Conair VL Series, VLA-7.5, VLA-10, VLA-15, VLA-20 User Manual

...
Installation
Maintenance
Operation
Troubleshooting
Portable Chillers
VL Series Air-Cooled and Water-Cooled with Capacities from 2 to 40 tons
The Conair Group, Inc. One Conair Drive Pittsburgh, PA 15202 Phone: (412) 312-6000 Fax: (412)-312-6227
UGH021/0301
It’s a good idea to record the model and serial number(s) of your equipment and the date you received it in the User Guide. Our service department uses this information, along with the manual number, to provide help for the specific equipment you installed.
Please keep this User Guide and all manuals, engineering prints and parts lists together for documentation of your equipment.
Date:
Manual Number: UGH021/0301
Serial number(s):
Model number(s):
DISCLAIMER: The Conair Group, Inc., shall not be liable for errors
contained in this User Guide or for incidental, consequential dam­ages in connection with the furnishing, performance or use of this information. Conair makes no warranty of any kind with regard to this information, including, but not limited to the implied warranties of merchantability and fitness for a particular purpose.
Please record your
equipment’s model and
serial number(s) and
the date you received it
in the spaces provided.
Copyright 2001 All rights reserved
THE CONAIR GROUP, INC.
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 3
TABLE OF CONTENTS
1.0 GENERAL 5
1.1 Introduction 6
1.2 Unit location for air cooled models 6
1.3 Unit location for water cooled models 6
1.4 Efficiency 6
1.5 Safety 7
1.6 Clean air act 7
1.7 Miscellaneous 7 Chiller features identified 8
2.0 INSTALLATION 9
2.1 General 10
2.2 To and From process connections 10
2.3 Water supply connection 11
2.4 Air cooled condenser 11
2.4 Water cooled condenser 13
2.5 Electrical connection 13
3.0 OPERATIONS 17
3.1 General 18
3.2 Start up/operations procedure 18
3.3 Instrument operation 23
3.4 Shut down procedure 26
4.0 TROUBLESHOOTING 27
4.1 Sensors 28
4.2 Process pump 28
4.3 Compressor 28
4.4 Blower/fan 28
4.5 Low flow 28
4.6 High Pressure 29
4.7 Low pressure 29
4.8 Freezestat 29
4.9 Oil pressure 30
4.10 Crankcase heater 30
4.11 Electronics 30
5.0 MAINTENANCE 31
5.1 Warranty service procedure 32
5.2 Periodic preventative maintenance 32
5.3 Special maintenance 33
5.4 Solenoid valve service 34
5.5 Pump seal service 36
5.6 Checking the refrigerant charge 39
5.7 Proper cleaning procedure for brazed plate evaporators 40
6.0 COMPONENTS 43
6.1 Water system 44
6.2 Refrigeration system 44
Page: 4
7.0 RELATED DRAWINGS 47
7.1 VLA-5/7.5/10 mechanical schematic 48
7.2 VLA-15/20/25/30 mechanical schematic 49
7.3 VLA-5 physical 50
7.4 VLA-7.5/10 physical 51
7.5 VLA-15/20/25/30 physical 52
7.6 Duct schematic for air cooled chillers 53
7.7 VLA-5/ 7.5/ 10 electrical 54
7.8 VLA-15/ 20/ 25/ 30 electrical 55
7.9 VLW-5/7.5/10 ton mechanical schematic 56
7.10 VLW-15/20/25/30 ton mechanical schematic 57
7.11 VLW-5/7.5/10 physical 58
7.12 VLW-15/20/25/30 ton physical 59
7.13 VLW-5/ 7.5/ 10 ton electrical 60
7.14 VLW-15/ 20/ 25/ 30 ton electrical 61
8.0 APPENDIX 63
8.1 Specifications 64
8.2 Operations below 48°F 66
8.3 Water quality control 68
8.4 Inhibited propylene glycol 68
8.5 Maintaining proper water flow 70
8.6 Low flow bypass circuits 71
8.7 Overhead piping kit 72
8.8 Chiller capacity and derate chart 73
8.9 Pressure-temperature chart for R-22 refrigerant 74
8.10 Engineering formulas 75
8.11 Spare parts list- water-cooled models 76
8.12 Spare parts list- air-cooled models 77 A-1 Service Information 79 A-2 Warranty information 80
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 5
1.0 GENERAL
1.1 INTRODUCTION
1.2 UNIT LOCATION FOR AIR COOLED MODELS
1.3 UNIT LOCATION FOR WATER COOLED MODELS
1.4 EFFICIENCY
1.5 SAFETY
1.6 CLEAN AIR ACT
1.7 MISCELLANEOUS
Page: 6
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
1.1 INTRODUCTION
A. This manual covers most ‘VL’ series portable chiller models. Most
‘VL’ series portable chillers are basically identical with exception of the type of condenser (air cooled or water cooled).
