Condair Links Series, ProtoCessor FPC-ED4, ProtoCessor FPC-ED2 Installation And Operation Manual

INSTALLATION AND OPERATION MANUAL
ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4 Condair LINKS
2587516_
B_EN_1
810
Humidification and Evaporative Cooling
Document Revision: 2.I
Web Configurator
Template Revision: 60
For Interfacing Condair Products:
Nortec… NH-EL, GS, EL, RS
To Building Automation Systems:
BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks
Technical Support
Thank you for purchasing the ProtoCessor for Condair. Please call Condair for Technical support of the ProtoCessor product. Sierra Monitor Corporation does not provide direct support. If Condair needs to escalate the concern, they
will contact Sierra Monitor Corporation for assistance. Support Contact Information:
U.S.A.
Condair Inc. 2700 90th Street Sturtevant, WI 53177 USA
Canada
Condair Ltd. 2740 Fenton Rd Ottawa, Ontario K1T 3T7
Condair Service:
1.866.667.8321 Fax:
1.613.822.9764 Email: na.info@condair.com Website: www.condair.com
APPLICABILITY & EFFECTIVITY
Explains ProtoCessor FPC-ED2 hardware and how to install it. The instructions are effective for the above as of OCT 2018.
INSTALLATION AND OPERATION MANUAL
Condair LINKS ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4
2587516_B_EN_1810
Thank you for choosing Condair
Installation date (DD/MM/YYYY):
Commissioning date (DD/MM/YYYY):
Site:
Model:
Serial number:
Manufacturer Condair Ltd.
2740 Fenton Road, Ottawa, ON, Canada K1T 3T7 Tel. 1.866.667.8321, Fax 613.822.7964 na.info@condair.com, www.condair.com
Proprietary Notice This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this docu-
ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Condair Ltd., except to the extent required for installation, operation or maintenance of the customer's equipment.
Liability Notice Condair Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the
equipment, or due to the use of parts/components/equipment that are not authorized by Condair Ltd.
Copyright Notice Copyright 2018, Condair Ltd, All rights reserved.
Technical modification rights reserved.
Contents
1 Quick Start Guide ........................................................................................................ 7
2 Certifications ................................................................................................................ 8
3 Introduction .................................................................................................................. 9
3.1 ProtoCessor Gateway ................................................................................................... 9
4 Setup for ProtoCessor ...............................................................................................10
4.1 Record Identification Data ............................................................................................10
4.2 Point Count Capacity and Registers per Device ...........................................................10
4.3 Configuring Device Communications ............................................................................10
4.3.1 Input COM Settings for Device with an Inserted ProtoCessor ..................................10
4.3.2 Set Modbus RTU Node-ID for the Device ................................................................11
5 Interfacing ProtoCessor to Device ............................................................................12
5.1 ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board .........................................12
5.2 ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports................................13
5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network ..........................14
5.4 LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network ....................................14
6 Use ProtoCessor Web Configurator to Setup the Gateway .....................................15
6.1 Connect the PC to ProtoCessor via the Ethernet Port ..................................................15
6.2 Connecting to ProtoCessor Web Configurator ..............................................................16
6.3 Selecting Profiles for Device Connected to ProtoCessor ..............................................16
6.4 BACnet/IP Setting IP Address for Field Network ..........................................................19
6.5 Select Field Protocol ....................................................................................................21
6.5.1 BACnet MS/TP Configuration ..................................................................................21
6.5.2 BACnet/IP Configuration .........................................................................................22
6.5.3 Metasys N2 Configuration .......................................................................................23
7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign
Specific Device Instances ...........................................................................................24
8 How to Start the Installation Over: Clearing Profiles ...............................................25
9 LonWorks (FPC-ED4): Commissioning ProtoCessor on a lonworks Network .......26
9.1 Commissioning ProtoCessor FPC-ED4 on a LonWorks Network .................................26
9.1.1 Instructions to Download XIF File from ProtoCessor FPC-ED4 Using Browser........26
A Troubleshooting ........................................................................................................... i
A.1 Lost or Incorrect IP Address ............................................................................................ i
A.2 Viewing Diagnostic information ...................................................................................... ii
A.3 Check Wiring and Settings ............................................................................................. ii
A.4 LED Diagnostics for Communications Between ProtoCessor and Device ..................... iii
A.5 Take Diagnostic Capture With the FieldServer Utilities .................................................. iv
Condair LINKS 2587516_B_EN_1810 I V
A.6 Update Firmware .......................................................................................................... vii
A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet ............. vii
A.8 Securing the ProtoCessor with Passwords .................................................................. viii
B Vendor Information - Condair ................................................................................... viii
B.1 NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ....................... viii
B.2 GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ............................. ix
B.3 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ............................... x
B.4 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks .............................. xi
C Reference ................................................................................................................... xiii
C.1 Specifications .............................................................................................................. xiii
C.2 Compliance with UL Regulations ................................................................................. xiii
VI | 2587516_B_EN_1810 Condair LINKS
1 Quick Start Guide
1. Record the information about the unit. (Section 4.1)
2. Set the device’s Modbus RTU serial settings (i.e. baud rate, parity, stop bits) and Modbus Node-ID’s for the device that will be connected to ProtoCessor FPC-ED2 or FPC-ED4. (Section 4.3)
3. Metasys N2 (FPC-ED2): Set the Node-ID. (Section 4.3.2)
4. BACnet MS/TP or BACnet/IP: Set the BACnet Device Instance. (Section 7)
5. Connect ProtoCessor FPC-ED2’s 3 pin RS-485 port to the Field Protocol cabling, (Section 5.3) or connect ProtoCessor FPC-ED4’s 2 pin LonWorks port to the Field Protocol cabling. (Section 5.4)
6. Use a browser to access the ProtoCessor’s embedded tool, which is referred to in this manual as the Web Configurator, to select the device that will be attached to ProtoCessor and set the Modbus Node-ID. Once the device is selected, the ProtoCessor Automatically builds and loads the Configuration. (Section 6)
7. BACnet/IP (FPC-ED2): Use a browser to access the ProtoCessor Web Configurator to change the IP Address. No changes to the configuration are necessary. (Section 6.4)
8. LonWorks (FPC-ED4): The ProtoCessor must be commissioned on the LonWorks Network. This needs to be done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 9)
Condair LINKS 2587516_B_EN_1810 I 7
2 Certifications
The BTL Mark on ProtoCessor is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. Go to http://www.BACnetInternational.net/btl/ for more information about the BACnet Testing Laboratory. Click here for BACnet PIC Statement.
LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and end users. LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices work together. Sierra Monitor has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier and ProtoCessor for OEM applications and the full featured, configurable gateways.
BTL MARK – BACNET TESTING LABORATORY
LONMARK CERTIFICATION
8 | 2587516_B_EN_1810 Condair LINKS
1
2
3
1 2 3
3 Introduction
3.1 ProtoCessor Gateway
ProtoCessor is an external, high performance Building Automation multi-protocol gateway that is preconfigured to automatically communicate between Condair’s products (hereafter called “device”) connected to the ProtoCessor and automatically configures them for BACnet
®
BACnet/IP, Metasys
N2 by JCI or LonWorks
It is not necessary to download any configuration files to support the required applications. The ProtoCessor is pre-loaded with tested Profiles/Configurations for the supported devices.
®
.
®
MS/TP,
BACnet is a registered trademark of ASHRAE Metasys is a registered trademark of Johnson Controls Inc. LonWorks is a registered trademark of Echelon Corporation
Condair LINKS 2587516_B_EN_1810 I 9
4 Setup for ProtoCessor
Model
Part Number
ProtoCessor FPC-ED2
FPC-ED2-1409
ProtoCessor FPC-ED4
FPC-ED4-1410
Part Number
Total Registers
FPC-ED2-1409
1500
FPC-ED4-1410
1500
Devices
Registers per Device
Nortec NHEL
35
Nortec GS
22
Nortec EL
35
Nortec RS
59
4.1 Record Identification Data Each ProtoCessor has a unique part number located on the side or the back of the unit.
This number should be recorded, as it may be required for technical support. The numbers are as follows:
Table 1: ProtoCessor Part Numbers
FPC-ED2 units have the following 2 ports: RS-485 + Ethernet FPC-ED4 units have the following 2 ports: LonWorks + Ethernet
4.2 Point Count Capacity and Registers per Device
The total number of Registers presented by the device attached to the ProtoCessor cannot exceed:
Table 2: Supported Point Count Capacity
Table 3: Registers per Device
4.3 Configuring Device Communications
4.3.1 Input COM Settings for Device with an Inserted ProtoCessor
Set the serial device that the ProtoCessor is plugged into to have the same Baud Rate,
Data Bits, Stop Bits, and Parity settings as the ProtoCessor.
Table 4: COM Settings specifies the device serial port settings required to communicate
with the ProtoCessor.
10 | 2587516_B_EN_1810 Condair LINKS
Serial Port Setting
Device
Protocol
35
Baud Rate
9600
Parity
Even
Data Bits
8
Stop Bits
1
Table 4: COM Settings
4.3.2 Set Modbus RTU Node-ID for the Device
Set Modbus Node-ID for the device the ProtoCessor is plugged into. (See Section 6.5 to
input Node-ID)
The Modbus Node-ID needs to be uniquely assigned between 1 and 255.
o The Modbus Node-ID that is assigned for the device needs to be
documented
The Modbus Node-ID assigned is used for designating the Device
Instance for BACnet/IP and BACnet MS/TP
The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be
the same value as the Node-ID of the Modbus RTU device.
Condair LINKS 2587516_B_EN_1810 I 11
5 Interfacing ProtoCessor to Device
5.1 ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board
Figure 1: Mounted ProtoCessor BACnet FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower)
12 | 2587516_B_EN_1810 Condair LINKS
5.2 ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports
Figure 2: ProtoCessor FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower)
Condair LINKS 2587516_B_EN_1810 I 13
5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network
BMS RS-485 Wiring
ProtoCessor Pin #
Pin Assignment
RS-485 +
Pin 1
RS-485 +
RS-485 -
Pin 2
RS-485 -
-
Pin 3
RS-485 GND
+
End-of-Line Switch
Connect the BACnet MS/TP or Metasys N2 RS-485 network wires to the 3-pin RS-485
connector on ProtoCessor ED2 as shown below in
Figure 3.
o The RS-485 GND (Pin 3) is not typically connected
See Section 7 for information on connecting to BACnet/IP network. If the ProtoCessor is the last device on the BACnet MS/TP or Metasys N2 trunk,
then the End-Of-Line Termination Switch needs to be enabled (Figure 4).
o The default setting from the factory is OFF (switch position = right side) o To enable the EOL Termination, turn the EOL switch ON (switch position
= left side)
Figure 3: Connection from ProtoCessor to RS-485 Field Network
Figure 4: RS-485 BMS Network EOL Switch
5.4 LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network
Connect ProtoCessor to the field network with the LonWorks terminal using approved
cable per the FT-10 installation guidelines. LonWorks has no polarity.
