Compaq Pro UPS 500 Operation And Reference Manual

Page 1
Compaq Pro UPS 500
Operation and Reference Guide
First Edition (February 2000) Part Number 146293-001 Compaq Computer Corporation
Page 2

Notice

The information in this publication is subject to change without notice.
COMPAQ COMPUTER CORPORATION SHALL NOT BE LIABLE FOR TECHNICAL OR EDITORIAL ERRORS OR OMISSIONS CONTAINED HEREIN, NOR FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE FURNISHING, PERFORMANCE, OR USE OF THIS MATERIAL. THIS INFORMATION IS PROVIDED “AS IS” AND COMPAQ COMPUTER CORPORATION DISCLAIMS ANY WARRANTIES, EXPRESS, IMPLIED OR STATUTORY AND EXPRESSLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, GOOD TITLE AND AGAINST INFRINGEMENT.
This publication contains information protected by copyright. No part of this publication may be photocopied or reproduced in any form without prior written consent from Compaq Computer Corporation.
© 2000 Compaq Computer Corporation.
All rights reserved. Printed in the U.S.A.
The software described in this guide is furnished under a license agreement or nondisclosure agreement. The software may be used or copied only in accordance with the terms of the agreement.
Compaq, Deskpro, Fastart, Compaq Insight Manager, Systempro, Systempro/LT, ProLiant, ROMPaq, QVision, SmartStart, NetFlex, QuickFind, PaqFax, ProSignia, registered United States Patent and Trademark Office.
Netelligent, Systempro/XL, SoftPaq, QuickBlank, QuickLock are trademarks and/or service marks of Compaq Computer Corporation.
NeoServer is a trademark of Compaq Information Technologies Group.
Microsoft, MS-DOS, Windows, and Windows NT are registered trademarks of Microsoft Corporation.
Pentium is a registered trademark and Xeon is a trademark of Intel Corporation.
Other product names mentioned herein may be trademarks and/or registered trademarks of their respective companies.
Compaq Pro UPS 500 Operation and Reference Guide First Edition (January 2000) Part Number 146293-001
Page 3

Contents

About This Guide
Text Conventions....................................................................................................... vi
Symbols in Text....................................................................................................... vii
Symbols on Equipment............................................................................................ vii
Precautions............................................................................................................... vii
Getting Help ............................................................................................................ viii
Compaq Technical Support ...............................................................................viii
Compaq Website ...............................................................................................viii
Compaq Authorized Reseller...............................................................................ix
Chapter 1
Introduction
Compaq Pro UPS 500 Models................................................................................. 1-2
Front Panels ............................................................................................................. 1-3
Rear Panels .............................................................................................................. 1-4
Compaq Pro UPS 500 Features ............................................................................... 1-6
Communications Port ....................................................................................... 1-6
Power Management Software........................................................................... 1-6
Phone/Fax Surge Protector ............................................................................... 1-7
Warranties................................................................................................................ 1-8
$25,000 Computer Load Protection Guarantee ................................................ 1-8
Pre-Failure Battery Warranty ........................................................................... 1-8
Chapter 2
Installation
Installation Requirements ........................................................................................ 2-2
Items Not Supplied with the UPS Kit............................................................... 2-2
Items Supplied with the UPS Kit...................................................................... 2-2
Page 4
iv Compaq Pro UPS 500 Operation and Reference Guide
Installation (continued)
Before Starting the UPS........................................................................................... 2-3
UPS Requirements............................................................................................ 2-3
Connecting the UPS Communications Port...................................................... 2-4
Connecting the UPS Phone/Fax Surge Protector.............................................. 2-5
Verifying a Safe UPS Load............................................................................... 2-6
Starting the UPS....................................................................................................... 2-7
Connecting Devices to the UPS........................................................................ 2-7
Circuit Requirements ...................................................................................... 2-10
Connecting the UPS to Utility Power: 120VA and 100VA Models ............... 2-10
Connecting the UPS to Utility Power: 230VA Model.................................... 2-11
Connecting the UPS to an AC Generator........................................................ 2-11
Completing the Installation.................................................................................... 2-14
Installing Compaq Power Manager Pro UPS Software ................................. 2-14
Selecting the UPS Operating Mode ................................................................ 2-14
Chapter 3
Operation
Operation Precautions.............................................................................................. 3-2
Front Panel Overview .............................................................................................. 3-3
Front Panel Controls ................................................................................................ 3-4
ON/STANDBY Button..................................................................................... 3-4
TEST/ALARM RESET Button ........................................................................ 3-8
Front Panel Indicators and Audio Alarms.............................................................. 3-10
LINE STATUS Indicator (Green)................................................................... 3-10
ON BATTERY Indicator (Yellow)................................................................. 3-10
BATTERY LOW/REPLACE Indicator (Red)................................................ 3-11
UPS LOAD Indicator (Red)............................................................................ 3-11
Rear Panel Overview .............................................................................................3-12
Rear Panel Features................................................................................................ 3-13
Battery-and-Surge-Protected Receptacles....................................................... 3-13
RJ11 Phone/Fax Surge Protector .................................................................... 3-14
Communications Port ..................................................................................... 3-14
Surge-Protected Receptacle(s)........................................................................ 3-14
AC Power Input Receptacle (230VA Model Only) ........................................ 3-14
Battery Replacement Door.............................................................................. 3-14
Chapter 4
Software
Software Overview ..................................................................................................4-2
Software Functions ..................................................................................................4-2
Displaying UPS Status...................................................................................... 4-2
UPS Control Functions ..................................................................................... 4-3
Configuration Parameters ........................................................................................4-3
Page 5
Chapter 5
Battery Maintenance
Battery Precautions.................................................................................................. 5-2
Charging Batteries ................................................................................................... 5-2
When to Replace Batteries....................................................................................... 5-3
Pre-Failure Battery Warranty................................................................................... 5-3
Obtaining New Batteries.......................................................................................... 5-4
Care and Storage of Batteries .................................................................................. 5-4
Disposing of Used Batteries .................................................................................... 5-4
Chapter 6
Troubleshooting
Troubleshooting During UPS Start.......................................................................... 6-2
Troubleshooting After UPS Start............................................................................. 6-3
Repairing the UPS ................................................................................................... 6-4
Appendix A
Regulatory Compliance Notices
Federal Communications Commission Notice ........................................................A-1
Class B Equipment ...........................................................................................A-1
Modifications....................................................................................................A-3
Cables ...............................................................................................................A-3
FCC Part 68 Notice ..........................................................................................A-3
Canadian Notice (Avis Canadien) ...........................................................................A-3
Class B Equipment ...........................................................................................A-3
European Union Notice ...........................................................................................A-4
Japanese Notice .......................................................................................................A-4
China Taiwan Notice...............................................................................................A-5
Battery Replacement Notice....................................................................................A-5
About This Guide v
Appendix B
Specifications
Physical Specifications ............................................................................................ B-2
Input Specifications .................................................................................................B-2
Output Specifications...............................................................................................B-3
Output Specifications (continued) ...........................................................................B-4
Battery Specifications..............................................................................................B-5
Environmental Specifications..................................................................................B-5
Index
Page 6
This guide is designed to be used as step-by-step instructions for installation
and as a reference for operation, troubleshooting, and future upgrades.