B. All instructions in this manual apply to most ‘VL’ series portable
chiller models regardless of the type of condenser or instrumentation. Specific instructions relating only to air cooled condensers, water cooled condenser, or instrumentation are identified and should be noted by the operator.
C. When calling for assistance from the Conair Service Department, it
is important to know the model and serial number of the particular unit. The model number encodes critical unit information which is helpful in any attempt to troubleshoot operating difficulties. The serial number allows the service team to locate manufacturing and testing records which can have additional information relating to a particular unit.
1.2 UNIT LOCATION FOR AIR COOLED MODELS
A. The ‘VL’ air cooled portable chiller is designed for indoor use only.
For most efficient operation, locate the chiller in a clean, dry and well ventilated environment.
B. The ‘VL’ air cooled portable chiller has an air cooled refrigerant
condenser. For air cooled condensers, a motor driven fan (on models from 2 to 10 tons) or a centrifugal blower (on models from 15 to 30 tons) generates air flow through the condenser to remove heat from the refrigerant system. The air cooled condenser on the ‘VL’ portable chiller will discharge a maximum of 15,000 BTU’s per hour per ton of cooling.
C. The ‘VL’ air cooled portable chiller must have a minimum entering
air temperature of 60°F and a maximum entering air temperature of 95°F for efficient operation.
D. The ‘VL’ air cooled portable chiller must have a minimum of two
feet clearance at the air intake and six feet at the vertical exhaust air discharge.
1.3 UNIT LOCATION FOR WATER COOLED MODELS
A. The ‘VL’ water cooled portable chiller is designed for indoor use
only. For most efficient operation, locate the chiller in a clean, dry and well ventilated environment.
1.4 EFFICIENCY
A. Long term efficiency of operation is largely determined by proper
maintenance of the mechanical parts of the unit and the water
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 7
quality. Conair recommends filtering where required to prevent solids from plugging critical parts (pumps, heaters, seals for example). Conair highly recommends the services of a competent water treatment specialist be obtained and his recommendations followed. Conair accepts no responsibility for inefficient operation, or damage caused by foreign materials or failure to use adequate water treatment.
1.5 SAFETY
A. It is important to become thoroughly familiar with this manual and
the operating characteristics of the Conair ‘VL’ series portable chiller.
B. It is the owner’s responsibility to assure proper operator training,
installation, operation, and maintenance of the Conair ‘VL’ series portable chiller.
C. Observe all warning and safety placards applied to the chiller.
Failure to observe all warnings can result in serious injury or death to the operator and severe mechanical damage to the unit.
1.6 CLEAN AIR ACT
A. The ‘VL’ series portable chiller contains HVLC-22
(chlorodifloromethane). This is a class 2 substance.
B. Effective July 1, 1992, it is unlawful for any person in the course of
maintaining, servicing, repairing, or disposing of refrigeration equipment to knowingly vent or otherwise dispose of any class 2 substance used as a refrigerant in the manner which permits such substance to enter the atmosphere.
C. De minimis releases associated with good faith attempts to
recapture, reclaim or recycle such substance shall not be subject to the prohibition set forth in the preceding paragraph.
1.7 MISCELLANEOUS
A. The ‘VL’ series portable chiller is designed to circulate temperature
stabilized fluid through the process resulting in process temperature control.
