug connection (installation mandatory) V UV lamp for water sterilisation (Option)
cross section 1.5 mm
2
Connecting
box
Page 48
48
5 Operation
Proceed as follows when putting the Condair SH2 into operation:
1. Examine the Condair SH2 and installation for possible damage.
DANGER!
Damaged devices or devices with damaged installation may present danger to human life or cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation must not be operated.
2. Models flow C, flow SC, REflow, REflow C and REflow SC: Make sure the connecting box(es)
and the control unit are closed and that all cables are lead through cable glands.
3. Open the shut-off valve in the water supply line.
4. Switch on the service switch in the mains supply.
5. Models flow SC, REflow C and REflow SC: switch on the control unit SH2 (the unit switch
lights up). Note: regarding the operation of the control unit SH2 please observe the information given in the separate operating instructions to the control unit SH2.
6. Check the settings of the humidistat/thermostat or the humidity controller, respectively. If neces­sary, adjust settings.
5.1 Putting into operation
5.2 Adjust the volume controlling valves
After first time commissioning of the Condair SH2 the volume controlling valves must be adjusted to the local operating conditions according to the separate instructions.
Page 49
49
5.3 Notes on operation
During operation of the Condair SH2 the humidification system has to be inspected weekly. On this occasion check the following:
• thewaterforanyleakage.
• thehumidierandtheothersystemcomponentsforcorrectxingandanydamage.
• theelectricinstallationforanydamage.
• UnitmodelswithcontrolunitSH2:Checkoperatinginformationindisplaylevelandwhetheror
not a warning or error message is present.
If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged components take the Condair SH2 out of operation as described in chapter 5.4. Then, have the malfunction be eliminated or the damaged component be replaced by a well trained specialist or a service techni­cian from your Condair supplier.
5.4 Taking out of operation
In order to take the Condair SH2 out of operation (e.g. to perform maintenance works, to eliminate a malfunction, etc.) perform the following steps:
1. Close the shut-off valve in the water supply line.
2. Models REflow, REflow C and REflow SC: empty the water tub.
– Model REflow: Open the shut-off valve in the water drain line. If the water tub is empty close
the shut-off valve again.
– Models REflow C and REflow SC: Start manual draining (see operating instructions of the
control unit SH2) and wait until the water tub is empty.
3. Models flow SC, REflow C and REflow SC: switch off control unit. Important: If the unit has to be switched off because of a malfunction, please note the code of the actual error message.
4. Isolate all components of the Condair SH2 from the mains and secure system against ac- cidentally being reconnected to the mains.
5. If work has to be carried out on the Condair SH2, switch off the ventilation system and secure the system against accidentally being switched on.
Note: if the Condair SH2 is not be used for a longer period of time the models flow, flow C and RE­flow should be taken out of operation as described above. However, the models flow SC, REflow C and REflow SC should stay operable to keep the hygiene functions (e.g. periodical flushing of supply
pipe) active.
Page 50
50
6 Maintenance
Qualification of personnel
All maintenance work must be carried out only by well qualified and trained personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.
General note
The instructions and details for maintenance work must be followed and upheld.
Only the maintenance work described in this documentation may be carried out.
Only use original Condair spare parts to replace faulty parts.
Safety
Before carrying out any maintenance work take the Condair SH2 out of operation as described in chapter 5.4 and secure the unit against inadvertent power-up. In addition the take ventilation
system out of operation as described in the operations instructions of the ventilation system and secure the ventilation system against inadvertent power-up.
The Condair SH2 must be maintained in the prescribed intervals, the cleaning work must be carried out correctly and the humidification boxes and the mist eliminator boxes must be replaced after their prescribed lifetime has elapsed.
WARNING!
If the unit is insufficient maintained ill-making germs may grow in the water tub and the humidi­fication boxes (and the mist eliminator) of the Condair SH2 and may can affect the air passing through the humidifier.