Text Conventions
This document uses the following conventions to distinguish elements of text:
Keys Keys appear in boldface. A plus sign (+) between
USER INPUT User input appears in a different typeface and in

About This Guide

two keys indicates that they should be pressed simultaneously.
uppercase.
FILENAMES File names appear in uppercase italics.
Menu Options, Command Names, Dialog Box Names
COMMANDS, DIRECTORY NAMES, and DRIVE NAMES
Type When you are instructed to type information, type
Enter When you are instructed to enter information, type
These elements appear in initial capital letters.
These elements appear in uppercase.
the information without pressing the Enter key.
the information and then press the Enter key.
Page 7
vii Compaq Pro UPS 500 Operation and Reference Guide
Symbols in Text
These symbols may be found in the text of this guide. They have the following meanings.
WARNING: Text set off in this manner indicates that failure to follow directions in the warning could result in bodily harm or loss of life.
CAUTION: Text set off in this manner indicates that failure to follow directions could result in damage to equipment or loss of information.
IMPORTANT: Text set off in this manner presents clarifying information or specific instructions.
NOTE: Text set off in this manner presents commentary, sidelights, or interesting points of information.
Symbols on Equipment
These icons may be located on equipment in areas where hazardous conditions may exist.
Precautions
Any surface or area of the equipment marked with these symbols indicates the presence of electrical shock hazards. Enclosed area contains no operator serviceable parts. WARNING: To reduce the risk of injury from electrical shock hazards, do not open this enclosure.
WARNING: There is a risk of personal injury from the hazardous energy levels associated with handling the UPS battery. The maintenance and replacement of the battery must be carried out by qualified service personnel.
IMPORTANT: Please refer to the Important Safety Information guide (included with the UPS kit) before installing this product.
Page 8
Getting Help
If you have a problem and have exhausted the information in this guide, you
can get further information and other help in the following locations.
Compaq Technical Support
About This Guide viii
In North America, call the Compaq Technical Phone Support Center at
1-800-OK-COMPAQ (1-800-652-6672)
day, 7 days a week.
Outside North America, call the nearest Compaq Technical Support Phone
Center. Telephone numbers for world wide Technical Support Centers are
listed on the Compaq website. Access the Compaq website at:
http://www.compaq.com.
Be sure to have the following information available before calling Compaq:
Technical support registration number (if applicable)
Product serial number(s)
Product model name(s) and number(s)
Applicable error messages
Add-on boards or hardware
Third-party hardware or software
Operating system type and revision level
Detailed, specific questions
Compaq Website
1
. This service is available 24 hours a
For more information on Compaq products, access the Compaq website at:
http://www.compaq.com.
1
For continuous quality improvement, calls may be recorded or monitored.
Page 9
ix Compaq Pro UPS 500 Operation and Reference Guide
Compaq Authorized Reseller
For the name of the nearest Compaq authorized reseller:
In the United States, call 1-800-345-1518.
In Canada, call 1-800-263-5868.
Elsewhere, access the Compaq website at:
http://www.compaq.com.
Page 10
Introduction
This chapter provides information on the following topics:
Compaq Pro UPS 500 models
Compaq Pro UPS 500 features
Warranties
Chapter 1
Page 11
1-2 Compaq Pro UPS 500 Operation and Reference Guide
Compaq Pro UPS 500 Models
The Compaq Pro UPS 500 includes the following models and part numbers:
Compaq Pro UPS 500 Model Descriptions
Table 1-1
UPS Model UPS Kit
Part Number
500 136386-001 120VA; North America; Tower
500 136386-291 100VA; Japan; Tower
500 136386-B31 230VA; International; Tower
Comments
Table 1-2
Compaq Pro UPS 500 Model – Additional Part Information
UPS Model Spare Parts
Kit Number
500 155373-1 112666-010
500 155373-291 112666-010
500 155373-2 Not Applicable
RJ11 Phone/Fax Surge Protector
Cable Part Number
Page 12
Front Panels
The Compaq Pro UPS 500 models feature the following front panel
configuration:
Figure 1-1. Front panel configuration
Introductio n 1-3
5 62 3 41
ON/STANDBY button
LINE STATUS indicator
ON BATTERY indicator
BATTERY LOW/REPLACE indicator
UPS LOAD indicator
TEST/ALARM RESET button
Symbol
Page 13
1-4 Compaq Pro UPS 500 Operation and Reference Guide
Rear Panels
The Compaq Pro UPS 500 models feature the following rear panel configurations:
6
5
4
Figure 1-2. Rear panel configuration - 100VA and 120VA models
Communications port
Noise and surge-protected
receptacles
Non-detachable input power
cord with NEMA 5-15 plug
1
2
3
Battery compartment
Battery, noise, and surge-protected
receptacles
RJ11 Phone/Fax Surge Protectors
Page 14
5
4
Figure 1-3. Rear panel configuration - 230VA model
Introductio n 1-5
1
2
3
Communications port
Noise and surge-protected
receptacle
IEC-320 power inlet
Battery compartment
Battery, noise, and surge-protected
receptacles
Page 15
1-6 Compaq Pro UPS 500 Operation and Reference Guide
Compaq Pro UPS 500 Features
500VA of reliable battery backup supports critical loads, such as
computers and monitors.