B. The ability of the ‘VL’ series portable chiller to maintain process
temperature control is significantly affected by the method of installation as outline in section 2 of this manual.
C. If the operator has any questions concerning the location and
operation of the ‘VL’ series portable chiller, contact the Conair Service Department at 800-458-1960 or 814-437-6861.
Page: 8
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
To Process Connection
From Process
Connection
Hot Gas
Bypass
Valve
VLA-10
pictured
Compressor
Expansion
Valve
Liquid Line
Solenoid
Refrigerant Sight Glass
Insulated
Fiberglass
Reservoir
Centrifugal
Pump
Electrical
Cabinet
Galvanized
Steel Frame
Fan Motor
Air Cooled
Condenser
Fiberglass Fan Shroud
Caster
Filter-Drier
To Process Connection
From Process
Connection
VLW-10
pictured
Condenser Supply
Condenser
Condenser Return
Condenser
Expansion
Valve
Liquid Line
Solenoid
&
Hot Gas
Bypass Valve
&
Filter-Drier
(not visible in
photograph)
Refrigerant Sight Glass
Insulated
Fiberglass
Reservoir
Centrifugal
Pump
Electrical
Cabinet
Galvanized
Steel Frame
Caster
Compressor
Condenser
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 9
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 WATER SUPPLY CONNECTION
2.4 AIR COOLED CONDENSER
2.5 WATER COOLED CONDENSER CONNECTION
2.6 ELECTRICAL CONNECTION
Page: 10
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
2.1 GENERAL
A. All process piping materials (such as hose, rigid piping, valves or
filters) used in process water piping circuitry must be rated for 100°F minimum temperature and 100 PSI minimum pressure.
B. All such materials must have the equivalent or larger diameter of
the particular process connection that length of process water piping is connected to.
2.2 TO AND FROM PROCESS CONNECTIONS
(see figures 2.2A & 2.2B)
A. Connect the ‘TO PROCESS’ to the ‘water in’ manifold on the mold
or process.
B. Connect the ‘FROM PROCESS’ port to the ‘water out’ port on the
process manifold.
C. Process water piping circuitry should be designed to avoid an
excessive use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists or curls and excessive lengths.
D. Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance provided that such devices maintain the full inside diameter of the process connection. If installed, all such devices must be open and clean during unit operation.
To process connection:
connect to “water in” on process manifold
From process connection:
connect to “water out” on process manifold
Condenser water in
connection:
connect to tower or city water supply
Condenser water out
connection:
connect to tower or city water return
Water supply connection:
(not shown on this unit)
connect to plant’s city water source
Figure 2.2A
Typical process connections for water cooled chiller
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 11
To process connection:
connect to “water in” on process manifold
From process connection:
connect to “water out” on process manifold
Water supply connection:
(not shown on this unit)
connect to city water source
Figure 2.2B
Typical process connections for air cooled chiller
2.3 WATER SUPPLY CONNECTION
A. The automatic water supply make-up system continually monitors
the reservoir tank and fills it when needed. Connect as follows:
1. Connect the chiller’s ‘WATER SUPPLY’ port to the plant’s
city water source.
2. Minimum water supply pressure requirement is identified
on the equipment data plate. This is normally 20 psi.
3. Be certain to use a water supply line equipped with a back
flow prevention device to prevent contamination of potable water.
2.4 AIR COOLED CONDENSER
A. Air cooled condensers require ambient air temperatures between
60°F and 95°F for efficient operation. Operating above above 95°F may result in elevated condensing pressures and eventual shut­down on the high pressure safety switch. In such cases, a water assist unit may be necessary for operations. Air temperatures below 60°F may result in below normal condensing pressures and poor condensing. In such cases, a low-ambient damper assembly is required. Check with the Conair service department for more information on operating with ambients air temperatures above 95°F or below 60°F.
Page: 12
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
B. Air flow is generated by the motor
driven fans (figure 2.4A) or centrifugal blowers (figure 2.4B). Air flow is from the outside of the chiller, through the condenser and exhausted through the top of the unit. On centrifugal blowers models, exhaust air can be ducted outside of the plant’s interior environment. Special duct work is required and a HVAC contractor should be consulted for sizing and material specifications. Exhaust air can not be ducted on motor driven fan models.
