Thank you for purchasing a Concept Smoke Screen Titanium system. Your choice to protect your property
and premises with this equipment has given you the use of one of the most effective security systems
currently available. Concept Smoke Screen systems have been in service for over 35 years and have
protected many millions of pounds worth of property, defeating criminals and securing premises on an almost
daily basis.
The Titanium line in particular is home to some incredibly sophisticated and flexible security fog generators,
borne from years of development and refinement.
Please take the time to read and understand this guide to ensure you achieve the maximum performance
from your Smoke Screen. If you have any questions that remain unanswered, please call our experts at
Concept Smoke Screen and we will help. Once again, thank you for your decision; we hope that it's one that
never needs to be tested.
Matt Gilmartin, Managing Director
Page 3 of 30
Page 4
CONTENTS
Section
Subject
Page
1
General
1.1
Safety instructions
4
1.2
How does your Smoke Screen work ?
4
1.3
Introduction 5 1.4
Overview 5 1.5
Typical insta ll at i on
5
2
Location
2.1
Positioning 6 2.2
Installation procedure
7
2.3
Access 8 2.4
Mounting
8/9
2.5
Nozzle changing
9
3
Function
3.1
Controlling the smoke
10
3.2
Outputs
10
4
Connections
4.1
Circuit board layout
11
4.2
Generic connection diagram
12
5
Settings
5.1
Screen Sensor
13
5.2
Energy saving mode
13
5.3
Isolate mode
13
5.4
Tamper
13
5.4
Fluid management
14
5.6
Battery management
14
5.7
IP integration
15
5.8
Programming
16
6
Commissioning
6.1
Testing
24
7
Servicing
7.1
LED and sound indications
25
7.2
Thermal Cut Out (TCO) Reset
26
7.3
Action after every activation
27
7.4
Servicing and fluid replenishment
27
8
Miscellaneous
8.1
FAQ
27
8.2
Installer notes
28
Page 4 of 30
Page 5
WARNING
CAUTION
1.1 SAFETY INSTRUCTIO NS
Before installing and using the Smoke Screen read, follow and retain this manual and safety
instructions for future reference.
To reduce the risk of severe injury or death to persons, or damage to the Smoke Screen:
• Do not work on the Smoke Screen unless qualified by the manufacturer to do so.
• Disconnect the mains power supply before working in the heater block compartment or
anywhere that mains voltage is indicated by the warning labels shown below.
• Install in accordance with the instructions in this manual.
• Operate the Smoke Screen only from the type of power source indicated on the label.
• Do not modify the Smoke Screen.
• Adjust only those controls specified in this manual.
• Use only consumables and replacement parts specified by the manufacturer.
• Do not spill liquid of any type on, or inside, the Smoke Screen.
The following signs, or a variation, may be used for safety notices in this manual or on the Smoke
Screen:
This type of warning note is
used to indicate possible
electrical shock hazards that
may cause serious injuries
or death.
This type of warning note is
used to indicate the
possibility of injury caused by
hazards other than electrical
shock.
1.2 HOW DOES YOUR SMOKE SCREEN WORK?
Your Smoke Screen passes a non-toxic fluid through an efficient heat exchanger to create smoke,
or more accurately a thermally generated fog, that obscures visibility, discouraging intruders from
entering your premises.
This fog is very persistent and will stay suspended in the room for a significant length of time unt il it
is vented by opening the doors and windows.
The Smoke Screen uses a sophisticated electronic control system to ensure it heats up to, and
maintains, its ideal operating temperature using a minimal amount of electricity.
This control system similarly provides a flexible interface with intruder detectors, alarm systems
and remote monitoring centres to ensure that you are always protected and free of inadvertent
activations.
Page 5 of 30
Page 6
1.3 INTRODUCTION
Smoke Screen
Alarm Panel
IP status outputs
IP command inputs
Alarm Hold-off (PI R or
similar dev ic e )
Smoke Screen
User Interface
(Optional)
Status
Test Facility
Status outputs
Activation commands
Activation comm ands
for test facility
This manual covers the Titanium line of products
Before commencing instal lation of the Smoke Screen ensure that you have all o f the following
equipment suppli ed in the box:
• 1 x Smoke Screen
• 1 x Mounting Bracket
• 1 x Swift-fit fluid reservoir
• 2 x 12v Batteries.
• 1 x Literature Pack & Warning Sign
You will also require:
• Mains power supply and connections into the Alarm Panel or other triggering system.
• PIR (or equivalent) to provide the hold-off where required.
