Compu-aire SYSTEM 2200 Plus 3L, SYSTEM 2500 S User Manual

Page 1
Rev.03C 02-19-14
Page 1 of 82
Compu-Aire
SYSTEM 2200+3L
PROGRAMMABLE CONTROLLER
-USER MANUAL-
8167 Byron Road Whittier, CA 90606
Phone: (562) 945-8971 Fax: (562) 696-0724
SUBJECT TO CHANGE WITHOUT INCURRING OBLIGATION
Page 2
Rev.03C 02-19-14
Page 2 of 82
Compu-Aire
Table of Contents
1.0 INTRODUCTION ..................................................................................................................................... 8
2.0 QUICK REFERENCE GUIDE ..................................................................................................................... 8
3.0 SEQUENCE OF OPERATIONS ................................................................................................................. 9
3.1 Standard Units in General ............................................................................................................. 9
3.2 How to Turn the Unit ON .............................................................................................................. 9
3.3 Lead/Lag Redundancy – p-LAN Network ...................................................................................... 9
3.4 Air Cooled DX With Chilled Water Plus ....................................................................................... 10
3.5 Air Side Economizer .................................................................................................................... 11
3.6 Water Side Economizer Energy miser (EM) Unit Using 2-Way Valves ........................................ 11
3.7 Water Cooled Energy Miser ........................................................................................................ 13
3.8 Dry Fluid Cooler With Energymizer............................................................................................. 14
3.9 Special Pump and Dry Fluid Cooler control logic ........................................................................ 16
3.10 Optional features ........................................................................................................................ 16
4.0 CONFIGURATION ................................................................................................................................. 17
4.1 Main menu .................................................................................................................................. 17
4.2 Screen Settings ............................................................................................................................ 18
4.3 Network Configuration ............................................................................................................... 19
4.4 Network Monitor ........................................................................................................................ 19
4.5 Assigning Private and Shared terminals ...................................................................................... 20
4.6 P-LAN Setup ................................................................................................................................ 21
4.6.1 Master Unit (ID=1) .............................................................................................................. 21
4.6.2 Slave Unit (ID=2).................................................................................................................. 21
4.6.3 P-LAN WIRING ..................................................................................................................... 22
4.7 General Options .......................................................................................................................... 23
5.0 TECHNICAL SPECIFICATIONS ............................................................................................................... 24
5.1 Controller and Display ................................................................................................................. 24
5.2 General Characteristics ............................................................................................................... 24
5.3 Mechanical Characteristics ......................................................................................................... 25
5.4 Electrical Characteristics ............................................................................................................. 26
Page 3
Rev.03C 02-19-14
Page 3 of 82
Compu-Aire
5.5 Digital Inputs ............................................................................................................................... 26
5.6 Analog inputs .............................................................................................................................. 26
5.7 Analog Outputs ........................................................................................................................... 27
5.8 Digital Outputs ............................................................................................................................ 27
5.9 P-LAN Network Terminal ............................................................................................................ 27
5.10 Cable Length ............................................................................................................................... 27
5.11 Standard Input / Outputs ............................................................................................................ 28
5.12 Optional Features ....................................................................................................................... 29
5.13 Functional characteristics ........................................................................................................... 29
5.14 Building Management System .................................................................................................... 29
6.0 CONTROLLER INTERFACE .................................................................................................................... 30
6.1 LED Indicators ............................................................................................................................. 30
6.2 Navigation Buttons ..................................................................................................................... 30
7.0 Navigation Menu ................................................................................................................................. 30
7.1 Menu Tree ................................................................................................................................... 31
7.2 Accessing Submenus ................................................................................................................... 32
7.3 Main Menu Selection .................................................................................................................. 32
7.4 Unit Status ................................................................................................................................... 32
7.5 Trending ...................................................................................................................................... 34
7.5.1 Graph Overviews ................................................................................................................. 34
7.5.2 Icon Description and function ............................................................................................. 35
7.6 Alarms ......................................................................................................................................... 37
7.6.1 Alarm Viewing and Function ............................................................................................... 37
7.6.2 Alarm Reset ......................................................................................................................... 37
8.0 SETUP MENU ....................................................................................................................................... 38
8.1 Entering a password .................................................................................................................... 38
8.2 Setup Menu Tree ........................................................................................................................ 39
8.3 Setpoints ..................................................................................................................................... 40
8.3.1 Changing Setpoints ............................................................................................................. 40
8.3.2 Changing Alarm Setpoints ................................................................................................... 41
8.4 Clock Setup .................................................................................................................................. 41
Page 4
Rev.03C 02-19-14
Page 4 of 82
Compu-Aire
8.4.1 Time and Date Setup ........................................................................................................... 41
8.4.2 Night Setback ...................................................................................................................... 41
9.0 RUN TIME HOUR METERS ................................................................................................................... 42
10.0 BUILDING MANAGEMENT SYSTEM (BMS) .......................................................................................... 43
10.1 Modbus ....................................................................................................................................... 43
10.1.1 Mounting ............................................................................................................................. 43
10.2 POINTLIST .................................................................................................................................... 46
10.3 LONWORKS ................................................................................................................................. 48
10.3.1 General characteristics ....................................................................................................... 48
10.3.2 Physical channels ................................................................................................................ 48
10.3.3 Physical Circuit Board Layout .............................................................................................. 48
10.3.4 LED Color Description ......................................................................................................... 49
10.3.5 Installation .......................................................................................................................... 49
10.3.6 Connection to the PCO3 Controller .................................................................................... 50
10.3.7 Connection to the LonWorks® network .............................................................................. 50
10.3.8 Service pin ........................................................................................................................... 50
10.3.9 WINK event ......................................................................................................................... 51
10.4 BACNET OVER TCP/IP .................................................................................................................. 52
10.4.1 Installation .......................................................................................................................... 52
10.4.2 Functions ............................................................................................................................. 52
10.4.3 Default parameters ............................................................................................................. 52
10.4.4 Restarting the software ...................................................................................................... 53
10.4.5 Configuration ...................................................................................................................... 53
10.4.6 Web server .......................................................................................................................... 55
10.4.7 Accessing the operating system by authentication ............................................................ 55
10.4.8 CGI script ............................................................................................................................. 56
10.4.9 SNMP ................................................................................................................................... 56
10.4.10 BACnet............................................................................................................................. 56
10.4.11 WARNINGS ...................................................................................................................... 56
10.5 BANET over MS/TP ...................................................................................................................... 57
10.5.1 Installation .......................................................................................................................... 57
Page 5
Rev.03C 02-19-14
Page 5 of 82
Compu-Aire
10.5.2 Meaning of the jumpers ...................................................................................................... 58
10.5.3 Operation ............................................................................................................................ 58
10.5.4 Recalling the factory configuration (“factory bootswitch” mode) ..................................... 60
10.5.5 Configuration ...................................................................................................................... 60
10.5.6 BACNET Parameter Description .......................................................................................... 61
11.0 TECHNICIAN MENU ............................................................................................................................. 62
11.1 Alarm Setup................................................................................................................................. 62
11.1.1 Available Alarms .................................................................................................................. 64
11.1.2 Sensor Offset ....................................................................................................................... 66
11.1.3 Digital Input ......................................................................................................................... 66
11.2 Network Setup ............................................................................................................................ 67
11.2.1 Define a Network ................................................................................................................ 67
11.2.2 Network Assist .................................................................................................................... 67
11.3 Manual Control ........................................................................................................................... 68
12.0 FACTORY SETTING ............................................................................................................................... 69
12.1 Factory Setting Menu Tree ......................................................................................................... 69
12.1.1 Digital Inputs and Digital Outputs ....................................................................................... 70
12.1.2 HVAC ................................................................................................................................... 72
12.1.3 Analog Inputs and Analog Outputs ..................................................................................... 75
12.1.4 Changing Passwords ............................................................................................................ 77
12.2 Factory Reset .............................................................................................................................. 77
13.0 TROUBLESHOOTING GUIDE ................................................................................................................ 78
Page 6
Rev.03C 02-19-14
Page 6 of 82
Compu-Aire
Table of Figures
Figure 1– Configurations screen ................................................................................................................. 17
Figure 2 - Screen calibration ....................................................................................................................... 18
Figure 3–Changing unit ID ........................................................................................................................... 20
Figure 4 - Touch sensitive graphical display ............................................................................................... 24
Figure 5 – Controller ................................................................................................................................... 24
Figure 6 - Internal built in display ............................................................................................................... 24
Figure 7 – Graphical user interface ............................................................................................................. 30
Figure 8 - Main Menu .................................................................................................................................. 31
Figure 9 - Unit general status ......................................................................... Error! Bookmark not defined.
Figure 10 - Room demand icons .................................................................... Error! Bookmark not defined.
Figure 11- Graphical sensors representation .............................................................................................. 34
Figure 12 - Graph description ..................................................................................................................... 34
Figure 13 - Pressure graph .......................................................................................................................... 34
Figure 14– Alarm History ............................................................................... Error! Bookmark not defined.
Figure 15–Password prompt ....................................................................................................................... 38
Figure 16 - Entering a password ................................................................................................................. 39
Figure 17 - Setup menu ............................................................................................................................... 39
Figure 18 - Setup Menu Tree ...................................................................................................................... 39
Figure 19 - Room temperature setpoints ................................................................................................... 40
Figure 20 - Room humidity setpoints .......................................................................................................... 40
Figure 21 - Clock setup ................................................................................................................................ 41
Figure 22 - Component run time meters .................................................................................................... 42
Figure 23 - Building management system................................................................................................... 43
Figure 24 - Communication protocol .......................................................................................................... 43
Figure 25 - LONTalk Card ............................................................................................................................ 48
Figure 26 - Remove plastic cover ................................................................................................................ 50
Figure 27- Cut out window ......................................................................................................................... 50
Figure 28 - Installing plugin card ................................................................................................................. 50
Figure 29 - Replacing windows cover.......................................................................................................... 50
Figure 30 - PCOWeb .................................................................................................................................... 54
Figure 31 - Window cover ........................................................................................................................... 54
Figure 32 - Installing PCOWeb .................................................................................................................... 54
Figure 33 - Installing plastic cover ............................................................................................................... 54
Figure 34 - Alarm configuration .................................................................................................................. 62
Figure 35 - Alarm delays.............................................................................................................................. 64
Figure 36 -Alarm switch over ...................................................................................................................... 64
Figure 37 - Network Setup .......................................................................................................................... 67
Figure 38 - Network Assist .......................................................................................................................... 67
Figure 39 - Factory Setting .......................................................................................................................... 69
Page 7
Rev.03C 02-19-14
Page 7 of 82
Compu-Aire
Figure 40 - Digital input configuration ........................................................................................................ 70
Figure 41 - Digital output configuration ..................................................................................................... 71
Figure 42 Fan Setup .................................................................................................................................... 72
Figure 43 Sensor Setup ............................................................................................................................... 72
Figure 44 Compressor Setup ....................................................................................................................... 72
Figure 45 Compressor Option ..................................................................................................................... 72
Figure 46 Compressor Stage ON/OFF ......................................................................................................... 73
Figure 47 Low Pressure Retry ..................................................................................................................... 73
Figure 48 Humidifier ................................................................................................................................... 73
Figure 49 Humidity Lockout ........................................................................................................................ 73
Figure 50 Heater Setup ............................................................................................................................... 73
Figure 51 Heating Demand ......................................................................................................................... 73
Figure 52 - Analog input configuration ....................................................................................................... 75
Figure 53 - Analog output configuration ..................................................................................................... 76
Figure 54 - Changing default password....................................................................................................... 77
Figure 55 - Factory reset / Set Unit Mode .................................................................................................. 77
Page 8
Rev.03C 02-19-14
Page 8 of 82
Compu-Aire

1.0 INTRODUCTION

The System 2200+3L is a programmable controller based on a double microprocessor, designed for precise "Smart" control of an air conditioning system. The System 2200+3L is made up of a microprocessor based MAIN BOARD equipped with a set of terminals used to interface the microcontroller board to the controlled devices; such compressors, fans, heaters, humidifiers, and valves. The program is retained in a flash based memory and configuration parameters are permanently stored (even in the case of a power failure) in a non-volatile memory.
The System 2200+3L also includes a microprocessor based TERMINAL unit complete with graphical touch screen display with built in navigation keypad and led indicators allowing the users to easily set the controlled parameters for set points, dead bands, alarm thresholds, and carry out the main working operations (on/off, displaying controlled variables, printouts). The controller and graphical display terminal are powered by 24VAC power supply using low voltage control transformers from the unit. Connection between the terminal unit and main board is necessary only when programming the System 2200+3L basic parameters. The controller is linked to a graphic display terminal via standard three wire cable.

