Conair VL User Manual

Portable Chillers
Instant Access
Parts and Service
(800) 458-1960 (814) 437-6861
www.conairnet.com
The Conair Group, Inc. One Conair Drive Pittsburgh, PA 15202 Phone: (412) 312-6000 Fax: (412)-312-6227
VL Series, 0.25 to 1.5 ton models
UGH020/0301
Installation
Maintenance
Operation
Troubleshooting
It’s a good idea to record the model and serial number(s) of your equipment and the date you received it in the User Guide. Our service department uses this information, along with the manual number, to provide help for the specific equipment you installed.
Please keep this User Guide and all manuals, engineering prints and parts lists together for documentation of your equipment.
Date:
Manual Number: UGH020/0301
Serial number(s):
Model number(s):
DISCLAIMER: The Conair Group, Inc., shall not be liable for errors
contained in this User Guide or for incidental, consequential dam­ages in connection with the furnishing, performance or use of this information. Conair makes no warranty of any kind with regard to this information, including, but not limited to the implied warranties of merchantability and fitness for a particular purpose.
Please record your
equipment’s model and
serial number(s) and
the date you received it
in the spaces provided.
Copyright 2001 All rights reserved
THE CONAIR GROUP, INC.
Page: 3
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
TABLE OF CONTENTS
1.0 GENERAL 5
1.1 Unit location 6
1.2 Efficiency 6
1.3 Safety 6
1.4 Clean air act 6
1.5 Miscellaneous 7
2.0 INSTALLATION 9
2.1 General 10
2.2 To and From process connections 10
2.3 Unit drain 11
2.4 Air-cooled condenser 11
2.5 Electrical connection 12
3.0 OPERATIONS SEQUENCE 13
3.1 General 14
3.2 Start up / operations procedure 14
3.3 Instrument operation 15
3.4 Shut down / disconnect sequence 18
4.0 TROUBLESHOOTING 19
4.1 Unit will not start 20
4.2 Pump will not start 20
4.3 Compressor will not start 20
4.4 Unit shuts down on high pressure switch 20
4.5 Unit shuts down on low pressure switch 20
5.0 MAINTENANCE 23
5.1 Warranty service procedure 24
5.2 Periodic preventative maintenance 24
5.3 Special maintenance 25
5.4 Pump repair 25
6.0 COMPONENTS 27
6.1 Water system 28
6.2 Refrigeration system 28
7.0 RELATED DRAWINGS 29
7.1 Electrical (typical) 30
7.2 Circuit schematic 31
8.0 APPENDIX 33
8.1 Specifications 34
8.2 Operations below 48°F 35
8.3 Water quality control 37
8.4 Inhibited propylene glycol 37
8.5 Chiller capacity and derate chart 39
8.6 Pressure - temperature chart for R-22 40
8.7 Engineering formulas 41
8.8 Spare parts list 42
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
Page: 4
THIS PAGE INTENTIONALLY BLANK
Page: 5
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
1.0 GENERAL
1.1 UNIT LOCATION
1.2 EFFICIENCY
1.3 SAFETY
1.4 CLEAN AIR ACT
1.5 MISCELLANEOUS
Page: 6
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
1.1 UNIT LOCATION
A. The unit is designed for indoor use only. For most efficient
operation, locate the chiller in a clean, dry and well ventilated environment.
B. The unit has an air-cooled refrigerant condenser. For air-cooled
condensers, a motor driven fan generates air flow through the condenser to remove heat from the refrigerant system. The air­cooled condenser on the unit will discharge a maximum of 15,000 BTUs per hour per ton of cooling.
C. The unit must have a minimum entering air temperature of 60°F
and a maximum entering air temperature of 95°F for efficient operation.
D. The unit must have a minimum of two feet clearance at the air
intake and six feet at the exhaust air discharge.
E. If the operator has any questions concerning the location and
operation of the unit, contact the Conair service department at 800-458-1960.
1.2 EFFICIENCY
A. Long term efficiency of operation is largely determined by proper
maintenance of the mechanical parts of the unit and the water quality. Conair recommends filtering where required to prevent solids from plugging critical parts (pumps, heaters, seals for example). Conair highly recommends the services of a competent water treatment specialist be obtained and his recommendations followed. Conair accepts no responsibility for inefficient operation, or damage caused by foreign materials or failure to use adequate water treatment.
1.3 SAFETY
A. It is important to become thoroughly familiar with this manual and
the operating characteristics of the unit.
B. It is the owner’s responsibility to assure proper operator training,
installation, operation, and maintenance of the unit.
C. Observe all warning and safety placards applied to the unit. Failure
to observe all warnings can result in serious injury or death to the operator and sever mechanical damage to the unit.
1.4 CLEAN AIR ACT
A. The unit contains HCFC-22 (chlorodifloromethane). This is a class 2
substance.
Page: 7
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
B. Please be aware that effective July 1, 1992, it is unlawful for any
person in the course of maintaining, servicing, repairing, or disposing of refrigeration equipment to knowingly vent or otherwise dispose of any class 2 substance used as a refrigerant in the manner which permits such substance to enter the environment.
C. De minimis releases associated with good faith attempts to
recapture, reclaim, or recycle such substance shall not be subject to the prohibition set forth in the preceding paragraph.
1.5 MISCELLANEOUS
A. The purpose of the unit is to circulate temperature stabilized fluid
through your process, resulting in process temperature control.
B. The ability of the unit to maintain process temperature control is
significantly affected by the method of installation.
C. If the operator has any questions concerning the location and
operation of the unit, please contact the Conair service at 800-458-1960 or 814-437-6861
Illuminated ‘On’ Switch
Controller
Air Cooled Condenser
Condensing Fan
Electrical Panel
Pump
Reservoir
Thermocouple
Bypass Valve
Refrigerant Sight Glass
Filter-Drier
Power Cord
Refrigerant Safety Switches
Liquid Receiver
Caster
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
Page: 8
THIS PAGE INTENTIONALLY BLANK
Page: 9
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 UNIT DRAIN
2.4 AIR COOLED CONDENSER
2.5 ELECTRICAL CONNECTION
2.1 GENERAL
A. All process piping materials (such as hose, rigid piping, valves or
filters) used in process water piping circuitry must be rated for 100°F minimum temperature and 100 PSI minimum pressure.
B. All such materials must have the equivalent or larger diameter of
the particular process connection that length of process water piping is connected to.
Page: 10
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
2.2 TO AND FROM PROCESS CONNECTIONS
A. Connect the chiller’s “to process” connection to the “water in”
manifold on the mold or process.
B. Connect the chiller’s “from process” connection the “water out”
manifold at the mold or process.
C. Process water piping circuitry should be designed to avoid an
excessive use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists or curls and excessive lengths.
D. Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance provided that such devices maintain the full inside diameter of the process connection. If installed, all such devices must be open and clean during unit operation.
To process connection:
connect to “water in” on process manifold
From process connection:
connect to “water out” on process manifold
Page: 11
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
2.3 DRAIN CONNECTION:
A. The unit is supplied as standard with a ProCon type pump. In some
cases, it may be necessary to drain the unit. This is done by removing the pump volute plug in the pump assembly.
B. Note that if chemical treatment of process fluid or additives are use,
drainage shall be done according to local codes.
C. It is important to note that drainage procedures must be done prior
to shipment or outdoor storage or the unit. If not, freezing damage can occur.
2.4 AIR COOLED CONDENSER
A. Air-cooled condenser require ambient air temperatures between
60°F and 95°F for efficient operation. Operating above 95°F may result in elevated condensing pressures and eventual shut-down on the high pressure safety switch. Check with the Conair service department for more information on operating with ambient air temperatures above 95°F or below 60°F.
B. Air flow is generated by the motor driven fan. Air flow is from the
outside of the chiller, through the condenser and exhausted through the unit. Exhaust air can not be ducted on motor driven fan models.
C. A free air space of at least four (4) feet is required at the condenser
intake and four (4) feet at the condenser discharge to allow for proper air flow.
D. At full load, this chiller will discharge approximately 15,000 BTU/hr
per hour per ton of cooling.
Thermocouple
Motor
Pump
Drain plug
Page: 12
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
2.5 ELECTRICAL CONNECTION
A. NEMA 1 MODELS
1. Electrical power supply requirements for Nema 1 units
(figure 2.5A) are identified on the equipment data plate. Verify that available voltage supply is the same as the unit’s voltage requirements. WARNING: Do not connect the
unit to a voltage supply source not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. A factory supplied, four conductor cable is installed for
connection to a customer supplied fused power disconnect device. The fused disconnect device shall be sized and installed according to the unit’s power supply requirements and local electrical codes.