• Optionally a Screen Sensor fo r top-up functionality
1.4 OVERVIEW
The Smoke Screen is designed to form part of an ex istin g intruder alar m syste m but m ay also be
configured as a ‘stand-alone’ system or as part of a cent rally monitored , comm and and con trol sy stem .
A typicalinstallation is sho wn i n the following schematic:
1.5 TYPICAL INSTALLATION
A typical installation can be configured in the following way:
• The Smoke Scre en is wall or ceiling mounted in the appropriate location.
• A Hold-off PIR (or similar device) located within the same area as the Smoke Screen providing
a confirmation signal to the Smoke Screen to start, or re-start, ‘smoke’ production.
• A Set command supplied by an Alarm Control Panel, or equivalent, in the form of an N/C
(Normally closed) or an N/O (Normally open) relay changing state when the Alarm system is
set for operation.
Page 6 of 30
Page 7
• A Trigger command supplied by the Alarm Control Panel, or equivalent, in the form of an N/C
(Normally closed) or an N/O (Normally open) relay changing state when the Alarm system
confirms an intruder alert.
2.1 POSITIONING
The Smoke Scre en should ideally be sited in a covert position away from prying eyes and thereby
reducing the possibility of tamper or an attack. The ideal place for the Smoke Screen is above a
ceiling from where the smoke plume is used to its best effect, bursting on the ground and
spreading outwards and upwards through 360°. If no suitable ceiling location is available then the
next best location is a wall mounting as close to ceiling height as possible.
Wall-mounting.
The optimum wall mounting position for the Smoke Screen is 2.5 metres above the floor facing the
area to be protected and using an appropriate angle nozzle. The maximum recommended
mounting-height above floor level is 3 metres, the minimum is 1 metre and there should be no
obstacle within 1 metre of the smoke output nozzle.
Ceiling-mounting.
The optimum ceiling mounting height for the Smoke Screen is 2.5 metres above the floor over the
area to be protected and using a straight nozzle. The maximum recommended mounting-height
above floor level is 3 metres and there should be no obstacle within 1 metre of the smoke output
nozzle.
Page 7 of 30
Page 8
2.2 INSTALLATION PROCEDUR E
1. Site the Smoke Screen, fix to the wall or ceiling as appropriate.
2. For wall mounting leave minimum 150mm clearance on all sides of the generator.
3. Make connections as required to the Alarm Panel and Hold-off PIR.
4. Make connection to the Smoke Screen Interface (if used) and set the key switch to isolate.
5. Connect mains power.
6. The Sm oke Scre en will heat up to operating temperature in approximately 20 minutes.
7. Make relevant programming settings and set smoke timing for the specified room size.
8. With the power applied insert and connect the fluid consumable.
9. Make sure all tamper switches are closed and you are ready for test.
Page 8 of 30
Page 9
2.3 ACCESS
1 2 3
To access the PCB connections, programming panel and mounting holes (battery and fluid access
is covered in the relevant sections) remove the front cover by unscrewing the 2 set screws on
either side and unhooking it from the top of the case; refitting is the reverse process. Installation
cable entry is through the serrated grommet on the left back of the case.
2.4 MOUNTING
The Smoke Screen can be mounted on a ceiling or a w all using the simple standard brac ket supplied
with the unit. This flush-fitting bracket maximizes security by concealing all the mounting fastenings
such that they can only be acce ssed, o r the S moke Screen dismounted, by di smantling the uni t.
Moreover, the Smoke Sc reen has a ta mper pro tection sw itch to provide an al ert in the unlikely event that
it is disturbed. In all cases, the installer must attach the Smoke Screen to the building structure using
appropriate fasteners.
NB: When mounting the Smoke Screen ensure that the airflow through the vent holes in the rear
of the unit is no t obstruc ted.
Wall and ceiling mounting
Ceiling or wall mounting is the same process except that rather than fixing the Smoke Screen
direct to a ceiling an intermediate unistrut section may be used or it can be suspended as
described in the next section. Attach the bracket to the wall or ceiling using appropriate fixings (1).
Carefully hook the slots on the back of the Smoke Screen onto the bracket (2) and slide along to
align the screw fixing holes. The unit will now hang on the bracket. Fit, and ensure tight, 4 x M6
set screws with washers in the holes in the back of the Smoke Screen alongside each mounting
slot (3) - access to the fixing holes is through the fluid and heater block compartments.
Page 9 of 30
Page 10
Suspension mounting
Be aware of high voltage in
This operation is usually
cool.