Special surge-protected receptacle(s) safeguard non-critical equipment
without devoting battery power for their support.
Automatic Voltage Regulation (Boost) supports connected equipment
through periods of low voltage (brownouts) without using battery power.
Intelligent communications port and Compaq Power Manager Pro UPS
software provide unattended shutdown and power monitoring.
Surge-protected RJ11 Phone/Fax connection (available on select
models) safeguards equipment on-line.
Communications Port
The Compaq Pro UPS 500 includes a communications port for data exchange with the host computer. Compaq Power Manager Pro UPS software (supplied with the UPS) enables the user to access status reporting and power management features.
Compaq Power Manager Pro UPS Software
Compaq supplies Compaq Power Manager Pro UPS software with each Compaq Pro UPS 500. This power management software allows system administrators to monitor and manage the power being supplied to an entire network of servers and workstations.
Software capabilities include:
Monitoring utility power, and the power supplied by the UPS.
Logging events.
Setting up messaging and protective actions in response to events.
Checking and resetting alarms.
Saves work-in-progress and initiates orderly shutdown of operating
systems when an extended utility power failure occurs.
Powering down battery-protected devices.
Page 16
For example, if the software detects an extended utility power blackout, the
program will initiate messaging across the system and will start an operating
system shutdown.
For more information on using the Compaq Power Manager Pro UPS
software, see Chapter 4, “Software.”
NOTE: Select Compaq NeoServers have UPS power management software preinstalled. Some NeoServer customers may not need to install Compaq Power Manager Pro UPS software. Please see the NeoServer documentation included with the NeoServer unit for specific power management software installation requirements.
RJ11 Phone/Fax Surge Protector
Select Compaq Pro UPS 500 models include a Phone/Fax Surge Protector that
safeguards communications equipment (such as a fax machine or a modem)
from spikes and surges from transients present on telephone lines.
Introductio n 1-7
Page 17
1-8 Compaq Pro UPS 500 Operation and Reference Guide
Warranties
$25,000 Computer Load Protection Guarantee
To back up the wide range of features offered with the UPS, Compaq provides a two-year limited warranty. In addition, Compaq offers a $25,000 Computer Load Protection Guarantee.
The $25,000 Computer Load Protection Guarantee only applies in the following circumstances:
The UPS is plugged into a suitably grounded and wired outlet using no
extension cords, adapters, other ground wires, or other electrical connections.
The UPS installation complies with all applicable electrical and safety
codes specified by the National Electrical Code (NEC).
The UPS is used under normal operating conditions. (Users comply with
all instructions and labels.)
The UPS is not damaged by accident (other than a utility power
transient), misuse, or abuse.
Pre-Failure Battery Warranty
The Pre-Failure Battery Warranty, standard on all Compaq Uninterruptible Power Systems, extends the advantage of a Compaq two-year limited warranty by applying warranty coverage to the battery before the battery actually fails. Specifically, the Pre-Failure Battery Warranty ensures that when customers receive notification from Compaq Power Manager Pro UPS software that the battery may fail, the unit is replaced free of charge under the warranty.
Compaq maintains the highest standards in the industry, as evidenced by the Compaq Pre-Failure Battery Warranty. The Pre-Failure Battery Warranty is beneficial in at least two significant ways:
Reduced total cost of ownership
Reduced downtime
Page 18
This chapter provides information on the following topics:
Installation requirements
Procedures to complete before starting the UPS
UPS requirements
Connecting the UPS communications port
Connecting the UPS Phone/Fax Surge Protector
Verifying a safe UPS load
Chapter 2
Installation
Starting the UPS
Connecting devices to the UPS
Circuit requirements
Connecting the UPS to utility power
Connecting the UPS to an AC generator
Completing the installation
Installing Compaq Power Manager Pro UPS software
Selecting the UPS operating mode
Page 19
2-2 Compaq Pro UPS 500 Operation and Reference Guide
Installation Requirements
Items Supplied with the UPS Kit
The UPS kit should contain the following components:
Software/Reference Material
The Compaq Power Manager Pro UPS Software and Documentation CD
containing the:
Compaq Power Manager Pro UPS software
Compaq Pro UPS 500 Operation and Reference Guide
The Software Installation Instructions (insert included with the Compaq
Power Manager Pro UPS software CD) containing information on the installation requirements for Compaq Power Manager Pro UPS software
Important Safety Information guide (included with the UPS kit) to be
reviewed before installing this product
Hardware
The UPS ships with one or more of the following:
The 120VA and 100VA models ship with a non-detachable input power
cord with a NEMA 5-15 plug, and an RS-232 UPS/computer interface cable, Compaq part number 159074-001.
The 230VA model ships with an IEC-320 jumper cord (for load
equipment power), and an RS-232 UPS/computer interface cable, Compaq part number 159074-001.
Compaq Pro UPS 500 models ship with an RS-232 UPS/computer interface cable. The computer interface cable is not needed for normal operation. If power management of the UPS is desired, connect the interface cable between the UPS communications port and the serial port on the host computer.
IMPORTANT: If the UPS does not include a power cord that is suitable for the application, contact an authorized Compaq service representative to obtain the appropriate power cord. Please refer to the “Precautions for Power Products” section of the Important Safety Information guide (included with the UPS kit).