2.0 QUICK REFERENCE GUIDE

The controller is fully programmed and pre-configured per system configuration. Further
tweaking may be required to better fit the application.
For remote mounted controllers, make sure the UNIT ID is matching with the Tag ID
number.
Page 9
Rev.03C 02-19-14
Page 9 of 82
Compu-Aire

3.0 SEQUENCE OF OPERATIONS

3.1 Standard Units in General

In general, the controller is operated as follows. Note that the followings are applicable while the controller is in active mode and only apply to DX and Chilled Water units.
Fan starts up on demand for cooling, heating, humidifying or dehumidifying, or operates
continuously
Sequences the compressors on in stages with programmable delays to meet demand for
cooling and dehumidification
Sequences the heaters on in stages with programmable delays to meet demand for heating
or reheat during dehumidification mode
Activates the humidifier as needed to meet the humidity demand
Dehumidification is achieved by means of cooling to reduce the humidity level. During the
dehumidification process, if the temperature falls below the room set point, heating is brought on to reheat the air and maintain room temperature.
The controller monitors the complete system for any sensors, fans, compressors, heaters
and humidifier failure. Upon critical failures, the complete system will shut down with alarm. For certain component failures, the applicable feature is disabled to insure safe operation. For example, when compressor failure occurs, the failed compressor shall be locked out but the system shall provide cooling by other compressor if available. On a heater failure, the heaters are locked out. The system will not use that function until manually reset on the display. The controller also keeps the history of last 100 alarms after you reset them.

3.2 How to Turn the Unit ON

Press the Power button ON/OFF key once to turn it ON and press it again to turn it OFF The System Status screen should indicate the current system operating mode Default time delay is 30 seconds to avoid short cycling Unit will automatically control the necessary mode of operation to maintain room setpoints

3.3 Lead/Lag Redundancy – p-LAN Network

System 2200+ series controllers can be set for n+ redundancy setup. A maximum of 16 units can be linked together on the p-LAN network. The p-LAN networked units are identified with unit ID numbers. The p-LAN software resides in the unit ID# U01 which is also called as a MASTER unit. All the other units on that network are considered as SLAVE units. Each controller is self-dependent with necessary sensors and it can be used as a stand-alone unit. When used on the p-LAN Network, each unit must have the same software revision and set to maintain the same set points and safety alarms. The unit U01 must be set for the total units on the network.
When more than one unit are connected through p-LAN network for lead/lag operation, the first controller, unit ID# U01 is defined as the “Master” and the rest (U02, U03 ….U16) are define as
Page 10
Rev.03C 02-19-14
Page 10 of 82
Compu-Aire
“Slave”. The Master always starts first to maintain the temperature and humidity set points. The Slave is kept on standby as long as the Master is able to achieve the set points within the dead band. When the Master fails to do so, it calls in the Slave to assist. Then both units will be running towards the targets set on the Master (set points on the Slave is irrelevant in this situation). The Slave drops out when set points are achieved. When the Master fails by any of the selectable failures (such as compressor high/low pressure failure and fire alarm), the Master drops off and the Slave comes in to work independently according to its own set points until the Master is recovered. When the system is reset and restarted, the Master comes in first and follows the above rules.
The units can be set to cycle to achieve equal run time on each unit. At the end of each cycle, the role of each unit switches to its counterpart, meaning the Master becomes the Slave and the Slave becomes the Master during the next cycle. During each cycle, the units operate according to the above lead/lag logic.

3.4 Air Cooled DX With Chilled Water Plus

Summary of Equipment
The primary system shall be Chilled Water Cooling. Direct Expansion Cooling shall be setup as a back up to the Chilled Water system. Both systems are designed to work independent of each other.
The Chilled Water System comes standard with a three (3) way water modulating valve, coil, and an optional “no water flow switch. The DX system is equipped with a DX coil, compressor(s), and outdoor air cooled condenser. Optional heaters and humidifiers are also available if needed.
A unique feature of Air Cooled/Chilled Water Plus units is that the chilled water coil is located at the side of the direct expansion coil. The auxiliary chilled water coil is custom sized so that it provides identical cooling capacity obtained during the refrigeration cycle with the compressor operating.
Cooling-Chilled Water
Chilled Water cooling is the primary cooling system for C+ units. For optimum performance, the controller is programmed to call chilled water cooling for the first 300 seconds regardless of the chilled water temperature.
The C+ unit can switch over from one cooling mode to another based on sensing Chilled Water flow or Chilled Water temperature. The standard practice is to sense the Chilled Water flow for switching.
If No Water flow switch is selected, the unit senses the flow of chilled water by using a pressure differential switch and switches over to DX cooling based on loss of water flow. When no water flow switch is selected for switch over, the unit will only work on either DX or C.W. cooling mode.
Page 11
Rev.03C 02-19-14
Page 11 of 82
Compu-Aire
If chilled water supply temperature is selected for switch over, than the unit shall continue with chilled water cooling if the chilled water supply temperature is below the required temperature set point and switch over to the DX cooling.
Cooling-Direct Expansion
Direct Expansion Cooling is designed to operate when the water flow switch senses that there is no water flow. A digital signal is sent to the system from the controller to modulate the three (3) way valve to cut water flow to the chilled water coil and the backup system direct expansion cooling should start. The controller signals the compressor to start cooling. The outdoor condenser gets energized as needed.

3.5 Air Side Economizer

Summary of Equipment
The Economizer Mixing Box is factory provided; however, it might be installed in the field by others. Typically, the Air Side Economizer Mixing Box is provided for our Maxi-Kool unit with System 2200 series controller.
Sequence of Operation
The evaporator fan and a set of dampers for the economizers are energized depending on heating or cooling demands. The PCO3 controller commands the economizer box to bring either the minimum amount of outside air or only outside air based on outside air temperature and humidity. The controller determines whether the outdoor air temperature and humidity is suitable for “economizer-cooling”. If the outdoor air is suitable, mechanical cooling shall be locked out by the outdoor enthalpy control. The set of economizer damper actuators shall be energized, operating the outdoor air and the return air dampers. The economizer damper actuators shall be regulated to maintain proper discharge air temperature. When outdoor air is not suitable for “economizer-cooling”, the Economizer shall be locked out and the outdoor air damper shall maintain minimum position while the indoor fan is operating. Upon unit shutting down or power loss, the spring return motor actuator shall close the outdoor air damper. The Economizer shall be automatically locked out during the heat mode (if applicable).
The Air Side Economizer box shall include: prewired modulating spring return damper actuators, economizer control logic with compressor assist option, minimum outside air damper position control, economizer control sensors including outdoor air temperature and humidity (enthalpy) sensor, supply air and/or mixed air sensors. The supply air temperature sensor is used to maintain the desire supply air temperature using DX and Economizer cooling together. The exhaust of room air during economizer cooling mode shall be done by others in the field.

3.6 Water Side Economizer Energy miser (EM) Unit Using 2-Way Valves

Summary of Equipment
Energy miser units are provided with Dual Cooling options. DX cooling using Compressor based system and Economizer cooling using Water Side Economizer Coil.
Page 12
Rev.03C 02-19-14
Page 12 of 82
Compu-Aire
The primary system shall be Direct Expansion Cooling. The free cooling Energy miser coil is provided together with the DX cooling coil. If the Water temperature drops below the Energy miser set point, the condenser water is diverted to the free cooling coil and DX cooling will be programmed to either turned off or made available to assist based on demand.
The Energy miser System shall be provided with a Two (2) way water regulating valve for condenser coil, a Two (2) way modulating chilled water valve for energy miser coil, DX coil(s), compressor(s) and co-axial water condenser(s). The water valves on water cooled condensers and free cooling energy miser CW Valves will allow the water flow in either condenser coil or free cooling EM coil. The two way control valve shall control the amount of flow to auxiliary energy miser cooling coils to meet the demand when in EM cooling mode. The Two way water regulating valve will control the amount of water flow in condenser based on the refrigerant pressure in DX cooling mode. System shall be programmed to do either DX cooling or EM cooling based on entering water temperature.
Energy miser systems are connected to Cooling Tower or Dry Fluid Coolers to obtain re-circulating water or water glycol solution. In addition, the system is equipped with steam generating humidifier, electric reheat and microprocessor based controller.
A unique feature of Energy miser system is that the free cooling water coil is located just before the direct expansion coil and is properly sized to provide the same cooling capacity as the DX system at 45 Deg. F entering water temperature. The indoor unit will send a signal to enable and disable the outdoor auxiliary equipment. The outdoor equipment has its own control logic to provide water temperature suitable for either EM mode or DX cooling mode.
Cooling-Direct Expansion
Direct Expansion Cooling shall operate when the water temperature increases above the specified EM set point. A digital signal is sent to the system by microprocessor to signal the compressors and the two (2) way valves will regulate the water flow into the water cooled condensers based on the refrigerant pressure. Each compressor system shall have separate 2-Way water regulating valves. The Energy miser mode depends on the entering water temperature and it is adjustable.
Cooling-Energy miser Mode
The unit can switch over from DX cooling mode to Free cooling Energy miser mode based on the Entering Water temperature.
Unit shall start in DX cooling mode. If the temperature of water supply drops below the set point for the Energy miser mode, the unit will switch over to the Energy miser free cooling mode. The outdoor fluid cooler shall be provided with energy miser control panel to maintain lower fluid temperature during energy miser mode.
In the free cooling energy miser mode the compressors will remain shut off while the fans of the unit shall be on. Humidification and Dehumidification modes shall be operating as needed.
Page 13
Rev.03C 02-19-14
Page 13 of 82
Compu-Aire

3.7 Water Cooled Energy Miser

Note: Continuous water shall be flowing through the chilled water valve and will only supply
water to coil when called upon.
Summary of Equipment
Energy miser units are provided with Dual Cooling options. DX cooling using Compressor based system and Economizer cooling using Water Side Economizer Coil.
The primary system shall be Direct Expansion Cooling. The free cooling Energy miser coil is provided together with the DX cooling coil. If the Water temperature drops below the Energy miser set point, the condenser water is diverted to the free cooling coil and DX cooling will be programmed to either turned off or made available to assist based on demand.
The Energy miser System shall come standard with a three (3) way water regulating valve for condenser coil, a three (3) way modulating chilled water valve for energy miser coil, DX coil(s), compressor(s) and co-axial water condenser(s). The water valves on water cooled condensers and free cooling energy miser CW Valves are Three Way mixing type designed to divert the flow in either condenser coil or free cooling EM coil. Three (3) way is used to maintain pressure drop, as constant GPM is required for free cooling systems. The (3) three way control valve shall control the amount of flow to auxiliary energy miser cooling coils and maintain constant temperature and relative humidity
Energy miser systems are connected to Cooling Tower or Dry Fluid Coolers to obtain re-circulating water or water glycol solution. In addition, the system is equipped with steam generating humidifier, electric reheat and microprocessor based controller.
A unique feature of Energy miser system is that the free cooling water coil is located just before the direct expansion coil and is properly sized to provide the same cooling capacity as the DX system at 45°F entering water temperature.
Cooling-Direct Expansion
Direct Expansion Cooling shall operate when the water temperature increases above the specified set point. A digital signal is sent to the system by microprocessor to signal the three (3) way valve to divert the water flow from the free cooling coil to the water cooled condensers and the direct expansion cooling mode shall start. The microprocessor shall signal the compressor to start cooling and at the same time energize the water regulating valve to supply water flow to the co­axial condenser. The Energy miser mode depends on the entering water temperature and it is adjustable.
Cooling-Energy miser Mode
The unit can switch over from DX cooling mode to Free cooling Energy miser mode based on the Entering Water temperature.
Page 14
Rev.03C 02-19-14
Page 14 of 82
Compu-Aire
Unit shall start in DX cooling mode. If the temperature of water supply drops below the set point for the Energy miser mode, the unit will switch over to the Energy miser free cooling mode. The controller will send signal to the auxiliary equipment to run Energy miser mode for fluid temperature control. The outdoor fluid cooler shall be provided with energy miser control panel to maintain lower fluid temperature during energy miser mode.
In the free cooling energy miser mode the compressors may shut off while the fans of the unit shall be on. Humidification and Dehumidification modes shall be operating as needed. The Compressors can be locked to remain off during energy miser mode if necessary.