C. A free air space of at least two (2)
feet is required at the condenser intake and six (6) feet at the condenser discharge to allow for proper air flow.
D. At full load, the chiller will discharge
approximately 15,000 BTU’s per hour per ton of cooling.
E. On blower units, air discharge
duct work should be sized by a qualified HVAC engineer. Sizing shall be according to rated VLM at the static pressure of .90 inches of water. See figure 2.4C at right.
F. On blower units, a damper
control assembly is required in low ambient temperature areas or when outdoor air make-up is used. The assembly works in conjunction with refrigerant head pressure to regulate air flow to maintain proper refrigerant head pressure when condenser intake air temperature will be less than 60°F. See figure 2.4D to the right.
Figure 2.4C
Figure 2.4D
Figure 2.4A
Typical fan assembly
Figure 2.4B
Typical blower assembly
MODEL CFM
VLA-15 15,000 VLA-20 20,000 VLA-25 25,000 VLA-30 30,000
CFM RATINGS
Damper assembly
1/4" copper line connection
Angle valve and cap
Punch hole in top panel
1/4" Copper line
Liquid receiver (located inside chiller on base)
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 13
2.5 WATER COOLED CONDENSER CONNECTION
A. Connect the ‘CONDENSER WATER
IN’ port to the plant’s city water
supply or tower system supply.
1. Required consumption from
a city water source is 1.5 gpm at 65°F per ton of rated capacity.
2. Required consumption for a
tower water source is 3 gpm at 85°F per ton of rated capacity.
B. Connect the chiller’s ‘CONDENSER
WATER OUT’ port to the plant’s
drain or tower system return.
1. Note: if dumping to the
plant’s open drain, drainage shall be done according to local codes.
C. The pressure differential requirement
between the condenser “water in” and the condenser “water out” lines must be 30 psi for adequate efficiency.
D. The installation of a strainer in the condenser “water in” line is
recommended. This removes solids from the water supply and serves to protect the water saver (regulator) valve.
E. An optional water saver (regulator) valve may be installed in the
condenser “water in” line. During winter months, or cold seasons, the valve will throttle the water flow through the condenser. The amount of flow is based on the refrigerant head pressure and the regulator will modulate the valve’s orifice to maintain a head pressure of 210 psig for best efficiency.
2.6 ELECTRICAL CONNECTION
A. NEMA 1 MODELS
1. Electrical power supply requirements for Nema 1 units are
identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements. WARNING: Do not connect the unit to a
voltage supply not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and
Figure 2.5A
Condenser connections ­30 ton unit - optional regulator valve shown
Figure 2.5B
Condenser connections ­10 ton unit- optional regulator valve shown
Page: 14
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
cause a significant hazard that may result in serious personal injury and unit damage.
2. A customer supplied, four conductor cable is required for
connection to a customer supplied fused disconnecting means. The fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes. See figure 2.5A (next page) for details on water cooled power cable routing.
3. Connect the four conductor power cable to power entry terminal block on the unit’s electrical panel. Then connect the power cable to the fused disconnect switch.
B. NEMA 12 MODELS
1. NEMA 12 units are constructed with a dust tight electrical
enclosure and branch circuit fusing. Electrical power supply requirements are identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements. WARNING: Do not connect
the unit to a voltage supply source not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. Appropriate conduit and fittings should be selected which
will maintain the integrity of the cabinet.
3. Supply a power conductor sized according to the unit’s power supply requirements. Connect the power conductor to the unit’s power supply entry terminal block or the fused disconnect switch. Some Nema 12 models may be supplied with an optional disconnect switch. The owner supplied fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes.
C. CONTROL CIRCUIT WIRING
1. The unit’s supplied control circuit is 110 volt, 1 phase, 60
cycle. The control circuit is supplied by the factory installed transformer. An inline control circuit fuse is provided.
D. GENERAL
1. Make certain all ground connections to the unit are
properly affixed.
2. Make certain power conductor, disconnecting means, and fusing are properly sized according to the unit’s power supply requirements.
