Conair UGH031-0209 User Manual

Page 1
EarthSmart
TM
ECM Series, 0.50 to 0.75 ton models
Corporate Office: 724-584-5500 l Instant Access 24/7 (Parts and Service): 800.458.1960 l Parts and Service: 814.437.6861
USER GUIDE
UGH031-0209
www.conairgroup.com
Page 2
Please record your equipment’s model and serial number(s) and the date you received it in the spaces provided.
It’s a good idea to record the model and serial number(s) of your equipment and the date you received it in the User Guide. Our service department uses this infor­mation, along with the manual number, to provide help for the specific equipment you installed.
Please keep this User Guide and all manuals, engineering prints and parts lists together for documentation of your equipment.
Date:
Manual Number: UGH031-0209
Serial Number(s):
Model Number(s):
DISCLAIMER: The Conair Group, Inc., shall not be liable for errors contained in this User Guide or for incidental, consequential damages in connection with the furnishing, performance or use of this information. Conair makes no warranty of any kind with regard to this information, including, but not limited to the implied warranties of merchantability and fitness for a particular purpose.
Copyright 2009 l The Conair Group l All rights reserved
Page 3
Table of Contents
1-1 Introduction
Purpose of the user guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
How the guide is organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Your responsibilities as a user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
ATTENTION: Read this so no one gets hurt . . . . . . . . . . . . . . . . . . . 1-4
2-1 Description
What is the EarthSmart ECM Series Chiller?. . . . . . . . . . . . . . . . . . .2-2
Typical applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
How it works: Process circulation. . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Refrigeration circulation . . . . . . . . . . . . . . . . . . . . . . 2-5
Component listing . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Specifications: EarthSmart ECM Series Chiller. . . . . . . . . . . . . . . . . 2-8
Pump curve: EarthSmart ECM Series Chiller . . . . . . . . . . . . . . . . . . 2-9
3-1 Installation
Unpacking the boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Warning and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Making process plumbing connections . . . . . . . . . . . . . . . . . . . . . . 3-5
Filling the chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Drain connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Checking the refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Connecting the main power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
4-1 Operation
EarthSmart ECM Series Chiller: Control descriptions . . . . . . . . . . . . 4-2
Starting the chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Table of Contents l i
Page 4
Stopping the chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Changing temperature units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Chiller operation sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Resetting the high pressure switch of the compressor . . . . . . . . . . 4-8
5-1 Maintenance
Preventative maintenance schedule . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Checking electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Cleaning the brazed plate adapter . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Cleaning the air-cooled condenser . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Checking the reservoir level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Cleaning the pump strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Checking the refrigerant charge and quality . . . . . . . . . . . . . . . . . 5-12
6-1 Troubleshooting
Before beginning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
A few words of caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
DIAGNOSTICS
How to identify the cause of a problem . . . . . . . . . . . . . . . . . . . . . 6-3
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Checking or replacing the temperature sensor . . . . . . . . . . . . . . . . 6-8
Checking or resetting the circuit breakers . . . . . . . . . . . . . . . . . . . . 6-9
A Appendix
We’re here to help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
How to contact customer service . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Before you call... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Equipment guarantee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Performance warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Warranty limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
ii l Table of Contents
Page 5
B Appendix
Safety adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
C Appendix
Water quality control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
D Appendix
Chiller capacity and derate chart . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
E Appendix
Pressure-temperature chart for R-134A refrigerant . . . . . . . . . . . . . E-1
F Appendix
RTD resistance chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
G Appendix
Overhead plumbing details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1
H Appendix
Electrical schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-1
I Appendix
Control Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-1
J Appendix
Plumbing schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J-1
Table of Contents l iii
Page 6
iv l Table of Contents
Page 7
Introduction
Purpose of the user guide. . . . . . . . . . . . . . 1-2
How the guide is organized . . . . . . . . . . . . . 1-2
Your responsibilities as a user. . . . . . . . . . . 1-3
ATTENTION: Read this so no one gets hurt . . . 1-4
SECTION
1
Introduction l 1-1
1
Introduction
Page 8
Purpose of the User Guide
This User Guide describes the EarthSmart ECM Series Chiller and explains step-by-step how to install, operate, maintain and repair this equipment.
Before installing this product, please take a few moments to read the User Guide and review the diagrams and safety information in the instruction packet. You also should review manuals covering associated equipment in your system. This review won’t take long, and it could save you valuable installation and operating time later.
How the Guide is Organized
Symbols have been used to help organize the User Guide and call your attention to important information regarding safe installation and operation.
Symbols within triangles warn of conditions that could be hazardous to users or could damage equipment. Read and take precautions before proceeding.
Numbers indicate tasks or steps to be performed by the user.
A diamond indicates the equipment’s response to an action performed by the user.
An open box marks items in a checklist.
A circle marks items in a list.
Indicates a tip. A tip is used to provide you with a suggestion that will help you with the maintenance and the operation of this equipment.
Indicates a note. A note is used to provide additional information about the steps you are following throughout the manual.
1
1-2 l Introduction
Page 9
Introduction l 1-3
Your Responsibility as a User
You must be familiar with all safety procedures concerning installation, opera­tion and maintenance of this equipment. Responsible safety procedures include:
Thorough review of this User Guide, paying particular attention
to hazard warnings, appendices and related diagrams.
Thorough review of the equipment itself, with careful attention
to voltage sources, intended use and warning labels.
Thorough review of instruction manuals for associated equipment.
Step-by-step adherence to instructions outlined in this User Guide.
1
Introduction
Page 10
ATTENTION: Read this so no one gets hurt
We design equipment with the user’s safety in mind. You can avoid the potential hazards identified on this machine by following the procedures outlined below and elsewhere in the User Guide.
WARNING: Improper installation, operation or servicing may result in equipment damage or personal injury.
This equipment should be installed, adjusted and serviced by a quali­fied technician who is familiar with the construction, operation and potential hazards of this type of machine.
All wiring, disconnects and fuses should be installed by a qualified electrical technician in accordance with electrical codes in your region. Always maintain a safe ground. Do not operate the equipment at power levels other than what is specified on the machine serial tag and data plate.
WARNING: Voltage hazard
This equipment is powered by single-phase alternating current, as specified on the machine serial tag and data plate.
A properly-sized conductive ground wire from the incoming power supply must be provided. Improper grounding can result in severe personal injury and erratic machine operation. (Units are supplied with a grounded plug that must be plugged into a grounded out.)
Always disconnect and lock out the incoming main power source before opening the electrical enclosure or performing non-standard operating procedures, such as routine maintenance. Only a qualified technician should perform troubleshooting procedures that require access to the electrical enclosure while power is on.
1-4 l Introduction
(continued)
Page 11
1
Introduction
Introduction l 1-5
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller, especially when working on or around the compressor and condenser. These devices can be over 160°F {71°C}. Allow these devices to cool before performing any maintenance or troubleshooting.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should examine and correct problems involving the refrigerant circuit.
ATTENTION: Read this so no one gets hurt
(continued)
Page 12
1-6 l Introduction
Page 13
Description l 2-1
Description
What is the EarthSmart ECM Series Chiller?. . 2-2
Typical applications. . . . . . . . . . . . . . . . . . 2-2
Limitations. . . . . . . . . . . . . . . . . . . . . . . . 2-3
How it works: Process circulation . . . . . . . . 2-4
Refrigeration circulation . . . . . 2-5
Component listing . . . . . . . . . 2-6
Specifications: EarthSmart ECM
Series Chillers . . . . . . . . . . . . . . . . . . 2-8
Pump curve: EarthSmart ECM
Series Chillers . . . . . . . . . . . . . . . . . . 2-9
SECTION
2
2
Description
Page 14
What is the EarthSmart ECM Series Chiller?
The Conair EarthSmart ECM Series Chillers provide self-contained sources of chilled water and are available with compressor ranges of 0.5 Hp or 0.75 Hp (nominal capacities of 0.41 tons or 0.70 tons of refrigeration).
IMPORTANT: Nominal chilling capacities are based on 95°F {35°C} ambient air conditions and processing 50°F {10°C} leaving water.
ECM Series Chillers are designed to provide chilled fluid for industrial applica­tions requiring 24-hour-a-day performance. Units are totally self-contained for easy, economical installation. All parts wetted by the process are non-ferrous.
Typical Applications
ECM Series Chillers can be used anywhere a reliable source of process cooling water at temperatures ranging from 45° to 65°F {7.2°C to 18.3°C} is required. These chillers at full load, will discharge approximately 7,500 or 12,500 BTU/hr of heat into the atmosphere (depending on model).
Chillers are available for:
Injection molding Dryer intercoolers/aftercoolers
Blow molding Heatset/web offset printing presses
Thermoforming Degreasing
Extrusion Laser
Air compressors Anodizing
Metal plating
2-2 l Description
NOTE: Chiller’s environment
and cooling temperatures
below the default cooling
ranges will affect cooling
capacities.
Page 15
Description l 2-3
2
Description
Limitations
Conair EarthSmart ECM Series Chillers are chosen based on the cooling load, ambient temperature and cooling temperature.