5 6 7
4
Suspending the Smoke Screen is achieved using a ‘Suspension Kit’ comprising a length of Unistrut, two sections of threaded bar and fixings (4). Prepare the Smoke Screen by fitting the angle
brackets as described above. Fix the required length of M8 threaded bar to the bracket using 4 x
nuts and 4 x 25mm washers (5). Fix the uni-strut into place. There are a range of fixings to
accommodate concrete ceiling, girders etc; if in doubt contact the fixing supplier. Attach the
threaded bar to the uni-strut using the channel nuts, 38mm washers and M8 nuts (6). Once this is
done the Smoke Screen can be lifted into position and the set screws tightened as above (3). Any
fine adjustments can be made at this stage as the nuts and the threaded bar will take the weight of
the Smoke Screen. The final assembly, viewed ‘through the ceiling’ is in photo (7).
Suspension Kit (All M8)
Uni-strut 1 x 1 metre
Threaded bar 2 x 1 metre
Fixings:
1 x ceiling hole surround
2 x drop-in anchor
6 x full nut
4 x 25mm washer
2 x 38mm washer
2 x channel nuts
2.5 NOZZLE CHANGING
WARNING
To change the nozzle, first remove the front cover then remove, and replace, the nozzle using a
12mm ring spanner. Always use a new PTFE tape (S35/S55) or a new copper washer
(S70/TI70/TI100) and ensuring that an angled nozzle is seated in the correct orientation. The
the block area. The
electrical supply should be
switched off before working
in the heater block
compartment.
Page 10 of 30
CAUTION
carried out during
installation. If the Smoke
Screen has been in service
the nozzles will be extremely
hot and will cause injury if
touched. Therefore, the
Smoke Screen should be
switched off and time should
be allowed for the nozzles to
Page 11
Smoke Screen is delivered with a single-hole straight nozzle and the following are also available –
2-hole horizontal, 3-hole horizontal, 1-hole 30 deg angle down and 2-hole 30 deg angle down.
3.1 CONTROLLING THE SMOKE
Inputs. There are 6 sets of input control connections on the Smoke Screen that control activation -
Alarm Set (Z1), Trigger (Z2), Top-Up (Z3), Hold Off (Z4), Panic (Z5) and Isola te (Z6). These input pins
should be connected to the PCB Ground throu gh clean contacts and can be programmed to “Normally
closed”, “Close = Alarm”, a variety of E OL resistance settings or “input not used”.
Starting an activation. The Smoke Screen will produce ‘ smo ke’ in the following 3 circumstances:
• The 3 connections normall y used in an ins tallation, i .e. Alarm Set (Z1), Trigge r (Z2), and Hold
Off (Z4) (if selected to on) must all be in alarm.
or
• The Panic (Z5) connection must change sta te from restore to an alarm condition. This inpu t is an
edge input and will not trigger a genera tor if it is alre ady i n its alar m condition w hen the genera tor
reaches a “ready” state.
or
• The Alarm Set (Z1) and a tamper are in alar m.
Stopping an activation. Once activated the Smoke Screen will stop producing ‘smo ke’ before the end
of the programmed smoke time only if the Alarm Set (Z1) is selected to a n on-alarm state; in the event of
a Panic activation it may be nece ssary to cycle th e A larm Set (Z1) to “on” then “off”. If ‘Hold-O ff’ is
closed during an activation the S moke Sc reen w il l continue to produce smo ke for the set S moke Time.
Re-triggering smoke (Hold-off attached and set to “On”). If, after it has made smoke for the set time
and reached the end of it’s p rogrammed “Smo ke on” time, the Smoke Screen receiv es anothe r hold -off
alarm while both ‘Set’ and ‘Trigger’ inputs remain open, it w ill ‘re-trigger’ and make smoke again. The
re-trigger smoke time, as a % of the smoke time set, and the number of repea ts are se t in t he Ins taller
menu.
Preventing an activation. To prevent the S moke S creen from making s moke unde r any
circumstances:
• Select Isolate to “On” in the Installer menu .
or
• Select programmable Z6 to “Isolate” and eithe r conn ect (if se t to ‘cl ose = Alarm ’) or disc onnect (if
set to ‘Normally closed’) the zone from Ground. This i nput is an edge i nput and care must be
taken that when the generator is first ins talled, the input is correctly confi gured to avoid
unintended effects.
3.2 OUTPUTS
Outputs. Clean contact outputs are provided for connection to the Alarm Panel for ‘Ready’,
‘Tamper’, ‘Battery Failure’, ‘Mains Failure’, ‘Fluid Low’, ‘Fluid Empty’, ‘Making Smoke’. There are
also 3 programmable clean contact outputs (PGM 1, PGM 2 and PGM 3) that can be set to
"Disabled", "Follow Trouble", "Follow Run Dry", "Follow Isolate", "Timer Relay" or "Follow Zone".