Figure 5: LonWorks Terminal Connector
14 | 2587516_B_EN_1810 Condair LINKS
6 Use ProtoCessor Web Configurator to Setup the Gateway
6.1 Connect the PC to ProtoCessor via the Ethernet Port
Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC
and ProtoCessor.
The Default IP Address of ProtoCessor is 192.168.168.243, Subnet Mask is
255.255.255.0. If the PC and ProtoCessor are on different IP Networks, assign a static
IP Address to the PC on the 192.168.168.xxx network.
For Windows XP:
Go to > > Right-click on Local Area Connection > Properties
Highlight >
For Windows 7:
Go to > > > >
Right-click on Local Area Connection > Properties
Highlight >
For Windows XP and Windows 7, use the following IP Address:
Click twice.
Condair LINKS 2587516_B_EN_1810 I 15
6.2 Connecting to ProtoCessor Web Configurator
After setting a local PC on the same subnet as the ProtoCessor (Section 6.1), open a
web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.168.243.
NOTE: If the IP Address of the ProtoCessor has been changed by previous
configuration, the assigned IP Address must be gathered from the network administrator.
6.3 Selecting Profiles for Device Connected to ProtoCessor
In the Web Configurator, the Active Profiles section is shown on the lower left side of the
screen.
The Active Profiles section lists the currently active device profiles, including previous
Web Configurator additions. This list will be empty for new installations, or after clearing all configurations. (
   Figure 6) To add an active profile to support a device, click the ADD button under Active Profiles.
This will present a drop-down box underneath the Current Profile column that lists all the available profiles. (
  Figure 7)  For every device that is added, assign a unique Modbus Node-ID. This specification
must match the device’s network settings.
16 | 2587516_B_EN_1810 Condair LINKS
Figure 6: Web Configurator Showing no Active Profiles
Once the Profile for the device has been selected from the drop-down list, enter the
value of the device’s Modbus Node-ID which was assigned in Section 4.3.2.
Condair LINKS 2587516_B_EN_1810 I 17
Figure 7: Web Configurator Showing Available Profiles for Selection
Then press the “Submit” button to add the Profile as a device to be configured.  Completed additions will be listed under “Active Profiles” as shown in   Figure 8.
18 | 2587516_B_EN_1810 Condair LINKS
Figure 8: Web Configurator Showing Active Profile Additions
6.4 BACnet/IP Setting IP Address for Field Network
After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.168.243.
The Web Configurator is displayed as the landing page. (Figure 9) To access the Web GUI, click on the “Diagnostics & Debugging” button in the bottom right side of the page.
Condair LINKS 2587516_B_EN_1810 I 19
Figure 9: Web Configurator Screen
From the Web GUI landing page, click on “Setup” to expand the navigation tree and
then select “Network Settings” to access the IP Settings menu. (Figure 10)
Figure 10: Changing IP Address via Web GUI
Modify the IP Address (N1 IP Address field) of the ProtoCessor Ethernet port. If necessary, change the Netmask (N1 Netmask field). Type in a new Subnet Mask. If necessary, change the IP Gateway (Default Gateway field). Type in a new IP Gateway. NOTE: If the ProtoCessor is connected to a router, the IP Gateway of the ProtoCessor
should be set to the IP Address of that router.
Reset ProtoCessor. Unplug Ethernet cable from PC and connect it to the network hub or router. Record the IP Address assigned to the ProtoCessor for future reference.
20 | 2587516_B_EN_1810 Condair LINKS
6.5 Select Field Protocol For ED2 – Use the Protocol Selector by typing in the corresponding number next to the
desired protocol:
o BACnet MS/TP 1 o BACnet/IP 2 o Metasys N2 3
Then click “System Restart” to bring up options to configure the desired protocol.
For ED4 – There are no device details to be entered for this protocol combination.
6.5.1 BACnet MS/TP Configuration
Enter the appropriate details for BACnet MS/TP (   Figure 11):
Condair LINKS 2587516_B_EN_1810 I 21
Figure 11: Web Configurator Showing BACnet MS/TP Configuration
6.5.2 BACnet/IP Configuration
Enter the appropriate details for BACnet/IP (Figure 12):
22 | 2587516_B_EN_1810 Condair LINKS
Figure 12: Web Configurator Showing BACnet/IP Configuration
6.5.3 Metasys N2 Configuration
Enter the appropriate details for Metasys N2 (Figure 13):
Condair LINKS 2587516_B_EN_1810 I 23
Figure 13: Web Configurator Showing Metasys N2 Configuration
24 | 2587516_B_EN_1810 Condair LINKS
7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign
Specific Device Instances
After setting a local PC to the same subnet as the ProtoNode (Section 6.1), open a web
browser on the PC and enter the IP Address of the ProtoNode; the default address is
192.168.168.243.
o The Web Configurator will be displayed as the landing page. ( o o Figure 11 or Figure 12)
The Node_Offset field shows the current value (default = 50,000).
o The values allowed for a BACnet Device Instance can range from 1 to 4,194,303.
To assign a specific Device Instance (or range), change the Node_Offset value accordingly.
o Given that: Node_Offset + Modbus Node_ID = Device Instance o Then: Node_Offset (required) = Device Instance (desired) – Modbus
Node_ID
For example, if the desired Device Instance for the device is 1,001:
o Device has a Modbus Node-ID of 1 o Node_Offset (required) = 1,001 – (Modbus Node_ID) = 1,001 – 1 = 1,000
NOTE: The Node_Offset value will be applied to the device.
o Device Instance will then be = 1,000 + Modbus Node_ID = 1,000 + 1 = 1,001
Click “Submit” once the desired value is entered.