6.1 Important notes on maintenance
Page 51
51
6.2 Maintenance intervals
In order to maintain operational safety the Condair SH2 must be maintained in regular intervals. The time interval for the maintenance is to be adapted to the operating conditions. The hygiene status depends mainly on the quality of the humidifier water but also on the adherence to the exchange intervals of the upstream air filter, the air velocity and the micro-biological and chemical composi­tion of the supply air. Therefore the maintenance intervals must be determined for each system separately. The first maintenance must be carried out after 800 operating hours. Depending on the encountered hygiene status during the first maintenance the interval time must be decreased or increased.
In any case the Condair SH2 is to be maintained however at least twice annually.
On units equipped with a SH2 control unit (flow SC, REflow C and REflow SC) the maintenance interval can be programmed. As soon as the maintenance time has elapsed, a maintenance mes­sage is displayed to draw your attention to the pending maintenance. To determine the maintenance interval time the above described procedure can be used.
6.3 Maintenance work
Component Work to be carried out
Humidification boxes and mist eliminator boxes
Dismantle and check the humidification boxes (and mist elimi­nator boxes). Clean the frame of the boxes with a combined detergent and disinfectant. If the humidifier fleece is heavily soiled, the humidification boxes have to be replaced. Note: If the humidification boxes indicate strong dust deposit, the air filter of the ventilation system is to be controlled (recom-
mended filter quality: F7/EU7 or better).
Water tub Check water tub for soiling (dust, slime, mineral deposit, etc.)
and clean with a combined detergent and disinfectant. Note: the actual hygiene status indicates, whether the mainte­nance interval time must be decreased or increased.
Frame structure Check screw connections of the frame structure, tight loose
screw connections. Clean frame structure with a combined detergent and disinfectant.
Duct section downstream of the humidifier
Check the duct section behind the humidifier (downstream) for collection of residual water. If residual water is present: Check air velocity above the humidification boxes (without mist elimina­tor max. 3.8 m/s, with mist eliminator max. 4.5 m/s or 5.5 m/s, respectively). Mount mist eliminator if necessary.
Clean duct with a combined detergent and disinfectant.
Hydraulic unit Check connections and components for sealing and correct
fastening. Seal/replace leaky components, replace defective components, fasten loose components. Carefully clean the components of the hydraulic unit with a combined detergent and disinfectant.
Page 52
52
Water installation Check water the water hoses of the humidifier for cracks and
correct fastening, replace defective hoses. Carefully clean the hoses with a combined detergent and dis­infectant.
Check water supply line for sealing and seal if necessary. Dis­mantle water filter (if present), clean it, then reinstall it.
Trickling hood Dismantle the trickling hoods and check the holes in the water
distribution pipes for mineral deposit. If necessary, dismantle the water distribution pipes and remove the mineral deposit.
Clean trickling hood and water distribution pipes with a combined detergent and disinfectant.
Drain line with Siphon Check and clean with a combined detergent and disinfectant,
if necessary.
UV water treatment (Option)
Dismantle the UV lamp. Carefully clean glass tube and UV lamp (see chapter 6.4.2). After max. of 8000 operating hours the UV lamp must be re­placed.
Electric installation Check all cables and components for correct fastening, correct
function and defects. Let have defective components be replaced or loose components be fastened by a qualified specialist.
Page 53
53
6.4 Dismantling and installation works
6.4.1 Dismantle and install the mist eliminator and humidification boxes
1. Undo the hose clamps, then pull off the hoses from the connections on the trickling hoods.
2. Lift the trickling hoods on the water connection side and remove them to the front.
3. Starting from the top remove the mist eliminator boxes (push box upwards and remove it to the front).
4. Release the fixing clip in the middle of the mounting bracket by pressing slightly on the vertical support, then carefully push the mounting bracket upwards and remove it. Repeat this step for all mounting brackets.
5. Starting from the top remove the humidification boxes (push box upwards and remove it to the front).
The installation of the cleaned or the new humidification boxes/mist eliminator boxes follows the reverse dismantling order.