3.8 Dry Fluid Cooler With Energymizer

Summary of Equipment
DRY FLUID COOLER (DFC): The Dry Fluid Cooler Shall Consist of Casing, Coil, Direct-drive Propeller Fan(s) driven by individual Fan Motor(s), Fan Guard and Mounting Legs. All fan motors shall be factory wired to a common electrical control box. The Dry Fluid Cooler shall be arranged for Vertical Air Flow.
The Glycol Coil shall have aluminum fins bonded to copper tubes and shall have full collars that completely cover the copper tubes. The coil shall be pressure tested to 350 psig and shall be designed for counter flow for high heat transfer efficiency.
The Dry Fluid Cooler casing shall be made from a non-corrosive metal to minimize maintenance. Adjustable mounting legs and supports shall be furnished with the DFC. Vibration isolators of the rubber and shear or spring type are to be field provided by others. The motors shall be permanently lubricated, sealed ball bearings, with inherent overload protection. Motors shall be mounted inside the Dry Fluid Cooler Casing for weather protection. The direct drive fan blades shall be aluminum, and shall be protected by a heavy gauge, steel wire, zinc plated, and epoxy coated fan guard. Full width baffles to prevent bypass air shall separate each fan section.
Dry Fluid Cooler (DFC) requires separate power supply and one set of dry contact from indoor unit to Enable/Disable.
DFC is equipped with its own control panel that includes power block, fan contactors, aqua stats, freeze stats, relays and single or dual pump package control as necessary. Aqua stats are installed in the control panel and bulbs to be attached with leaving water header of the coil. For understanding purpose use 4 fan dry fluid cooler with drawing # 700-232-041 The fluid cooler shall be provided with ambient T-stats to control the water temperature during DX cooling mode. The fluid cooler shall bypass the T-Stat control logic and run all fans continuously during Energy Miser mode.
Condenser cooling mode
Page 15
Rev.03C 02-19-14
Page 15 of 82
Compu-Aire
If the water temperature is above 50Deg. F. (Default setting) the DFC will be in normal condenser cooling mode. Aqua stat # 1 will be open above 50 Deg. F. In normal cooling mode, DFC will be enabled by either of the compressor from indoor unit. The Freeze stat is installed in series of the enabling signal. If the freeze stat opens, the DFC unit will be fully disabled.
1. The first fan of DFC runs continuously as long as enabling signal is present.
2. The default setting for second fan to cycle OFF is 60 Deg. F and below with aqua
stat
3. The default setting for third fan to cycle OFF is 70 Deg. F. and below with aqua
stat #
4. The default setting for forth fan to cycle OFF is 75 Deg. F. and below with aqua
stat #
5. All these default settings are field adjustable to fine tune the unit operation.
Energy miser cooling mode
During winter months, when water temperature drops bellow the 50Deg. F. the aqua stat # 1 will close and DFC unit will switch over to free cooling energy miser mode. In Energy miser mode, all other aqua stat (aqua stat 2, 3 and 4) will be bypassed and all fans will run continuously. The free cooling temperature set point on Aqua stat # 1 must synchronize with Energy miser water temperature set point for indoor unit.
Pumps
Summary of Equipment
PUMP PACKAGE: The pump package shall include a close coupled, industrial duty pump with heavy-duty ball bearings motors, stainless steel shafts and bronze fitted construction. The pump package shall include pump starter, aqua-stats, and fan cycling contactor(s) to control the condenser glycol temperature. The control panel shall be factory provided for filed installation in a weatherproof box provided on the Dry Fluid Cooler. The pump shall be protected with a base and weather shield from the ambient conditions.
DUAL PUMP PACKAGE (Optional): The dual pump package shall include close-coupled, industrial duty pumps with heavy-duty ball bearings motors, stainless steel shafts and bronze fitted construction. The pump package shall include pump starters, aqua-stats, and fan cycling contactor(s) to control the condenser glycol temperature. The control panel shall be factory provided for filed installation in a weatherproof box provided on the Dry Fluid Cooler. The pumps shall be protected with a base and complete vented weather enclosure from the ambient conditions. The optional Pressure Differential (No Water Flow)Switch shall be provided for field installation.
GLYCOL PUMP: A matching centrifugal circulating pump is provided for field mounting and piping.
Pump Operation
Page 16
Rev.03C 02-19-14
Page 16 of 82
Compu-Aire
When compressor is on the pump and fluid cooler will be enabled. Note that this is in DX cooling. In free cooling the logic is the same, as pumps is enabled with economizer cooling.

3.9 Special Pump and Dry Fluid Cooler control logic

Pump speed adjusted based on differential pressure across pumps as 2-way control valves modulate.
Dry cooler and Pump controller Sequence of operation
Free cooling mode
Either outdoor air temperature is monitored or a signal from each crac unit (free cooling and DX condenser) is sent to the pump controller to determine which function is provided.
Fan speed may be increased sufficiently to allow pump minimum operating speed to be maintained should zone loads decrease, thus decreasing flow below safe pump operation.
Outside air temperature reaches 48F
Pump controls switch to free cooling mode – Fans run 100% until condenser outlet temperature reaches 38F, at which time fans speed will reduce to maintain 38F or minimum pumps speed is reached, then fans will reduce speed to maintain minimum pump speed, which is accomplished by 2-way valves modulating open is response to increased condenser water supply temperature.
Controls shall monitor both fan KW and Pump KW energy consumption and determine best speed combination to maintain lowest condenser supply water temperature during free cooling more.
DX Cooling mode
Outside air temperature 50F
Pump control increases fan speed as condenser water temperature increases. Maintain 65F condenser outlet water by modulating fan speed. At 75F exiting condenser water temperature fan speed is 100%.
Controls shall monitor both fan KW and Pump KW energy consumption and determine best speed combination to maintain lowest condenser supply water temperature during DX cooling more.

3.10 Optional features

Discharge air temperature sensor to prevent overheating or cooling of the air stream
Outside air temperature sensor for automatic temperature adjustment or economizer
action
Free-cooling temperature sensor for water cooled systems
Hot gas bypass either by solenoid or by modulating electronic valve
Page 17
Rev.03C 02-19-14
Page 17 of 82
Compu-Aire
Redundant system operation of two or more units with automatic crossover and
compensation
Networking to a central command computer, or to an existing building automation system
The System 2200+3L is truly one of the most powerful and flexible controllers available for HVAC units today.

4.0 CONFIGURATION

The display unit is pre-configured at the factory for the most common user requirements. Nonetheless, some settings can be changed to adapt the device specific needs. The menus can be accessed by pressing any point on the touch screen together with the (up) and (Prg) buttons for at least one second. Alternatively, press the (up) + (down) + (enter) buttons together for at least one second.
The following operations exit the menu.
1. Pressing the Esc button
2. Automatically 1 minute after a button was pressed or the touch screen touched
3. Pressing the “X” symbol when displayed at the top right
As shown in the Figure 1 in the “Configuration screen”, a combination navigating buttons and touch screen can be used to input new configuration parameters.
To access an item, simply press the touch screen on the corresponding indication, or
press the (up) / (down) buttons until selecting it and then confirm by pressing (enter).
To modify the value of a field, after having activated it (a field is active when the cursor
is flashing inside), press the (up) / (down) buttons to change the value and press (enter) to save it.
Pressing Esc before the Enter key will cancel the modifications made to the field.
Figure 1– Configurations screen

4.1 Main menu

The main menu is used to select the three main configuration categories
Screen Settings: Settings relating to the screen
Network Configuration: Settings relating to the RS485 network
General Options: Various settings
Page 18
Rev.03C 02-19-14
Page 18 of 82
Compu-Aire

4.2 Screen Settings

The following options are available
Contrast - Used to set the contrast of the display (from 0 to 100, default: 50)
Normal Brightness After - Used to set the time after the touch screen or the buttons are
last pressed that the display switches from “high brightness” to “normal brightness”.
Possible values are ranged from 30 s to 15 min, default: 1 min
Screen Saver Timeout - Used to set the time after the touch screen or the buttons are last
pressed that the display switches off
After having switched to “normal brightness”. Possible values are range from 30 s to 4
hours (4 hrs.), default: 15 min;
Calibrate Touch Screen - The touch screen can be calibrated if it is evidently misaligned. To
align the touch screen, press the center of the crosses displayed in sequence. When the message “Done: touch the screen to ESC” indicates that the operation has been completed successfully. If the screen displays “Bad: touch to ESC and repeat”, repeat the calibration process.
Figure 2 - Screen calibration
Page 19
Rev.03C 02-19-14
Page 19 of 82
Compu-Aire

4.3 Network Configuration

Icon
Description
pCO controller active in the network
Any type of terminal active in the network
Current terminal
Device not connected
The following options are available under network configuration screen.
Terminal Address - Used to set the address of the terminal (from 1 to 32, default: 32). If
the value “--” is set (two dashes are displayed), the terminal will communicate with the pCO board using the “Point-Point” protocol (not pLAN) : the “Baud Rate”,
Network Monitor and Setup I/O Board fields will then disappear, as they have no
meaning.
Baud Rate - Used to set the pLAN communication baud rate. The possible values are 62500
(default) or 115200 (used only if all the devices in the network are configured for this speed). Note that not all the pLAN devices support the 115200 setting.
Network Monitor - This is used to display the status of the network (see next paragraph)
Setup I/O Board / Setup- These fields are used to modify the list of terminals associated
with each individual pCO board, as described in paragraph “pCO: Assigning the list of private unit ID number.

4.4 Network Monitor

This screen is used to display the status of the network, indicating graphically which devices are connected for each address. The meanings of the symbols are the following.
If activity is detected on the network, the message “Online” is displayed. Press the Esc button to exit the screen.
Page 20
Rev.03C 02-19-14
Page 20 of 82
Compu-Aire

4.5 Assigning Private and Shared terminals

The list of terminals associated with each individual controller board can be modified from the Network Configuration” menu as follows.
1. Select the address of the required board using the (up) / (down) buttons in the “Setup I/O
Board” field (only the boards that are effectively on-line can be selected) and confirm by pressing (enter). If the pLAN network is not working correctly, or no controller board is present, the field is not modifiable, and “--“(two dashes) will be displayed.
2. Press the “Setup” button: the screens will be displayed in sequence, see Figure 3 for detail.
3. Use the enter button to move the cursor from one field to the next, and (up) / (down)
change the value of the current field. The P:xx field shows the address of the selected board (in the example, board number 12 has been selected).
4. To exit the configuration procedure and save the data, select the “OK?” field, set “Yes” and
confirm by pressing (enter). Alternatively, if the terminal remains inactive (no button is pressed) for more than 30 s, the configuration procedure is automatically ended without saving the changes.
Important: the pGD terminals cannot be configured as “Sp” (shared printer) as the printer output is not featured. Selecting this mode has no effect on the management of printed messages sent via pLAN.
Figure 3–Changing unit ID
Page 21
Rev.03C 02-19-14
Page 21 of 82
Compu-Aire

4.6 P-LAN Setup

Note: For unit 3 and up, use SLAVE UNIT setup instructions and increase the Address ID by 1 and terminal ID by 1.

4.6.1 Master Unit (ID=1)

1. Turn the power off
2. Verify the connection between the PCO3 Controller and the PGD3 (graphical display).
3. Turn the power on
4. Hold down the Up + Enter + Down buttons
5. Select Network configuration
6. Set Terminal Address = 0
7. Turn the power OFF
8. Turn the power ON and immediately hold down the Up + Alarm buttons(about 10 seconds)
9. Release the buttons when you see “Self-test” screen
10. Use the Up/Down button to set the ID=1 then press enter. The screen may look like a fault
occurred but, this is normal.
11. Turn the power OFF
12. Turn the power ON and immediately press Up + Enter + Down buttons
13. Select Network Configuration
14. Set the Terminal Address=17 and press ENTER
15. Select Setup for I/O board
16. Follow on screen direction to complete the setting.

4.6.2 Slave Unit (ID=2)

1. Turn the power OFF
2. Verify the connection between the PCO3 Controller and the PGD3 (graphical display).
3. Turn the power ON
4. Hold down the Up + Enter + Down buttons
5. Select Network configuration
6. Set Terminal Address = 0
7. Turn the power off
8. Turn the power ON and immediately hold down the Up + Alarm buttons(about 10 seconds)
9. Release the buttons when you see “Self-test” screen
10. Use the Up/Down button to set the ID=2 then press enter. The screen may look like a fault
occurred but, this is normal.
11. Turn the power OFF
12. Turn on the power and immediately press Up+Enter+Down buttons
13. Select Network Configuration
14. Set the Terminal Address=18
15. Select Setup for I/O board
16. Follow on screen direction to complete the setting.
Page 22
Rev.03C 02-19-14
Page 22 of 82
Compu-Aire

4.6.3 P-LAN WIRING

Page 23
Rev.03C 02-19-14
Page 23 of 82
Compu-Aire

4.7 General Options

The following options are available
Beep Volume: Used to set the volume associated to the buttons and the touch screen
pressing. The possible values are “off”, “low”, “high”. Default: high. This parameter has no
effect on the alarm signal, which is activated or deactivated by the pCO;
• Beep On: Used to set when the “Beep” sounds. The possible values are: “active items”
(associates a sound with the active area of the display), “screen” (associates a sound with any point on the touch screen) and “screen & keys” (associates a sound with both the touch
screen and the keypad). Default: “screen & keys”;
• Download Bar: activates (“yes”) or deactivates (“no”) the display of the status bar that
indicates the progress of the page. Default: “yes”;
Clear Cache Memory: deletes the cache memory used to accelerate the display of the
screens. This function may be useful if there are errors in the graphics. Pressing the button
displays a window that prompts for confirmation. Press “yes” to confirm the operation or “no” to abort it;
Display Firmware Update: starts the pGD firmware update procedure, as described in the
next paragraph.
Page 24
Rev.03C 02-19-14
Page 24 of 82
Compu-Aire

5.0 TECHNICAL SPECIFICATIONS

Figure 4 - Touch sensitive graphical display
Figure 5 – Controller Figure 6 - Internal built in display

5.1 Controller and Display

5.2 General Characteristics

PCO3 is a microprocessor-based electronic controller developed in compliance with the European RoHS standards. It provides a solution for many applications in the air-conditioning and refrigeration sectors ensuring absolute versatility, allowing specific products to be created to customer request. PCO3 runs the control program, and is fitted with the set of terminals required
for connection to the devices (compressors, fans…). The program and the parameters are saved to
FLASH-MEMORY and E2promfor safe keeping even in the event of power failures (without requiring a backup battery). PCO3 also allows connection to the pLAN (pCO Local Area Network) and can be connected, as well as to other pCO3 controllers. All the controllers in the pLAN can exchange information (variables, digital or analogue, depending on the application software used) at high transmission speed. Up to 32 units can be connected, including pCO controllers and terminals, so as to share the information effectively. The connection to the supervisor serial line, via the CAREL or Modbus™ communication protocol over the RS485 standard, is performed by inserting an optional serial board in the pCO3. Other optional cards can be used to connect to a supervisor via standards other than RS485. Finally, the serial field bus interface, using the optional board, ensures connection to the field devices controlled.
Page 25
Rev.03C 02-19-14
Page 25 of 82
Compu-Aire

5.3 Mechanical Characteristics

Dimension:
110x315x60mm
Installation:
DIN rail according to DIN 43880 and CEI EN 50022 standards
Materials:
Techno polymers
Flame Retardant:
V0 (UL94) and 960°C (IEC 695)
Ball Pressure Test:
125°C
Resistance to creeping current:
≥250 V Color:
Grey RAL7035
Page 26
Rev.03C 02-19-14
Page 26 of 82
Compu-Aire

5.4 Electrical Characteristics

Power Supply
24VAC 50/60Hz P=40 VA
Terminal Block
Plug-in male/female connectors, max voltage 250 Vac; cable cross-section: min. 0.5 mm2 - max 2.5 mm2
CPU
H8S2320, 16 bit, 24 MHz
Memory
2+2 MB
Clock
Built in with battery backup
I/O
18
Classification Circuits
Category I (J5, J7, J20) 24 Vac/Vdc, Category III (J8, J19) 230 Vac
Note: Separate as much as possible the probe and digital input signal cables from the cables carrying the inductive loads and the power cables, to avoid possible Electromagnetic disturbance.
A/D conversion
10 bit
Type
Universal: (inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor (-
50T90°C; R/T 10 kΩ at 25°C), HT NTC 0T150°C, voltage: 0 to 1 Vdc, 0 to 5 V
ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4 to 20 mA, selectable via software. Input resistance in 0 to 20 mA= 100Ω passive: (inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal type), PT1000 (-100T200°C; R/T 1000 Ω at 0°C) or voltage-free digital input (5 mA), selectable via software
Delay
0.5s
Precision
± 0.3 % of full scale

5.5 Digital Inputs

WARNING:
230 Vac 50/60 Hz (10/-15%) Two 230/24Vac inputs present on J8 and J12 have the same common pole and
consequently will be both 24 Vac/Vdc or both 230 Vac. Basic insulation between the two inputs for DC inputs, connect the negative pole to the common terminal.