Figure 14: Active Profiles with Node-ID
Condair LINKS 2587516_B_EN_1810 I 25
8 How to Start the Installation Over: Clearing Profiles
After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a
web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.168.243.
If the IP Address of the ProtoCessor has been changed by previous configuration,
the assigned IP Address must be gathered from the network administrator.
The Web Configurator is displayed as the landing page. At the bottom-left of the page, click the “Clear Profiles and Restart” button. Once restart is complete, all past profiles discovered and/or added via Web
configurator are deleted. The unit can now be reinstalled.
26 | 2587516_B_EN_1810 Condair LINKS
9 LonWorks (FPC-ED4): Commissioning ProtoCessor on a
lonworks Network
Note: Commissioning may only be performed by the LonWorks administrator
9.1 Commissioning ProtoCessor FPC-ED4 on a LonWorks Network
The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoCessor FPC-ED4 at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool.
If an XIF file is required, see steps in Section 9.1.1 to generate XIF.
Figure 15: LonWorks Service Pin Location
9.1.1 Instructions to Download XIF File from ProtoCessor FPC-ED4 Using
Browser
Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and
ProtoCessor.
The Default IP Address of ProtoCessor is 192.168.168.24, Subnet Mask is
255.255.255.0. If the PC and ProtoCessor are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network.
For Windows XP:
Go to > > Right-click on Local Area Connection > Properties
Highlight >
Condair LINKS 2587516_B_EN_1810 I 27
For Windows 7 or later:
Go to > > > >
Right-click on Local Area Connection > Properties
Highlight >
For Windows XP and Windows 7, use the following IP Address:
Click twice.
Open a web browser and go to the following address: [IP Address of
ProtoCessor]/fserver.xif
Example: 192.168.168.24/fserver.xif If the web browser prompts to save the file, save the file onto the PC. If the web browser
displays the xif file as a web page, save the file onto the local PC as “fserver.xif”.
Figure 16: Sample of Fserver.XIF File Generated
28 | 2587516_B_EN_1810 Condair LINKS
This page intentionally left blank
Condair LINKS 2587516_B_EN_1810 I 29
Ethernet Port
A TROUBLESHOOTING
A.1 Lost or Incorrect IP Address
Ensure that FieldServer Toolbox is loaded onto the local PC. If not, download
FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care­Resource Center, Software Downloads:
http://www.sierramonitor.com/customer-care/resource-center?filters=software­downloads
Extract the executable file and complete the installation.
Figure 17: Ethernet Port Location
Disable any wireless Ethernet adapters on the PC/Laptop. Disable firewall and virus protection software if possible. Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor. Double click on the FS Toolbox Utility. Check IP Addresses from the Device listings.
Correct IP Address(es) by right clicking the settings icon and changing the IP Address.
Condair LINKS 2587516_B_EN_1810 Appendix I i
A.2 Viewing Diagnostic information
Type the IP Address of the ProtoCessor into the web browser or use the FieldServer
Toolbox to connect to the ProtoCessor.
Click on Diagnostics and Debugging Button, then click on view, and then on
connections.
If there are any errors showing on the Connection page, please refer to A.3 for the
relevant wiring and settings.
Figure 18: Error messages screen
A.3 Check Wiring and Settings
No COMS on Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is
a COM issue. To fix, check the following:
o Visual observations of LEDs on ProtoCessor (A.4) o Check baud rate, parity, data bits, stop bits o Check device address o Verify wiring
Field COM problems:
o Visual observations of LEDs on ProtoCessor (A.4) o Check dipswitch settings (using correct baud rate and device instance)
ii | Appendix 2587516_B_EN_1810 Condair LINKS
Tag
Description
Run
The Run LED will start flashing 20 seconds after power indicating normal operation. The Heat Beat LED has the same functionality but flashes more rapidly.
o Verify IP Address setting o Verify wiring
NOTE: If the problem persists, a Diagnostic Capture needs to be taken and sent to
support. (A.5)
A.4 LED Diagnostics for Communications Between ProtoCessor and Device
Please see the diagram below for ProtoCessor FPC-ED2 (left) and FPC-ED4 (right) LED Locations.
Figure 19: Diagnostic LEDs
Table 5 :Diagnostic LEDs
Condair LINKS 2587516_B_EN_1810 Appendix I iii
Sys/Config Error
The Sys/Config Error LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on ProtoCessor. If this occurs, immediately report the
related “system error” shown in the error screen of the GUI interface to
Sierra Monitor Corporation for evaluation.
Node Offline
The Node Offline LED will turn on and stay solid if there is no communication with the device.
RX
The RX LED will flash when a message is received on the field port.
TX
The TX LED will flash when a message is sent on the field port.
PWR
This is the power light and should show steady green at all times when ProtoCessor is powered.
Ethernet Port
A.5 Take Diagnostic Capture With the FieldServer Utilities
Once the Diagnostic Capture is complete, email it to na.info@condair.com. The Diagnostic Capture will accelerate diagnosis of the problem.
Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care: Resource Center, Software Downloads:
http://www.sierramonitor.com/customer-care/resource-center?filters=software­downloads
Extract the executable file and complete the installation.
Figure 20: Ethernet Port Location
Disable any wireless Ethernet adapters on the PC/Laptop. Disable firewall and virus protection software if possible. Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor. Double click on the FS Toolbox Utility.
