Compass CPL25 Installation Instructions Manual

Page 1
CPL25
UNIVERSAL INPUT, AC OUTPUT, BATTERY PACK
INSTALLATION INSTRUCTIONS
! IMPORTANT SAFEGUARDS !
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS
BE FOLLOWED, INCLUDING THE FOLLOWING:
1. To prevent high voltage from being present on the orange/black and yellow/black output leads prior to installation, battery connection must be open. Install battery connector after the battery pack has been installed and before the AC power is supplied.
2. For use with fluorescent, incandescent or LED fixtures up to 25 W (20°C to 40°C including driver/ballast) at unity power factor.
3. Make sure all connections are in accordance with the National Electrical Code and any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and auxiliary power supplies and battery connector of the battery pack before servicing.
5. This battery pack is suitable for factory or field installation.
6. An AC power source (120, or 277 VAC, 60 Hz) ahead of any wall switch is required to provide battery charging current.
7. Do not install near gas or electric heaters.
8. This product is for use with indoor or damp locations where ambient temperature is 20°C to 40°C. Not suitable for wet or hazardous locations.
9. This is a sealed unit. Integral battery is not replaceable. Replace entire unit when necessary.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
SAVE THESE INSTRUCTIONS
WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects
and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
INSTALLER:
SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
CAUTION: DISCONNECT POWER DURING INSTALLATION AND BEFORE SERVICING.
READ ALL INSTRUCTIONS COMPLETELY BEFORE STARTING INSTALLATION.
1
Page 2
INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON ORANGE/BLACK AND YELLOW/BLACK OUTPUT LEADS PRIOR TO INSTALLATION, BATTERY CONNECTOR MUST BE OPEN. INSTALL BATTERY CONNECTOR AFTER INSTALLATION IS COMPLETE AND BEFORE AC POWER IS SUPPLIED.
NOTE: Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required. The unswitched and switched power source must be fed from the same branch circuit.
INSTALLING THE BATTERY PACK
The battery pack will be located between the AC power sources and the AC ballast/driver as shown in wiring diagram section of instructions.
NOTE: The battery pack may be installed in close proximity to the fixture or remote from the fixture.
The maximum remote distance using 16 AWG wire is 250 ft. Contact the factory for more information.
The AC power is fed to the battery pack.
The AC ballast/driver receives power from the battery the orange/black and yellow/black leads .
pack. The output wires of the battery pack are
STEP 1 - DISCONNECT AC POWER FROM FIXTURE
Disconnect all power sources from lighting fixture and ensure they are locked out during installation or maintenance.
Disconnect power leads from the AC ballast/driver.
Select a suitable location for the battery pack and install such that its output leads can connect to the input leads of the AC ballast/driver.
See Illustration 1, for typic
al installation and select appropriate mounting method.
STEP 2 - WIRING THE BATTERY PACK
Use the wiring diagram found on page 4 as reference.
Connect the AC power source leads to the input of the battery pack.
Connect the output leads of battery pack to the AC ballast/driver.
Wire the AC ballast/driver with the lamp in accordance with manufactures installation instructions. No ballast/driver is necessary for incandescent lamp application.
Make sure all connec
Connect the indicator LED by matching violet and brown leads.
In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And DC Power Supply (Battery Connector) Before Servicing.”
tions are in accordance with the National Electrical Code and any local regulations.
2
Page 3
STEP 3 – INSTALL BATTERY CONNECTOR & APPLY POWER
After installation is complete, join the battery connector and apply AC power.
Power should now be connected to both the AC ballast and the battery pack, and the Charging Indicator Light should illuminate indicating the battery is charging.
A short-term discharge test may be conducted by pressing the test switch after the battery pack has been charging for 1 hour. The battery should be fully charge
d in 32 hours and ready for a long term discharge test.
TEST/MONITOR
PLATE
1 – Flexible conduit (supplied) to connect ballast wires. 2 – Existing conduit to run existing wires to lamp holder. 3 – AC line in. 4 – Conduit and junction box (not supplied).
3
Page 4
OPERATION
During normal operation, AC power is supplied to the AC ballast/driver through the battery pack as it charges the battery. Installing the battery connector enables the emergency circuit and supplies power to the control/monitor circuit. The battery pack detects AC input line voltage (120 or 277 Volts) and automatically sets the output voltage during emergency mode.
When AC power fails, the battery pack automatically switches to emergency mode, keepi for a minimum of 90 minutes. When AC power is restored, the battery pack returns to charging mode. The battery pack detects normal and fault conditions and signals those conditions through the Red LED as follows:
LED OPERATION:
Steady on: normal charging
Single blink:
1. Test switch pressed before completing one hour charging.
2. Battery voltage less than or equal to 6 volts.
3. Battery voltage less than 12 volts after charging for 32
Double blink:
1. Load current too high.
2. Charge current too low.
NOTE: Press test switch to clear error, stop blinking and restart
hours.
ng the load illuminated
MAINTENANCE
Although no routine maintenance is required to keep the battery pack functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals should operate at full illumination.
3. Conduct a 90-minute discharge test once a year. The lamp should operate at full illumination for at least 90 minutes.
for a minimum of 30 seconds. The lamp
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL.
BATTERY PACK AND AC BALLAST/DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
4
Page 5
INSTALLATION WIRING DIAGRAM
AC Battery Pack CPL25
Charging Light +
Charging Light
Battery Connector
Battery Connector
AC Ballast/Driver with Lamp 25 Watts Max
AC Line
Unswitched 120VAC or 277VAC, 60Hz
AC Neutral
Orange/Black (AC Ballast/Driver Line 120/277VAC)
Yellow/Black (AC Ballast/Driver Neutral)
WALL SWITCH
White/Red
Black
White
AC Line Out
AC Neutral Out
120/277 VAC Switched
120/277 VAC Unswitched
Neutral
REMOVAL INSTRUCTIONS
To avoid a shock hazard, the following steps must be done in the order shown:
Charge LED
Brown
Red
Violet
Red
Test Switch
Connect on Installation
a. Turn-off AC power to the battery pack by disconnecting the AC Branch Circuit Breakers or Fuses. b. Disconnect the battery connector of the battery pack. c. All wiring may then be disconnected as needed to remove the battery pack.
Copyright© Hubbell Lighting, Inc.• 701 Millennium Bvld • Greenville, SC 29607 • (864) 678-1000 • FAX(864) 678-1415 • www.dual-lite.com