5.6 Analog inputs

WARNING: The 21VDC available at the +Vdc terminal (J2) can be used to power any active probes, the maximum current is 150 mA, thermally protected against short-circuits. To supply the ratiometric 0 to 5 V probes, use the +5VREF (Imax: 60 mA) present at terminal J24.
Page 27
Rev.03C 02-19-14
Page 27 of 82
Compu-Aire

5.7 Analog Outputs

Number I/O
6
Type
0-10V
Resolution
8bit
Max load
8 ohm
Precision
± 2 % of end scale on outputs: Y1, Y2, Y3 and Y4
-2%/+5% of end scale on: Y5 and Y6
Type
Relay
Max I/O
18
Type
RS485 half duplex asynchronous
Speed
62.5kbps or 115.2kbps
Terminal
6-pin telephone (J10)
P-LAN
3-pin plugin (J11)
Cable Type
Power Supply Distance
Power Supply
Telephone
50m
150mA from PCO3
AWG24 shielded cable
200m
150mA from PCO3
AWG20/22 shielded cable
500m
Separate power via TCONN6J000
Note:
A maximum of one terminal (pCOT, pCOI, pGD0, pGD1) can be connected, or two
terminals but without using use the backlighting on display. One version of the pCO3 features optically-isolated connection to the pLAN network.
The graphic terminal and aria terminal should be always powered with a separate
power supply.
The 21VDC present at +Vterm (J24) can be used to power an external terminal
with a maximum input of 2 W. Only one terminal can be connected (for example PLD terminal or ARIA terminal) in addition to the one connected to terminal J10.

5.8 Digital Outputs

5.9 P-LAN Network Terminal

5.10 Cable Length

The maximum cable length between the two PCO3 controllers using AWG20/22 shielded cable is 500 meters.
Page 28
Rev.03C 02-19-14
Page 28 of 82
Compu-Aire

5.11 Standard Input / Outputs

The following table defines standard I/O ports for the PCO3 controller. Refer to the electrical wiring diagram for actual wiring.
Page 29
Rev.03C 02-19-14
Page 29 of 82
Compu-Aire

5.12 Optional Features

Option
Function
RS-485 CARD Protocol: MODBUS
PCO-WEB CARD Protocol: BACNET, SNMP,HTTP,FTP,TCP/IP
PCO-NET Protocol: BACNET MS/TP
LONCARD Protocol: LONWORKS

5.13 Functional characteristics

Multiple controllers may be used to combine cooling units into a p-LAN network that operates as a single entity, enhancing the already-high performance and efficiency of units.
PCO3 controller is available as a factory-installed assembly. Remote console box with graphic touch sensitive display wall-mount version is available for remote operation and monitoring of cooling units.
Supported Protocol: pLAN protocol, “Point-Point” protocol with up to 32 nodes Backlighting Level: Two levels of brightness, “high” and “normal”

5.14 Building Management System

BMS Protocol: LONWorks
BACnet over TCP/IP BACnet over MS/TP Modbus over RS-485
Page 30
Rev.03C 02-19-14
Page 30 of 82
Compu-Aire

6.0 CONTROLLER INTERFACE

LED Light
Function
Alarm LED (Red)
ON: Pending alarm events. Press alarm button to view active alarms. OFF: No alarm
Power LED (Green)
ON: System is active. OFF: System is off Blinking: Display is off in power saving mode. System still operates normally
Fan LED (Yellow)
ON: Fan is active OFF: Fan is off
Key Name
Function
Display
Touch sensitive graphical interface
Up
Navigate up to previous entry
Down
Navigate down to next entry
Enter
Execute current selection
Power
Turn the unit ON/OFF
Alarm
View and Reset active alarms
Program
View Setup Menu
Escape
Exit and return to previous screen
Power LED
Fan LED
System ON
Version
Touch Screen
Physical Buttons
Figure 7 – Graphical user interface

6.1 LED Indicators

6.2 Navigation Buttons

7.0 Navigation Menu

Table 1- LED indicators
Table 2 - Navigating buttons
Page 31
Rev.03C 02-19-14
Page 31 of 82
Compu-Aire

7.1 Menu Tree

Main Menu
Status
Trending
Alarms
Setup
Room
Temperature
Room Humidity Compressors Heaters ON/OFF Status Fan Status Water in
Temperature
Discharge Air
Temperature
High Pressures Low Pressures Pressure
Transducers
Room
Temperature
Room Humidity Compressor
pressures from transducers
No Air Flow Dirty Filter Fire Alarm Global Alarm No Water Flow Condensate Low Pressure High Pressure Compressor
Short Cycling
Heater over heat Sensor Failures Over/Under
Temperatures
Over/Under
Humidity
Alarm Reset
Setpoints Clock Run Time BMS Technician Factory Alarm Log Exit
Scroll Up
Enter
Scroll Down
ON/OFF
Alarms
Setup Menu
Exit
Figure 8 - Main Menu
Page 32
Rev.03C 02-19-14
Page 32 of 82
Compu-Aire

7.2 Accessing Submenus

Note: Viewing settings require a password
Level 1 Password = 1 Leve2 Password = 2 Factory Setting = 1798
Icon
Function
Status
Displays current temperature, humidity, and system demands, and current operation
Trending
Graphical display of current/past status reading for temperature and humidity
Alarms
Display or Reset current/previous alarms
Setup
Unit setup
Return Air Humidity
p-LAN ID
Setpoint
Cooling Demand
Cooling Stages
Unit Mode
Supply Air Temperature
Heating Stages
Icon Descriptions
Menu Navigation
EC Fan Speed
C.W Valve Position
While viewing the menu, use the up and down arrow keys to scroll through the icons page-by­page. To scroll through the icons one-by-one, press the enter key then use the up and down arrow keys.

7.3 Main Menu Selection

Table 3 - Main menu description for Figure 7

7.4 Unit Status

Figure 9 - DX Based System Status
Figure 10 - Chilled Water System Status
Page 33
Rev.03C 02-19-14
Page 33 of 82
Compu-Aire
Figure 11 - Dew Point System Status
Icon
Function
Demands
Displays Fan, cooling, heating, humidification, dehumidification, excess humidity draining, and humidifier
Cooling
Displays current active cooling stages
Heating
Displays current active heating stages
Dew Point Setpoint
Return Air Dew Point
Return Air Temperature
Supply Air Temperature
General unit status shows the current room temperature, humidity, heating, and cooling
demands. Additional sensors are listed by pressing the (up ) or (down ) buttons as shown in
Figure 8. Pressing the (help?) button brings up the help screen as shown in Figure 9.
Figure 12 - Legends
Table 4 – Unit general status
Page 34
Rev.03C 02-19-14
Page 34 of 82
Compu-Aire

7.5 Trending

7.5.1 Graph Overviews

Figure 13- Graphical sensors representation
Figure 14 - Graph description
Figure 15 - Pressure graph
Page 35
Rev.03C 02-19-14
Page 35 of 82
Compu-Aire

7.5.2 Icon Description and function

Icon
Description
Action
Indicates that the downloading of the data relating to the Trend from the pCO* has failed. Next to the letter X (see the image to the right) a number is displayed identifying the type of error in more detail: 4: the pCO does not have enough memory to manage the graphs. 5: the variable displayed is not a Public Variable.
Press the key. 4: use a pCO with more memory (pCO XM-Expanded Memory).
5: declare the variable as a Public Variable.
Indicates that no data is available for one of the two trends. This condition only occurs when attempting to display the two trends at the same time.
Nothing, or move the view to display the data for the other trend.
Indicates that there are no available data in the current view.
Move the time interval.
Indicates that the data relating to the trend is being downloaded from the pCO, but the remaining time is unknown.
Wait Indicates that for at least one of the trends the
data are outside of the current value interval.
Move the view in high or in the lower.
Key
Description
Pan mode is activated. When pressed, all the keys relating to zooming mode go to the Normal position.
Move the view to the left
Move the view to the right
Move the view up
Move the view down
View is moved so as to display the first data saved (the oldest data).
View is moved so as to display the last data saved (the most recent data).
Page 36
Rev.03C 02-19-14
Page 36 of 82
Compu-Aire
View is moved so as to display the last data saved (the most recent data).
When pressed, all the keys relating to zooming mode go to the Normal position. When pressed, changes the status from Normal to Pressed. When in Normal status, selecting a point on the graph the graph cursor is positioned at the closest value saved. The corresponding Y1, Y2 and X values can be displayed in a text box under the X Axis. When in Pressed status, selecting a point on the graph, the view is moved so the point selected is in the center.
Activate Zoom mode. When pressed, all the keys relating to Pan mode go to the Normal position.
Activate Zoom mode, all the other keys relating to Zoom mode switch to Normal status and Zoom In on the horizontal axis. When in Pressed status, selecting a point on the graph the view Zoom In on the horizontal axis
Activate Zoom mode, all the other keys relating to Zoom mode switch to Normal status and Zoom Out on the horizontal axis. When in Pressed status, selecting a point on the graph the view Zoom Out on the horizontal axis.
Activate Zoom mode, all the other keys relating to Zoom mode switch to Normal status and Zoom In on the vertical axes. When in Pressed status, selecting a point on the graph the view Zoom In on the vertical axes.
Activate Zoom mode, all the other keys relating to Zoom mode switch to Normal status and Zoom Out on the vertical axes. When in Pressed status, selecting a point on the graph the view Zoom Out on the vertical axes.
Reset the scales of the X axis as defined
Reset the scales of the Y1/Y2 axes as defined
Reset the scales of the X, Y1 and Y2 axes. This is the combination of the previous two commands.
Enable the display of trend no. 1 Normal=hidden Pressed=visible When pressed changes the status from Normal to Pressed.
Indicate that trend no.1 is available.
Enable the display of trend no. 2 Normal=hidden Pressed=visible When pressed, changes the status from Normal to Pressed.
Indicate that trend no.2 is available.
Page 37
Rev.03C 02-19-14
Page 37 of 82
Compu-Aire

7.6 Alarms

Action
Function
Alarm
Pressing the alarm button at any time
Next
Shows the next alarm
Previous
Shows previous alarm
Reset
Clears out active alarms and turns off the alarm LED
Note: All active alarms remain active until the root cause of the event is rectified.
Previous Alarm
Reset Alarms
Active Alarms
Previous Menu
Alarm Code
Alarm LED
PCO3 controller provides both audible and visual alarm event log. Up to 100 event entries are automatically saved in a non-volatile memory area in descending order. The last event always displays when the alarm button is depressed from the any screen.

7.6.1 Alarm Viewing and Function

Only active alarms are accessible under the “Alarm button”. Consult the alarm history, under setup, to view the remaining alarms.

7.6.2 Alarm Reset

The controller generates both visual and audible alarm continuously until cleared. To reset alarm, press the alarm button and scroll down to the reset menu by pressing the down button. Press the Reset button on the screen.
Figure 16 - Alarms Message
Page 38
Rev.03C 02-19-14
Page 38 of 82
Compu-Aire

8.0 SETUP MENU

Password
Level
Accessibility
1 1 Setpoint Menu
2 2 Technician Menu
1798
3
Factory Setup (Consult factory for more information)
Note: Entering a service menu requires a password. Default password is listed in Table 5.
Tap the screen to enter password
“SETUP MENU” has three (3) levels of passwords to control the access for accessing end user, technician, and setting reserved for factory setup. A password must be supplied to gain access to any setting. Level1 and level2 passwords are not enabled by default.
Note: Your system 2200+ series controller is already programmed, configured, and tested for your application. The system can be turned ON by using the ON/OFF button. The operating mode (Active System, System OFF, or Standby) is indicated under System Status screen. Minor tweaking might be required.