Cooling load - Choose a chiller that has 0 - 10% more cooling capacity than
the process load to be chilled.
Ambient temperature - The chiller’s air-cooled condenser requires an
ambient air temperature between 40° to 95°F {4.4° to 35°C} for efficient operation. Operation above 95°F {35°C} may result in elevated condensing pressures and will eventually cause the chiller to shut down due to a high pressure safety switch. Contact Conair Service for information for operating within ambient air temperatures above 95°F {35°C} or below 40°F {4.4.°C}.
Temperature - As standard, ECM Series Chillers can provide cooling
temperature ranges of 45°F to 65°F {7.2°C to 18.3°C}. For cooling temperatures below 45°F {7.2°C}, contact Conair Service.
Use this information as a general guide. Consult your Conair representative for assistance when choosing a Conair EarthSmart ECM Series Chiller.
Page 16
2-4 l Description
How it Works: Process Circulation
Hot fluid from the process enters the chiller through the “From Process” inlet into the chiller’s reservoir.
Pump moves fluid from the reservoir through evaporator where it is chilled.
Fluid is chilled in the evaporator and exits through the “To Process” outlet, returning to the process.
1
2
3
1
2
3
(Left-side as viewed from the control)
Page 17
2
Description
Description l 2-5
How it Works: Refrigerant Circulation
The evaporator extracts heat from the process fluid, causing the refrigerant to vaporize (evaporate) into a gas.
Vaporized refrigerant travels to the compressor, where the low-pressure vapor is compressed into a high-pressure, high-temperature vapor.
The high-pressure, high-temperature vapor travels from the compressor through the condenser, where the fan cools and condenses the vapor into a high-pressure, high­temperature liquid.
High-pressure, high-temperature liquid is metered back to the evaporator by the expansion valve (TXV), changing it to a low-pressure, low-temperature vapor.
1
3
3
To Process outlet
From Process inlet
Drain/Fill
Pump
(Left-side as viewed from the control)
(Right-side as viewed from the control)
1
2
4
2
4
Page 18
How it Works: Component Listing
Water system
Motor/Pump assembly - The motor/pump assembly circulates chilled
coolant through the process loop. The pump assembly is built with brass to maintain water quality.
Refrigeration system
Compressor - Hermetic compressor takes low-pressure, low-temperature
refrigerant gas and compresses the gas into high-pressure, high-temperature vapor.
Air-cooled condenser - The air-cooled condenser removes heat BTUs from
the compressor refrigerant gas. The action causes the gas to “condense” into a liquid state still under high pressure. Air flow across the condenser is achieved by a motor driven fan.
Fan cycling switch - The fan cycling switch is adjustable when the chiller is
in an environment cooler than 95°F {35°C}. See Appendix J entitled,
Plumbing Schematic.
Filter-dryer - The filter-drier removes contaminants and moisture from the
liquid refrigerant.
Liquid receiver - Serves as a collection tank for high-pressure liquid
refrigerant to ensure total charge at all times.
Refrigerant sight glass - The refrigerant sight glass indicates refrigerant
charge and moisture content. Refrigerant charge is determined by a clear liquid flow. Bubbles indicate low refrigerant. Moisture content is indicated by the color of the sight glass view port element. The element’s color is normally green. If the color of the element is dark brown or yellow, the system has been contaminated with moisture and the refrigerant circuit needs to be serviced by a qualified refrigerant service technician. See Maintenance
section entitled, Checking the Refrigerant Charge and Quality.
Expansion valve - The expansion valve meters flow of liquid refrigerant
into the evaporator and creates a pressure drop in the refrigerant system that allows the liquid refrigerant to “boil off” inside the evaporator.
2-6 l Description
(continued)
Page 19
Evaporator - The evaporator is a brazed plate heat exchanger where the
liquid refrigerant is allowed to evaporate (boil off) to absorb the heat (BTU) from the process fluid. As the heat is absorbed, the process fluid is chilled.
High/Low Pressure Switches: The high/low pressure switches protect the
refrigeration system from unsafe operating levels. The high pressure switch is factory set to open at 230 PSI and protects the refrigeration components and personnel from potential damage or injury from excessively high pressure. The high pressure safety must not be altered in the field for any reason. The low pressure switch is factory set to open at 25 PSI and to close at 35 PSI. The low pressure switch protects the chillers from possible damage due to low operating pressure. The low pressure switch is field adjustable for setpoints below 45°F {7.2°C}, contact a Conair representative for more information.
How it Works: Component Listing
(continued)
Description l 2-7
2
Description
IMPORTANT: Altering the High Pressure Switch setting will void any chiller warranty.
NOTE: The fan cycling switch
is adjustable when the chiller
is in an environment cooler
than 95°F {35°C}.
See
Appendix J entitled, Plumbing
Schematic.
Page 20
2-8 l Description
Specifications: EarthSmartTMECM Series Chillers
A
B
C
TPHS039-1208
MODEL ECM-0.5 ECM-0.75
Performance characteristics
Capacity* tons 0.41 0.70 Compressor Hp {kW}
0.5 {0.37} 0.75 {0.56} Pump Hp {kW} 0.25 {0.19} 0.5 {0.37} Chilled water flow‡gpm {lpm} 0.9 {3.4} 1.7 {6.4} Chilled water pressure‡psi {bar} 60 {4.1} 60 {4.1} Reservoir capacity gal {liters} 10 {37.8} 10 {37.8}
Dimensions inches {mm}
A - Height 39.7 {1008} 39.7 {1008} B - Width 18.7 {475} 18.7 {475} C - Depth 24.2 {615} 24.2 {615}
Process connections inches {mm}
Process (to and from) 0.5 0.5
Weight lb {kg}
§
Installed 223 {101} 233 {106} Shipping 170 {77} 180 {82}
Voltages full load amps
**
115V/1 phase/60Hz 14 NA 220V/1 phase/60Hz NA 11
Refrigerant
R-134A
Refrigerant charge lb {kg}
1.3 {0.6} 1.3 {0.6}
SPECIFICATION NOTES:
* Ton capacity at 12,000 BTU/ton @ 50°F {10°C} leaving
water temperature @ 115°F {46°C} condensing tempera­ture. Capacities may be ± 5% as reserved by the compressor manufacturer. Capacity multipliers are: 50°F {10°C} - 1.00; 40°F {4.4°C} - 0.80.
The ECM Series Chiller uses a hermetic reciprocating compressor.
Consult pump curve for exact characteristics relating to pump performances.
§
Chiller installed weight includes a completely filled
reservoir.
**
No allowance for inrush current. Ground fault interruption to be supplied by the customer. Full load amps must be used to size supply conductors. Consult a Conair repre­sentative for 50 Hz operation.
Specifications can change at any time. Contact your Conair representative for the most current information.
Page 21
Description l 2-9
2
Description
Pump Curve: EarthSmartTMECM Series Chillers
25
50 75 100 125 150 175 200 225 25025
20
30
40
50
60
70
80
90
100
110
120
130
140
10
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
Outlet Pressure* (PSI)
Horsepower
Flow Rate (GPH at 1725 RPM)
SPECIFICATION NOTES
* Pump curves do not reflect pressure drops due to internal piping.
This pump curve is non-overloading using the service factor of the motors.
Specifications may change without notice. Check with your Conair representative for the most current information.
100 GPH
100 GPH
Horsepower Flow rate
Page 22
2-10 l Description
Page 23
Installation l 3-1
Installation
Unpacking the boxes . . . . . . . . . . . . . . . . . 3-2
Warnings and cautions . . . . . . . . . . . . . . . . 3-3
Preparing for installation . . . . . . . . . . . . . . 3-4
Making process plumbing connections . . . . . 3-5
Filling the chiller . . . . . . . . . . . . . . . . . . . 3-6
Drain connection . . . . . . . . . . . . . . . . . . . . 3-7
Checking the refrigerant charge . . . . . . . . . 3-8
Connecting the main power . . . . . . . . . . . . . 3-9
SECTION
3
3
Installation
Page 24
3-2 l Installation
Unpacking the Boxes
The EarthSmart ECM Series Chiller comes fully assembled in a single crate. Units are shipped with the casters attached.
1 Carefully uncrate the chiller and its components.
2 Remove all packing material, protective paper, tape and plastic. Compare
contents to the shipping papers to ensure that you have all the parts.
3 Carefully inspect all components to ensure no damage occurred during ship-
ping. If any damage is found, notify the shipping agent immediately to file a claim. Check all wire terminal connections, bolts and any other electrical con­nections, which may have come loose during shipping. Check for pinched wires and kinked hoses.
4 Cut the bands holding the chiller onto the pallet.
5 Record serial numbers and specifications for the chiller in the blanks
provided on the back of this User Guide’s title page. This information will be helpful if you ever need service or parts.
CAUTION: Lifting
Conair EarthSmart ECM Series Chillers are designed to easily roll on casters. If, for some reason you need to lift the chiller, take all precautions to avoid personal injury or damage to the chiller. Lift the chiller using a forklift or hoist with straps that have been positioned at the chiller’s center of gravity. Do not try to lift the chiller manually.