C. CONTROL CIRCUIT WIRING

1. The unit’s supplied control circuit is indicated in the
electrical diagrams. The control circuit is supplied by the factory installed transformer.
D. GENERAL
1. Make certain all ground connections to the unit are
properly affixed.
2. Make certain power conductor, disconnect device, and fusing are properly sized according to the unit’s power supply requirements.
3. Make certain all electrical connections are tightly affixed. Any loose wiring connections must be tighten before engaging the power supply.
4. Make certain no moisture or standing water is present inside the electrical cabinet.
Microprocessor
controller
Illuminated on/off
switch
Motor starter
Transformer
3.0 OPERATIONS
3.1 GENERAL
3.2 START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT OPERATION
3.4 SHUT DOWN/DISCONNECT SEQUENCE
Page: 13
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
Page: 14
VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
3.1 GENERAL
A. Failure to follow the factory required operation procedures may
adversely affect the unit’s ability to control process temperature and may create a hazardous operating condition which may result in unit damage and serious operator injury or death.
B. The Operations segment of this manual is outlined below:
3.2 Machine start-up/operations procedure - follow this
segment to start the unit after the initial installation or to restart the unit after reinstallation to the same or different process. This section includes information on system fill, electric motor phasing (pump rotation) and process flow adjustments.
3.3 Instrument - follow this segment to start up and operate the instrument controller. This section includes information on automatic and manual venting, setpoint selection and adjustment, and feature explanations.
3.4 Shut down procedure - follow this segment to shut down the unit. This segment includes information on system cool down, shut down, electrical power supply precautions, and disconnection from system.
3.2 START UP/OPERATIONS PROCEDURE

A. SYSTEM FILL

1. The unit has an internal reservoir which must be filled and
maintained for proper operation.
2. Conair recommends the addition of 20% inhibited propylene glycol to the process fluid. This should help prevent the process fluid from freezing and internal components from rusting. A biocide must be added to the water to prevent organism growth in the chilled water system. See water treatment section in section 8 of this manual for more information.
3. Remove the top panel to access the reservoir. Add fluid directly to the reservoir tank. Please note, when the pump is first started, and after the process lines are filled and entrained air is purged, additional fluid may be required to restore the reservoir to the correct level.
Reservoir
Loading...
+ 30 hidden pages