Step 1: Take a Log
o Click on the diagnose icon of the desired device
iv | Appendix 2587516_B_EN_1810 Condair LINKS
o Select “Full Diagnostic"
NOTE: If desired, the default capture period can be changed
o Click on Start Diagnostic
Condair LINKS 2587516_B_EN_1810 Appendix I v
o When the capture period is finished, the Diagnostic Test Complete window will appear
Step 2: Send Log
o Once the diagnostic test is complete, a .zip file will be saved on the PC
o Click “Open to launch explorer and have it point directly at the correct folder,
then email the diagnostic zip file to na.info@condair.com
o
vi | Appendix 2587516_B_EN_1810 Condair LINKS
A.6 Update Firmware
To load a new version of the firmware, follow these instructions:
1. Extract and save the new file onto the local PC.
2. Open a web browser and type the IP Address of the FieldServer in the address bar.
NOTE: Default IP Address is 192.168.168.243 NOTE: Use the FS Toolbox utility if you do not know the IP Address (A.1)
3. Click on the “Diagnostics & Debugging” button.
4. In the Navigation Tree on the left hand side, do the following: a. Click on “Setup” b. Click on “File Transfer” c. Click on the “Firmware” tab
5. In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step
1.
6. Click on the orange “Submit” button.
7. When the download is complete, click on the “System Restart” button.
A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet
For both BACnet MS/TP and BACnet/IP, if more than one ProtoCessor is connected to the same subnet, they must be assigned unique Network_Number values.
On the main Web Configuration screen, update the Network Number with the “network_nr” field and click submit. The default value is 50.
Figure 21: Configuration Parameters – Setting Network Number for BACnet
Condair LINKS 2587516_B_EN_1810 Appendix I vii
Point Name
BACnet Object Type
BACnet Object ID
2Data Type
N2 Address
LonWorks Name
LonWorks SNVT
nvoStatus
AV 1 AO 1 nvoStatus_XXX
SNVT_lev_per cent
nviSigSource
AV 2 AO
2
nvi/nvoSigSource_X XX
SNVT_lev_per cent
nviCtrlMode
AV 3 AO
3
nvi/nvoCtrlMode_XX X
SNVT_lev_per cent
nviCtrlChannel
AV 4 AO 4 nvi/nvoCtrlCh_XXX
SNVT_lev_per cent
nviBMStimeout
AV 5 AO
5
nvi/nvoBMStmeout_ XXX
SNVT_time_se c
nvoHourOpt_A
AV 6 AO 6 nvoHrOpt_A_XXX
SNVT_time_ho ur
nvoHourWeight_A
AV 7 AO 7 nvoHrWght_A_XXX
SNVT_time_ho ur
nvoRHDem_A1
AV 8 AO 8 nvoRHDem_A1_XXX
SNVT_lev_per cent
nvoRHDem_A2
AV 9 AO 9 nvoRHDem_A2_XXX
SNVT_lev_per cent
nvoSysDem_A
AV
10
AO
10
nvoSysDem_A_XXX
SNVT_lev_per cent
nviManCapacity_A
AV
11
AO
11
nvi/nvoManCap_A_X XX
SNVT_lev_per cent
nviSetPoint_A1
AV
12
AO
12
nvi/nvoSetPnt_A1_X XX
SNVT_lev_per cent
nviSetPoint_A2
AV
13
AO
13
nvi/nvoSetPnt_A2_X XX
SNVT_lev_per cent
nviDRHDem_A1
AV
14
AO
14
nvi/nvoDRHDem_A1 _XXX
SNVT_lev_per cent
nviDRHDem_A2
AV
15
AO
15
nvi/nvoDRHDem_A2 _XXX
SNVT_lev_per cent
A.8 Securing the ProtoCessor with Passwords
Access to the ProtoCessor can be restricted by enabling a password. There are 2 access levels defined by 2 account names: Admin and User.
The Admin account has unrestricted access to the ProtoCessor.  The User account can view any ProtoCessor information, but cannot make any changes or
restart the ProtoCessor.
The password needs to be a minimum of eight characters and is case sensitive.
If the password is lost, click cancel on the password authentication popup window, and email the password recovery token to na.info@condair.com to receive a temporary password from the support team. Access the ProtoCessor to set a new password.