Page 25
Installation l 3-3
3
Installation
Warnings and Cautions
WARNING: Improper installation, operation, or servicing may result in equipment damage or personal injury.
This equipment should only be installed, adjusted and serviced by a qualified technician who is familiar with the construction, operation and potential hazards of this type of machine.
All wiring, disconnects and fuses should be installed by a qualified electrical technician in accordance with electrical codes in your region. Always maintain a safe ground. Do not operate this equipment at power levels other than what is specified on the machine data plate.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller, especially when working on or around the compressor and condenser. These devices can over 160°F {71°C}. Allow these devices to cool before performing any maintenance or troubleshooting.
CAUTION: Ventilation
The unit requires a clean and well ventilated operating environment. Do not place anything on top of the unit while operating.
Units require enough clearance around the perimeter for access panels to be removed completely. Units require a minimum of 2 ft {0.6 m} clearance around the perimeter for proper air flow.
WARNING: Refrigerant hazard
Only certified refrigerant technicians should examine and correct problems involving the refrigerant circuit.
Page 26
Preparing for Installation
Plan the location for the chiller and prepare the area properly.
Position the chiller as close to the process machine as possible. Place the chiller in position near the process machine so that coolant lines can be connected from the process machine to the chiller and back.
Make sure the area where the chiller is installed has:
A grounded power source.
Check the chiller’s serial tag for the correct amps, voltage, phase and cycle. All wiring should be completed by a qualified technician and comply with your region’s electrical codes.
Clearance for safe operation and maintenance.
Ensure there is 2 ft {0.6 m} of clearance at the air intake and 2 ft {0.6 m} of clearance at the exhaust discharge for proper operation. Air flow is generated by the motor driven fan. Air flow is from the outside of the chiller, through the condenser and exhausted through the unit. Exhaust air can not be ducted on motor driven fan models.
Position the locking casters to prevent the chiller from moving. For maintenance and servicing, be sure there is enough clearance to remove all access panels completely.
Available water source.
Ensure water make-up source is plumbed to the chiller’s installation location. High points in the plumbing require vent valves; low points require drain valves.
3-4 l Installation
NOTE: Models must be posi-
tioned so that the condenser
air inlet is no warmer than
95°F {35°C} and the condenser
air outlet is not blocked or
restricted in any way.
Chiller
Process machine
Alternate locations
NOTE: Locate models away
from heat producing equip-
ment. These items will affect
ambient air conditions and the
performance of the chiller.
Page 27
Installation l 3-5
3
Installation
Making Process Plumbing Connections
All process piping materials (such as hoses, rigid piping, valves or filters) used with process water piping circuitry must be rated for 100°F {37.8°C} minimum temperature and 150 PSI {10.3 bar} minimum pressure.
All such materials must have the equivalent or larger diameter of the particular process connection that the length of process water piping is connected to.
Process water piping circuitry should be designed to avoid an excessive use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists or curls and excessive lengths.
Valves and filters may be installed in the process water piping circuitry to facilitate service and maintenance provided that these devices maintain the full inside diameter of the process connection. If installed, all devices must be open and clean during unit operation.
Warm coolant from process equipment enters the chiller at the “From Process” inlet and chilled coolant returns to the process equipment through the “To Process” outlet.
To connect process plumbing:
1 Remove the shipping plastic pipe plugs from the female “To Process” and
“From Process” connections on the back of the portable chiller.
2 Make sure the male pipe threads are clean and new.
3 Wrap the male pipe threads with Teflon tape or pipe dope.
4 Connect the “From Process” valve (factory optional) on the back of the
chiller to the “From Process” tubing that is from the “Water Out” mani­fold on the mold or process. Start by hand until the threads engage and then
tighten with an appropriately-sized pipe wrench. Tighten only enough to pre­vent leaks; do not over-tighten.
5 Connect the “To Process” valve (factory optional) on the back of the chiller
to “To Process” tubing that is from the “Water In” manifold on the mold or process. Start by hand until the threads engage and then tighten with an
appropriately-sized pipe wrench. Tighten only enough to prevent leaks; do not over-tighten. If process lines are higher than the chiller, see Appendix G, entitled
Overhead Plumbing Details.
From Process inlet
To Process outlet
Fill/drain port
NOTE: The ability of the unit to
maintain process temperature
control depends on the method
of installation.
NOTE: Assure the piping
installation has continuous
flow at all times. If using a
mechanical valve to regulate
process flow you MUST install
a bypass in the process
piping.”
Page 28
3-6 l Installation
Filling the Chiller
The chiller is shipped without coolant. The chiller is manually filled during instal­lation using water as its coolant.
For atypical process temperatures below 45°F {7.2°C}, use the table below to determine the percentage (by volume) of glycol needed for the process tempera­ture that is required. Mix the proper percentage of glycol with water.
To fill with water:
1 Attach the water supply to the Fill/Drain valve, located on the back of the
chiller.
2 Open the “To Process” and “From Process” valves (factory optional).
3 Open the Fill/Drain valve or water supply and fill the chiller to the 7/8 full
level on the water level gauge. If the chiller is overfilled, the excess water spills out the vent tube. DO NOT OVERFILL.
4 Close the Fill/Drain valve.
5 Check the coolant level. When the chiller is turned on the coolant level drops
as it begins to circulate, filling the connected plumbing. Check the coolant level on the back of the chiller. Make sure the coolant level is filled to the 7/8 full level on the water level gauge. Shut down the chiller and add more coolant, if needed.
6 Disconnect water hose from Fill/Drain valve, if the chiller is to be used
elsewhere.
Recommended Percentages of Glycol for
Chilled Water Freeze Protection (by volume)
Discharge water % Propylene % Water
Temperature Glycol
40°F 20 80
30°F 30 70
25°F 40 60
IMPORTANT: The chiller’s control does not monitor the percentage mixture of glycol.
IMPORTANT: Evaporator freeze-ups
are not
covered under warranty.
Page 29
Installation l 3-7
3
Installation
Drain Connection
To drain the chiller for storage or transport:
1 Rotate the chiller’s drain valve counterclockwise. If using chemicals or
additives with your process coolant, observe local disposal laws and regulations.
2 Close the chiller’s drain valve by turning it clockwise once final
evacuation of all process coolant is complete.
IMPORTANT: Drainage procedures must be done prior to shipment or outdoor storage of the unit. If not, freezing damage can occur.
From Process inlet
To Process outlet
Fill/drain port
Water level gauge
IMPORTANT: Ensure long-term storage environments are above freezing temperatures. If not, allow the chiller to thaw for several hours before returning it to operation or fill the chiller’s internal piping with a high mixture of glycol to water during storage.
Page 30
3-8 l Installation
Checking the Refrigerant Charge
WARNING: Refrigerant hazard
Only certified refrigerant technicians should examine and correct problems involving the refrigerant circuit.
All chillers are fully charged with R-134A refrigerant from Conair. Your chiller’s model nameplate identifies the type and amount of total refrigerant charge required.
Check the refrigerant charge while the chiller is running through the sight glass. Locate the sight glass by removing the left-side panel and using a flashlight, if necessary to check the sight glass:
Under full load conditions, the refrigerant should be clear (no bubbles).
Under low load conditions, when the Hot-gas Bypass valve is energized,
bubbles may be visible in the sight glass. This is normal.
If the charge is low and the unit is under warranty, contact Conair service. Otherwise have a local, certified refrigeration technician add R-134A refrigerant to the system.
Sight glass
NOTE: In this diagram, the
chiller’s panels are removed
for clarity.
CAUTION: Always disconnect and lock out the main power sources before making electrical connections. Electrical connections should be made only by a qualified electrical technician.
Page 31
Connecting the Main Power
The Conair EarthSmart ECM Chiller uses standard 115 Volt, 60 Hz or 220 Volt, 60Hz single-phase power, depending on model.
To connect the the main power to the chiller:
1 Connect the chiller’s plug into a properly-sized and rated electrical outlet.
IMPORTANT: Always refer to the wiring diagrams that came with your chiller to locate specific electrical components. Illustrations in the User Guide are intended to be representative only.
CAUTION: Always disconnect and lock out the main power sources before making electrical connections. Electrical connections should be made only by a qualified electrical technician.
Installation l 3-9
3
Installation
220 Volt/60 Hz, 20 amp plug
IMPORTANT: Depending on the state of the refrigeration system the compressor may turn on
momentarily upon connecting power. The compressor will stop when the refrigerant is
pumped into the condenser and a low pressure condition exists in the evaporator.
Page 32
3-10 l Installation
Page 33
SECTION
4
4
Operation
Operation
EarthSmart ECM Series Chiller:
Control descriptions . . . . . . . . . . . . . . . 4-2
Starting the chiller . . . . . . . . . . . . . . . . . . 4-3
Stopping the chiller . . . . . . . . . . . . . . . . . . 4-4
Changing temperature units . . . . . . . . . . . . 4-5
Chiller operation sequence . . . . . . . . . . . . . 4-6
Resetting the high pressure switch
of the compressor . . . . . . . . . . . . . . . . 4-8
Operation l 4-1
Page 34
12 %
SD
EarthSmart ECM Chiller: Control Descriptions
Hot-Gas Bypass Status
Indicates the status of the Hot-Gas Bypass valve.
