Compu-aire CELHP, CELAC, CELLU-KOOL CELHP, CELLU-KOOL CELAC Installation, Operation, Maintenance And Parts Manual

Page 1
INSTALLATION
OPERATION
MAINTENANCE
AND PARTS
MANUAL
CELLU – KOOL SERIES
MODEL
CELHP HEAT PUMP 1 ½ TO 5 TON
CELAC AIR CONDITIONER 1 ½ TO 5 TON
TYPE
SIZE
COMPU – AIRE INC.
8167 BYRON RD. WHITTIER, CA 90606
PH : (562) 945 – 8971 FAX : (562) 696 - 0724
Page 2
--GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump.
You can
usually find these at your local publisher.
Be sure to consult current edition of each standard.
National Electrical Code Standard For The Installation
Of
Air
Conditioning and Ventilating Systems
Standard For Warm
Air
Heating
and
Air
Conditioning Systems
Load Calculation For Residential Winter and Summer
Air
Conditioning
Duct
Air
Conditioning and Equipment Selection
Manual
Manual D
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS
AIR
CONDITIONING CONTRACTORS OF AMERICA 1513 16th Street Washington,
20036
Telephone: (202) 483
-
9370 Fax: (202) 234-4721
ANSI
AMERICAN
NATIONAL STANDARDS INSTLTUTE
11
West Street, 13th Floor New York, NY 10036 Telephone: (212) 642
-
4900 Fax: (212) 302-1286
ASHRAE:
AMERICAN SOCIETY OF HEATING REFRIGERATING AND
AIR
CONDITIONING ENGINEERS, INCORPORATED 1791 Tullie Circle, N.E. Atlanta,
30329-2305
-
8400 Fax: (404) 321-5478
t
NFPA: NATIONAL FIRE PROTECTION ASSOCIATION
Batterymarch Park P.
0. Box 9101
Quincy,
MA
02269-9901
Telephone: (800) 344
-
3555 Fax: (617) 984-7057
COPYRIGHT NOVEMBER
1995
I
RE
I
90606
Page 3
CELLU-
KOOL
AIR CONDITIONER
PUMP
AIR
OUT
ELECTRIC HEATER (OPTIONAL)
-
EVAPORATOR COIL
EVAPORATOR BLOWER
HIGH EFFICIENCY MOTOR
7
HIGH
COMPRESSOR
'AGE CONTROL PANEL
CONDENSER COIL
MODEL
3 3
4
HASE
SINGLE PHASE
THREE PHASE
YSTEM CAPACITY
4=4
TON
YSTEM TYPE
HP= HEAT PUMP
ERTICAL WALL HUNG UNITS
Page 4
Page 5
SUPPLY
ACCESS
AND
BLOWER MOTOR
FREE
CONDENSER
AIR
INLET
DRAIN
-
HOLE
.
FREE
INLET
CONDENSER
AIR
REAR VIEW
ACCESS
CONDENSING
FRONT
VIEW
Ram
Page 6
7
COOLING
COIL
DAMPER BLADE
OUTSIDE
AIR
COND.
AIR
CONDENSER
EXHAUST AIR
Page 7
GENERAL
The
equipment covered in this manual is to be installed by tralned, experienced service and
technicians. The refrigerant system is conpletely assembled and charged.
All
internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the reconmended method to install the air cooled self
-
contained unlt and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire
air conditioning system should
be
carefully read before beginning the installation. Note particularly
"
Starting Procedure" and any tags and/or labels attached to the equiplent.
While these instructions are intended as a general recormended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is
1
for information on codes and standards.
Size of unit for a proposed installation should
be
based on heat loss calculation made according to nethods
of Air Conditioning Contractors of Amer~ca (ACCA). The air duct should
be
installed in accordance wlth the
Standards of the National Fire
and
Ventilating systems of Other Than Residence Type. NFPA
No.
Conditioning Systems.
Where local regulations are at a variance with instruct~ons, Installer
should adhere to local codes.
DUCT
WORK
is nore critical of proper operating charge and an adequate duct system than a straight air
conditioning unit. All duct work, supply and return.
the
design air flow requirement of the equipment. Air Conditioning Contractors of America sizing. A11 duct work or portions thereof not in the conditioned space should
be
properly insulated in order
to both
Design the duct work according to
When
duct runs through unheated spaces, it should
be
insulated with a mininun of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct
A
Ill-inch clearance to conbustible material for the first three feet of duct attached to the outlet air
frame is required.