Page 20
Battery
Compaq Pro UPS 500 models are shipped with the battery already installed.
Before Starting the UPS
This section provides procedures to be carried out before starting the UPS.
Determine the steps required for the application:
Understanding the UPS requirements
Connecting the UPS communications port to the host computer
Connecting the UPS Phone/Fax Surge Protector (select models only)
Verifying a safe UPS load
NOTE: Although some of these steps can be carried out after the UPS is installed, the UPS will need to be powered down to safely perform these tasks.
UPS Requirements
Installation 2-3
Confirm that the UPS power, at the outlet, does not routinely get turned
off. The UPS interprets any AC line failure as a blackout, and will operate accordingly. Even with the connected load equipment turned off, if the UPS inverter is enabled, the battery charge would slowly deplete.
For best performance, keep the indoor temperature between 32°F and
104°F (between 0°C and 40°C).
Compaq Pro UPS 500 models are intended for installation in a
temperature-controlled, indoor area free of conductive contamination. The unit must be kept dry at all times. Avoid exposing the UPS to high heat or humidity.
Do not block the cooling vents on the UPS unit. These vents must be
open for the UPS to operate properly.
Position the UPS at least 6 inches away from any monitors or floppy
disks. Small magnetic fields present during backup operation can cause monitor interference, and can disrupt information on disks.
Page 21
2-4 Compaq Pro UPS 500 Operation and Reference Guide
Connecting the UPS Communications Port
The Compaq Pro UPS 500 includes a communications port for data exchange with the host computer.
Connect the RS-232 UPS/computer interface cable (supplied) from the communications port on the UPS to the appropriate communications port on the host computer.
CAUTION: The Compaq Pro UPS 500 uses a standard RS-232 cable. To avoid damage to the equipment, do not use the communications cables supplied with other UPS models.
IMPORTANT: The Compaq Power Manager Pro UPS software requires the use of the communications port.
NOTE: Communications port connection is optional. The UPS will function properly without communications port connection. However, without this connection, the Compaq Power Manager Pro UPS software will not be able to shut down connected equipment in the event of a blackout.
Figure 2-1. Connecting the UPS/computer interface cable
Page 22
Connecting the UPS Phone/Fax Surge Protector
Select Compaq Pro UPS 500 models include a Phone/Fax Surge Protector that
allows the UPS to protect a communications device from surges on a single
phone line.
Connect a phone cord (user supplied) from the wall outlet to the UPS
connection labeled “IN” (
the UPS connection labeled “OUT” (
CAUTION: To avoid damage to the equipment, connect the Phone/Fax Surge Protector with an analog phone line or network only—not with a digital PBX.
NOTE: Phone/Fax Surge Protector connection is optional. The UPS will function properly without this connection.
). Connect a phone cord from your equipment to
).
1 2
Installation 2-5
Figure 2-2. Connecting the UPS Phone/Fax Surge Protector
Page 23
2-6 Compaq Pro UPS 500 Operation and Reference Guide
Verifying a Safe UPS Load
Before connecting any devices, verify that the Battery-and-Surge-Protected receptacles of the UPS will not overload. The cumulative VA rating of all devices (the load) to be connected to the Battery-and-Surge-Protected receptacles cannot exceed the 500VA rating.
Use the following conversion equation:
For devices listing the power in amperes:
Volts x Amps = VA per device
For devices listing the power in watts:
Watts x 1.35 = VA per device
NOTE: Verifying a safe load does not include the devices connected to the Surge-Protected receptacle(s).
Page 24
Starting the UPS
Starting the UPS for the first time requires the following procedures:
Connecting devices to the UPS
Understanding circuit requirements
Connecting the UPS to utility power
Powering up the UPS
Connecting Devices to the UPS
After verifying that the UPS will not overload, connect the power cords from
the devices to the appropriate receptacles of the UPS. Observe the following
precautions:
WARNING: Risk of electric shock or personal injury. This device has not been evaluated for use with medical equipment. Do not use this UPS in conjunction with any medical equipment application.
WARNING: To reduce the risk of electric shock, the combined earth conductor leakage current from all connected devices must not exceed 3.5 mA.
Installation 2-7
CAUTION:
Do not plug laser printers into the Battery-and Surge-Protected receptacles
of the Compaq Pro UPS 500. The instantaneous current drawn by this type of printer may overload the UPS circuit.
Never plug a UPS into itself. This WILL result in damage to the unit.
Always use the 3-prong grounding type plug, if the device is equipped
accordingly. Do not use an adapter or otherwise bypass the ground pin.
The use of an external surge protector plugged into the OUTPUT of the UPS
may cause the UPS to become overloaded when operating from battery power. Since the UPS already has surge suppression circuitry, adding extra surge suppression is not recommended.
The load equipment must be turned OFF before plugging into the UPS.
Page 25
2-8 Compaq Pro UPS 500 Operation and Reference Guide
Connecting Devices to the Battery-and-Surge-Protected Receptacles
Plug the equipment that needs battery backup support in the event of a blackout (such as the computer, monitor, and external modem) into the
Battery-and-Surge-Protected receptacles ( 100VA/120VA (left) and 230VA (right) models are illustrated below.
1 1
Figure 2-3. Connecting devices to the Battery-and-Surge-Protected receptacles ()
) on the UPS rear panel. The
Page 26
Installation 2-9
Connecting Devices to the
Surge-Protected Receptacle(s)
Plug non-critical equipment into the Surge-Protected receptacle(s) on the UPS
rear panel, as illustrated in the following figure. The Surge-Protected
receptacle(s) (
without committing valuable battery power to support the peripherals during
blackouts. The 100VA/120VA (left) and 230VA (right) models are illustrated
below.