B VENDOR INFORMATION - CONDAIR
B.1 Nortec NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
viii | Appendix 2587516_B_EN_1810 Condair LINKS
nvoHourOpt_B
AV
16
AO
16
nvoHrOpt_B_XXX
SNVT_time_ho ur
nvoHourWeight_B
AV
17
AO
17
nvoHrWght_B_XXX
SNVT_time_ho ur
nvoRHDem_B1
AV
18
AO
18
nvoRHDem_B1_XXX
SNVT_lev_per cent
nvoRHDem_B2
AV
19
AO
19
nvoRHDem_B2_XXX
SNVT_lev_per cent
nvoSysDem_B
AV
20
AO
20
nvoSysDem_B_XXX
SNVT_lev_per cent
nviManCapacity_B
AV
21
AO
21
nvi/nvoManCap_B_X XX
SNVT_lev_per cent
nviSetPoint_B1
AV
22
AO
22
nvi/nvoSetPnt_B1_X XX
SNVT_lev_per cent
nviSetPoint_B2
AV
23
AO
23
nvi/nvoSetPnt_B2_X XX
SNVT_lev_per cent
nviDRHDem_B1
AV
24
AO
24
nvi/nvoDRHDem_B1 _XXX
SNVT_lev_per cent
nviDRHDem_B2
AV
25
AO
25
nvi/nvoDRHDem_B2 _XXX
SNVT_lev_per cent
nvoConnection
BV 1 DO 1 nvoConnectn_XXX
SNVT_switch
nvoService
BV 2 DO 2 nvoService_XXX
SNVT_switch
nvoFault
BV 3 DO 3 nvoFault_XXX
SNVT_switch
nviDisable
BV 4 DO 4 nvi/nvoDisable_XXX
SNVT_switch
nvoSecurity_A
BV 5 DO 5 nvoSecurty_A_XXX
SNVT_switch
nvoBlowerAct_A
BV 6 DO 6 nvoBlwrAct_A_XXX
SNVT_switch
nvoFanAct_A
BV 7 DO 7 nvoFanAct_A_XXX
SNVT_switch
nvoSecurity_B
BV 8 DO 8 nvoSecurty_B_XXX
SNVT_switch
nvoBlowerAct_B
BV 9 DO 9 nvoBlwrAct_B_XXX
SNVT_switch
nvoFanAct_B
BV
10
DO
10
nvoFanAct_B_XXX
SNVT_switch
Point Name
BACnet Object Type
BACnet Object ID
N2 Data Type
N2 Address
LonWorks Name
LonWorks SNVT
nvoStatus
AV 1 AO 1 nvoStatus_XXX
SNVT_lev_per cent
nviSigSource
AV 2 AO
2
nvi/nvoSigSource_X XX
SNVT_lev_per cent
nviCtrlMode
AV 3 AO
3
nvi/nvoCtrlMode_XX X
SNVT_lev_per cent
nviCtrlChannel
AV 4 AO 4 nvi/nvoCtrlCh_XXX
SNVT_lev_per cent
nviBMStimeout
AV 5 AO
5
nvi/nvoBMStmeout_ XXX
SNVT_time_se c
nvoHourOpt_A
AV 6 AO 6 nvoHrOpt_A_XXX
SNVT_time_ho ur
nvoHourWeight_A
AV 7 AO 7 nvoHrWght_A_XXX
SNVT_time_ho ur
nvoRHDem_A1
AV 8 AO 8 nvoRHDem_A1_XXX
SNVT_lev_per cent
nvoRHDem_A2
AV 9 AO 9 nvoRHDem_A2_XXX
SNVT_lev_per cent
B.2 Nortec GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
Condair LINKS 2587516_B_EN_1810 Appendix I ix
nvoSysDem_A
AV
10
AO
10
nvoSysDem_A_XXX
SNVT_lev_per cent
nviManCapacity_A
AV
11
AO
11
nvi/nvoManCap_A_X XX
SNVT_lev_per cent
nviSetPoint_A1
AV
12
AO
12
nvi/nvoSetPnt_A1_X XX
SNVT_lev_per cent
nviSetPoint_A2
AV
13
AO
13
nvi/nvoSetPnt_A2_X XX
SNVT_lev_per cent
nviDRHDem_A1
AV
14
AO
14
nvi/nvoDRHDem_A1 _XXX
SNVT_lev_per cent
nviDRHDem_A2
AV
15
AO
15
nvi/nvoDRHDem_A2 _XXX
SNVT_lev_per cent
nvoServInterval_A
AV
16
AO
16
nvoSrvIntv_A_XXX
SNVT_lev_per cent
nvoDaysService_A
AV
17
AO
17
nvoDaySrvc_A_XXX
SNVT_count_f
nvoConnection
BV
18
DO
18
nvoConnectn_XXX
SNVT_switch
nvoService
BV
19
DO
19
nvoSrvc_XXX
SNVT_switch
nvoFault
BV
20
DO
20
nvoFault_XXX
SNVT_switch
nviDisable
BV
21
DO
21
nvi/nvoDisable_XXX
SNVT_switch
nvoSecurity_A
BV
22
DO
22
nvoSecurty_A_XXX
SNVT_switch
Point Name
BACnet Object Type
BACnet Object ID
N2 Data Type
N2 Address
LonWorks Name
LonWorks SNVT
nvoStatus
AV 1 AO 1 nvoStatus_XXX
SNVT_lev_per cent
nviSigSource
AV 2 AO
2
nvi/nvoSigSource_X XX
SNVT_lev_per cent
nviCtrlMode
AV 3 AO
3
nvi/nvoCtrlMode_XX X
SNVT_lev_per cent
nviCtrlChannel
AV 4 AO 4 nvi/nvoCtrlCh_XXX
SNVT_lev_per cent
nviBMStimeout
AV 5 AO
5
nvi/nvoBMStmeout_ XXX
SNVT_time_se c
nvoHourOpt_A
AV 6 AO 6 nvoHrOpt_A_XXX
SNVT_time_ho ur
nvoHourWeight_A
AV 7 AO 7 nvoHrWght_A_XXX
SNVT_time_ho ur
nvoRHDem_A1
AV 8 AO 8 nvoRHDem_A1_XXX
SNVT_lev_per cent
nvoRHDem_A2
AV 9 AO 9 nvoRHDem_A2_XXX
SNVT_lev_per cent
nvoSysDem_A
AV
10
AO
10
nvoSysDem_A_XXX
SNVT_lev_per cent
nviManCapacity_A
AV
11
AO
11
nvi/nvoManCap_A_X XX
SNVT_lev_per cent
nviSetPoint_A1
AV
12
AO
12
nvi/nvoSetPnt_A1_X XX
SNVT_lev_per cent
nviSetPoint_A2
AV
13
AO
13
nvi/nvoSetPnt_A2_X XX
SNVT_lev_per cent
nviDRHDem_A1
AV
14
AO