Ducts through the walls must
be
insulated and all joints taped or sealed to prevent air or moisture entering
the wall cavity,
CAUTION:
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not
be
larger than
inches.
Any grille that meets the
5/8
inch louver criteria, may
be
used. It
is
be
installed when no return duct is used. Contact distributor
or factory for ordering
be
of
sufficient size to allow a maximum velocity of
400
If
no return air duct is used, applicable installation codes may limit this cabinet to installation
only in a single story structure.
Page 8
FILTERS
A 1-inch throwaway filter is supplied with each unit.
The filter slides into position
service.
This filter can
be
serviced from the outside by renoving the service dm. A 1-inch washable filter and 2-'inch pleated are adjustable to accommodate the 2-inch filter
by
the brackets apart to the required width and retightening the
4
screws.
OPTIONAL
FRESH AIR INTAKE
All units are built with a fresh air inlet slots punched in the service panel.
The fresh air damper assembly is standard
with the unit because of the variety of state or local
codes
requiring fresh air capability. It is shipped already attached to each unit.
All capacity, efficiency and cost of operation information as required for
Pact Sheets is based upn the fresh air blank-off plate in place and is recommended for max~mua energy efficiency.
-
off plate is available upon request from the factory and is installed in place of the fresh air
CONDENSATE DRAIN
A plastic drain hose extends fron the drain pan at the top of the unit down to the unlt base, There are
openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to
a
drain systea of some type, it must
be
an open or vented type system to assure proper drainage.
INSTALLATION INSTRUCTIONS
WALL
1.
holes, for the supply and return air openings, must
be
cut through the wall as shown in Figure
2,
On
wood-frame walls, the wall construction must
be
strong and rigid enough to carry the welght of the un~t
without transmitting any unit vibration. WARNING:
Fire hazard can result if 119-inch clearance to
3.
Concrete block walls must
be
thoroughly inspected to insure that they are capable of carrylnq the weight
of the installing unit.
THE
UNIT
1.
These units are secured
by
wall mounting brackets which secure the unit to the outside wall surface at
bath sides. A bottom
2.
The unit itself is suitable for
inch clearance, but the supply air duct flange and the first three
feet of supply air duct require a
If
a
combustible wall. use a
x
dimensions
sizing. However,
it
is generally
recommended that a
clearance is used for ease of installation and maintaining the required clearance
to combustible material.
The supply air opening would then
be
30
"
x
10".
See Fiqures 2 and
2A
for
details.
Page 9
Locate and nark lag bolt locations and bottom mounting bracket location,
if
desired. See Figure
2,
Book
top rain flashing under back bend of top. Top rain flashing is shipped attached to the back of the
unit on the right side. Position unit in opening and secure with
5/16
lag bolts: use
inch diameter flat washers on the lag
bolts. Secure rain flashing to wall and caulk across entire length of top. See Figure
7.
For additional munting rigidity, the return air and supply air frames or collars can
be
drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
On
side
by
side installations, maintain a minimum of
20
inches clearance on right
side
to allow access to
control panel and heat strips and allow proper airflow to the
nay
be
required to meet local or national codes.
TOP OUTLET ONLY
Coat angles with
beads of silicone as shown.
Silicone
shipped in the control panel, See
Figure Secure angles to the top of the unit with
screws provided.
Use of prepunched holes provided.
not relocate. See Figure After installation of ductwork, seal around airframe and ductwork to provide a rain tlght seal. It is strongly recommended, but not required, that this unit
be
installed under a soffit area Iarqe
enough to shield the top of the unit. See Figure
2C.
Page 10
IT
IS
A
BEAD
OF
SILICONE CAULKING
BE
PLACED
BEHIND
TEE
SIDE
FLANGES
AND
UNDER
TO?
FLASHING
AIR
A
a
Page 11
ELECTRIC
BEAT
NOTE
Side section view of supply air duct for wall naunted unit showing
clearance to conbustible surfaces.
WARNING
A
clearance must
be
This
is
required for the first 3 feet of ducting.
It
is important to insure that the
Failure to do this could result in overheating the mnbuntible material and nay result
in
a
fire.
Page 12
Page 13
Refer to the unit rating
plate for wire sizing
information and maximum fuse or
"
HACR Type
"
circuit breaker size.
Each outdoor unit is marked with a
This means
that the field wiring used must
be
sized to carry that amount of current.