) will provide connected peripherals with surge protection
2
2
Figure 2-4. Connecting devices to the Surge-Protected receptacles ()
NOTE: When the UPS is connected to utility power for the first time, all receptacles are energized regardless of the UPS mode of operation selected. All receptacles provide AC line power (during normal operating conditions) and complete surge and line noise protection.
Page 27
2-10 Compaq Pro UPS 500 Operation and Reference Guide
Connecting the UPS to Utility Power: 120VA and 100VA Models
WARNING: To reduce the risk of personal injury resulting from electric shock or
to avoid damage to the equipment:
Plug the input line cord into a grounded (earthed) electrical outlet that is
installed near the equipment and is easily accessible.
Do not disable the grounding plug on the input line cord. The grounding
plug is an important safety feature.
Do not use an extension cord.
CAUTION: Some motor-powered AC generators have voltage and frequency outputs that can fluctuate beyond nominal accepted ranges and can cause damage to the UPS if connected to the generator output. Consult the generator manufacturer before connecting the UPS to a generator.
Since the 120VA and 100VA models ship with a non-detachable input power cord (with a NEMA 5-15 plug), the only required step is to connect the UPS to a grounded utility wall outlet.
After connecting the UPS to utility power, check the front panel indicators. The green LINE STATUS indicator, either illuminated constantly (ON mode) or flashing (STANDBY mode), indicates the UPS mode of operation. If the UPS is in STANDBY mode, an audio alarm will sound.
1
Figure 2-5. The LINE STATUS indicator ()
Page 28
IMPORTANT: When the UPS is connected to utility power, all receptacles will immediately be energized regardless of the UPS operating mode selected (using the UPS ON/STANDBY button).
IMPORTANT: If any of the indicators on the front panel are red (indicating an alarm condition), press the TEST/ALARM RESET button to clear the red indicators. If this does not clear the red indicators, see Chapter 6, “Troubleshooting.”
IMPORTANT: If the UPS does not include a power cord that is suitable for the application, contact an authorized Compaq service representative to obtain the appropriate power cord.
For more information on the front panel indicators and controls, see Chapter 3,
“Operation.”
Connecting the UPS to Utility Power: 230VA Model
WARNING: To reduce the risk of personal injury resulting from electric shock or
to avoid damage to the equipment:
Plug the input line cord into a grounded (earthed) electrical outlet that is
installed near the equipment and is easily accessible.
Installation 2-11
Do not disable the grounding plug on the input line cord. The grounding
plug is an important safety feature.
Do not use an extension cord.
CAUTION: Some motor-powered AC generators have voltage and frequency outputs that can fluctuate beyond nominal accepted ranges and can cause damage to the UPS if connected to the generator output. Consult the generator manufacturer before connecting the UPS to a generator.
Page 29
2-12 Compaq Pro UPS 500 Operation and Reference Guide
The 230VA model ships with one IEC-320 jumper cord. To connect this model to utility power:
Connect the IEC-320 jumper cord (supplied) from a UPS receptacle (
to the power input receptacle of the host computer.
Connect the power cord of the host computer from the UPS power input
receptacle (
Figure 2-6. Connecting the UPS to utility power – 230VA model
) to a grounded utility wall outlet.
1
2
)
Page 30
Installation 2-13
After connecting the UPS to utility power, check the front panel indicators.
The green LINE STATUS indicator (
), either illuminated constantly (ON mode) or flashing (STANDBY mode), indicates the UPS mode of operation.
1
Figure 2-7. The LINE STATUS indicator ()
IMPORTANT: When the UPS is connected to utility power, all receptacles will immediately be energized regardless of the UPS operating mode selected (using the UPS ON/STANDBY button).
IMPORTANT: If any of the indicators on the front panel are red (indicating an alarm condition), press the TEST/ALARM RESET button to clear the red indicators. If this does not clear the red indicators, see Chapter 6, “Troubleshooting.”
NOTE: If the UPS does not include a power cord that is suitable for the application, contact an authorized Compaq service representative to obtain the appropriate power cord.
For more information on the front panel indicators and controls, see Chapter 3, “Operation.”
Page 31
2-14 Compaq Pro UPS 500 Operation and Reference Guide
Completing the Installation
With the UPS in STANDBY mode, allow the battery to charge before putting the UPS into service.
IMPORTANT: The battery will charge to 90% of their capacity within approximately 4 hours. Compaq recommends allowing the battery to charge for 12 hours before using them to supply backup power to devices.
Installing Compaq Power Manager Pro UPS Software
Refer to Software Installation Instructions (insert included in the CD packaging) for information on the installation requirements for the Compaq Power Manager Pro UPS software.
Selecting the UPS Operating Mode
Select the appropriate UPS operating mode using the ON/STANDBY
button (
). For more information, see “Front Panel Controls” in Chapter 3.
The ON/STANDBY button is a momentary switch that toggles between two UPS operating modes (ON and STANDBY). To toggle back and forth between the two operating modes, press and hold the ON/STANDBY
button (
Figure 2-8. Selecting the UPS operating mode
) for 2 seconds, until you hear a beep.
21
Page 32
Installation 2-15
“ON” Mode
Function: ENABLES battery backup.
UPS Conditions: The UPS battery is charging. Power is ON at the UPS
receptacles. The green LINE STATUS indicator (
Setting Advantages: Provides battery backup in the event of a blackout
) is illuminated.
or brownout.
“STANDBY” Mode
Function: DISABLES battery backup.
UPS Conditions: The UPS battery is charging. Power is ON at the UPS
receptacles. The green LINE STATUS indicator ( UPS audio alarm is sounding once per minute.
Setting Advantages: Continues to charge the battery when power is
present, while turning OFF the inverter to prevent battery backup operation when equipment is not in use.
CAUTION: When the UPS is in the STANDBY mode, the UPS will not provide battery backup during a blackout or brownout.
) is flashing. The
NOTE: The Compaq Pro UPS 500 can be used as a standalone power source when utility power is not present. For more information, see Start-On-Battery Operation in Chapter 3.