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 15
3. Make certain all electrical connections are tightly affixed. Any loose wiring connections must be tighten before engaging the power supply.
4. Make certain no moisture or standing water is present inside the electrical cabinet (figure 2.5B).
Refrigerant High
Pressurestat
Refrigerant Low
Pressurestat
Fuse Block
Transformer
Power Entry
Freezestat
Cabinet Door
Figure 2.6B Typical electrical cabinet detail.
Motor Starter
Overload Relay
Compressor Starter
Figure 2.6A
5 THRU 10 TON MODELS
ELECTRICAL CABINET
MICROPROCESSOR
CONTROLLER
5 THRU 10 TON MODELS
WATER COOLED
WATER COOLED
ROUTE POWER CORD
OUT OPEN BACK OF UNIT
TO DISCONNECT
ELECTRICAL CABINET
MICROPROCESSOR
CONTROLLER
WATER COOLED
WATER COOLED
15 THRU 30 TON MODELS
15 THRU 30 TON MODELS
TO DISCONNECT
ROUTE POWER CORD
OUT OPEN BACK OF UNIT
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
Page: 16
THIS PAGE INTENTIONALLY BLANK
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 17
3.0 OPERATIONS
3.1 GENERAL
3.2 START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT/OPERATION
3.4 SHUT DOWN PROCEDURE
Page: 18
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
3.1 GENERAL
A. Failure to follow the factory required operations procedure may
adversely affect the units ability to adequately control process temperature and may create a hazardous operating condition which may result in serious operator injury and/or unit damage.
B. IMPORTANT: each chiller is equipped with a crankcase heater on
the compressor. While the compressor is idle, the crankcase heater prevents freon vapor from migrating to and condensing in the compressor crankcase. If freon is allowed to condense in the crankcase, it can be drawn into the cylinders upon start up. This can cause catastrophic damage to the connecting rods, pistons, and valve plates. To avoid this, BEFORE THE UNIT IS STARTED,
THE POWER SUPPLY SHOULD BE APPLIED TO THE UNIT FOR AT LEAST 12 HOURS, OR UNTIL THE BOTTOM OF THE COMPRESSOR IS WARM TO THE TOUCH. If the power has been
disconnected more than two hours, the power should be applied for six hours before restarting. Power should be applied to the unit continuously, except for service purposes. The crankcase heater should be checked for proper operation on a regular basis.
C. The OPERATIONS segment of this manual is divided into the
following sections:
3.2 Start up/operations - follow this segment to start the unit after the initial install to the process system or to restart the unit after reinstallation to the same or different process system. This section includes information on system fill, electric motor phasing (pump rotation) and process flow adjustments.
3.3 Instrument - follow this segment to start up and operate the instrument. This section includes information on setpoint selection and adjustment, and feature explanations.
3.4 Shut down procedure - follow this segment to shut down the unit. This segment includes information on system shut down, electrical power supply precautions, and disconnection from system.
3.2 START UP/OPERATION PROCEDURE
A. SYSTEM FILL
1. The VL series portable chiller has an internal reservoir which
must be filled and maintained for proper operation. All VL series chillers have a level switch mounted at the proper water level in the reservoir.
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 19
2. Conair recommends the addition of 20% inhibited propylene glycol to the process fluid. This should help prevent the process fluid from freezing and internal components from rusting. A biocide must be added to the water to prevent organism growth in the chilled water system. See water treatment section in section 8 of this manual for more information.
3. FOR AUTOMATIC FILL (IF EQUIPPED): engage the
water supply to unit. The level switch will activate the make-up solenoid (figure
3.2A), which will open and the water supply will fill the reservoir tank. During operations, with the water supply source on, the unit will automatically maintain the correct reservoir level.
4. MANUAL FILL: disconnect the electrical power supply and remove all necessary cover panels to access the reservoir tank. Add fluid directly to the reservoir tank. When the pump is first started, as process lines are filled and air is purged, additional fluid may be required to restore the reservoir to the correct level.