Depending on the
installed
of electric heat, there may
be
two field power circuits required.
If this is the
case, the unit serial plate will so indicate.
All
copper wire.
Each unit and/or wiring diagram wi
be
marked "Use Copper Conductors On1 y". These
instructions MUST
BE
adhered
to.
Refer to the National Electrical Code (NEC) for complete
current carrying capacity data on the various insulation grades of wiring material.
All
wiring
must conform to NEC and all local codes. The electrical data lists fuse and wire sizes various models with heaters. The unit rating plate
ists a "Maximum Time Delay Relay Fuse" or "HACR Type" circuit breaker that
is to be used with the equipment. The correct size must
be
used for proper circuit protection
and also to assure that there will
be
no
nuisance tripping due
to
the momentary high starting
current of the compressor motor.
SERVICE
HINTS
1.
Caution homeowner to maintain clean air filters at all times. Also, not
to
needlessly
close off supply and return air registers. This reduces air flow through the system,
which shortens
2.
Switching
to
heating cycle at
or higher outside temperature may cause a nuisance
trip of the
reset high pressure switch. Turn thermostat off, then on the reset
the high pressure switch.
3.
The heat pomp wall thermostats perform multiple functions.
Be
sure that all function
switches are correctly set for the desired operating mode before trying to diagnose any
reported service problems.
4.
Check all power fuses or circuit breakers to be sure they are the correct rating.
5.
Periodic cleaning of the outdoor coil to permit full and unrestricted airflow
circulation is essential.
Page 14
SEQUENCE OF OPERATION
-
Y makes at thermostat pulling In conpressor contactor, starting the compressor and outdoor
The
be
energized
by
solenoid coil on reversing valve controls heating cycle operation.
Two
one allowing
"
Auto" changeover fron cycle to cycle and the other constantly energizmg solenold coll during
heating season and thus elininating pressure equalization
be
used.
On
"
Auto" option. a circuit is conpleted from R-Ul and
R-Y
on each heating "on" cycle,
valve solenoid and pulling in compressor contactor startlng compressor and outdoor notor.
also make
starting indoor blower motor. Heat Pump heating cycle now in operation.
The second option has no
"
Auto
" changeover position. but instead energizes the revering valve solenoid constantly whenever the systen sw~tch on subbase is placed in "Heat" position. the
R.
A thermostat
demand for heat completes
R-Y
circuit, pulling in compressor contactor starting compressor and outdoor
mtor.
PRESSURE SERVICE PORTS
pressures can
be
observed. Pressure curves can be found later in the nanual covering all nodels on both cooling and heatlng cycles. It is imperative to match the correct pressure curve to the unit
by
DEFROST CYCLE
The
defrost cycle is controlled by temperature and time on the solid state heat pu~p control,
is
or below.
This
coil temperature is sensed by the coil sensor nounted near the bottom of the
or below. the coil sends a signal to the control logic
of
the heat
control and the defrost timer will start.
After
60
or
belov, the heat punp control will place the system in the defrost
node. During the
stops,
electric heaters are energized, and hot gas passing through the outdoor coil me1 ts any accunulator frost.
the coil sensor will send a signal to the heat punp
control which will return the
If
cycle, the heat punp control will restore the
Page 15
TROUBLESHOOTING
SOLID
STATE
HEAT
1.
Turn on AC power supply to indoor and outdoor units.
2.
Turn thermostat blower switch to fan on--the indoor blower should start. (If it doesn't, troubleshoot indoor unit and correct problem).
Turn thermostat blower switch to auto position. Indoor blower should stop.
4.
Set system switch
to
heat or cool. Adjust thermostat to call for heat or cool--The
indoor blower, compressor, and outdoor fan should start.
NOTE:
If there was
no
power
to
24
volt transformer, the compressor and outdoor fan motor will
not start for
5
minutes. This is because of the compressor short cycle protection.
Page 16
FAN
SETTING DIMENSIONS
Shown
in the drawing below are the correct fan blade setting dimensions for proper air delivery across the
service
requiring renxral or adjustment in the fan andlor notor area
will
require that the
dinensions below
be
checked and blade adjusted in or out on the motor shaft accordingly.
REMOVAL
OF
THE
FAN
SHROUD
2.
the
3.
screws.
5.
Slide complete motor, fan blade, and shroud asseably out the left side of the unit.
6.
7.
Rwerse steps to reinstall
Loading...