8.1 Entering a password

No password is required to view system status, active alarm, or turning the unit ON/OFF. System is automatically locked out after 5 minutes of inactivity and returned to the main screen. A new password must be entered to regain access to the setting. Once a password is entered, it times out in five (5) minutes if no screen and button activity are detected. A higher level of password also grants access to lower level access. If a factory password (level3) is enter, the screen will return the main menu.
Figure 17–Password prompt
Table 5 - Default Passwords
Page 39
Rev.03C 02-19-14
Page 39 of 82
Compu-Aire
Figure 18 - Entering password
Figure 19 - Setup menu
SETUP MENU
Setpoints
Clock
Run Time
BMS
Technician
Factory
Alarm Log
-Room Temperature
-Temp High Alarm
-Temp Low Alarm
-Humidity
-Hum High Alarm
-Hum Low Alarm
-Temp Water In
-Temp Discharge Air
-Economizer setpoints
-Time
-Date
-Night Setback
-Fan
-Economizer
-Compressors
-Heaters
-Unit ID
-Baud Rate
-Protocol *Modbus *BACnet *LONWorks *Carel
-Alarm Setup
-Sensor Offsets
-Digital Setup
-Network
-Manual Control
-Digital Inputs
-Digital Outputs
-Analog Inputs
-Analog Outputs
-HVAC
-Password
-Factory Reset
-Alarm
-Time/Date
-Event

8.2 Setup Menu Tree

Setpoints and other settings are organized as shown below in Figure 17. Not all settings are available to all units. Press Esc button at any time to return to the previous screen.
Figure 20 - Setup Menu Tree
Page 40
Rev.03C 02-19-14
Page 40 of 82
Compu-Aire

8.3 Setpoints

Figure 21 - Room temperature setpoints
Figure 22 - Room humidity setpoints
Figure 23 - Dew Point Control
Figure 24 - Dew Point Setpoints
Setpoint
Alarms
Relative Humidity
Dew Point
The controller is shipped with default selections for all necessary settings. In some cases, adjustments can be made to meet the application requirements. Use Up and Down arrow buttons to navigate between settings for different sensor.
Default Setting:
Temperature: 72°F Humidity: 50%

8.3.1 Changing Setpoints

Tap the Temperature/Humidity display Enter a new value from the virtual keyboard Tap on the enter button once done
Page 41
Rev.03C 02-19-14
Page 41 of 82
Compu-Aire

8.3.2 Changing Alarm Setpoints

Note: The controller is programmed to shut down the entire system once the return air temperature reaches 125°F. This alarm event supersedes all other events.
The alarm High and Low setpoints trigger an alarm event when the room returns temperature falls below or exceed the set limits.
Tap on the High/Low value Enter a new value from the virtual keyboard Tap the enter button when done

8.4 Clock Setup

The controller features an internal clock. Current time and date are backed up by an internal Lithium-Ion battery. Consult the factory for battery replacement.

8.4.1 Time and Date Setup

Tap on the corresponding number on the touch screen. Enter a new number from the virtual keypad. Press Enter when finished. Changes take effect immediately and require no system reset.

8.4.2 Night Setback

The controller supports 7 days unoccupied and occupied modes. Separate temperature and humidity setpoints are available and take priority when the night setback mode is active.
To active the Night Setback, change its setting to “YES” and follow the on screen directions. Use the arrow keys to navigate through the different screens to program each individual day.
Default Setting:
Night Setback: NO
Figure 25 - Clock setup
Page 42
Rev.03C 02-19-14
Page 42 of 82
Compu-Aire
Note: It is not recommended to set the Night Setback for computer room cooling.

9.0 RUN TIME HOUR METERS

The controller keeps track of run time for each individual component for servicing purposes. Each counter can be reset individually.
Setting Timer
Change the Reset setting from “NO” to “YES” Press Enter from the virtual screen The run time hour is reset immediately Repeat the same process for other components
Figure 26 - Component run time meters
Page 43
Rev.03C 02-19-14
Page 43 of 82
Compu-Aire

10.0 BUILDING MANAGEMENT SYSTEM (BMS)

Figure 27 - Building management system
Figure 28 - Communication protocol
Protocol
Description
Default Baud Rate
Modbus
Serial communication through RS-485
19,200
LONWorks
LONTalk communication
4,800
BACnet MS/TP
BACnet over MS/TP
4,800
BACnet TCP/IP
BACnet over TCP/IP, SMNP, HTML, FTP
19,200
PCO3 controller is capable of communicating with external remote Building Management System (BMS). Supporting protocol is enabled by a plug-in communication card.
PCO3 controller also features an alternative method of networking multiple cooling unit in a built in standalone p-LAN network through terminal J11. Baud Rate setting under BMS menu is only applied for Modbus protocol. Other protocol required separate software interface. Consult factory for more information.
Default Setting:
Unit Identification: 1 Baud Rate: 19200 Protocol: Modbus

10.1 Modbus

The PCO3 controller supports an optional RS-485 card, which allows you to interface directly the pCO3 to a supervisory network RS485. The max baudrate available is 19200 baud (it can be set by software).

10.1.1 Mounting

To install the card in the pCO unit follow these instructions:
1. Remove the "serial card" placement cover with a screwdriver.
2. Remove the pre-punctured plastic piece corresponding to the card being installed.
Page 44
Rev.03C 02-19-14
Page 44 of 82
Compu-Aire
3. Insert the optional card into the corresponding connector; confirm the card is firmly
placed on both plastic supports on the pCO3 case.
4. Close the cover using the screwdriver making sure the outside card terminal fits within
the punched hole made on the cover.
The connection with the RS485 network is carried out by means of the plug-in terminal connector on the card Pin-wiring of the connector is stamped on the card. If the card is placed in the last position of the supervision serial line, pins 2 and 3, you must connect a 120 Ω - 1/4 W end line resistors.
Table 6 - Modbus card installation
Warning
When handling the card, please follow the advice below. Electrical damage may occur to the electronic components as a result of electrostatic discharges from the operator. Suitable precautions must be taken when handling these components.
Before using any electronic component or card, ground yourself (not touching the card
does not prevent a spike, as static electricity can produce a 10000V spike discharge which can form an arc of about 1cm)
Page 45
Rev.03C 02-19-14
Page 45 of 82
Compu-Aire
All components must be kept inside their original package as long as possible. If
necessary, take the board from its package and place it into an antistatic package without touching the back of the board with your hands
Absolutely avoid non-antistatic plastic bags, polystyrene or sponge.
Do not pass the card directly to other operators (to prevent from electrostatic induction
and discharges).
Page 46
Rev.03C 02-19-14
Page 46 of 82
Compu-Aire

10.2 POINTLIST

Modbus BACnet
Type Index pCO Name NV Type NV Register Analog Value Direction Description
ANL 1 nvoTmpSet/nviTmpSet 105 40002 1 R/W Temperature set point ANL 2 nvoTmpBand/nviTmpBand 105 40003 2 R/W Temperature band ANL 3 nvoHighTmpSet/nviHighTmpSet 105 40004 3 R/W Temperature High alarm set point ANL 4 nvoLowTmpSet/nviLowTmpSet 105 40005 4 R/W Temperature Low alarm set point ANL 5 nvoHumSet/nviHumSet 81 40006 5 R/W Humidity set point / Dewpoint set point ANL 6 nvoHighHumSet/nviHighHumSet 81 40007 6 R/W Humidity High alarm set point ANL 7 nvoLowHumSet/nviLowHumSet 81 40008 7 R/W Humidity Low alarm set point ANL 8 nvoHumBand/nviHumBand 81 40009 8 R/W Humidity band ANL 9 nvoTemperature 105 40010 9 R T emperature reading ANL 10 nvoHumidity 81 40011 10 R Humidity reading ANL 11 40012 11 R Outside Air Humidity ANL 12 40013 12 R Discharge Temperature ANL 13 40014 13 R Outside Air Temperature ANL 14 40015 14 R W ater Temperature ANL 15 40016 15 R User Sensor 1 ANL 16 40017 16 R User Sensor 2 ANL 17 40018 17 R User Sensor 3 ANL 18 40019 18 R User Sensor 4 ANL 19 nvoHighPr_1 40020 19 R High Pressure 1 (For pressure tranducer) ANL 20 nvoLowPr_1 40021 20 R Low Pressure 1 (For pressure tranducer) ANL 21 nvoHighPr_2 40022 21 R High Pressure 2 (For pressure tranducer) ANL 22 nvoLowPr_2 40023 22 R Low Pressure 2 (For pressure tranducer) ANL 23 nvoCondPr_1 40024 23 R Condenser Pressure 1 (For pressure tranducer) ANL 24 nvoCondPr_2 40025 24 R Condenser Pressure 2 (For pressure tranducer) ANL 25 nvoOAEcono_Set 40026 25 R/W Outside Air Economizer Setpoint ANL 26 40027 26 R/W Discharge Air Economizer Setpoint ANL 27 40028 27 R/W Water Economizer Setpoint ANL 28 40029 28 R W ater Out Temperature ANL 29 40030 29 R/W Outside Air Humidity From BMS ANL 30 40031 30 R/W Outside Air Temperature From BMS ANL 31 40032 31 R Coil 1 Temperature Reading ANL 32 40033 32 R Coil 2 Temperature Reading ANL 33 40034 33 R/W Room Humidity From BMS ANL 34 40035 34 R/W Room Temperature From BMS ANL 35 40036 35 R/W Analog Out Y1 Signal From BMS ANL 36 40037 36 R/W Analog Out Y2 Signal From BMS ANL 37 40038 37 R/W Analog Out Y3 Signal From BMS ANL 38 40039 38 R/W Analog Out Y4 Signal From BMS ANL 39 40040 39 R/W Analog Out Y5 Signal From BMS ANL 40 40041 40 R/W Analog Out Y6 Signal From BMS
Modbus BACnet
Type Index pCO Name NV Type NV Register Integer Value Direction Description
INT 1 nvoTmpInt/nviTmpInt 8 40130 1001 R/W Temperature control Integration time INT 2 nvoHumInt/nviHumInt 8 40131 1002 R/W Humidity control Integration time
INT 3 nvoStatus 8 40132 1003 output
0=System off, 1=system on, 2=active,3=standby,4=override,5=Remote Shutdown by digital Input, 6=Manual Control from Technician menu, 7=BMS Offline default manual contro, 8=Sensor failed, system override with default controlled values, 9=BMS Offline, system
INT 4 Analog Out Y1 81 40133 1004 R Analog Out Y1 INT 5 Analog Out Y2 81 40134 1005 R Analog Out Y2 INT 6 Analog Out Y3 81 40135 1006 R Analog Out Y3 INT 7 nvoHumStatus 81 40136 1007 R Humidity demand (0-100%) INT 8 40137 1008 R Analog Out Y4 INT 9 40138 1009 R Analog Out Y5 INT 10 40139 1010 R Analog Out Y6 INT 11 40140 1011 R Current Day INT 12 40141 1012 R Current Hour INT 13 40142 1013 R Current Minute INT 14 40143 1014 R Current Month INT 15 40144 1015 R Current Second INT 16 40145 1016 R Current W eekday INT 17 40146 1017 R Current Year INT 18 40147 1018 R/W 0 = NO ECONOMIZER 1= AIR 2= WATER 3= CHILLED WATER VALVE (HVAC) INT 19 40148 1019 R 0 = Off 1= Vent 2 = Heat 3 = Cool 4 = Humidify 5 = Dehumidify 6 = Economizer 7 = Defrost
Carel
LONworks
Carel
LONworks
The following point list is available for LONWORKS, Modbus, and BACnet communication card. Use the corresponding register or index value to monitor it from the remote BMS system.
Page 47
Rev.03C 02-19-14
Page 47 of 82
Compu-Aire
Modbus BACnet
Type Index pCO Name NV Type NV Register Digital Value Direction Description
DGT 1 nvoOnOffStat/nviOnOffStat 95 2 1 R/W Unit ON/OFF Control (0=Off, 1=ON) DGT 2 nvoTmpCntr/nviTmpCntr 95 3 2 R/W Tem perature control type 0=P 1=PI DGT 3 nvoHuCntr/nviHuCntr 95 4 3 R/W Humidity control type 0=P 1=PI DGT 4 nvoAirflowAlm 95 5 4 R no airflow alarm DGT 5 nvoHighHtAlm 95 6 5 R High heat Alarm DGT 6 nvoSmokeAlm 95 7 6 R Smoke alarm DGT 7 nvoC1LPAlm 95 8 7 R Com pressor 1 low pressure alarm DGT 8 nvoC1HPAlm 95 9 8 R Compressor 1 high pressure alarm DGT 9 nvoC2LPAlm 95 10 9 R Compressor 2 low pressure alarm DGT 10 nvoC2HpAlm 95 11 10 R Compressor 2 high pressure alarm DGT 11 nvoC1CycAlm 95 12 11 R Com pressor 1 short cycle alarm DGT 12 nvoC2CycAlm 95 13 12 R Com pressor 2 short cycle alarm DGT 13 nvoDrainAlm 95 14 13 R Dr ain/Condensate/Leak detector alarm DGT 14 nvoHighTmpAlm 95 15 14 R High Temperature alarm DGT 15 nvoLowTmpAlm 95 16 15 R Low Temperature alarm DGT 16 nvoHighHuAlm 95 17 16 R High Hum idity alarm DGT 17 nvoLowHuAlm 95 18 17 R Low Humidity alarm DGT 18 nvoWtrFlAlm 95 19 18 R W ater Flow alarm DGT 19 nvoFireAlm 95 20 19 R Fire alarm DGT 20 nvoHeat1Out 95 21 20 R Heat1 output status DGT 21 nvoHeat2Out 95 22 21 R Heat 2 output status DGT 22 nvoHeat3Out 95 23 22 R Heat 3 output status DGT 23 nvoHeat4Out 95 24 23 R Heat 4 output status DGT 24 nvoC1Out 95 25 24 R Compressor 1 output status DGT 25 nvoC2Out 95 26 25 R Compressor 2 output status DGT 26 nvoC3Out 95 27 26 R Compressor 3 output status DGT 27 nvoC4Out 95 28 27 R Compressor 4 output status DGT 28 29 28 R humidifier alarm DGT 29 30 29 R DGT 30 31 30 R DGT 31 32 31 R standby unit on DGT 32 33 32 R filter alarm DGT 33 34 33 R discharge heat did not raise alarm DGT 34 35 34 R discharge cool did not fall alarm DGT 35 36 35 R fan overload DGT 36 37 36 R/W BMS Control Unit ON/OFF (Legacy, Need to Enable Under HVAC Option) DGT 37 38 37 R/W BMS Online Heart Beat (W rite Digital 1 every 15 second) DGT 38 39 38 R Compressor 4 low pressure / User DGT 39 40 39 R Compressor 4 hi pressure / User DGT 40 41 40 R User with Humidify Lockout DGT 41 42 41 R User with Reheat Lockout DGT 42 43 42 R/W Em ergency Economizer Off By BMS DGT 43 44 43 R DGT 44 45 44 R a unit is off pLAN network DGT 45 46 45 R user1 low alarm DGT 46 47 46 R user1 high alarm DGT 47 48 47 R user2 low alarm DGT 48 49 48 R user2 high alarm DGT 49 50 49 R user3 low alarm DGT 50 51 50 R user3 high alarm DGT 51 52 51 R user4 low alarm DGT 52 53 52 R user4 high alarm DGT 53 54 53 R Fan Output DGT 54 55 54 R Heater 1 Output DGT 55 56 55 R Heater 2 Output DGT 56 51 56 R Bypass 4 Output DGT 57 58 57 R Humidifier Output DGT 58 59 58 R Dehumidifier Output DGT 59 60 59 R DGT 60 61 60 R/W Res et Alarm Command DGT 61 62 61 R Unloader 1 Output DGT 62 63 62 R Unloader 2 Output DGT 63 64 63 R Bypass 1 Output DGT 64 65 64 R Bypass 2 Output DGT 65 66 65 R System Alarm DGT 66 67 66 R Remote On comm and via digital input DGT 67 68 67 R DGT 68 69 68 R Bypass 3 Output DGT 69 70 69 R Alarm 2 DGT 70 71 70 R Condenser Fan Output
Carel
LONworks
Page 48
Rev.03C 02-19-14
Page 48 of 82
Compu-Aire