Actual Chiller Temperature
Shows the (process) actual temperature value.
On/Off Toggle Switch
Used to turn the power to the chiller on or off.
Alarm Indication
Indicates the alarm sta­tus. (High Temperature Alarm only.)
Setpoint Temperature
Shows the user­entered setpoint temperature value.
4-2 l Operation
Control Codes
See See Trouble-
shooting section for
a list of possible causes and solutions for alarm condi­tions.
Infinity Button
Pressing the “Infinity” button will acknowledge alarms and return the user to the Main screen.
Return Button
Pressing the “Return” button will scroll through the chiller’s menu screens.
Increment/ Decrement Buttons
Used to increase or decrease the user­entered process temperature set­point.
Page 35
4
Operation
Operation l 4-3
Starting the Chiller
To start the chiller:
1 Toggle the power switch to the On or “I” position. The control display will
illuminate. Facing the chiller’s control, the “To Process” actual temperature will be on the left, the setpoint temperature is on the right. See Operation
section entitled, Chiller Sequence of Operation.
2 Set the cooling temperature setpoint. Use the up arrow button on the
control, to raise the setpoint. Use the down arrow button to lower the set­point. The temperature will ramp up at approximately 1 (one) degree per second. After 2 (two) seconds of inactivity the setpoint entered will become the targeted setpoint temperature.
On Position
NOTE: If the setpoint displays “OFF” in the display, raise the setpoint with the up arrow button
to see
the actual setpoint.
12 %
SD
Infinity Button
Pressing the “Infinity” button will acknowledge alarms and return the user to the Main screen.
Page 36
4-4 l Operation
Stopping the Chiller
To stop the chiller:
1 Toggle the power switch to the Off or “O” position.
Off Position
12 %
SD
IMPORTANT: Do NOT rapidly cycle the chiller’s power on and off (short cycle). Once the power has been turned off, wait at least three (3) minutes before cycling the chiller’s power back on.
Page 37
4
Operation
Operation l 4-5
Changing Temperature Unit
To stop the chiller:
1 Press the green “Return” button once to access the Temperature Units
Selection screen. Press the or buttons to toggle between fahrenheit and celsius temperature units.
2 Press the “Infinity” button to lock in the selection and return to the
Main screen. The control will default back to the Main screen if no buttons are pressed after 1 minute.
12 %
SD
Return Button
12 %
SD
Infinity Button
NOTE: The temperature display will not indicate Fahrenheit or Celsius temperature units. The chiller’s control is set for Fahrenheit tem­perature units as standard from Conair.
Page 38
4-6 l Operation
Chiller Operation Sequence
The EarthSmart ECM Series Chiller has a unique user interface that controls the process temperature and prevents refrigeration migration during compressor off times.
When the main power is connected:
1 Depending on the state of the refrigeration system, the compressor may
turn on momentarily upon connecting power. The compressor will stop when the refrigerant is pumped into the condenser and a low pressure condition exists in the evaporator.
When the power toggle switch is turned to the “On”or “I” position:
2 Turning the toggle switch on immediately starts the process pump and
illuminates the control. When flow is established and the unit is not in a low temperature alarm, the Liquid Line Solenoid valve (LLSV) will open. This allows the refrigerant to migrate to the evaporator and increase the pressure. When the low refrigerant pressure switch is satisfied the compressor will turn on and process coolant will begin cooling.
3 When the process temperature is above setpoint the compressor will run
and the Hot-Gas Bypass valve (HGBP) will not open. If the process temperature falls below the setpoint, the HGBP valve will energize, raising the actual process temperature to maintain the user-entered setpoint temperature. The HGBP valve can energize up to 9 out of 10 seconds. If there is less load on the chiller and the temperature continues to fall to 4°F {2.2°C} below the user-entered setpoint the controller will alarm (A2.lo) and close the LLSV. The compressor will pump the refrigerant out of the evaporator and the low pressure switch will shut off the compressor. This is a normal function of the chiller and will not require troubleshooting.
4 The controller stays in this alarm condition (A2.lo) until the temperature is
2°F {1.1°C} above the user-entered setpoint, at which point the controller allows the LLSV to re-open and the compressor to restart.
(continued)
Page 39
Operation l 4-7
4
Operation
Chiller Operation Sequence (continued)
5 The condenser fan can energize anytime the toggle switch is in the “On”
or “I” position. The fan is controlled by the fan cycling (high refrigeration) pressure switch. This switch maintains the high side refrigeration pressure under cooler ambient temperatures and lower loads. The fan will turn on when the high refrigeration pressure reaches 200 PSI {13.8 bar}. It will turn off when the pressure drops below 125 PSI {8.6 bar}.
6 The high refrigeration safety pressure switch shuts off the compressor
immediately when the high refrigeration pressure reaches 230 PSI {15.9 bar} without going through pump down during a low pressure cycle.
If the high pressure switch trips, it must be manually reset by pressing the “Reset” button on the switch. The compressor can start immediately when this is reset so caution should be exercised. See Operation section entitled,
Resetting the Compressor’s High Pressure Switch.
CAUTION: The compressor can start immediately when the High Pressure “Reset” button is pressed.
Page 40
4-8 l Operation
Resetting the High Pressure Switch of the Compressor
The high refrigeration safety pressure switch shuts off the compressor immediately when the high refrigeration pressure reaches 230 PSI {15.9 bar} without going through pump down during a low pressure cycle. If the high pressure switch trips, it must be manually reset by pressing the “Reset” button on the switch. The compressor can start immediately when this is reset so caution should be exercised.
To reset the high refrigeration safety switch:
1 Be sure the main power is disconnected and the chiller is locked out. Always
disconnect/unplug and/or lockout the main power source before opening the unit for servicing.
2 Remove the chiller’s right-side panel, as viewed from the control.
3 Locate the high refrigeration safety switch within the top portion of the
chiller’s cabinet.
4 Push the “Reset” button, until there is a “click”.
5 Replace the chiller’s right-side panel, as viewed from the control.
6 Reapply main power.
Reset Button
NOTE: The High Pressure Safety switch may not reset due to the chiller’s refrigerant state. Allow the refrigerant to cool before attempting to reset.
CAUTION: The compressor can start immediately when the High Pressure “Reset” button is pressed.
Page 41
Maintenance
Preventative maintenance schedule . . . . . . . 5-2
Checking electrical connections. . . . . . . . . . 5-4
Cleaning the brazed plate adapter . . . . . . . . 5-5
Cleaning the air-cooled condenser . . . . . . . . 5-7
Checking the reservoir level . . . . . . . . . . . . 5-9
Cleaning the pump strainer . . . . . . . . . . . . 5-10
Checking the refrigerant charge
and quality . . . . . . . . . . . . . . . . . . . . 5-12
SECTION
5
Maintenance
5
Maintenance l 5-1
Page 42
5-2 l Maintenance
Preventative Maintenance Schedule
Daily, or as often as needed
Checking process fluid level in the pump tank
Check the process fluid level in the water level gauge on the back of the chiller. If low, see Maintenance section entitled, Checking the Reservoir
Level.
Verifying pump discharge pressure
While the pump is running, check to ensure that the pump pressure gauge (located on the front of the chiller) is within range. To change the pressure, open or close the “To Process” valve (factory optional).
Inspecting piping for leaks
Check to see that pipes are not leaking. Look for standing water on the floor or inside the chiller cabinet.
Inspecting the condenser coil for debris
Check the condenser for adequate air flow. Check the condenser face for dirt and clogging. If dirt or clogs are present, clean the condenser, see
Maintenance section entitled, Cleaning the Air-cooled Condenser. Check,
clean, and/or replace the filter at the air inlet of the air-cooled condenser coil, as needed.
Weekly, or as often as needed
Checking temperature and pressure readings
Check that the temperature displays on the control screen and the reading on the pressure gauge (located on the front of the chiller) indicates normal operation. See Description section entitled, Pump Curve: EarthSmart ECM
Series Chillers.
Inspecting the filter
Check, clean and/or replace the filter at the air inlet of the air-cooled con­denser coil, as needed. see Maintenance section entitled, Cleaning the Air-
cooled Condenser.
Checking refrigerant site glass
There should not be any bubbles. See Maintenance section entitled,
Checking the Refrigerant Charge and Quality.
Checking reservoir level
Check the water level gauge on the back of the chiller. If fluid level is low, fill, see Maintenance section entitled, Checking Reservoir Level.
(continued)
Page 43
Maintenance l 5-3
Preventative Maintenance Schedule
(continued)
Monthly
Inspecting cooling water treatment system
If your chiller uses a cooling water treatment system, maintain proper chemi­cal levels and follow the recommendations of your water treatment specialist. Change water in the reservoir tank monthly to reduce water hardness.
Checking electrical connections, amps and volts
Check to ensure the electrical connections are properly seated and that the chiller is operating at its rated amps and voltage. See Description section
entitled, Specifications: EarthSmart ECM Series Chillers.
Cleaning
Wipe all external surfaces to maintain performance.