Page 54
54
6.4.2 Dismantle and install the UV lamp (option)
1. Undo the union nut, then carefully pull off the con­nection plug upwards.
2. Carefully pull the UV lamp out of the socket and remove it to the top.
3. Remove glass tube to the top. Clean glass tube outside and inside with a lint-free and soft cloth.
6.5 Resetting the maintenance indication
When maintenance work has been completed the maintenance indication must be reset on the unit models flow SC, REflow C and REflow SC (yellow LED lights). For that purpose, please observe the information given in the separate operating instructions for the SH2 control unit.
The installation of the UV lamp follows the reverse dismantling order.
CAUTION!
When installing the UV lamp, make sure to hold the lamp until it is completely inserted. Under no circumstances let the lamp fall inside the holder, since this could damage the lamp.
Page 55
55
7 Malfunctions
Important! Most operational malfunctions are not caused by faulty equipment but rather by improper
installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always in­volves a thorough examination of the entire system.
7.1 Malfunction list
Malfunction Cause Remedy
Residual water in the section of the duct behind (downstream) the Condair SH2.
Air velocity above the humidifi­cation boxes is too high. Units without mist eliminator max
3.8 m/s, Units with a 100 mm mist eliminator max. 4.5 m/s, with a 200 mm mist eliminator max. 5.5 m/s
Install mist eliminator or reduce air velocity in the duct.
Water drain is leaking. Check/seal water drain.
Humidity/Cooling demand present however the Condair SH2 does not humidify.
Shut-off valve in the water supply line closed.
Open shut-off valve.
Models REflow: pump fuse F5 or circulation pump defective.
Check/replace pump fuse F5 or circulation pump.
Maximum humidification/cool­ing capacity is not reached.
System incorrectly dimensioned (insufficient capacity).
Contact your Condair supplier.
Insufficient water supply capacity. Check water supply, increase water
pressure.
Volume controlling valves incor­rectly adjusted.
Adjust volume controlling valves correctly (see operating instructions for volume controlling valves).
Models with SH2 control unit: Out­put limitation active.
Deactivate output limitation (see separate operating instructions for SH2 control unit)
Step valves do not open (flow SC and REflow SC only).
No demand. Check control signal.
Supply pressure too high (flow SC only).
Reduce supply pressure to 1.5 bar.
Safety chain open (safety humidis­tat, ventilation interlock, etc. have triggered).
Check safety chain.
Note: On units equipped with a SH2 control unit (flow SC, REflow C and REflow SC) malfunctions dur­ing operation are indicated by a corresponding event message in the display. For that purpose, please observe the information given in the separate operating instructions for the SH2 control unit .
Page 56
56
7.2 Notes on fault elimination
DANGER!
In order to eliminate faults, the Condair SH2 must be set out of operation as described in chapter
5.4. Disconnect the unit from the mains and secure the unit against inadvertent power-up.
Only allow trained and qualified personnel to repair faults. Faults relating to electrical installation must only be carried out by authorized personnel or your Condair representative’s service technician.
Repair work and replacement of faulty components must only be carried out by your Condair rep­resentative’s service technician!
Page 57
57
8 Taking out of service/Disposal
8.1 Taking out of service
If the Condair SH2 must be replaced or if the humidification system is not needed any more, pro­ceed as follows:
1. Take the unit out of operation as described in chapter 5.4.
2. Have the unit (and all other system components, if necessary) unmounted by a qualified service technician.
8.2 Disposal/Recycling
Components not used any more must not be disposed of in the domestic waste. Please dispose of the unit or the individual components in accordance with local regulations at the authorised collecting point.
If you have any questions, please contact the responsible authority or your local Condair representative.
Thank you for your contribution to environmental protection.