Alarm Panel ouput contacts should be clean
relay closed pairs energising open*.
"Panic" input.
Detects a n/c circuit going open.
RS485 communication connections.
Ground output.
DC output for additional devices.
Ground pin to prevent the Smoke Screen from activating.
Alarm Panel detects n/c circuit going open to
signal the specified event*.
Outputs
3 x programmable outputs - see manual for options.
Internal Tamper indication.
Smoke top up facility - see manual for options.
Smoke Screen making smok e indication.
Fluid reservoir empty.
Fluid reservoir contents low .
* - Smoke S creen output can be individually programmed to n/o or n/c
through the menu settings.
These are clean contacts changing state
when the marked function changes status .
Total output must not be greater than 1000mA.
Connect to Smoke Screen ground through
clean contacts changing state on "Alarm".
Power f rom Smoke
Screen
Power f rom Smoke
Screen
Mains power failure.
Battery pow er failure.
"Hold-off" input from PIR or similar device.
Ground output.
4.2 GENERIC CONNE CTION DIAGRAM
The Smoke Screen can be progra mmed to use “No rmally closed”, “Close = Alarm”, or a variety of EOL resistance configurations (used to detect tampers on
the circuits); for clarity the diagram below uses “Normally closed” connections . EOL resistors are fitted a s usual be tw een the relevant pin and ground when
used.
A Concept Smoke Screen “Screen Sensor” can be used on Zone 3 of the Titanium. When this is
integrated, the system detects a drop in the fog density in the protected area and will re-trigger the
Titanium to maintain the fog level. To ensur e that an installer can set an appropriate “top up” of fog
and avoid overdosing the area the Titanium can be programmed to limit the number of times the
Screen Sensor can initiate a re-trigger. Moreover, the re-trigger “on time” can also be set as a
percentage of the normal running time.
NB: It is critical that the Screen Sensor is installed in an area that receives the maximum fog
coverage. It will not operate correctly if this is not achieved.
5.2 ENERGY SAVING MO DE ( ESM )
There are 3 settings for ESM – “Off” , “ On” and “Extreme ”.
“Off”. When ES M is set to “Off” the Smoke Screen maintains full operating temperature at
all times.
“On”. When ESM is set to “On” and the Alarm Panel input to the Smoke Screen is “Unset”
the Smoke Screen lowers its running temperature to a standby level to reduce power
consumption and cost. When the Smoke Screen receives an “Alarm Set” input it
automatically heats to its normal operating temperature. The Smoke Screen is capable of
satisfying an activation demand immediately after the Alarm Panel is “Set”.
“Extreme”. With ESM to “Extreme” and the Alarm Panel input to the Smoke Screen is
“Unset” the Smoke Screen goes cold and reheats to operating temperature when it
receives an “Alarm Set” input.
NB: IN “EXTREME” ESM MODE THE SMOKE SCREEN WILL NOT BE ABLE TO MAKE
SMOKE FOR THE FIRST 20-30 MINUTES AFTER THE ALARM PANEL IS “SET”.
5.3 ISOLATE MODE
To prevent the Smoke Screen from making smoke whilst work is conducted with power applied it
can be put into a servicing mode by selecting the “Isolate” function at the start of the Installer
Configuration Menu to ‘on’.
FAILURE TO DISABLE ISOLATE WHEN NO LONGER REQUIRED WILL PREVENT THE
SMOKE SCREEN OPERATING.
5.4 TAMPER
There are 4 internal tamper circuits on the Smoke Screen, one on each cover (front, battery and
fluid) and one through the rear of the case for a bracket tamper. There is also an external tamper
input on the PCB for the monitoring of peripheral devices. On a tamper alarm t he Smoke S creen
provides an output indication of the event and automatically activates if the Zone 1 (Set ) is in
alarm. If the Smoke Screen is not mounted on its bracket the bracket tamper should be by-passed
to prevent unwanted tamper warnings.
Page 14 of 30
Page 15
Removal and replacement. To remove the batteries, open the access
intending to use the battery facility.
5.5 FLUID MANAGEMENT
The Smoke Screen has a replaceable 1 litre fluid reservoir (using Fluid R, also known as p roduct code
SFL-1000) that is accesse d by remov ing the cover o n the right-hand side of the unit. The fluid l evel is
monitored using sensors in the fluid reservoir.
Fluid Replenish: Obtain a replacement fluid reservoir from your Smoke Screen supplier (a
discount is available if the empty container is returned). Open the right-hand access panel. Lift the
reservoir out of the compartment by removing the lower end first (see photo below). Disconnect
the fluid monitoring cable and the fluid feed pipe (pull collar to release). Refit ting the reservo i r is
the reverse of the removal process.