Inspecting condenser
Check the air-cooled condenser for adequate air flow. Check the condenser face for dirt and clogging. If dirt or clogs are present, clean the condenser. Check, clean and/or replace the filter at the air inlet of the air-cooled con­denser coil, as needed. See Maintenance section entitled, Cleaning the Air-
cooled Condenser.
Inspecting the control panel
Check for loose wires, burned contacts and signs of overheated wires. Check that all panel lights illuminate. See Maintenance section entitled,
Checking Electrical Connections.
Checking refrigerant charge and quality
With the compressor running, check the sight glass between the receiver and evaporator for proper refrigerant condition. See Maintenance section entitled,
Checking Refrigerant Charge and Quality.
Checking the pump strainer.
Check to ensure the pump strainer is not clogged or damaged, replace as needed. See Maintenance section entitled, Cleaning the Pump Strainer.
Annually
Cleaning the evaporator
See Maintenance section entitled, Cleaning the Brazed Plate Evaporator.
Check refrigerant piping
Verify that no oil is present on fittings or cabinet. Wipe clean and check charge/operation of circuit.
5
Maintenance
Page 44
5-4 l Maintenance
Checking Electrical Connections
WARNING: Electrical Hazard
Before performing any work on this item, disconnect and lock out electrical power sources to prevent injury from unexpected energization or startup. Be sure that power to the chiller is OFF when doing any maintenance on the chiller. Follow all safety rules when performing any maintenance on this equipment.
WARNING: Improper installation, operation or servicing may result in equipment damage or personal injury.
This equipment should only be installed, adjusted and serviced by a qualified technician who is familiar with the construction, operation and potential hazards of this type of machine.
All wiring, disconnects and fuses should be installed by a qualified electrical technician in accordance with electrical codes in your region.
To check electrical connections:
1 Be sure the main power is disconnected and/or the chiller is locked out. Always
disconnect/unplug and lockout the main power source before opening the unit for servicing.
2 Remove the chiller’s top lid, by first removing both side panels and then the four
(4) retaining bolts that secure the chiller’s top lid.
3 Inspect all wires and connections.
Look for loose wires, burned contacts and signs of over-heated wires. Compare the wiring to the wiring diagrams you received with your chiller. Have a qualified electrician make any necessary repairs or replacements.
4 Replace the chiller’s side panels and then the top lid by replacing the four (4)
retaining bolts.
5 Inspect the exterior power cords.
Cords should not be crimped, exposed or rubbing against the frame. If the main power cord runs along the floor, make sure it is positioned where it could not rest in pooling water or could not be ran over and cut by wheels or casters.
NOTE: Always refer to the wiring dia­grams you received with your chiller to locate specific elec­trical components.
NOTE: Also inspect the chiller’s plug wiring terminations.
Page 45
Cleaning the Brazed Plate Evaporator
Minerals and other contaminants produce deposits, scales, slime or algae on the heat transfer surfaces exposed to water. Fouled surfaces could result in decreased cooling capacity. Implement a water treatment program to slow the fouling.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller, espe­cially when working on or around the compressor and condenser. These devices can reach over 160°F {71°C}. Allow these devices to cool before performing any maintenance or troubleshooting.
Water quality should be maintained at a pH level of 7.4, but not less than 6.0 for proper heat exchanger life.
To clean the brazed plate adapter:
1 Prepare a 5% solution of Phosphoric acid or Oxalic acid and water. Do not
heat the acid solution.
2 Disconnect and/or lockout main power to the chiller.
3 Shut the “To” and “From Process” valves (factory optional) and the drain
reservoir. See Installation section entitled, Drain Connection.
4 Remove the chiller’s side panels.
5 Disconnect the pump from the heat exchanger. Install a cap in the opening of
the heat exchanger where the pump was connected.
Maintenance l 5-5
NOTE: These connections may vary depending on the model you have purchased. Be sure to see the labeling on your particular unit.
5
Maintenance
From Process inlet
To Process outlet
Fill/drain port
Water level gauge
(continued)
Page 46
5-6 l Maintenance
Cleaning the Brazed Plate Evaporator
(continued)
5 Remove RTD from bottom of evaporator.
6 Connect 3/8-inch tubing to the 3/8-inch connections of the heat exchanger.
SEE below to install customer-supplied chemical pump and solution fitted to the heat exchanger.
7 Back-flush the solution through the heat exchanger and the chiller.
8 Flush the heat exchanger and the chiller piping with fresh water after
cleaning.
9 Reconnect the chiller pump to the heat exchanger. Remove the cap in the heat
exchanger and reconnect the hose to the pump.
NOTE: These connections may vary depending on the model you have purchased. Be sure to see the labeling on your particular unit.
Acid solution
Fluid circuit
Heat Exchanger
To pump
To Process connection
Valve
Pump
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller, especially when working on or around the compressor and condenser. These devices can reach over 160°F {71°C}. Allow these devices to cool before performing any maintenance or troubleshooting.
Page 47
5
Maintenance
Cleaning the Air-Cooled Condenser
WARNING: Electrical Hazard
Before performing any work on this item, disconnect and lock out electrical power sources to prevent injury from unexpected energization or startup. Be sure that power to the chiller is OFF when doing any maintenance on the chiller. Follow all safety rules when performing any maintenance on this equipment.
CAUTION: Hot Surfaces
Always protect yourself from hot surfaces when working on the chiller, especially when working on or around the compressor and condenser. These devices can reach over 160°F {71°C}. Allow these devices to cool before performing any maintenance or troubleshooting.
The air-cooled condenser and condenser filter can accumulate dirt and clog quickly if it is ran in a dusty or dirty environment. A clogged condenser or condenser filter increases refrigerant discharge pressure, lowers performance, and may cause the fan motors and compressor to overheat.
To clean the air-cooled condenser:
1 Disconnect and/or lockout main power to the chiller.
2 Remove the chiller’s top lid, by first removing both side panels and then the four
(4) retaining bolts that secure the chiller’s top lid.
3 Remove the filter, that is located towards the back of the chiller, by lifting it
straight up and out of the chiller.
4 Inspect the condenser coils. Use a flashlight to check between coil surfaces.
5 Clean the dirty coils with a soft brush.
6 Flush with cool water or a commercial coil cleaner that is compatible with
aluminum alloys. It is recommended that the coil cleaner is sprayed from inside the cabinet.
Maintenance l 5-7
(continued)
Page 48
Cleaning the Air-Cooled Condenser
(continued)
7 Check the air filter. If the filter is blinded or torn, replace the filter.
8 Replace the chiller’s side panels and then the top lid by replacing the four (4)
retaining bolts.
9 Reapply main power.
CAUTION: Wear eye protection.
If you use compressed air to clean the equipment, you must wear eye pro­tection and observe all OSHA and other safety regulations pertaining to the use of compressed air.
Replacement air filters are available from Conair.
Contact Conair Parts (800) 458 1960 From outside of the United States, call: (814) 437 6861
5-8 l Maintenance
Page 49
Maintenance l 5-9
Checking Reservoir Level
WARNING: Electrical Hazard
Before performing any work on the chiller, disconnect and lock out electrical power sources to prevent injury from unexpected energization or startup. Be sure that power to the chiller is OFF when doing any maintenance on the chiller. Follow all safety rules when performing any maintenance on this equipment.
Check the coolant level in the reservoir. The coolant level in the sight glass on the back of the chiller should be 7/8 full.
To manually fill the reservoir:
1 Disconnect and lockout power to the chiller.
2 Locate the Fill/Drain valve on the back of the chiller. Open the Fill/Drain valve
or coolant supply and fill the chiller to the 7/8 full level on the water level gauge. If the chiller is overfilled, the excess water spills out the vent tube. DO NOT OVERFILL.
3 Refill the reservoir. Monitor the level using the water level indicator on the back
of the chiller, ensuring you are adding the correct fluid for your application.
4 Close the Fill/Drain valve.
5 Check the coolant level. When the chiller is turned on the coolant level drops
as it begins to circulate, filling the connected plumbing. Check the coolant level on the back of the chiller. Make sure the coolant level is filled to the 7/8 full level on the water level gauge. Shut down the chiller and add more coolant, if needed.
6 Disconnect water hose from Fill/Drain valve, if the chiller is to be used
elsewhere.
Fill/drain port
Water level gauge
5
Maintenance
Page 50
Cleaning the Pump Strainer
EarthSmart Chillers use a rotary pump to flow process coolant through their internal piping and to the process. A strainer on the pump may periodically need cleaning, depending upon the quality of the process coolant.
WARNING: Electrical Hazard
Before performing any work on the chiller, disconnect and lock out electrical power sources to prevent injury from unexpected energization or startup. Be sure that power to the chiller is OFF when doing any maintenance on the chiller. Follow all safety rules when performing any maintenance on this equipment.
To clean the pump’s strainer:
1 Be sure the main power is disconnected and/or the chiller is locked out. Always
disconnect/unplug and lockout the main power source before opening the unit for servicing.
2 Drain all process coolant from the chiller, see Installation section entitled, Drain
Connection.
3 Remove the chiller’s right-side panel. (As viewed from the control)
4 Locate the chiller’s pump. It is located in the lower portion of the chiller’ cabinet
and towards the front of the chiller.