B. ELECTRIC MOTOR PHASING (PUMP ROTATION)
1. The operator must determine the unit is phased correctly.
This is done by visually inspecting the rotation of the pump motor shaft and is outlined below. Incorrect phasing results in poor operation and eventual damage to the unit.
a. Supply electrical power to the unit by engaging the
units disconnect switch. Once the correct voltage is supplied to the unit, the POWER light on the units instrument display will illuminate.
b. Remove the necessary covers panel to access the
pump motor. Note that electrical power is
engaged at this point and caution must be observed while the electrical supply is engaged and cover panels are removed.
c. Locate the electric motor (figure 3.2B) The operator
must identify the motor shaft inside the electric motor housing. The motor shaft can be seen through the vent slots in the motor housing or by removing the shaft cover (figure 3.2C).
Figure 3.2ATypical make-up solenoid valve
Page: 20
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
d. Toggle the CHILLER
ON switch. This will quickly cycle the electrical motor on and then off.
e. Observe the motor
shaft. When the CHILLER ON switch is turned on, the motor shaft will rotate. When the CHILLER ON switch is turned off, the motor shaft will slowly coast to a stop. As the shaft slows to a stop, the operator must identify its rotation. Correct rotation (correct phase) is clockwise, when viewed from the rear of the motor. Incorrect rotation is counter­clockwise (incorrect phase) when viewed from the rear of the motor. If the shaft does not rotate when the PUMP switch is toggled, the operator must identify the cause as outlined in this manual’s troubleshooting and repair section.
f. If the motor shaft is phased correctly (shaft turns in
a clockwise direction), continue with step C. If the motor shaft is NOT phased correctly (shaft turns in a counter-clockwise direction), continue the procedure with step 2.
2. If the motor shaft is NOT phased correctly, the operator must:
a. Disengage the electrical power supply to the unit at
the disconnect switch. Follow proper lockout procedures before proceeding. Verify the POWER light on the instrument display is off.
b. With the electrical power supply is disengaged,
reverse any two power leads of the power cord at the disconnect terminals.
c. Note: reversing any two power leads of the power
cord will correctly phase an incorrectly phased
Figure 3.2C
Motor shaft
Vent slots
Figure 3.2B
Electric motor
Pump
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 21
power supply. The operator must reverse the
power leads at the disconnect switch only and NOT at the power entry terminals on the unit’s electrical panel. The units internal electrical
system wiring is phased correctly at the factory and must not be altered in the field.
d. Visually inspect the rotation of the motor as
outlined step 1 to determine the unit is phased correctly.
C. PROCESS FLOW ADJUSTMENTS
1. The operator must determine and set proper water flow
rate for the most efficient and trouble free operation.
a. Water flow rate through the process is determined
by the pressure losses in the process loop. Generally, higher flow rates result in turbulent flow achieving maximum temperature control and lower maintenance. Since the evaporator in most liquid chillers is flow sensitive, the efficiency of operation is directly related to the flow of liquid.
b. Maximum chiller efficiency is obtained at
approximately 2.4 gpm per ton of rated capacity. Low liquid flow can reduce efficiency and in some cases allow ice to form in the evaporator which can damage the evaporator. Excessive flow will trip the motor overload protection circuit.
2. Activate the CHILLER ON rocker switch on the display to activate the process pump. Wait a few moments to allow air to be purge from system. Two items the operator must look for are low or excessive flow conditions.
3. LOW FLOW... to allow operation under a low flow condition, it is necessary to install a flow bypass system in the process circuitry. This will allow a portion of the flow to bypass the process and return directly to the chiller. This keeps the total flow above the cutoff point. Figure 3.2D illustrates a typical bypass loop.
Figure 3.2D Typical low flow by-pass loop
21 GPM 5 GPM
BYPASS
CHILLER PROCESS
THROTTLING VALVE ­16 GPM
5 GPM21 GPM
Page: 22
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
4. EXCESSIVE FLOW... excessive flow can overload the process pump motor and cause eventual failure. This is a result of the process loop’s ability to flow water at a great rate than can be provided by the process pump. This eventually results in tripping the thermal motor overload relay (overload relays open) and the unit will shut down.
a. If an excessive flow situation is encountered and
the motor overload circuit has tripped, the operator must manually reset the overload relay (figure 3.2E) before operations can continue. This is done by opening the electrical panel cover, identifying the reset lever on the overload relay, and pushing the reset lever in until the overloads are reset (evidenced by a clicking sound as the overloads reset).