Fluid resevoir
Fluid sensor
Cable plug
Fluid feed pipe
connector
5.6 BATTERY MANAG EMEN T
Operation. The Smoke Screen is fitted with a battery to provide power to the electronic circuits
and pump (not to the fluid heater) in the event of a mains power failure. This ensures that a
minimum of 90 minutes after a mains power failure at an ambient temperature of 20 deg C the
Smoke Screen can provide a minimum 30 second activation.The Smoke Screen is capable of
activating in the event of a battery fault or if the batter ies are not fitted. The Smoke S creen is
supplied with a set of batteries but they are not fitted on delivery. Replacement batteries may be
obtained from your Smoke Screen installer or Concept Smoke Screen.
panel on the left side of the Smoke Screen. Slide out the old batteries
and replace with new units ensuring that the battery is upright and the
contacts enter the battery compartment first.
Battery Switch. The Smoke Screen has a switch in the battery
compartment to permit the batteries to be disconnected from the system
whilst remaining in place. The delivery setting is “Off” ; select to “On” if
THE SMOKE SCREEN WILL NO T FUNCTIO N AT ALL DURING A MAINS POWER FAILURE IF
THE BATTERIES ARE NOT FI TTED.
Page 15 of 30
Page 16
5.7 Enhanced Communi c ation and integrat i on
All Titanium Smoke Screen generators equipped with HW V6 have a number of additional and
enhanced communication options. These are provided over and above the communication
available at the standard contacts.
The generators provide the following:
- SNMPv3 communication over IP and RS485 serial bus
- Master and slave functionality over RS485 serial bus
These communications features can be used in the following ways:
5.7.1 SNMPv3
SNMPv3 IP communication allows the Smoke Screen to be fully integrated with any PSIM solution
which supports this protocol. Additionally, connection to a dedicated SmokeNet server is possible
allowing full remot e command and control capability of the Smoke Screen system. It is also
possible for Smoke Screen installers to remotely diagnose and configure Smoke Screen systems
using the TitanConfig application.
N.B. important – when making changes to IP addresses, the system must be restarted in
order for the change to be registered. To restart the system use the command from the
installer menu.
5.7.2 RS485 serial bus
When this is utilized, one Smoke Screen can be set as the Master system which will then control
up to 9 slaves on the same bus. It is possible to chain many more using a SmokeIPXL.
When making use of this feature, the following things become true:
1. The master SSM operates as a global input and output point for the controlling alarm
system (where used).
In this scenario, any attached slave system that develops a local fault, will trigger a global
fault at the master.
The slaves will follow the “Set” and “Trigger” status of the master and will then operate
when they detect movement on a locally attached hold off detector. If “hold-off chain” is
selected on the master, a slave that detects a hold off alarm, will pass the signal to all
attached generators (including the master) and the whole system will trigger.
Equally, if “Panic propagate” is selected at the master, a triggered panic input at the master
or any attached slave, will trigger the whole chain. When this is de-selected, each panic
input will operate only the SSM it is attached to.
2. The master generator is capable of providing full information over a serial connection
relating to the condition of itself and all of the attached slaves to TitanConfig. This can then
be displayed as a wall of information providing easy visual information of the entire system.
See TitanConfig manuals for more information on this feature.
3. When using the onboard RS485 bus in a master/slave configuration, the amount of
attached slaves must be set at the master, and each slave must have a unique address
assigned from Slave 1-9 in sequence. For instance, It is not possible to assign slaves 1,2
& 3 and jump to 5 without assigning slave 4.
4. It is not possible to have 2 masters on the same bus – each assignment must be unique.
Page 16 of 30
Page 17
Main Menu
Time and Date
Hist ory
User Menu
Critical Faults
Inst aller men uMan uf acture r Men u
Coded access
Coded access
Navigation by arrow keys
Ent = Ad vance one level /save setting
Esc = G o ba ck one level/c anc el set t ing (if not sa ve d)
Read Only
Read Only
18.03.2015
13:30
▼
▲
LCD and operating buttons
5.8 PROGRAMMING(Software version 1.51)
The installer menu is accessed via the LCD and operating buttons (illustrated below) located on the front of the Smoke Screen PCB. The menu flow
and a description of the programmable/read parameters are given below.
Menu flow.
Page 17 of 30
Page 18
Page 18 of 30
Page 19
Page 19 of 30
Page 20
Service Mode that stops any activation and makes the "Ready" output "Not Ready". The
Settings available:
"Isolate" – Zone can be used to externally prevent the Smoke Screen activating.
Menu item description.
Main menu.