5 Locate the pump strainer’s end cap, remove the cap by unscrewing it counter-
clockwise with an appropriately-sized wrench.
5-10 l Maintenance
Strainer end cap
NOTE: The front panel of the chiller has been removed in this image for clarity.
(continued)
Page 51
Cleaning the Pump Strainer (continued)
6 Remove the strainer from its housing.
7 Inspect the strainer for holes or blinding, clean or replace as necessary.
8 Re-install the strainer and strainer cap. Properly seal all piping with approved
Teflon tape or pipe dope.
9 Check to ensure no leaking has occurred before returning the chiller to normal
operation.
Replacement strainers are available from Conair.
Contact Conair Parts (800) 458 1960 From outside of the United States, call: (814) 437 6861
IMPORTANT: Check to ensure the strainer is properly seated before applying the strainer cap. Crushing of the strainer can occur if it is not fully inserted back into the strainer housing.
5
Maintenance
Maintenance l 5-11
Page 52
5-12 l Maintenance
Checking the Refrigerant Charge and Quality
WARNING: Refrigerant Hazard
Only certified refrigerant technicians should examine and correct problems involving the refrigerant circuit.
All chillers are fully charged with R-134A refrigerant from Conair. Your chiller’s model nameplate identifies the type and amount of total refrigerant charge required.
See Description section entitled, Specifications: EarthSmart ECM Series Chillers.
Check refrigerant charge while the chiller is running under normal load. Check the refrigerant charge through the sight glass. Use a flashlight, if necessary, and check the liquid-line sight glass:
Under full load conditions, the refrigerant should be clear (no bubbles).
Under low load conditions, when the Hot-Gas Bypass valve (HGBP) is
operating, bubbles may be visible in the sight glass. This is normal.
A refrigerant quality label is located within the sight glass. A green label is normal. A yellow or dark brown label indicates that the refrigerant is contaminated and must be replaced.
If the charge is low or contaminated and the chiller is under warranty, contact Conair service; or have a local, certified refrigeration technician service the system.
Sight glass
CAUTION: Always disconnect and lock out the main power sources before making electrical connections. Electrical connections should be made only by a qualified electrical technician.
NOTE: In this diagram, the
chiller’s panels are removed
for clarity.
Page 53
Troubleshooting
Before beginning . . . . . . . . . . . . . . . . . . . . 6-2
A few words of caution . . . . . . . . . . . . . . 6-3
DIAGNOSTICS
How to identify the cause of a problem . . . . 6-3
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Troubleshooting . . . . . . . . . . . . . . . . . . . . 6-5
Checking or replacing the
temperature sensor . . . . . . . . . . . . . . . 6-8
Checking or resetting the circuit breakers. . . 6-9
SECTION
6
6
Troubleshooting
Maintenance l 6-1
Page 54
Before Beginning
You can avoid most problems by following the recommended installation and maintenance procedures outlined in this User Guide. If you do have a problem, this section will help you determine what caused it and how to fix it.
Diagnose causes from the control panel.
1 Note the alarm and press the “Infinity” button once to acknowledge
the alarm and resume control if required.
2 Address the alarm message and fix the problem. See Troubleshooting
section for descriptions of possible alarm conditions.
3 If the alarm reappears the problem was not fixed.
Find the wiring and equipment diagrams that were shipped with your
chiller. These diagrams are the best reference for correcting a problem. The
diagrams also will note any custom features, such as special wiring or alarm capabilities, not covered in this User Guide.
12 %
SD
This red light indicates a High Temperature alarm condition
The “Infinity” button should be pressed once to acknowledge a High Temperature alarm.
6-2 l Troubleshooting
Page 55
6
Troubleshooting
A Few Words of Caution
Improper corrective actions can lead to hazardous conditions and should never be attempted to sustain production.
WARNING: Only a qualified electrical technician should examine and correct problems that require opening the chiller’s electrical enclosure or using electrical wires to diagnose the cause.
WARNING: High voltage. Always stop the chiller, disconnect and lock out the main power source before troubleshooting or performing repairs.
CAUTION: Hot surfaces. Always protect yourself from hot surfaces inside and outside of the chiller.
How to Identify the Cause of a Problem
The High Temperature Alarm is indicated by an illuminated alarm light on the EarthSmart ECM control panel and an alarm code, (A2.hi) is displayed in the control display.
When an alarm code is displayed in the control:
1 Find the error message in the diagnostics table of this
Troubleshooting section and reference the control labeling in the upper right-hand side of the control face.
2 Note that, after correcting the problem, pressing the “Infinity”
button will clear the alarm. The alarm will only clear if the condition causing the alarm has been corrected.
Troubleshooting l 6-3
Page 56
6-4 l Troubleshooting
Alarms
If the red alarm LED is illuminated, an alarm is activated. The chiller has automat­ically pumped down because it has detected a serious problem that could damage your process or chiller. Note that the alarm must be acknowledged before the con­trol will resume operation by pressing the “Infinity” button.
Problem
A2.hi (Alarm light illuminat­ed) – If the “To Process”
temperature exceeds the process high temperature devi­ation setpoint, it shuts down the chiller. Default is set to 20°F {11.1°C}.
Er.in (Input error)
A2.lo – (Alarm light illumi- nated) – If the “To Process”
temperature exceeds the process low temperature devi­ation setpoint, it closes the liq­uid line solenoid valve and the compressor pumps down and shuts down. Default is set to 4°F {2.2°C}.
Possible cause
The Hot-gas Bypass valve is not operating properly (stuck open).
Load is too high for the chiller.
Process coolant is not flowing between the supply outlet and return inlet.
Dirty condenser coil.
Ambient temperature is above 95°F {35°C}.
Warm process coolant.
Failed RTD.
Loose RTD connection to the control.
Reversed RTD input.
Load is too low for the chiller.
Solution
Have a certified refrigeration technician replace the solenoid valve.
Remove some load from the process.
Check for plugged pipes, closed valves, or failed flow switch(es).
Clean condenser coil. See Maintenance
section entitled, Cleaning the Air­cooled Condenser.
Lower ambient temperature or move the chiller to a lower temperature envi­ronment.
Lower the temperature of the process coolant.
Replace the RTD. See Troubleshooting
section entitled, Checking or Replacing the Temperature Sensor and Appendix F entitled, RTD Resistance Chart.
Check RTD connection to the controller. Resecure as necessary.
Check RTD wiring.
The chiller’s compressor will automati­cally restart once the “To Process” temperature exceeds the user-entered setpoint on the control by 2°F {1.1°C}.
Page 57
Troubleshooting l 6-5
6
Troubleshooting
Troubleshooting
Problem
The chiller will not start. (Control not illuminated)
Pump will not start.
Possible cause
Tripped circuit breaker.
Incorrect incoming voltage.
The power toggle switch is not turned to the “On” or “I” position.
Open motor winding.
Internal overload has tripped.
Loose wire connection or defective start capacitor.
CB2 circuit breaker has been tripped.
Solution
Verify resistance to ground. Reset breaker. See Troubleshooting section
entitled, Checking or Resetting the Circuit Breakers.
Check incoming power source for correct voltage and amperage as detailed on the chiller nameplate. See
Description section entitled, Specifications: EarthSmart ECM Series Chillers.
Turn the power toggle switch on the control to the “On” or “I” position.
Contact Conair Service.
Auto-resetting. Allow the chiller’s motor to cool and restart the chiller.
Check wiring diagrams, see Appendix
H entitled, Electrical Schematic,
replace connections or capacitor.
Verify resistance to ground. Reset breaker. See Troubleshooting section
entitled, Checking or Resetting the Circuit Breakers.
Page 58
Troubleshooting (continued)
Problem
Compressor will not start.
Possible cause
High pressure switch has been tripped.
Circuit breaker has been tripped.
Loose wire connection or defective start capacitor.
The actual “To Process” temperature is below the setpoint.
Damaged or defective start capacitor.
Poor water flow.
Damaged or defective compressor.
Solution
Reset the High Pressure switch. See
Operation section entitled, Resetting the High Pressure Switch.
Verify resistance to ground. Reset breaker. See Troubleshooting section
entitled, Checking or Resetting the Circuit Breakers.
Check wiring diagrams, see Appendix
H entitled, Electrical Schematic,
replace connections or capacitor.
Lower setpoint temperature value. See
Operation section entitled, Starting the Chiller.
Contact Conair Service.
Check pump rotation.
Clean the pump strainer. See
Maintenance section entitled, Cleaning the Pump Strainer.
Have a certified refrigeration technician replace the compressor.
6-6 l Troubleshooting
NOTE:
Also, see Troubleshooting section, entitled, Troubleshooting, “Chiller shuts down due to a High Pressure switch alarm” and “Chiller shuts down due to a Low Pressure switch”.
Page 59
Troubleshooting (continued)
Problem
Chiller shuts down due to a High Pressure switch alarm.
Chiller shuts down due to a Low Pressure switch.
Possible cause
Low air flow across the condenser.
Fan not operating.
High ambient temperature.
Insufficient clear space around unit.
Clogged air filter.