10.3 LONWORKS

Note: The LONTalk card is preprogrammed at the factory. Commissioning the device is required to have proper readings when probing.
1. Connector to the PCO3 Controller
2. Terminal block for LonWorks® network (GND, A, B)
3. Service pin
4. Green service LED
5. Red fault LED
Figure 29 - LONTalk Card
Note: The ground wire (GND) is not requires in some application.
The serial interface boards for LonWorks® networks are optional accessories for the PCO3 controller which allows the controllers to be connected directly to a LonWorks® network. The use of these boards requires knowledge of and experience with the LonWorks® network installation and maintenance tools.

10.3.1 General characteristics

The program installed on the board may correspond to a standard LonMark® profile. The board is programmed by the manufacturer when LonMark® profiles are used or in the field for custom profiles.

10.3.2 Physical channels

Depending on the model, the interface boards communicate via two physical channels, TP/FT-10 and TP-RS485-39, as described in the LonWorks® literature. The LONTalk card uses an Echelon® FTT-10 transceiver, approved for use on the TP/FT-10 channel. This channel has the following main characteristics:
Allows the connection of a maximum of 64 nodes for each network segment;
The nodes can be connected without any restrictions in the topology: that is, star, ring, on
one bus only, or with any combination of these;
Communication speed: 78,125 kbps;
Maximum distance (Belden 85102 cable): 500m for connections between the nodes with
free topology; 2700m for bus connections with double line terminator.

10.3.3 Physical Circuit Board Layout

Page 49
Rev.03C 02-19-14
Page 49 of 82
Compu-Aire

10.3.4 LED Color Description

The green service LED:
Signals the status of the node, as per the LonWorks® protocol
Hardware fault: always ON or always OFF
Node configured (normal operation): ½ second ON, then always OFF
Node NOT configured: flashing at ½ Hz
Node without software application: 1 second ON, 2 seconds OFF, then always OFF
Node in continuous reset: flashing
Remains on during the activation of the service pin
Remains on for one second when receiving a wink command via the network
The red fault LED:
Signals problems in the connection between the board and the pCO.
WARNING: If the red LED comes on make sure the instructions described under Installation have been carefully followed. THE COMMUNICATION BAUD RATE ON THE PCO HAS BEEN SET TO 4800 BAUD.

10.3.5 Installation

WARNINGS: precautions in handling the board. Electrical damage may occur to the electronic components as a result of electrostatic discharges from the operator. Suitable precautions must be taken when handling these components, specifically:
Before handling any electronic component or board, touch an earthed object
(simply not touching the component is not enough to prevent a spike, as static electricity can produce a 10000V discharge, which can form an arc of about 1cm)
All materials must be kept inside their original package as long as possible. If
necessary, take the controller from its package and place it into antistatic packaging, without touching the back of the board
Absolutely avoid non-antistatic plastic bags, polystyrene or sponges;
Do not pass the electronic components or boards directly to other operators (to
prevent electrostatic induction and discharges)
Page 50
Rev.03C 02-19-14
Page 50 of 82
Compu-Aire

10.3.6 Connection to the PCO3 Controller

Figure 30 - Remove plastic cover
Figure 31- Cut out window
Figure 32 - Installing plugin card
Figure 33 - Replacing windows cover
With reference to Figures 25-28 below, insert the board in the pCO3 as follows:
1. Disconnect the power supply to the pCO3 and use a screwdriver, remove the serial card
cover
2. Remove the pre-cut plastic part from the cover to make a rectangular window cutout
3. Insert the optional board in the corresponding plug-in connector, initially holding it
diagonally and then making sure it is properly inserted and pushed up against the two plastic supports on the case of the PCO3
4. Close the cover and aligning the connector on the serial board with the hole made in the
cover
5. Reconnect the power supply to the pCO. If the pCO supervisor serial communication
has been set to use the Carel protocol at 4800 baud, the red LED on the board will come on for a few seconds and then will go off immediately, indicating normal operation.

10.3.7 Connection to the LonWorks® network

The physical connection to the LonWorks® network is performed using the connector with removable terminals fitted on the board, according to the Echelon® instructions and specifications. For further information on installation, maintenance, the cross-section and type of cable, refer to the LonWorks® literature.

10.3.8 Service pin

To activate the service pin, simply momentarily short-circuit the two pins on the board (see Figure 24) with the tip of a screwdriver or a similar tool. The service pin must only be activated during the installation of the node. When the pin is activated, the node sends a broadcast message over the LonWorks® network, containing the information required for identification.
Page 51
Rev.03C 02-19-14
Page 51 of 82
Compu-Aire

10.3.9 WINK event

A generic supervisor can send the WINK command to a specific node on the LonWorks® network. This generates an event that the application on the specific node can respond to with any action decided by the programmer. In this specific case, the service LED on the interface comes on for one second, thus making it possible to check the correct operation of the connection between the interface and LonWorks® network.
Page 52
Rev.03C 02-19-14
Page 52 of 82
Compu-Aire

10.4 BACNET OVER TCP/IP

10.4.1 Installation

The board is installed in the PCO3 controller, when off, as follows
1. Remove the “Serial Card” cover from the PCO3 using a screwdriver.
2. Insert the board in the corresponding plug-in connector, making sure it is fully inserted
and in contact with the two supports located on the case of the PCO3. This operation may be difficult due to the limited space, consequently, it is recommended to insert the board at an angle and then turn it until aligning the connectors.
3. Close the cover again, using the cover supplied with the board, lining up the connector
on the serial board with the opening in the cover.
4. (optional): stick one or both labels supplied outside and/or inside the electrical panel
near the PCO3, so that the MAC ADDRESS can be read without needing to open the electrical panel for the connection to the Ethernet network, use an S/FTP cable, category 5e or higher.

10.4.2 Functions

The pCOWeb board is used to connect the pCO3 controller to an Ethernet network and consequently perform the following functions.
Access the information on the pCO3 (network variables and parameters) using an
Internet browser, such as Internet Explorer™ installed on a PC and connected to the
pCOWeb via TCP/IP (see Web server)
Connection to a supervisory network that uses one of the following standard protocols
o SNMP v1 & v2c o BACnet Ethernet ISO8802-2/8802-3 o BACnet/IP

10.4.3 Default parameters

In order to access the configuration (see the Configuration section), the pCOWeb can be started using the “factory bootswitch parameters”:
IP address= 172.16.0.1 Net mask= 255.255.0.0; “root” user password: froot “httpadmin” user password: fhttpadmin “guest” user password: fguest
Page 53
Rev.03C 02-19-14
Page 53 of 82
Compu-Aire
To start the pCOWeb with default parameters, proceed as follows:
Note: In “factory bootswitch parameters” mode, the pCOWeb does not save the
parameters recalled, but simply uses them, and therefore, when next restarted without pressing the button, it will use the parameters set by the user (if just acquired, with DHCP)
Note: For the correct operation of the pCOWeb, a number of basic parameters need to be set, such as the IP address and Netmask; each device connected to an Ethernet network, to communicate with a host, must have a unique IP address.
When the pCOWeb is off:
switch on the pCO3 controller with the pCOWeb already inserted and hold the button
for at least 20 s, until the status LED starts flashing SLOWLY 3 times, red-dark;
release the button while the LED is flashing, after having flashed 3 times, the LED turns
green, then, to confirm the recognition of the button, the LED will flash QUICKLY 3 times, red-dark.
To complete the pCOWeb boot phase, wait approximately 50 s until the status LED
flashes regularly. From this moment on, the pCOWeb can be accessed via the network
When the pCOWeb is already on:
• Restart the pCOWeb software (see “Restarting the software”)
After restarting, proceed as above for when the pCOWeb is off.

10.4.4 Restarting the software

To restart the software when the board is in stable operation (that is, with the status LED flashing regularly), press and hold the button for between 5 and 10 seconds; after around 10 s from releasing the button, the status LED will stop flashing, and after a further 15 seconds the software on the board will restart.

10.4.5 Configuration

PCOWeb is supplied with the DHCP function already active. Therefore, in a network served by a DHCP server, pCOWeb will automatically acquire the necessary parameters without requiring configuration. In the case of a network without DHCP, the parameters need to be configured manually (see the “Accessing the user configuration...” section).
Accessing the user configuration (via Ethernet network and configuration web pages)
Automatic network configuration (DHCP): ask the network administrator for the address that
has automatically been assigned to the pCOWeb already connected; the administrator will need to know the MAC ADDRESS of the pCOWeb.
Network without DHCP: when first using the board, it is recommended to connect pCOWeb
directly to a computer using a crossed Ethernet cable; then start the board with the “factory bootswitch” parameters (see “Pushbutton”).
Page 54
Rev.03C 02-19-14
Page 54 of 82
Compu-Aire
To allow the PC to access the pCOWeb:
Figure 34 - PCOWeb
Figure 35 - Window cover
Figure 36 - Installing PCOWeb
Figure 37 - Installing plastic cover
The PC used for the configuration must be in the same sub-network as the pCOWeb; set
the network parameters on the PC as follows:
o IP address= if DHCP: ask the network administrator; with “factory bootswitch
parameters”: 172.16.xxx.xxx (with xxx.xxx as desired, as long as different from
the 0.1 already used by pCOWeb);
o Netmask= 255.255.0.0.
The browser on the PC must have the option corresponding to the use of a proxy server
disabled. If the network settings on the PC and the browser are correct, typing the IP address of the pCOWeb in the address bar will access the default home page of the pCOWeb. Then enter the area reserved for the administrator, using the special link (Go to Administrator Area) and the following pre-set account:
o username= admin o password= fadmin
The basic parameters for communication and access are located in the “Configuration” area. Choose “Network”: the primary IP address of the board and three aliases can be set.
To configure the DHCP function type “DHCP” in the place of the IP address. If the network does
not use DHCP, ask the network administrator for a valid IP address and Netmask for the local network that the pCO3 will be connected to.
Page 55
Rev.03C 02-19-14
Page 55 of 82
Compu-Aire
Note: the parameters recalled with the “Pushbutton” cannot be modified and must not
be confused with the values that are modifiable by the user. For a complete description of all the parameters that can be set, consult the factory for user manual.