Menu item Sub-menu item Delivery Setting Description
History Log of the last 25 or 1500 events. Read only. Limit adjusted in installer configuration.
User Installer 1993 Coded access for the installer to set up the Smoke Screen.
Manufacturer Coded access available to Concept Smoke Screen only.
Critical Faults List of the current critical faults.
Installer time and date menu.
Menu item Sub-menu item Delivery Setting Description
Set Time 12:00 Set current time in hours and minutes.
Set Date 9:04:2015 Set current date in dd:mm:yyyy.
Set time zone 0 0=GMT. Each additional +1 or -1 is the respective amount away from GMT
Installer configuration menu.
These menu items permit the Smoke Screen to be set up for a particular installation. * = separate menu items combined for brevity.
Menu Item Sub-menu item Deliver y settin g
SSM Mode EN-50131-8
Isolate unit
Z6 Function
On
Isolate
Description
Determines whether the Smoke Screen will operate in EN-51031-8 mode or Iris mode
LCD flashes when selected "On".
"Disabled" – function not in us e.
Page 20 of 30
Page 21
RS485 configuration. SSM can be configured as Master, CCS Slave or Slave 1-9. When
Limits top up operations by time. When a Screen Sensor is used on Z3, this setting will
Sets top up operation as a % of “Smoke on time”. If the Screen sensor detects a drop in
Sets duration of first burst. Timer only runs when fog is being actively produced. Rest
Sets duration of Panic smoke time. Timer only runs when fog is being actively produced.
Enables hold-off retriggering. When “Smoke on” timer expires, and an intruder condition
Item available if Hold off set to "On". Can be set between 0 and 100% in 1% intervals.
Item available if Hold off set to "On". Can be set between 0 and 50 in 1 unit intervals.
Sets the time the Smoke Screen will wait after an activation demand before producing
Defines the type of input the Smoke Screen requires to sense an Alarm Set state.
Defines the type of input the Smoke Screen requires to sense a Trigger alarm Settings
Defines the type of input the Smoke Screen requires to sense an alarm state for the Top-
Menu Item Sub-menu item Deliver y settin g
Mbus Mode
Top up life cycle
Top up % time 25%
Smoke on time 01min 00 sec
Panic smoke time 01min 00 sec
Hold off
Hold off time 25%
CCS Slave
30 minutes
on
Description
configured as Master, options become available to propagate SNMP (remote) triggers to
the chain, propagate panic inputs from any point to the whole chain and propagate hold off
inputs from any point to the whole chain. Refer to RS485 section 5.7.2 for further
information.
cause the SSM to ignore further inputs from the Screen sensor after the timer has expired.
The timer begins after the first cycle of fog production i.e. if the “Smoke on” time is set to 2
minutes, the top up life cycle commences after 2 minutes.
fog density, the SSM will operate according to how this is set.
phases are ignored.
Rest phases are ignored.
still exists, if the hold-off reactivates, the SSM will re-trigger according to the sub-menu
settings.
Sets the re-triggering activation time as a % of the set “Smoke on” time.
Hold off rep nr 10
Smoke Delay
(Z1) Set Input
(Z2) Trigger Inp
(Z3) Top-up Detec
00 min 00 sec
Normally closed
Normally closed
Normally closed
Sets the number of times time that the SSM will retrigger when the hold-off reactivates.
smoke. Can be set between 0 and 2 minutes in 1 second intervals.
Settings available are “Normally closed”, “Normally open”, a range of EOL resistance
settings or “Not used”. Stops all activations except panic.
available are “Normally closed”, “Normally open”, a range of EOL resistance settings or
“Not used”.
up detector (Screen Sensor). Settings available are “Normally closed”, “Normally open”, a
range of EOL resistance settings or “Not used”.
Page 21 of 30
Page 22
Defines the type of input the Smoke Screen requires to sense a hold off alarm. Settings
Defines the type of input the Smoke Screen requires to sense a panic alarm state.
Defines the type of input the Smoke Screen requires to be isolated by this input. Settings
Sets the state of the PGM Outputs. Settings available are “Normally closed” and “Normally
Used to select which of the zones will trigger the PGM when the machine is in Iris mode
Set the time between 0 and 120 minutes in 1 second intervals that the PGM will change
Set the time between 0 and 3 minutes in 1 second intervals that the Smoke Screen will
Enables or disables the ESM. Settings available are "Off" (disabled), "On" (lowers the
Set the PCB temperature at which the onboard fan will operate (where fitted). 10-40oC in
Menu Item Sub-menu item Deliver y settin g
(Z4) Hold-Off Inp
(Z5) Panic Trig.