Attempting to operate the chiller with process coolant below 45°F {7.2°C}.
Low refrigerant charge.
Poor heat transfer in the evaporator tank due to a high percentage of glycol to water.
Low flow through the evaporator due to glycol foaming.
Low flow through the evaporator.
Faulty pump motor.
Clogged pump strainer.
Solution
Check for dirty condenser fins. Clean as necessary. See Maintenance section
entitled, Cleaning the Air-cooled Condenser.
Reset High Pressure switch. See
Operation section entitled, Resetting the High Pressure Safety Switch.
Check for loose fan blade or open/grounded motor winding.
Move the chiller to a lower ambient temperature location.
Increase clearance around the chiller.
Replace filter. See Maintenance section
entitled, Cleaning the Air-cooled Condenser.
Increase temperature setpoint above 45°F {7.2°C}. See Operation section
entitled, Starting the Chiller.
See Installation section entitled, Checking the Refrigerant Charge.
Reduce the glycol mixture of the process coolant. See Installation
section entitled, Filling the Chiller.
Replace the process coolant. See
Installation section entitled, Filling the Chiller.
See Maintenance section entitled, Cleaning the Brazed Plate Evaporator.
Contact Conair Service.
Clean or replace the strainer. See
Maintenance section entitled, Cleaning the Pump Strainer.
6
Troubleshooting
Troubleshooting l 6-7
NOTE: The is a normal shutdown for other alarm conditions when the chiller’s main power has been switch off.
Page 60
Checking or Replacing the Temperature Sensor
The EarthSmart ECM Series Chiller uses a RTD sensor to monitor the temperature of the process coolant.
To check or replace an RTD sensor:
1 Disconnect and/or lockout the main power supply.
2 Locate the RTD sensor.
3 Check the sensor’s position and condition. Temperature readings will be
incorrect if the sensor is touching the wall of a pipe or if the sensor or wiring is damaged. Sensor wires should be attached to the appropriate connection points on the chiller’s control center.
4 To check with ohm meter, measure the resistance across the RTDs. The
resistance should be approximately 110 ohm at room temperature. See
Appendix F entitled, RTD Resistance Chart.
5 Remove the sensor from its housing using an appropriately-sized wrench.
6 Inspect the sensor for cleanliness. Replace if necessary with another sensor of
the same rating.
7 Replace the RTD, by wrapping the its threads with Teflon tape or pipe dope.
8 Re-insert the RTD into its housing, start by hand until its threads engage.
Tighten with an appropriately-sized wrench, do not over tighten.
Typical location of the RTD at the chiller’s evaporator.
IMPORTANT
: Always refer
to the wiring diagrams that came with your chiller to locate specific electrical components. Illustrations in the User Guide are intended to be representative only.
Replacement RTDs are available from Conair.
Contact Conair Parts (800) 458 1960 From outside of the United States, call: (814) 437 6861
6-8 l Troubleshooting
Page 61
Troubleshooting l 6-9
Checking or Resetting the Circuit Breakers
The EarthSmart ECM Series Chiller uses electrical circuit breaker to protect the chiller from overloads or improper operating conditions.
To check or reset the chiller’s circuit breakers:
1 Disconnect and lockout the main power supply.
2 Remove the chiller’s top lid, by first removing both side panels and then the
four (4) retaining bolts that secure the chiller’s top lid.
3 Locate the appropriate circuit breaker(s), located behind the chiller’s
control panel. See the wiring diagrams that came with your chiller.
4 Check the circuit breaker(s) position and condition. The chiller will not
operate correctly if one or more circuit breakers have been tripped (facing down).
5 Reset the circuit breaker(s), if necessary.
6 Replace the chiller’s side panels and then the top lid by replacing the four
(4) retaining bolts.
7 Reapply main power.
IMPORTANT
: Always refer
to the wiring diagrams that came with your chiller to locate specific electrical components. Illustrations in the User Guide are intended to be representative only.
Circuit Breakers
Page 62
A-1 l Appendix
We’re Here to Help
Conair has made the largest investment in customer support in the plastics indus­try. Our service experts are available to help with any problem you might have installing and operating your equipment. Your Conair sales representative also can help analyze the nature of your problem, assuring that it did not result from misapplication or improper use.
How to Contact Customer Service
To contact Customer Service personnel, call:
You can commission Conair service personnel to provide on-site service by contacting the Customer Service Department.
Before You Call...
If you do have a problem, please complete the following checklist before calling Conair:
Make sure you have all model, control type and serial numbers from the serial tag, and parts list numbers for your particular equipment. Service personnel will need this information to assist you..
Make sure power is supplied to the equipment.
Make sure that all connectors and wires within and between control systems and related components have been installed correctly.
Check the troubleshooting guide of this manual for a solution.
Thoroughly examine the instruction manual(s) for associated equipment, especial­ly controls. Each manual may have its own troubleshooting guide to help you.
Check that the equipment has been operated as described in this manual.
Check accompanying schematic drawings for information on special considerations.
PARTS & SERVICE
U
S
8
0
0
4
5
8
1
9
6
0
I
N
T
E
R
N
A
T
I
O
N
A
L
+
1
8
1
4
4
3
7
6
8
6
1
Additional manuals and prints for your Conair equipment may be ordered through the Customer Service or Parts Department for a nominal fee. Most manuals can be downloaded free of charge from the product section of the Conair website. www.conairgroup.com
NOTE: Normal operating hours are 8:00 am - 5:00 pm (EST). After hours emergency
service is available at the same phone number.
Page 63
Appendix l A-2
Equipment Guarantee
Conair guarantees the machinery and equipment on this order, for a period as defined in the quotation from date of shipment, against defects in material and workmanship under the normal use and service for which it was recommended (except for parts that are typically replaced after normal usage, such as filters, liner plates, etc.). Conair’s guarantee is limited to replacing, at our option, the part or parts determined by us to be defective after examination. The customer assumes the cost of transportation of the part or parts to and from the factory.
Performance Warranty
Conair warrants that this equipment will perform at or above the ratings stated in specific quotations covering the equipment or as detailed in engineering specifica­tions, provided the equipment is applied, installed, operated and maintained in the recommended manner as outlined in our quotation or specifications.
Should performance not meet warranted levels, Conair at its discretion will exercise one of the following options:
Inspect the equipment and perform alterations or adjustments to satisfy
performance claims. (Charges for such inspections and corrections will be waived unless failure to meet warranty is due to misapplication, improper installation, poor maintenance practices or improper operation.)
Replace the original equipment with other Conair equipment that will meet
original performance claims at no extra cost to the customer.
Refund the invoiced cost to the customer. Credit is subject to prior notice by the
customer at which time a Return Goods Authorization Number (RGA) will be issued by Conair’s Service Department. Returned equipment must be well crated and in proper operating condition, including all parts. Returns must be prepaid.
Purchaser must notify Conair in writing of any claim and provide a customer receipt and other evidence that a claim is being made.
Warranty Limitations
Except for the Equipment Guarantee and Performance Warranty stated above, Conair disclaims all other warranties with respect to the equipment, express or implied, arising by operation of law, course of dealing, usage of trade or otherwise, including but not limited to the implied warranties of merchantability and fitness for a particular purpose.
Page 64
B-1 l Appendix
Safety Adjustments
To ensure safe and efficient operation at lower setpoints, adjustments of the low pressure switch from factory settings is required. The table below lists the appropriate settings.
The low pressure switch serves as the mainline defense against freezing. It shuts down the chiller if the coolant temperature ever decreases to its setting.
To adjust a mechanical low pressure switch:
1 Disconnect and lockout the main power supply.
2 Remove the chiller’s right-side panel, as viewed from the control.
3 Locate the low pressure switch within the top portion of the chiller’s cabinet.
4 Turn the low pressure cut-in and cut-out adjustment screws found on the
top of the low pressure switch, according the operating temperature located on the chart above.
5 Replace the chiller’s right-side panel and reapply main power.
Operating Low Low
Temperature Cut In Cut Out
45°F 35# 25# 40°F 30# 20# 35°F 25# 16# 30°F 20# 12#
NOTE: For chiller operation
below 45°F {7.2°C}, the
chiller’s control must
be
configured properly. Contact
Conair Service.
CAUTION: At any setpoint, the possibility of freezing exists and it is the operator’s responsibility to take necessary action to prevent freezing at all times.
NOTE: The high and low pres-
sure switches are enclosed
inside the same module.
IMPORTANT: A correct mixture of
glycol and water must be used as
process coolant for operation below
45°F {7.2°C}.
See Installation sec-
tion entitled, Filling the Chiller.
Cut-out adjustment
Cut-in adjustment
Page 65
Appendix l C-1
Water Quality Control
Insufficient or improper water treatment can damage the EarthSmart ECM Chiller. A certified water treatment specialist should be consulted for your particular application. It is the owner’s responsibility to prevent damage from foreign material or inadequate water treatment.
The two main points to consider for water treatment in chillers are:
• Corrosion
• Organism growth
Proper chemical treatment will control pH levels and algae growth.
Page 66
D-1 l Appendix
Chiller Capacity and Derate Chart
If operation of the chiller is less than 45°F {7.2°C}, a glycol and water mixture is required. See Operation section entitled, Filling the Chiller.