10.4.6 Web server

User Name
Description
Default Password
Allowed
root
administrator of the operating system
froot
no limitation
httpadmin
web administrator
Fhttpadmin
R/W access to the http directory; read-only to the other directories.
guest
guest
fguest
Note: The pages downloaded to the pCOWeb must have the correct properties and be able to be displayed with a browser; setting these attributes correctly via FTP is quite
difficult, and consequently the “auto-set attributes” function is available in the administrator pages. To activate this function, simply click the “Adjust HTML pages attributes” link; it is recommended to do this whenever modifying one or more HTML
pages.
The web server included in the pCOWeb is “thttpd”, compliant with the HTTP 1.1 specifications,
and is used to display HTML pages directly on the Internet browser. A client application can thus control and monitor the pCO3 controller that the pCOWeb board is installed on from a remote location.
The HTML pages can be easily created and downloaded to the pCOWeb by the end user with any FTP client. Common programs can be used to create the custom HTML pages (e.g.
Macromedia® Dreamweaver™ or Microsoft® FrontPage™) and download them to the pCOWeb via FTP client such as SmartFTP™ (www.smartftp.com).

10.4.7 Accessing the operating system by authentication

The system can be accessed via a telnet terminal or via FTP. Authentication with user name and password is required for each access. The following users are registered.
Table 7 - PCOWeb passwords
The password can be modified by accessing the administrator page. The password recalled with
the “Pushbutton” function will not be modified and must not be confused with the passwords
that are modifiable by the user. This page can also be used to set the access restrictions for each of the various directories in the http tree. Consequently, connecting via FTP and logging in as the web administrator, as follows will access the pCOWeb user file system
username= httpadmin;
password= fhttpadmin (note “f” as in “factory” as the first letter).
The customized pages should be saved in the following directory: /usr/local/root/flash/http.
Page 56
Rev.03C 02-19-14
Page 56 of 82
Compu-Aire

10.4.8 CGI script

CGI scripts can be written in bash language or compiled languages. These must have the .cgi extension and must reside in the http/usr-cgi directory. As for the HTML pages, these files must also have the properties correctly set and enabled. IMPORTANT: It is recommended to click on the “Adjust HTML pages attributes” link whenever modifying one or more .cgi scripts.

10.4.9 SNMP

PCOWeb is able to communicate using the SNMP protocol (v1 & v2c). It therefore acts as a gateway between the CAREL proprietary protocol and SNMP. The information available via SNMP relates to all the data sent to the supervisors by the application loaded on the pCO3.
PCOWeb manages some standard traps and allows a trap to be defined for each digital variable on the pCO3. The parameters relating to the management of the SNMP protocol can be set using the administrator configuration pages.

10.4.10 BACnet

PCOWeb is able to communicate using the BACnet protocol over Ethernet:
ISO8802-2 over 8802-3;
BACnet/IP.
It acts as a gateway between the controller proprietary protocol and BACnet. The information transferred involves all the data sent to the supervisor by the application loaded on the pCO3. The parameters relating to the management of the BACnet protocol are set using the administrator configuration pages.

10.4.11 WARNINGS

Precautions when handling the board!
The electrical damage that occurs to electronic components is almost always due to electrostatic discharges caused by the operator. Consequently, suitable precautions must be taken when handling these components, in particular:
Before handling any electronic component or board, touch an earthed object (avoiding
contact with a component is not sufficient, as a 10,000 V discharge, a voltage that can easily be reached by static electricity, creates an arc of around 1 cm);
The materials must remain as long as possible inside their original packages. If
necessary, remove the board from the packing and then place the product in antistatic packaging without touching the sides of the board containing the electronic components;
Always avoid using plastic, polystyrene or non-antistatic materials;
Always avoid passing the board between operators (to avoid the phenomena of
electrostatic induction and consequent discharges).
Page 57
Rev.03C 02-19-14
Page 57 of 82
Compu-Aire

10.5 BANET over MS/TP

Note: If the device used to read the data from the 485 network is grounded and the RS232-RS485 converter or the RS485 serial port on the device have functional insulation of less than 2kV, connector G0 on the PCO3 board must be grounded. The board cannot be installed in direct contact with the metal panel on the electrical panel.
Push
Button
Status
LED
RS-485
LED
Optional add on board is available for BACnet over Master/Slave application.

10.5.1 Installation

1. Disconnect the power supply from the pCO3 and remove the “Serial Card” cover.
2. Insert PCOnet card in the plug-in connector, making sure that it is fully inserted and in
contact with the two supports on the pCO3. As there is little space available, this operation may be complex: as a result, insert the PCOnet card at an angle then tilt it back until the connectors line up.
3. Insert the required jumpers (see below for the meanings of these).
4. Fit the cover supplied with the PCOnet.
Table 8- Installation guide
Page 58
Rev.03C 02-19-14
Page 58 of 82
Compu-Aire

10.5.2 Meaning of the jumpers

Jumpers P1, P2 and P3 are located inside the front opening of the cover. See table 7 for installation guide.
Jumper P1 adds a 510 ohm polarization resistance between the negative data line (-)
and GND
Jumper P2 adds a 120 ohm terminal resistance between the two data lines (+) and (-);
Jumper P3 adds a 510 ohm polarization resistance between the positive data line (+) and
the +5 VDC internal voltage.
Insert all three jumpers on the unit at the start of network and the unit at the end of the network. Do not insert the jumpers on the intermediate units. For compliance of the product with the European EMC standards, add the ferrite supplied to the network cable, as illustrated in Table 7.

10.5.3 Operation

The Status LED (left) indicates the status of communication with the controller and the status of the PCOnet.
Starting sequence: on power-up, or after restarting PCOnet, the Status LED switches in the following sequence:
OFF for 2 seconds;
2 seconds after restarting: quick flash red-green-red-green
5 seconds after restarting: green on steady
Approximately 50 seconds after restarting: flashing (color: see below - Status of
communication with the pCO3) PCOnet-pCO* communication starts.
Status of communication with the pCO3: Once the starting sequence has been completed, the Status LED flashes to indicate the quality of communication with the PCO3:
Quick green-OFF-green if communication with the pCO3 is OK (pCO* ON-LINE);
Slow red-OFF-red if communication has not been established with the pCO* (pCO3 OFF-
LINE)
Green-red-green if PCOnet detects errors or a temporary lack of response from the
pCO3.
Page 59
Rev.03C 02-19-14
Page 59 of 82
Compu-Aire
The RS485 LED (right) indicates the status of communication with the BACnet MS/TP network (RS485). The LED shows the following information:
Starting sequence: on power-up or after rebooting PCOnet, the RS485 LED switches in the following sequence:
Off for approximately 50 seconds;
Approximately 50 seconds after restarting PCOnet: slow green–redgreenred: at
the end, BACnet will be active.
Status of communication with the BACnet MS/TP network: once the starting sequence has been completed, the RS485 LED flashes to indicate the quality of communication with the BACnet MS/TP network:
Green with occasional red flashes if communication is OK (BACnet MS/TP meaning:
green ON = PCOnet keeps the Token (control of the MS/TP network); green OFF = PCOnet DOES NOT keep the Token; red on = Poll-For-Master, search for a Master to pass the Token to)
Green and red ON together (BACnet MS/TP meaning: continuous Poll-For-Master):
communication not established (connection problems, or no network device found); this may depend on electrical connection difficulties or communication settings that are not compatible with the other network devices connected. See the section on configuration.
The Pushbutton Function
restart PCOnet
recall the factory configuration
Restarting PCOnet
With the board on and in stable operation (Status LED flashing continuously), hold the button for more than 5 seconds and no more than 10 seconds. Approximately 10 seconds after releasing the button, the Status LED will stop flashing, and 15 seconds later PCOnet will be restarted: Status LED quickly flashing red-green-red-green.
Page 60
Rev.03C 02-19-14
Page 60 of 82
Compu-Aire

10.5.4 Recalling the factory configuration (“factory bootswitch” mode)

Note: If the values of the pCOnet parameters are not suitable, communication with
BACset may not be possible. To connect to pCOnet, restart pCOnet using “factory bootswitch” mode (see the section on Operation - Pushbutton).
With the following procedure, PCOnet uses the default parameters instead of the ones specified by the user. See the table of parameters and factory values in the section on Configuration. In
“factory bootswitch” mode, PCOnet does not save the recalled values, and consequently when
next restarted without pressing the button, PCOnet will again load the user settings. When purchasing PCOnet, the user parameters are set to the factory configuration values.
With PCOnet OFF:
Switch PCOnet on (i.e. switch on the pCO* controller with the PCOnet board inserted)
by pressing and holding the button for at least 20 seconds: the Status LED will flash SLOWLY 3 times, red-off
Release the button while the LED is flashing: after 3 red flashes, the LED comes on
green; the LED then confirms recognition of the button by flashing QUICKLY 3 times red­off, and then comes on green again
Complete start-up of the PCOnet will take another 40 seconds, then the RS485 LED starts flashing; only from this moment on can PCOnet be accessed via a remote connection. With PCOnet already ON:
Restart PCOnet (see above: Restarting PCOnet)
After the restart procedure, follow the steps described above for PCOnet OFF

10.5.5 Configuration

Configuring the PCOnet parameters for correct communication over an MS/TP network:
Connect PCOnet via RS485 to a computer: during configuration, the CAREL product code
CVSTDUMOR0 for USB ports can be used.
Converters should not be used in the installation due to the large volume of data
transmitted across a complex BACnet™ network.
• Install the CAREL “BACset” configuration tool, available free-of-charge at ksa.carel.com.
Page 61
Rev.03C 02-19-14
Page 61 of 82
Compu-Aire

10.5.6 BACNET Parameter Description

Parameter
Min
Max
Factory
Device Instance
0
4194303
77000
Station Address
0
127 0 Max Master
0
127
127
Max Info Frames
0
255
20
Baud Rate
9600, 19200, 38400,76800
Device Instance
This is a number that uniquely identifies a device inside the BACnet® network (the BACnet® network can also include non-MS/TP BACnet® devices). If two units have the same Device Instance, identification errors will be generated.
Station Address
This is a number that differentiates the units in the BACnet® MS/TP network. If two units have the same Station Address, identification errors will be generated. To speed up the data exchange between the Master units, the Station Address of the Master units should start from 0 and continue without skipping any numbers.
Max Info Frames
This establishes the maximum number of information packages exchanged, above which the Master unit will give up control (Token) of the network to another Master unit. It thus indirectly establishes a sort of priority between the Master units in the network: high numbers guarantee the Master a higher data exchange volume.
MaxMaster
To speed up data exchange between the Master units, Max Master should be set to the Station Address of the Master with the highest Station Address. In fact, each Master, after having used the network, passes over control to the next Master. The Max Master parameter specifies to pCOnet the address of the network Master with the highest Station Address: using this parameter, pCOnet will know that there is no other Master with a higher Station Address than Max Master; pCOnet will then give control of the network to the next Master, however not beyond Max Master; if no next Master is found, the cycle will begin again, with control being given to the Master with the lowest Station Address.
Baud Rate
Data transfer speed. The Baud Rate must be the same for all the devices connected. Otherwise the exchange of data will generate communication errors. For extended networks, low baud rates should be specified, as these guarantee less communication errors. If Baud Rate=76800, make sure the device supports this communication speed. This baud rate is not supported by the RS232 serial port on a normal PC.
Table 9 - BACnet MS/TP parameters
Page 62
Rev.03C 02-19-14
Page 62 of 82
Compu-Aire

11.0 TECHNICIAN MENU

Icon
Description
Alm Setup
Alarm sensor setup for temperature, humidity, smoke, no air flow, etc.
Sns. Ofs.
Sensor calibration offset
DI Setup
Controller digital input setup
Network
P-LAN network setup
Man. Ctrl
Manual control for each components
Switch over
The service menu has settings that assist the installation and maintaining process. Each setting is defined as shown below.
Table 10 - Technician menu
Table 11 - Technician menu description

11.1 Alarm Setup

The controller supports a general alarm or global alarm for the following events. Each individual alarm can be configured to be part of a global arm. R2 is the second relay which is connected to a normally opened dry contactor. Consult the electrical wiring diagram for more information.
Figure 38 - Alarm configuration
Page 63
Rev.03C 02-19-14
Page 63 of 82
Compu-Aire
Default Setting:
Configuration R2 SW
Temp. H/L Alarm: OFF OFF Hum. H/L Alarm: OFF OFF Compressor Alarm: OFF ON Air Flow Alarm: OFF ON Smoke Detect alarm: OFF OFF
Configuration R2 SW
Dirty Filter Alarm: OFF OFF Sensor Failure Alarm: OFF ON Drain Full Alarm: OFF OFF Fire Stat Alarm: OFF OFF
Note: Not all systems are equipped with a general alarm or global alarm. Setting the SW=ON will shut the current active unit down and switch the operation over to standby unit. The “Switch Over” column setting only available when more than one unit are networked together.
Page 64
Rev.03C 02-19-14
Page 64 of 82
Compu-Aire