Page 58
58
9 Product specifications
9.1 Technical data
Condair SH2 models
flow flow C flow SC REflow REflow C REflow SC
Control ––– Control RC Control SH2 ––– Control SH2 Control SH2
Control supply voltage ––– 230 VAC/50 Hz 230 VAC/50 Hz ––– 230 VAC/50 Hz 230 VAC/50 Hz
Circulation pump supply voltage ––– ––– ––– 230 VAC/50 Hz
Power consumption ––– 28 VA 62 ... 94 VA
1) 2)
310 VA 353 VA 393 ... 485 VA
1) 2)
Control signals ––– potential free
contact of an
external
humidistat/
thermostat
0...5 VDC
1...5 VDC
0..10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0..20 mA
4..20 mA
––– potential free
contact of an
external
humidistat/
thermostat
0...5 VDC
1...5 VDC
0..10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0..20 mA
4..20 mA
Control characteristics On/Off On/Off Step control On/Off On/Off Step control
Control accuracy Control accuracy depends on air conditions, control distance,
water quality and probably on the number of On/Off cycles
Max. admissible air speed above humidification boxes
3.8 m/s
(4.5 m/s with 100 mm mist eliminator, 5.5 m/s with 200 mm mist eliminator)
Water supply R 3/4” outside thread
Water drain ø 40/34 mm
Admissible water supply pressure 2...10 bar 2...10 bar 2...10 bar 2...10 bar 2...10 bar 2...10 bar
Admissible water temperature 5...45 °C
Water quality Tap water, softened or fully demineralised water with a max. of 100 cfu/ml
Pressure drop typically 70 Pa at 2.5 m/s, 90 %rh
Admissible ambient temperature (Control unit) ––– 1...40 °C 1...40 °C ––– 1...40 °C 1...40 °C
Admissible ambient humidity (Control unit) ––– max. 75 %rh max. 75 %rh ––– max. 75 %rh max. 75 %rh
Degree of protection of Control unit ––– IP54 IP54 ––– IP54 IP54
Degree of protection of pump, valves. etc. ––– IP54/IP65 IP54/IP65 IP54/IP65 IP54/IP65 IP54/IP65
Conformity CE marking
Fire classification of humidification medium DIN EN 53438 Class F1
Accessories
– Water connection unit S
– Duct humidistat HBC
– Room humidistat HSC
– Duct humidity sensor (continuous) EGH 110
– Room humidity sensor (continuous) EGH 130
– Remote indication PCB On/Error/Maintenance/Humidification
– EPDM sealing profile 300/3
Options
– UV water treatment
– Conductivity monitoring
S= Standard equipment
•= Accessory/option available
1)
Power consumption depending on the number of vertical humidification boxes rows
2)
If the optional “UV water treatment” is used the power consumption increases by 60 VA
Page 59
59
9.2 Unit dimensions
UH: 645 ...3945 mm (graduation 75 mm)
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
UH
UW
UD
97
100
76
R 3/4"
46
164
317
55
ø40/36
Unit dimensions flow
Page 60
60
UH: 645 ...3945 mm (graduation 75 mm)
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
Unit dimensions flow C
UH
UW
317252
ø40/36
88
UD
97
76
46
184
Page 61
61
UH: 645 ...3945 mm (graduation 75 mm)
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
Unit dimensions flow SC
UH
UW
UD
97
100
76
R 3/4"
46
164
317
55
ø40/36
Page 62
62
UH: 645 ...3045 mm (graduation 75 mm), >3045 mm on request
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
Unit dimensions REflow
UH
UW
UD
143
83
R 3/4"
46
ø40/36
184
88
88
317
252
Page 63
63
UH: 645 ...3045 mm (graduation 75 mm), >3045 mm on request
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
Unit dimensions REflow C
UH
UW
R 3/4"
317
258
ø40/36
UD
131
76
46
5
193
Page 64
64
UH: 645 ...3045 mm (graduation 75 mm), >3045 mm on request
UW : 604 ...4104 mm (graduation 100 mm)
UD:
Max. humidification
efficiency
Depth
Humidification box
Depth
Mist eliminator
Depth UD
85 % 200 mm ––– 581 mm 85 % 200 mm 100 mm 581 mm 85 % 200 mm 200 mm 681 mm 95 % 300 mm ––– 581 mm * / 681 mm 95 % 300 mm 100 mm 681 mm 95 % 300 mm 200 mm 781 mm
* Units with code 3 (mist eliminator not retrofittable)
Unit dimensions REflow SC
UH
UW
R 3/4"
317
258
ø40/36
UD
131
76
46
5
193
Page 65
65
Notes
Page 66
Notes
Page 67
© Condair Ltd., Printed in Switzerland Technical modifications reserved