Ambient conditions affect air-cooled chiller operation and capacity. Standard rating is at 95°F {35°C} entering air temperature. For ambient air conditions greater than 95°F {35°C}, chiller derating will occur.
Standard chiller rating is 50°F {10°C} leaving water. For all other temperature settings, output tonnage is altered as follows:
Output Full Available % Temperature °F {°C} Capacity
60°F {15.5°C} 105%
50°F {10°C} 100% 45°F {7.2°C} 90% 40°F {4.4°C} 80% 35°F {1.6°C} 70%
30°F {-1.1°C} 60% 25°F {-3.8°C} 50% 20°F {-6.7°C} 40%
NOTE: Models must be positioned so that the condenser air inlet is no warmer than 95°F
{35°C} and the condenser air outlet is not blocked or restricted in any way.
NOTE: Locate models away from heat producing equipment. These items will affect ambi-
ent air conditions and the performance of the chiller.
NOTE: For chiller operation
below 45°F {7.2°C}, the
chiller’s control must
be
configured properly. Contact
Conair Service.
IMPORTANT: A correct mixture of
glycol and water must be used as
process coolant for operation below
45°F {7.2°C}.
See Installation sec-
tion entitled, Filling the Chiller.
Page 67
Appendix l E-1
Pressure-Temperature Chart for R-134A Refrigerant
Refrigerant Pressure (PSIG)
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
100 105 110 115 120 125 130 135 140 145 150 155 160 170 180 190 200 210 220 230
Saturated Temperature
-3
°F {-19.4°C}
7°F {-13.9°C} 15°F {-9.4°C} 22°F {-5.5°C} 29°F {-1.6°C} 35
°F {1.6°C}
40°F {4.4°C}
45°F {7.2°C} 50°F {10°C} 54°F {12.2°C} 58°F {14.4°C} 62°F {16.7°C} 66°F {18.9°C} 69°F {20.5°C} 73°F {22.7°C} 76°F {24.4°C} 79°F {26.1°C} 82°F {27.7°C} 85°F {29.4°C} 88°F {31.1°C} 90°F {32.2°C} 93°F {33.8°C} 96°F {35.5°C} 98°F {36.6°C} 100°F {37.7°C} 103°F {39.4°C} 105°F {40.5°C} 107°F {41.6°C} 109°F {42.7°C} 112°F {44.4°C} 114°F {45.5°C} 116°F {46.6°C} 120°F {48.8°C} 123°F {50.5°C} 127°F {52.7°C} 130°F {54.4°C} 134°F {56.6°C} 137°F {58.3°C} 140°F {60°C}
NOTE: These pressure/ temperature relationships are in an “At-Rest”, saturated condition. For example, if the unit has been in a warehouse at 40°F {4.4°C} and it is brought to a room where it is 80°F {26.7°C}, it may require a few hours for the unit to warm and the pressure to rise to the surrounding ambient conditions.
Page 68
F-1 l Appendix
RTD Resistance Chart
You can use the following chart to determine if you need to replace your RTD.
Page 69
Appendix l G-1
Overhead Plumbing Details
Overhead piping installations above process connections require installing a check valve in the “To Process” line and a 12 inch {305 mm} riser with a check valve and vacuum break in the “From Process” line to prevent siphoning when shutting down the chiller. Install a vent tube at 12 inches {305 mm} above the highest system point to prevent over pressurization. Maximum height of piping above process connections is 25 ft {7.6 m}.
back view
Internal vent; 1 ft above highest water level
vacuum break
check valve
12 in. riser
From process
To process
Page 70
H-1 l Appendix
Electrical Schematic
9.00
9.00
8.00
8.00
4.04
4.04
1TC
1TC
1ENC
1ENC
1CAB
1CAB
1SW
1SW
2CB
2CB
1CB
1CB
1TB
1TB
1GB
1GB
1
2
2
2
2
3
4
6
7
7
8
9
10
10
2ENC
2ENC
1TC
1TC
1SW
1SW
7.88
7.88
1PL
1PL
2PL
2PL
3PL
3PL
2CAB
2CAB
4PL
4PL
5PL
5PL
7PL
7PL
6PL
6PL
Page 71
Appendix l I-1
Control Setup
1/32 DIN Watlow SD controller Setup Sheet
Enter the following parameters
Menu Parameter Description Setting Set Up Page Sen Input sensor type RTD up & down for C-F Temperature Units (degrees) F 3 seconds S.dec Temperature Decimal Places 0
IS.en Infosense no SP.Lo Set Point Low Limit 40.0 SP.hi Set Poing High Limit 65 Ftr.e Input Filter Both Flt.r Filter value - Seconds 5 Ot1 Output 1 function heat Ctr1 Control Method 1 ftb Ftb1 Cycle time 1 10 PL 1 Power Limit 1 100% PSL1 Output Power Limit Sacle Low 1 0% PSH1 Output Power Limit Sacle High 1 90% nLF1 Output Non-Linear Function 1 Off Ot2 Output 2 Function - SP devaition dE.AL hys2 Alarm Hysteresis 2 1.5F Lgc2 Alarm relay state on alarm - open Al o Lat2 Alarm 2 latching nLat dSP2 Alarm 2 Message on ACLF AC line frequency 60 Unit Units of Measurement SI I.Err Input error latching nLat FAIL Input Error Failure Mode bPLS Man Manual Error Level 0% dSP Active Displays nor rP Ramping Mode off LOC Security Lockout 3
Programming Adv and INF keys 6 seconds
P1 Temperature Units - C-F F P2 Low Temp Dev. alarm - A2.Lo -4 P3 High Temp dev Alarm - A2.HI 20 P4 Proportional Band Hot Gas - pb.ht 3 P5 Intergral Hot Gas - It.ht 3.4 P6 Derivative - dE.ht 0.1
Page 72
Plumbing Schematic
FROM PROCESS
1
2
"
TO PROCESS
1
2
"
LEVEL
WATER
TANK
1
PSL
FS
1
EVAPORATOR
(1/4" schraeder valve)
PI
1
RANGE= 40 TO 65 °F
TAHH
1
S
TE
1
TALLTIC
11
S
TO PROCESS
TEMP
(1/4" gauge port)
TXV
FILTER/DRYER
SIGHT GLASS
NOTES:
K OR L-TYPE COPPER TUBING TO BE USED FOR REFRIGERANT PIPING1.
PRESSURE TESTING, EVACUATION AND REFRIGERANT CHARGING OF THE 2.
CHILLER SHALL BE PERFORMED PER SECTION 3 OF THE CONAIR CHILLER
TEST STAND MANUAL.
SV-2 TO BE LOCATED ABOVE COMPRESSOR DISCHARGE.3.
VAPOR CHARGING & EVACUATION VALVE ON SUCTION LINE NOT REQUIRED 4.
IF SUCTION VALVE HAS A SERVICE PORT.
1/2" FILL/DRAIN
(HOSE BIBB)
VENT 3/8"
RECEIVER
0-150 PSI GAGE
XX
X
S
DESCRIPTION
BY
DATE
APP
ECN
REV
01
WDH
09/12/07
DEW
PROTOTYPE
02
DEW
REVISED
11/27/07
DEW
±
0.015
±
1/2
°
125
±
0.015
±
1/32
XX:
FINISH:
FORMED SHEETMETAL:
ANGLES:
FRACTIONS
DECIMAL MACHINING:
The Conair Group Inc.
Pittsburgh, PA 15202
One Conair Drive
ACAD
XXX:
PORTABLE CHILLER,AIRCOOLED
SINGLE PUMP, ENHANCED
MACHINING TOLERANCES:
01
REV:
1 OF 1
SHEET:
DWG NO.:
DRAWN BY:
DATE:
ECA.5 P&ID
±
0.005
04/02/08
WJS
DXF
CONDENSER FAN
SV-1
LIQUID LINE VALVE
SV-2
HOT GAS BYPASS
SEE NOTE 3
LINE SIZE REDUCTION
PRESSURE RELIEF VALVE
Thermostatic Expansion Valve
INLINE INSTRUMENT w/ TAG NUMBER
STRAINER
SOLENOID VALVE
Hand Valve
LEGEND
BYPASS
3
8
"
CUT OUT AT
230
PSIG
ON RISE MANUAL RESET
PSV SET AT
250
PSIG
CUT OUT AT
25
PSIG ON FALL
PSIG ON RISE35
CUT IN AT
PSIG ON RISE
1
PSH
200
PSIG ON FALL125
CUT IN AT
CUT OUT AT
PSH
2
(1/4" schraeder valve)
1
4
" OD TUBE
1
4
" OD TUBE
1
4
" OD TUBE
1
4
" OD TUBE
3
8
" OD TUBE
3/8" OD TUBE
REFRIGERATION ISOLATION VALVE
PSIG
PSV SET AT
50
1
8
" FPT
3
8
"
3
8
"
3
8
"
3
8
"
3
8
"
1
4
"
1
4
"
10 GALLON
3
8
" OD TUBE
1
4
"
END OF CONDENSING UNIT
1
4
"
J-1 l Appendix
Loading...