14
nvi/nvoDRHDem_A1 _XXX
SNVT_lev_per cent
nviDRHDem_A2
AV
15
AO
15
nvi/nvoDRHDem_A2 _XXX
SNVT_lev_per cent
B.3 Nortec EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
x | Appendix 2587516_B_EN_1810 Condair LINKS
nvoHourOpt_B
AV
16
AO
16
nvoHrOpt_B_XXX
SNVT_time_ho ur
nvoHourWeight_B
AV
17
AO
17
nvoHrWght_B_XXX
SNVT_time_ho ur
nvoRHDem_B1
AV
18
AO
18
nvoRHDem_B1_XXX
SNVT_lev_per cent
nvoRHDem_B2
AV
19
AO
19
nvoRHDem_B2_XXX
SNVT_lev_per cent
nvoSysDem_B
AV
20
AO
20
nvoSysDem_B_XXX
SNVT_lev_per cent
nviManCapacity_B
AV
21
AO
21
nvi/nvoManCap_B_X XX
SNVT_lev_per cent
nviSetPoint_B1
AV
22
AO
22
nvi/nvoSetPnt_B1_X XX
SNVT_lev_per cent
nviSetPoint_B2
AV
23
AO
23
nvi/nvoSetPnt_B2_X XX
SNVT_lev_per cent
nviDRHDem_B1
AV
24
AO
24
nvi/nvoDRHDem_B1 _XXX
SNVT_lev_per cent
nviDRHDem_B2
AV
25
AO
25
nvi/nvoDRHDem_B2 _XXX
SNVT_lev_per cent
nvoConnection
BV 1 DO 1 nvoConnectn_XXX
SNVT_switch
nvoService
BV 2 DO 2 nvoSrvc_XXX
SNVT_switch
nvoFault
BV 3 DO 3 nvoFault_XXX
SNVT_switch
nviDisable
BV 4 DO 4 nvi/nvoDisable_XXX
SNVT_switch
nvoSecurity_A
BV 5 DO 5 nvoSecurty_A_XXX
SNVT_switch
nvoBlowerAct_A
BV 6 DO 6 nvoBlwrAct_A_XXX
SNVT_switch
nvoFanAct_A
BV 7 DO 7 nvoFanAct_A_XXX
SNVT_switch
nvoSecurity_B
BV 8 DO 8 nvoSecurty_B_XXX
SNVT_switch
nvoBlowerAct_B
BV 9 DO 9 nvoBlwrAct_B_XXX
SNVT_switch
nvoFanAct_B
BV
10
DO
10
nvoFanAct_B_XXX
SNVT_switch
Point Name
BACnet Object Type
BACnet Object ID
N2 Data Type
N2 Address
LonWorks Name
LonWorks SNVT
MI_UnitStatusA
MI 1 ADI 1 nvoUnitStatA_XXX
SNVT_count
MI_UnitStatusB
MI 2 ADI 2 nvoUnitStatB_XXX
SNVT_count
MI_ServStatusA
MI 3 ADI 3 nvoServStatA_XXX
SNVT_count
MI_ServStatusB
MI 4 ADI 4 nvoServStatB_XXX
SNVT_count
MI_HumType
MI 5 ADI 5 nvoHumType_XXX
SNVT_count
MI_NomVoltage
MI 6 ADI 6 nvoNomVolt_XXX
SNVT_count
MI_LevelA
MI 7 ADI 7 nvoLevelA_XXX
SNVT_count
MI_LevelB
MI 8 ADI 8 nvoLevelB_XXX
SNVT_count
AI_ErrorCode
AI 1 AI 1 nvoErrorCode_XXX
SNVT_count
AI_OperatHours
AI 2 AI 2 nvoOperatHr_XXX
SNVT_time_ho ur
AI_HoursToServA
AI 3 AI 3 nvoHrToServA_XXX
SNVT_time_ho ur
AI_HoursToServB
AI 4 AI 4 nvoHrToServB_XXX
SNVT_time_ho ur
AI_SystemDemandA
AI 5 AI 5 nvoSysDem_XXX
SNVT_count
AI_InputA1
AI 6 AI 6 nvoInputA1_XXX
SNVT_count
AI_InputA2
AI 7 AI 7 nvoInputA2_XXX
SNVT_count
B.4 Nortec EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
Condair LINKS 2587516_B_EN_1810 Appendix I xi
AI_MaxHumOut
AI 8 AI
8
nvoMaxHumOut_XX X
SNVT_count
AI_CylMaxCapA
AI 9 AI 9 nvoCylMxCapA_XXX
SNVT_count
AI_CylMaxCapB
AI
10
AI
10
nvoCylMxCapB_XXX
SNVT_count
AI_ActCapHum
AI
11
AI
11
nvoAcCapHum_XXX
SNVT_count
AI_CylActCapA
AI
12
AI
12
nvoCylAcCapA_XXX
SNVT_count
AI_CylActCapB
AI
13
AI
13
nvoCylAcCapB_XXX
SNVT_count
AV_SetPointA1
AV 1 ADF
1
nvi/nvoSetPntA1_XX X
SNVT_count
AV_SetPointA2
AV 2 ADF
2
nvi/nvoSetPntA2_XX X
SNVT_count
AV_PropBandA1
AV 3 ADF
3
nvi/nvoPropBndA1_X XX
SNVT_count
AV_PropBandA2
AV 4 ADF
4
nvi/nvoPropBndA2_X XX
SNVT_count
AV_IntTimeA1
AV 5 ADF
5
nvi/nvoIntTimeA1_X XX
SNVT_count
AV_DampTimeA2
AV 6 ADF
6
nvi/nvoDmpTimeA2_ XXX
SNVT_count
AV_CapLimitA
AV 7 ADF
7
nvi/nvoCapLimitA_X XX
SNVT_count
AV_RemoteDrain
AV 8 ADF
8
AO_RemRHorDemA1
AO 1 AO
1
nvi/nvoRmRHrDmA1 _XXX
SNVT_count
AO_RemRHorDemA2
AO 2 AO
2
nvi/nvoRmRHrDmA2 _XXX
SNVT_count
BI_BlowerPackA
BI 1 DI 1 nvoBlwrPackA_XXX
SNVT_switch
BI_BlowerPackB
BI 2 DI 2 nvoBlwrPackB_XXX
SNVT_switch
BI_ExtSChStaA
BI 3 DI 3 nvoExtSChStA_XXX
SNVT_switch
BI_ExtSChStaB
BI 4 DI 4 nvoExtSChStB_XXX
SNVT_switch
BI_IntSChStaA
BI 5 DI 5 nvoIntSChStA_XXX
SNVT_switch
BI_IntSChStaB
BI 6 DI 6 nvoIntSChStB_XXX
SNVT_switch
BI_HeatVoltageA
BI 7 DI 7 nvoHeatVoltA_XXX
SNVT_switch
BI_HeatVoltageB
BI 8 DI 8 nvoHeatVoltB_XXX
SNVT_switch
BI_LevelSafetyA
BI 9 DI 9 nvoLvlSaftyA_XXX