5. To overcome an excessive flow condition, the operator should set the process flow rate according to the motor amperage:
a. Remove electrical cover panel. Note that the
electrical power is engaged at this point and caution must be observed while the cabinet panel is open.
b. Identify the motor
starter block. This block consists of the motor starter contactor and the overload relay.
c. Place an amp
meter on a single power lead emanating from the overload relay.
d. Locate the electric pump motor. Identify
the motor name plate on the motor housing (figure
3.2F). The full load amp rating for the motor is listed on the name plate.
e. Engage the electrical power supply and start the
motor by switching on the CHILLER ON rocker switch.
Figure 3.2E
Reset level on overload relay
Motor name plate
Figure 3.2F
UGH021/0301 VL Series Portable Chillers, 2 to 40 Tons
Page: 23
f. The amp meter will display the motor amps.
Compare the actual motor amps as displayed on the amp meter to the full load amp rating as listed on the motor name plate.
g. If the amp draw is excessive (higher than the listed
name plate amp rating), a throttling valve must be installed in the from process circuit line. The preferred throttling valve is a ball valve.
h. With the throttling valve installed, fully close the
valve and then engage the pump. Slowly open the throttling valve and monitor the motor amps as displayed on the amp meter until the actual motor amps equals the listed full load amp rating of the motor.
3.3 INSTRUMENT OPERATION
A. INSTRUMENT START-UP
1. When the correct electrical power and adequate water
supply pressure are supplied to the unit, it is possible to start the unit for temperature control duty.
2. When the electrical power supply is engaged to the unit, the instrument (figure 3.3A) will momentarily illuminate all indicating lights and digits on the display head. After a short delay, the instrument will display the software version number. At this time, the operator can verify that all lights and digits are functioning properly. If the operator
VL Chiller Control
Power
Pump
Compressor
Hot Gas Bypass
Temperature
To Process
Setpoint
On
Off
Page: 24
VL Series Portable Chillers, 2 to 40 Tons UGH021/0301
determines an indicating light or digit does not illuminate, the instrument must be removed and sent to the factory for repair. When power is supplied to the unit, the POWER light will illuminated.
3. Toggle on the CHILLER ON rocker switch to activate the chiller. The operator can stop process operations (refrigerant and coolant circuits) by switching off the CHILLER ON switch.
4. To select the operating setpoint, use the SELECT key to index through the TO PROCESS and SET POINT temperature functions until the SET POINT light is illuminated.
5. When the SET POINT light is illuminated, the setpoint temperature is shown in the temperature display window. Use the UP and DOWN ARROW keys to change the setpoint temperature.
6. PRECAUTIONS: the instrument is programmed from the factory with a setpoint range of 48° to 70°F. To operate below 48°F, the addition of inhibited propylene glycol and modification of the safety control settings are required. Diligent monitoring of the water/glycol solution is mandatory to prevent freezing of the evaporator. Freezing may cause the evaporator to rupture allowing water and freon to mix which will cause major damage to the refrigeration system. Operating above 70°F requires the addition of a refrigerant crankcase pressure regulating (CPR) valve. The CPR valve is necessary to prevent overloading of the compressor which can cause premature failure. Contact your local refrigeration contractor or the factory for further information. The operating range of the instrument may be changed to 20°F - 90°F by adjustment of the CPU DIP switch. Refer to the technical section of this manual for more information. The instrument is set up from the factory to give an alarm light and a 115 volt alarm output if the temperature to process deviates more than 10° from the setpoint.
7. After selecting the setpoint temperature, the operator may leave the display in the SET POINT state. The display will automatically return to the TO PROCESS temperature state after twenty seconds of inactivity.
8. The operator can stop operations by switching off the CHILLER ON rocker switch. This will disengage the refrigerant and coolant circuits.
Loading...
+ 56 hidden pages