(Z6) Isolate Normally closed
PGM 1/2/3 output* Normally closed
PGM 1/2/3 function*
PGM Z1-6 Z1-6=Disabled
Zone number 0>0
PGM Timer 1 sec
Normally closed
Normally closed
Disabled
Description
available are “Normally closed”, “Normally open”, a range of EOL resistance settings or
“Not used”.
Settings available are “Normally closed”, “Normally open”, a range of EOL resistance
settings or “Not used”. This input ignores the condition of all other inputs. A panic i nput wi ll
trigger the generator for the set “Panic smoke” time.
available are “Normally closed”, “Normally open”, a range of EOL resistance settings or
“Not used”.
open”
timer", "Follow Zone"
and the respective zone changes state. The Up arrow scrolls through the zones and the
down arrow selects between “enabled” and “disabled”. Enter saves the setting
Used to set the required Zone (1 to 5) if "Follow Zone" selected.
state if "Timer Relay" selected.
Entry/exit time
Energy Save Mode
Siren Loudness
Siren Frequency
Temperature PCB 25oC
00 min 00 sec
off
0
1000Hz
ignore activation demands after the Alarm Panel sets the Alarm Set (Z1) input.
block temperature when the Alarm Panel is “Unset”) and "Extreme" (the block is not
heated when the Alarm Panel is “Unset”). For more information see the separate manual
section 5.2 on “Energy Saving Mode”
Sets the audio output volume from 0-5
Sets the audio output frequency from 1000 to 5000Hz in 500Hz intervals.
1o increments.
Page 22 of 30
Page 23
Set the installer access code from 0000 to 9999 by selecting each digit and adjusting from
Set the time between 0 and 99 minutes in 1 minute intervals that the menu will stay open
Read only if DHCP = "On". Adjustable by digit. System must be restarted using the in
Adjustable by digit. System must be restarted using the in menu command to register
Adjustable by digit. System must be restarted using the in menu command to register
Adjustable by digit. System must be restarted using the in menu command to register
Adjustable by digit. System must be restarted using the in menu command to register
Allows a limited function set to become available to a remote user (i.e. security manager or
Contacts the TFTP Update Server, and downloads and deploys a new firmware set if one
Restarts the system. This must be done in order for a change to the ne tworking
Sets the length of the event history that can be viewed in the Main Menu. Cn be set to
Resets the fluid timer if the Smoke Screen uses an indirectly monitored fluid system, ie a
Defaults the system to factory settings (NB: These may be different to delivery
Menu Item Sub-menu item Deliver y settin g
Installer Code
Menu Timeout
DHCP
Subnet Mask 255.255.255.000
TFTP Update IP
SmokeNet IP
SNMP Username Default
Update Firmware
IP 192.168.010.10
Gateway 192.168.002.001
1993
30 min
On
080.112.203.006
192.168.002.199
Description
0-9.
before reverting to the “Date and Time” screen.
menu command to register a change.
a change.
a change.
a change.
a change.
remote fault monitoring centre). Select “ConceptSSM” to enable.
is available.
Restart System
History Limit
Fluid Replenish
Reset Settings
Long
settings to take effect.
“Short” (25 items) or “Long” (1000 items).
bag.
settings)
Installer system monitor menu.
Page 23 of 30
Page 24
Read only display of current block status. In a total failure of both heaters (0 resistance), a very high value will be shown here
(+20000C)
These menu items read only indications to permit system parameter status to be monitored.
Menu Item Description
Tamper Batt Cov
Tamper Fluid Cov
Tamper Front Cov
Tamper External
Tamp Back Cov
AC Detect Loss of ac power from the transformer; the most likely cause is mains power failure. Alarm = fault.
13v6 out State of the low voltage DC output. Alarm = fault.
Back up Pwr Volt Condition of back up power Voltage. Alarm = fault
Batt Volt Condition of battery Voltage. Alarm = fault
(Z1) Set Input
(Z2) Trigger
(Z3) Programmable
(Z4) Hold Off Input
(Z5) Panic Trigger
(Z6) Isolate
DC Fuse State of the low voltage DC fuse on the PCB. Alarm = fault.
State of the selected tamper. Alarm = tamper.
State of the selected input Zone. Alarm = active.
Pump Fuse State of the pump fuse on the PCB. Alarm = fault.
Batt Resistance Battery condition. Alarm = fault
Block temp
Page 24 of 30
Page 25
Menu Item Description
Battery State Status of the battery charging system. Indications are "Charging", "Discharging", "Testing" and "Not Connected".