The installation is now complete
For information on operating the UPS, see Chapter 3, “Operation.”
Use the Compaq website as an additional information source:
http://www.compaq.com.
Page 33
This chapter provides information on the following topics:
Precautions to be observed when using the UPS
Front panel overview
Front panel controls
ON/STANDBY button
TEST/ALARM RESET button
Front panel indicators and audio alarms
Chapter 3
Operation
Rear panel overview
Rear panel features
Page 34
3-2 Compaq Pro UPS 500 Operation and Reference Guide
Operation Precautions
Observe these precautions when using the UPS.
WARNING: To reduce the risk of personal injury from earth conductor leakage current:
Do not operate a UPS that is disconnected from the utility power source.
Disconnect protected devices from the UPS before disconnecting the UPS
from utility power.
Use the TEST/ALARM RESET button to test the battery rather than
unplugging the UPS. For more information, see “Initiating a UPS Self-Test,” in this chapter.
Page 35
Front Panel Overview
Compaq Pro UPS 500 models feature the same front panel, which includes indicator lights that alert you to UPS operating conditions and controls required to:
Select the UPS operating mode.
Initiate a self-test of the UPS battery.
Silence an audio alarm.
Operation 3-3
5 62 3 41
Figure 3-1. Front panel indicators and button controls
Symbol
ON/STANDBY button
LINE STATUS indicator
ON BATTERY indicator
BATTERY LOW/REPLACE indicator
UPS LOAD indicator
TEST/ALARM RESET button
Page 36
3-4 Compaq Pro UPS 500 Operation and Reference Guide
Front Panel Controls
ON/STANDBY Button
The ON/STANDBY button is a momentary switch that toggles between two UPS operating modes (ON and STANDBY) when utility power is present. To toggle back and forth between the two operating modes, press and hold the
ON/STANDBY button (
IMPORTANT: When the UPS is connected to utility power, all receptacles will immediately be energized regardless of the UPS operating mode selected by the UPS ON/STANDBY button.
NOTE: The ON/STANDBY button can also be used to turn the UPS OFF. The UPS battery charger will be turned OFF. Power will be turned OFF at all UPS receptacles, and all indicators will be turned OFF. To turn the UPS OFF, press and hold the ON/STANDBY button for 2 seconds, until you hear a beep. The UPS will return to the ON mode once utility power is restored.
1
) for 2 seconds, until you hear a beep.
Figure 3-2. Selecting the UPS operating mode
ON/STANDBY button
LINE STATUS indicator
ON BATTERY indicator BATTERY LOW/REPLACE indicator
Page 37
Operation 3-5
“ON” Mode
Function: ENABLES battery backup.
UPS Conditions: The UPS battery is charging. Power is ON at the UPS
receptacles. The green LINE STATUS indicator (
Setting Advantages: Provides battery backup in the event of a blackout
) is illuminated.
or brownout.
“STANDBY” Mode
Function: DISABLES battery backup.
UPS Conditions: The UPS battery is charging. Power is ON at the UPS
receptacles. The green LINE STATUS indicator ( UPS audio alarm is sounding once per minute.
Setting Advantages: Continues to charge the battery when power is
present, while turning OFF the inverter to prevent battery backup operation when equipment is not in use.
CAUTION: When the UPS is in the STANDBY mode, the UPS will not provide battery backup during a blackout or brownout.
) is flashing. The
Other Modes of Operation
The ON and STANDBY UPS operating modes can be manually selected by the user. There are, however, three additional UPS operating modes which occur automatically.
Battery Operate Mode: While the UPS is in the ON mode and a
blackout or severe brownout occurs, the UPS will automatically switch
to battery power. The yellow ON BATTERY indicator ( illuminated. AC power from the UPS battery is available at the Battery-and-Surge-Protected receptacles. AC power is not available at the Surge-Protected receptacles. An audio alarm sounds (the alarm can be muted).
Automatic Shutdown Mode: When the UPS detects that less than
2 minutes of battery power is available during a prolonged blackout or brownout at approximately full load, the UPS will automatically enter Automatic Shutdown mode. The red BATTERY LOW/REPLACE
indicator (
) is illuminated. Less than 2 minutes of AC Power is available at the Battery-and-Surge-Protected receptacles. A non-silenceable alarm sounds as the UPS prepares for shutdown.
) will be
Page 38
3-6 Compaq Pro UPS 500 Operation and Reference Guide
Automatic Voltage Regulation (Boost) Mode: When an undervoltage
occurs, the UPS will automatically correct the voltage level without switching to battery power. When this occurs, the UPS may emit a clicking sound. The more the UPS adjusts the voltage level, the more the UPS will click. This is a normal, automatic operation of the UPS, and no action is required.
Start-On-Battery Operation
Compaq Pro UPS 500 models have special circuitry that allows them to be used as standalone power sources when utility power is not present. The Battery-and-Surge-Protected receptacles will supply AC power for the time limits of the internal battery. The Surge-Protected receptacles, however, will not supply AC power until utility power returns.
To perform the UPS Start-On-Battery operation when you first plug in
the unit and power is not present, momentarily press the ON/STANDBY
button (
To perform the UPS Start-On-Battery operation when the unit is
plugged in and operating in the STANDBY mode, press the ON/STANDBY button (
beep; press the ON/STANDBY button a second time and release the button after the UPS emits a beep.
) and release the button after the UPS emits a beep.
) and release the button after the UPS emits a
1
Figure 3-3. Selecting Start-On-Battery Operation using the ON/STANDBY button ()
Page 39
Operation 3-7
WARNING: To reduce the risk of personal injury resulting from electric shock or to avoid damage to the equipment:
Plug the input line cord into a grounded (earthed) electrical outlet that is
installed near the equipment and is easily accessible.
Do not disable the grounding plug on the input line cord. The grounding
plug is an important safety feature.
Do not use an extension cord.