11.1.1 Available Alarms

Alarm
Function
Temperature H/L Alarm
High low alarm set under Setpoint
Humidity H/L Alarm
Humidity high/low set under setpoints
Compressor Alarm
Compressor fail
Air Flow Alarm
Air flow loss
Smoke Detect Alarm
Smoke is detected in the system
Dirty Filter Alarm
Filter is dirty, need replacement
Fire Stat Alarm
Temperature reaches 125°F
Figure 39 - Alarm delays
Figure 40 -Alarm switch over
The alarm status is notated by its current setting. To set the alarm, change the setting to either “ON/OFF” by tapping the screen and toggling via the virtual keyboard.
Table 12 - Global alarms
The PCO3 controller implements time out sensor delays to insure smooth operation. Each delay is dictated in second unless otherwise noted.
Page 65
Rev.03C 02-19-14
Page 65 of 82
Compu-Aire
Default Setting
RMT/OAH Sensor: 0s
FC/OAT/B10: 0s
Fire Stat: ON Temp: 125.0°F
Fire Stat Alarm Delay: 0s
Offline Alarm Delay: 60s
Alarm Buzzer: OFF
T/H Alarm Delay: 15M
All Alarm Switchover: OFF
Disc Cool/Heat: 0.2°F 0s
Page 66
Rev.03C 02-19-14
Page 66 of 82
Compu-Aire

11.1.2 Sensor Offset

PCO3 controller provides sensor calibration to match the reading to a reference device. Setting can be positive or negative offset. All adjustments take effect immediately.
Default Setting Offset: 0

11.1.3 Digital Input

Table 13 - Sensor calibration
Digital setup is reserved for factory used only. If required, adjustment can be made to fine tune the equipment to work with other applications. The controller is designed to recognize a 24VAC signal from the sensor and trigger a corresponding alarm which is commonly used in normally opened relay. In some cases, where a normally opened relay is use, a reverse logic must be set in the controller to get the alarm function to register properly. Available options are closed and open.
Table 14 - Digital Input Setting
Setting Description
Alarm If: CLOSED: Used for normally open sensor
OPEN: Used for normally closed sensor
Page 67
Rev.03C 02-19-14
Page 67 of 82
Compu-Aire
Currently: Read only OPEN/CLOSED
Figure 41 - Network Setup
Figure 42 - Network Assist
Note: A P-LAN network has a minimum of two units and a maximum of sixteen units. Only one master is allowed. The Network Setup screen is accessible by the master unit ID=1. This option is not available on the slave unit.
Icon
Function
Total Units
Total unit including the master
Standby Units
Number of standby units
Use U1 Sensors
Use master unit sensors for every units
Time Rotation
Number of day and time to rotate
Force Rotation
Force the standby unit to become active
Shows the current status of the input relay
Available Options
Smoke Alarm No Air Flow Hi Heat Limit Compressors Low Compressors High Dirty Filter Water Flow

11.2 Network Setup

The controller supports up to 16 units working together as single unity in a p-LAN network. A P­LAN network composes of one (1) master unit with up to fifteen (15) slave devices. Proper unit identification is required prior to proceeding. See P-LAN setup section for more information.

11.2.1 Define a Network

11.2.2 Network Assist

In a P-LAN network, all standby units are capable of assisting the active unit in cooling, heating, dehumidifying, and humidifying mode. The dead band of each individual mode can be set according to Figure 37. The delay of assistance is set to 600 seconds by default. After 600s, standby units become active and assist only if the active unit is unable to maintain the setpoints
Table 15 - Setting a P-LAN network
Page 68
Rev.03C 02-19-14
Page 68 of 82
Compu-Aire
in the elapsed time. Once the setpoints are satisfied, standby units return to standby and the
Note: Do not use this option to permanently turn off components such as reheat or humidifier. Refer to Factory->HVAC setting for detail.
cycle starts over.

11.3 Manual Control

Manual control is designed to turn on necessary components for a fixed amount of time. This function can be used to vacuum and charge the unit, service the unit, or perform a functional test. After an adjustable time out (defaults to 5 minutes, max 99 minutes), the designated component returns back to AUTO and resumes its normal operation. Applicable analog/digital outputs are selectable as ON, OFF, or AUTO mode. The following components are available in the manual setting.
Default Setting: AUTO for all components
Blower Low pressure bypass Heaters Compressors
Liquid Solenoids Humidifier Analog outputs Global alarm
Note: All analog outputs must be set to “0” for normal operation.
Page 69
Rev.03C 02-19-14
Page 69 of 82
Compu-Aire

12.0 FACTORY SETTING

Note: A level 3 password is required to gain access to the Factory Menu. Changes to the factory settings are crucial and only recommend for a well trained technician or under factory guidance.
FACTORY MENU
D. INPUTS
D. OUTPUTS
A. INPUTS
A. OUTPUTS
HVAC
PASSWORD
F. RESET
Air Flow Smoke Alarm High Heat Limit Compressor Condensate Water Flow Filter Alarm Fan Overload Remote ON/OFF Condensate
Blower Heater Heat Pump Compressors Unloaders Bypass Humidifier Global Alarm
Room Humidity Room Temperature Dsc. Temperature Coils Temperature Water In Temperature Pressure Transducer
Economizer Voltage Min/Max
Fan Mode Fan Delay Shut down Fan Fan Min/Max ON Unit °C/°F Compressor Setup Economizer DX Assist Low Pressure Retry Dead Bands
Level 1 Level 2 Level 3
Factory Reset Op. Mode Reset Alarm Hist.
The controller is fully programmed at the factory to meet its specifications. Adjustments to the default settings sometime are required in the field to fine tune the controller to adapt it to the environment.
Figure 43 - Factory Setting

12.1 Factory Setting Menu Tree

Page 70
Rev.03C 02-19-14
Page 70 of 82
Compu-Aire

12.1.1 Digital Inputs and Digital Outputs

All digital inputs and outputs are predefined and governed by the electrical wiring diagram. All settings are pre-configured at the factory prior to shipping. Changes are not recommended unless suggested by the factory. Consult the factory for more detail.
In general, the controller works with a 24VAC input from the normally opened relay. The internal relay from the controller sends out a 24VAC on the digital output terminals to designated coils in order to energize the high voltage components.
Figure 44 - Digital input configuration
Page 71
Rev.03C 02-19-14
Page 71 of 82
Compu-Aire
Figure 45 - Digital output configuration
Page 72
Rev.03C 02-19-14
Page 72 of 82
Compu-Aire

12.1.2 HVAC

The HVAC section contains crucial settings that can have great impact how the system perform. All changes made in this section should be dealt with extra. Consult the factory if assistance is needed. Not all options are available on all units.
Figure 46 Fan Setup
Mode: Continuous, Demand Speed: High, Low
Figure 47 Sensor Setup
Room T. Type: Proportional, Integral, PID Band: Deadband default 5.0 (±2.5°F)
Figure 48 Demand Ramps
*Do not use. Factory reserved
Figure 49 Compressor Option
Page 73
Rev.03C 02-19-14
Page 73 of 82
Compu-Aire
Figure 50 Compressor Options
Figure 51 Ramping
Figure 52 Low pressure setup
Figure 53 Humidity
Figure 54 Dehumdification
Figure 55 Heating
Page 74
Rev.03C 02-19-14
Page 74 of 82
Compu-Aire
Figure 56 BMS Control
Figure 57 BMS Offline Control
Figure 58 Sensor Failure control
Page 75
Rev.03C 02-19-14
Page 75 of 82
Compu-Aire

12.1.3 Analog Inputs and Analog Outputs

Analog input terminals on the controllers are used for a wide variety of analog sensors. The majority of input sensors are used for monitoring room temperature and humidity. NTC and transducers are also supported.
Analog output terminals are primarily used for economizer systems where modulating output signals are required. Consult the factory for any special equipment use request.
Figure 59 - Analog input configuration
Page 76
Rev.03C 02-19-14
Page 76 of 82
Compu-Aire
Warning: Consult the manufacturer prior making any changes.
Figure 60 - Analog output configuration
Page 77
Rev.03C 02-19-14
Page 77 of 82
Compu-Aire

12.1.4 Changing Passwords

Default passwords are defined by the factory. See Entering a password for more detail. Adjustment to the default password is sometime required by the end user. Password is protected and not retrievable. Changes to the default password must be stored in a safe place. The factory cannot retrieve the lost or forgotten password.
Figure 61 - Changing default password

12.2 Factory Reset

Factory reset is used to reset the controller to its default setting. Not all default settings are applicable to all units.
Warning: Do not perform this function. It will wipe out all the default settings and return the
controller settings back to its default values. A reconfiguration is required to set it back to its specifications.
Figure 62 - Factory reset / Set Unit Mode
Page 78
Rev.03C 02-19-14
Page 78 of 82
Compu-Aire

13.0 TROUBLESHOOTING GUIDE

SYMTOM
POSSIBLE CAUSE
REMEDY
Black screen
Loss of power
Check 24Vac at controller and display
No link
Wrong unit ID
Check Unit ID. See P-LAN setup for instruction.
Incorrect wires
Check wiring on J11 from the controller to the display.
Loss of communication link between controller & display
Make sure the controller and display get proper 24Vac voltage.
Cable length
Check to make sure cables meets specification and not exceeding 200 meters for 24AWG.
Buzzer ON
Alarm events
Press the Alarm button to view the alarm. Press up/down arrow key to view next alarm.
Alarm reset
Press the alarm button following by pressing
the down arrow key until “Reset” shows on
the screen. Tap the Reset button on the screen to clear the alarm.
Screen nonresponsive
Missed calibration
See “Screen Calibration” for detail on recalibration.
Modbus not communicating
Cabling
Check to make sure cable is comply with standard and not exceeding 1000 meters.
Speed
Make sure computer and controller are set to the same speed. Default speed on the PCO3 controller is 19.2k.
Add-on card not installed properly
Verify that the card is installed properly. Check the matting connectors with a flash light. Check for status light.
LONTalk not responding
Cabling
Verify the physical wires between the controller and the BMS system. A parallel cable should be in used.
Not commission
Decommission and commission the card. Use a Wink command to check response.
Wrong speed configured
Verify that the speed is set to 4800 from the controller under “Supervisor Setup”. Check for LED status error code.
BMS not accessible
Verify that the card is setup properly
PCOWeb fails communication
Wrong cable
A crossed over cable is required for direct connection from PC to controller
Add-on card not installed properly
Check for proper matting connectors between the controller and the add-on card
Page 79
Rev.03C 02-19-14
Page 79 of 82
Compu-Aire
Incorrect IP
Check DHCP server for correct IP. Boot up in factory setting for default IP: 172.16.0.1 to assign static IP. See PCOWeb setup for detail
Wrong Temperature or Humidity reading or sensor fail
Wrong jumper setting
Pop open the sensor module and verify that the setting on the temp/hum sensor board is set to 0-1V
Power supply
Check for proper 24VDC coming on +G and GND at the sensor board
Water damage
Check for water condensation on the probe. Dry it out for any moisture. Relocate the sensors if necessary.
Wrong offset / Calibration
Check for sensor offset and recalibrate against a reference point if necessary.
Alarm not reset
Alarm source not rectified
Check for the cause of the alarm. The alarm cannot be cleared if the cause of the alarm still persists.
Stuck in Manual Mode
Force components ON
Set all components under “Manual Ctrl”
screen to Auto mode
Compressor not ON
Incorrect setpoint
Check system setpoint for cooling temperature. Compressor only runs when temperature drops below room setpoint.
Reheat Lockout
Over amp protection
System incorporate a reheat lockout if cooling and humidifier are ON
High Temperature
Temperature rises above max setpoint
Room is too hot. Check sensor and reset alarm after fixing the problem.
Low Temperature
Temperature drops below min setpoint
Room is too cold. Check sensor and reset alarm after fixing the problem.
High Humidity
Humidity rises above max setpoint
Too much moisture in the air. Check and reset the alarm after fixing the problem.
Low Humidity
Humidity drops below min setpoint
Room is too dry. Check and reset the alarm after rectify the problem.
No Air Flow Static pressure drop
Check motor, duct work, and filter. Reset the alarm after rectifying the problem.
Sensitive switch
Check and recalibrate the switch if necessary. Consult the electrical wiring for more detail.
Dirty Filter
Clogged filter
Check and replace filter if necessary
Sensitive switch
Check the dirty air filter switch and recalibrate the sensitivity level if necessary. Consult the electrical wiring for more detail.
High Pressure
Refrigerant pressure rises above limit
Check the high head pressure and reset the alarm after a manual reset on the pressure switch.
Low Pressure
Refrigerant pressure drops below limit
Check for low pressure switch. Change low pressure bypass time out and reset the alarm after rectifying the problem.
Page 80
Rev.03C 02-19-14
Page 80 of 82
Compu-Aire
Compressors short cycling
Compress ON/OFF too frequent
Check discharge and return air temperature. Adjust compressor Max ON if needed.
Heater Overheat Heater overload
Check if heater is overloading. Check and reset alarm after rectifying the problem
Incorrect trigger level
Verify setting under “Technician->DI Setup- >Heater Overheat” Alarm IF=Closed
Smoke Alarm
Smoke detected
Check for fire hazard and reset alarm after rectifying the problem.
Condensate Alarm
Water detected
Check for water level on the bottom tray. Check drain valve and reset alarm after rectifying the problem.
Pump failed
Condensate pump failed
Check pump for proper voltage and wiring.
Check pump’s floaters for consistency. Check if water still resides in pump’s reservoir. Reset
alarm after rectifying the problems.
Page 81
Rev.03C 02-19-14
Page 81 of 82
Compu-Aire
Page 82
Rev.03C 02-19-14
Page 82 of 82
Compu-Aire
TECHNICAL SUPPORTS