Ready output
Tamper output
Battery output
Mains fault out
Fluid low output
Fluid empty out
Smoke output
PGM1 output
PGM2 output
PGM3 output
Fluid input Fluid full/fluid low/fluid empty
Firmware version Current firmware version
Boot version Current bootloader version
Recovery version Current recovery version
Current IP Current IP address of SSM
Up time SSM power on time.
State of the selected output. Alarm = active.
Page 25 of 30
Page 26
Audio
siren alarm
●
Smoke Screen heating to
operating temperature
●
Smoke Screen at operating
temperature and status ok.
●
Smoke verification
output.
Smoke Screen producing
smoke.
●
●
Smoke Screen is isolated by
software setting or Z6
6.1 TESTING
Full alarm test. Where possible a full alarm test should be conducted to chec k that all inpu ts, outputs
and wiring connections to the Smo ke Screen are cor rect. If a PIR or other detector is fitted the Smoke
Screen will fire for the designated Smoke Time period once the ‘Set’, ‘Trigger’ and ‘Hold Off’ (if fitted)
contacts are open. It will stop producin g smoke i f the ‘Set’ contacts are closed.
7.1 LED AND SOUND I NDICATIO NS
The Smoke Screen provides on-board status monitoring via an LCD, 4 x LED and an audio siren ou tput
connection. LED indications displayed are:
LED LED Colour
Flashing Nil. Nil.
Operation
Steady Nil. Ready output to ok.
Triggering
Fault
Isolate
Fault indications will automatically clear once resolved.
Steady On.
Flashing On. Ready output to alarm.
Steady On Ready output to alarm
Relay status change Indication Meaning
Smoke Screen critical fault.
Page 26 of 30
Page 27
Be aware of high voltage in
If the Smoke Screen has
to cool.
7.2 THERMAL CUT O UT (TCO) RESET
WARNING
the block area. The
electrical supply should be
switched off before working
in the heater block
compartment.
CAUTION
been in service the heater
block and connected parts
will be extremely hot and will
cause injury if touched.
Therefore, t he Smoke
Screen should be switched
off and time should be
allowed for the heater block
The TCO can be reset using the following procedure:
• Make sure the mains power to the machine is turned off before resetting the TCO.
• Reset the TCO by pressing on the little button on the top area. If the thermal device has
tripped it should be possible to hear a click when it resets.
• Switch on the mains power after resetting.
• Check the machine heats up to normal operating temperature and make sure it archives a
ready state. See the operating “LCD, LED and Sound Indications” for further information on
fault indications.
Note: The position of the TCO can be different depending on the machine version. The location
pictured is for an TI70/TI100 HW V6.
Page 27 of 30
Page 28
7.3 ACTION AFTER EVERY ACTIVATION
• Wait until the smoke production has ceased. Do not try to enter the affected area as you
will not be able to see through the fog.
• Look for signs of forced entry. If you find any, or you believe that intruders are on the
premises, call the Police and wait for them to arrive. Take no further action.
• Where there are no signs of forced entry, open all external doors and wait for the fog to
start clearing – this may take 10 to 15 minutes. Keep watch for intruders that may have
been screened by the fog.
• As visibility returns open more doors or windows to speed up the venting process.
• Check the fluid level for the Smoke Screen by checking the appropriate LEDs as described
above. It is recommended that the installer or Concept Smoke Screen are requested to
service/replenish the Smoke Screen if there have been 2 or more activations of the Smoke
Screen.
7.4 SERVICING AND FLUID REPLENISHMENT
Please note that it is a requirement of the standards relating to security fogging devices the Smoke
Screen is serviced/replenished by an engineer certified by the manufacturer. If you are unsure,
ask the engineer for his certification ID card. It is recommended that the Smoke Screen is checked
and the fluid changed annually by the installer or Concept Smoke Screen. Always ensure that the
Smoke Screen has sufficient fluid or it will not produce smoke when needed. It is recommended
that the installer or Concept Smoke Screen are requested to service/replenish the Smoke Scree n if
there have been 2 or more activations of the Smoke Scre en.
WARNING - only Smoke Screen fluid should be used as other smoke fluids may cause damage or
noxious fumes.
8.1 FAQ
Q: The Smoke Screen is indicating it is ready to operate but does not respond to a full alarm
test.
A. Ensure the smoke machine is not isolated.
A: With power applied, and keeping clear of the smoke nozzle, disconnect the
“Alarm”/”Trigger” and “Hold Off” connection plugs from the PCB. If the Smoke
Screen produces smoke there is a miss-connection in the system wiring.
Q: Th e Smoke Sc reen is puffing out smoke whilst heating up.
A: This is the result of very small amounts of air and residual fluid in the heater block
being changed into an insignificant volume of smoke and can happen particularly
after the Smoke Screen has been moved about when cold.