IMPORTANT:
Performing a UPS Start-On-Battery with load present requires more power than
keeping an already-operating load running. You may not be able to start as large a load as usual when performing a UPS Start-On-Battery using the Compaq Pro UPS 500.
After performing a UPS Start-On-Battery, the UPS drains the charge on the battery;
runtime is very limited.
If utility power returns, power WILL BE SUPPLIED at the Surge-Protected receptacles
if the unit is connected to the utility outlet.
Page 40
3-8 Compaq Pro UPS 500 Operation and Reference Guide
r
r
TEST/ALARM RESET Button
The TEST/ALARM RESET button () is a momentary switch that allows you to initiate a UPS self-test or silence an audio alarm.
Initiating a UPS Self-Test
2 31
Figure 3-4. Initiating a UPS self-test
BATTERY LOW/REPLACE indicato
UPS LOAD indicato
TEST/ALARM RESET button
In the ON mode, pressing and holding the TEST/ALARM RESET button () (until the UPS acknowledges with a beep) will initiate a self-test of the UPS battery, full function of the backup system, and the load condition of the Battery-and-Surge-Protected receptacles. During the test period, the load connected to the Battery-and-Surge-Protected receptacles is powered from the battery for about 10 seconds. All indicator lights will illuminate briefly and an audio alarm will sound.
If battery replacement is indicated by the internal microprocessor
circuitry of the UPS, the BATTERY LOW/REPLACE indicator (
) will illuminate. The audio alarm will sound once every 10 seconds until cleared by a successful self-test. The alarm will be muted and will not resume if the UPS switches to Battery Operate mode or is placed in the STANDBY mode.
If the Battery-and-Surge-Protected receptacles are overloaded, the UPS
LOAD indicator (
) will illuminate. Remove the excess load
immediately.
Page 41
Operation 3-9
CAUTION: Do not initiate the self-test procedures while critical computer or load functions are being performed.
IMPORTANT: For the Compaq Pro UPS 500, the only method of checking the battery and circuitry functionality is by performing a UPS self-test on a routine basis.
Silencing an Audio Alarm
The UPS may sound an audio alarm to warn the user that an alarm condition exists. To silence the alarm, momentarily press and release the TEST/ALARM
RESET button (
).
1
Figure 3-5. Silencing an audio alarm using the TEST/ALARM RESET button ()
IMPORTANT:
While an audio alarm may be silenced, the condition that caused the alarm may still
exist. See Chapter 6, “Troubleshooting,” for information on procedures if the UPS detects an alarm condition.
When the UPS is operating from the battery and battery power is nearly depleted,
the alarm cannot be silenced. This alerts the user to immediately shut down connected equipment.
Page 42
3-10 Compaq Pro UPS 500 Operation and Reference Guide
Front Panel Indicators and Audio Alarms
The front panel indicators signal the status of the UPS.
LINE STATUS Indicator (Green)
The LINE STATUS indicator illuminates whenever the UPS is connected to acceptable AC utility line power.
While the UPS is in the ON mode, the LINE STATUS indicator will remain constantly illuminated to indicate that battery backup is enabled and will be available at the Battery-and-Surge-Protected receptacles in the event of a blackout or brownout.
While the UPS is in the STANDBY mode, this indicator will flash (and an alarm will sound once per minute) to indicate that battery backup is disabled and will not be available at the Battery-and-Surge-Protected receptacles in the event of a blackout or brownout. The alarm can be silenced by momentarily pressing the TEST/ALARM RESET button.
NOTE: If the UPS is disconnected from utility power, the UPS will return to the mode (ON or STANDBY) the UPS was in when power was lost.
ON BATTERY Indicator (Yellow)
The ON BATTERY indicator illuminates whenever the UPS is operating from internal battery. After 10 seconds of continuous battery operation, an audio alarm will sound consisting of 4 short beeps, followed by an 8-second pause. The alarm can be silenced by momentarily pressing the TEST/ALARM RESET button. When the battery is nearly depleted, the ON BATTERY and BATTERY LOW/REPLACE indicators will both be illuminated and the alarm will resume (and cannot be silenced) to alert the user to immediately shut down connected equipment.
Page 43
BATTERY LOW/REPLACE Indicator (Red)
The BATTERY LOW/REPLACE indicator illuminates when the internal processor detects a low or weak battery.
The BATTERY LOW/REPLACE indicator will illuminate constantly to indicate low battery charge. This indicator will flash, after a self-test is initiated, to indicate the need to replace the battery. An audio alarm will sound once per 10 seconds. The alarm can be silenced by momentarily pressing the TEST/ALARM RESET button. If the BATTERY LOW/REPLACE indicator flashes, allow the UPS to recharge for 12 hours and repeat the self-test. See “Initiating a UPS Self-Test” in this chapter.
UPS LOAD Indicator (Red)
The UPS LOAD indicator illuminates automatically under the following conditions: utility power is absent, the UPS is operating from the battery, and an overload condition exists. This indicator flashes when the UPS detects overload conditions of 100 percent of rated load. The UPS will shut down and the indicator will illuminate continuously if the UPS load exceeds 100 percent of rating. Remove excess load immediately and initiate a self-test to clear the shutdown latch.
Operation 3-11
You can detect the presence of an overload by conducting a self-test. See “Initiating a UPS Self-Test” in this chapter.
Page 44
3-12 Compaq Pro UPS 500 Operation and Reference Guide
Rear Panel Overview
Compaq Pro UPS 500 models have the following rear panel configurations:
WARNING: To reduce the risk of personal injury resulting from electric shock, do not open the UPS for any reason. There are no user-serviceable parts inside the UPS.