SNVT_switch
BI_LevelSafetyB
BI
10
DI
10
nvoLvlSaftyB_XXX
SNVT_switch
BI_LeakA
BI
11
DI
11
nvoPressureA_XXX
SNVT_switch
BI_LeakB
BI
12
DI
12
nvoPressureB_XXX
SNVT_switch
BI_MainContactA
BI
13
DI
13
nvoMainContA_XXX
SNVT_switch
BI_MainContactB
BI
14
DI
14
nvoMainContB_XXX
SNVT_switch
BI_PumpA
BI
15
DI
15
nvoPumpA_XXX
SNVT_switch
BI_PumpB
BI
16
DI
16
nvoPumpB_XXX
SNVT_switch
BI_InletA1
BI
17
DI
17
nvoInletA1_XXX
SNVT_switch
BI_InletB1
BI
18
DI
18
nvoInletB1_XXX
SNVT_switch
BI_InletA2
BI
19
DI
19
nvoInletA2_XXX
SNVT_switch
BI_InletB2
BI
20
DI
20
nvoInletB2_XXX
SNVT_switch
BI_DrainA1
BI
21
DI
21
nvoDrainA1_XXX
SNVT_switch
BI_DrainB1
BI
22
DI
22
nvoDrainB1_XXX
SNVT_switch
BI_DrainA2
BI
23
DI
23
nvoDrainA2_XXX
SNVT_switch
BI_DrainB2
BI
24
DI
24
nvoDrainB2_XXX
SNVT_switch
BI_FanA
BI
25
DI
25
nvoFanA_XXX
SNVT_switch
BI_FanB
BI
26
DI
26
nvoFanB_XXX
SNVT_switch
BI_FlushValveA
BI
27
DI
27
nvoFlushVlvA_XXX
SNVT_switch
BI_FlushValveB
BI
28
DI
28
nvoFlushVlvB_XXX
SNVT_switch
xii | Appendix 2587516_B_EN_1810 Condair LINKS
ProtoCessor FPC-ED2
ProtoCessor FPC-ED4
Electrical Connections
One 3-pin Phoenix connector with
RS-485 port (+ / - / gnd)
One Ethernet 10/100 BaseT port
One 2-pin Phoenix connector with:
One FTT-10 LonWorks port
One Ethernet 10/100 BaseT port
Approvals
CE Certified; TUV approved to UL 916, EN 60950-1, EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15; DNP3 Conformance Tested; RoHS Compliant; CSA 205 Approved
BTL Marked
LonMark Certified
Power Requirements
Multi-mode power adapter: 9-30VDC or 12 - 24VAC
Physical Dimensions
6.9 x 3.0 x 2.0 cm
2.7 x 1.2 x 0.8 in.
8.5 x 3.0 x 2.0 cm
3.3 x 1.2 x .08 in.
Weight
0.03 kg (0.07 lbs)
Operating Temperature
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
C REFERENCE
C.1 Specifications
Figure 22: Specifications
C.2 Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating ProtoCessor.The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.The interconnecting power connector and power cable shall:
Comply with local electrical code Be suited to the expected operating temperature range Meet the current and voltage rating for ProtoCessor Furthermore, the interconnecting power cable shall: Be of length not exceeding 3.05m (118.3”) Be constructed of materials rated VW-1, FT-1 or better If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be
installed in a Restricted Access Area requiring a key or a special tool to gain access.
This device must not be connected to a LAN segment with outdoor wiring.
Condair LINKS 2587516_B_EN_1810 Appendix I xiii
Page intentionally left blank
xiv | Appendix 2587516_B_EN_1810 Condair LINKS
Warranty
Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever
date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise
expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing
replacement parts to the customer, F.O.B. THE COMPANY’s factory, provided that the defective
part(s) is returned freight prepaid by the customer. The replacement parts are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not manufactured by the COMPANY, such
as controls, humidistats, pumps, etc., is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase, and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage to the humidifier, supply lines, drain lines, or steam distribution systems caused by freezing.
THE COMPANY reserves the right to change the design, specifications and performance criteria of its products without notice or obligation.
Consulting, Sales and Service:
U.S.A.
835 Commerce Park Ave Ogdensburg, NY 1366-2209
CANADA 2740 Fenton Road Ottawa, ON, K1T 3T7
Tel: 1.866.667.8321 Fax: 613.822.7964
Email: na.info@condair.com Website: www.condair.com
Loading...