6
5
4
Figure 3-6. Rear panel configuration - 100VA and 120VA models
Communications port
Noise and surge-protected
receptacles
Non-detachable input power
cord with NEMA 5-15 plug
1
2
3
Battery compartment
Battery, noise, and surge-protected
receptacles
Phone/Fax Surge Protectors
Page 45
5
4
Figure 3-7. Rear panel configuration - 230VA model
Operation 3-13
1
2
3
Communications port
Noise and surge-protected
receptacle
IEC-320 power inlet
Rear Panel Features
Battery-and-Surge-Protected Receptacles
These receptacles provide connected equipment (such as computers, monitors, and other critical equipment) with AC line power during normal operation and safeguard the equipment against damaging surges and line noise.
The Battery-and-Surge-Protected receptacles also provide battery power during blackouts and brownouts only if the UPS is in the ON mode. For more information, see “Front Panel Controls ON/STANDBY Button” in this chapter.
Battery compartment
Battery, noise, and surge-protected
receptacles
Page 46
3-14 Compaq Pro UPS 500 Operation and Reference Guide
RJ11 Phone/Fax Surge Protector
Select Compaq Pro UPS 500 models include a Phone/Fax Surge Protector to safeguard communications equipment (such as a fax machine or a modem) from spikes and surges from transients present on telephone lines.
Communications Port
The communications port connects the UPS to any computer or workstation. Use the communications port with Compaq Power Manager Pro UPS software to enable automatic shutdown and power management functionality.
Surge-Protected Receptacle(s)
These receptacles provide connected equipment with AC line power during normal operation. They also safeguard equipment against damaging surges and line noise. Connect non-critical peripherals to these receptacles.
The Surge-Protected receptacles will not provide battery backup during blackouts and brownouts. They always supply AC power, when present, regardless of the UPS operating mode selected by the ON/STANDBY button.
AC Power Input Receptacle (230VA Model Only)
This receptacle accepts a detachable IEC-320 power cord. For more information, see Chapter 2, “Installation.”
Battery Replacement Door
Under normal conditions, the battery supplied in the UPS will last several years. Only qualified service personnel should perform battery replacement.
Page 47
This chapter provides information on the following topics:
Software overview
Software functions
Configuration parameters
Installation procedures
Chapter 4
Software
Page 48
4-2 Compaq Pro UPS 500 Operation and Reference Guide
Software Overview
Compaq Power Manager Pro UPS software is a web-based interface. Using either Netscape Navigator 3.0 or later, or Microsoft Internet Explorer 4.0 or later, system administrators can monitor and manage power being supplied by UPS units.
Software Functions
Compaq Power Manager Pro UPS software performs the following functions:
Displays UPS status.
Manages orderly shutdown of operating systems when an extended
utility power failure occurs.
Executes messaging functions to operators, system administrators, and
users.
Displaying UPS Status
View the status of any UPS on the network, including:
UPS communications.
Line state.
Operating system shutdown countdown.
Battery state.
Battery capacity.
Input voltage state.
Load state.
UPS self-test results.
Event log summary.
Page 49
UPS Control Functions
Perform the following UPS control functions, using the software security features to:
Protect access.
Execute a UPS self-test.
Shut down the operating system and UPS.
Configuration Parameters
System administrators and operators can configure Compaq Power Manager Pro UPS software parameters through the web-based interface, including:
Communications setting.
Poll rate
Broadcast settings.
Wait time before broadcasting message
Enable/disable broadcasting
Software 4-3
Shutdown settings.
Configured time delay before system shut down when on battery
Configured time delay before system shut down due to low battery
Enable/disable shutdown
Security settings.
Password protection
Enable/disable password
Page 50
4-4 Compaq Pro UPS 500 Operation and Reference Guide
Installation Procedures
To install Compaq Power Manager Pro UPS software:
1. Install Compaq Pro UPS 500 models. (For detailed installation instructions, please see Chapter 2, “Installation,” or refer to the Quick Installation Guide for Compaq Pro UPS 500, supplied with the UPS kit.)
NOTE: Select Compaq NeoServers have UPS power management software preinstalled. Some NeoServer customers may not need to install Compaq Power Manager Pro UPS software. Please see the NeoServer documentation included with the NeoServer unit for specific power management software installation requirements.
2. For Novell NetWare, log in to the NetWare system, using an account with administrative privileges, on a client machine running Microsoft Windows with a drive mapped to the SYS: volume on the target NetWare server.
3. Insert the CD-ROM into the drive. If your operating system has the automatic installation feature enabled, the Install Wizard starts automatically. (See “Installation Wizard Notification” in this chapter.)
IMPORTANT: When installing Compaq Power Manager Pro UPS software on a NetWare system, the CD should be place in the client workstation.
For systems without automatic installation, select the CD drive icon in the directory list (Drive D, for example) and double-click SETUP.EXE in the root directory.
4. Follow the Install Wizard instructions to set installation and configuration options.
Page 51
Installation Wizard Notification
Compaq Power Manager Pro UPS software takes advantage of the Microsoft AutoPlay feature. To install Compaq Power Manager Pro UPS software using this Install Wizard, follow the steps below:
1. The Compaq Power Manager Pro UPS software Select Language screen is displayed when the CD-ROM is inserted into the drive. Select the desired language.
Software 4-5
Figure 4-1. Select Language Screen
Page 52
4-6 Compaq Pro UPS 500 Operation and Reference Guide
2. After a language is selected, the Compaq Power Manager Pro UPS software Option screen will display. Select the Install Software button.
Figure 4-2. Option Screen
Page 53
Software 4-7
3. From the Installation Selection screen, select the desired application to install.
Figure 4-3. Installation Selection screen
4. Follow the Install Wizard instructions to set installation and configuration options.
For detailed installation and configuration requirements and procedures and usage options, please see the README.TXT file on the Compaq Power Manager Pro UPS Software and Documentation CD (included with the UPS kit).
Page 54
Battery Maintenance
This chapter provides information on the following topics:
Battery precautions
Charging the battery
When to replace the battery
Pre-Failure Battery Warranty
Obtaining a new battery
Care and storage of batteries
Chapter 5
Disposing of used batteries
Page 55
5-2 Compaq Pro UPS 500 Operation and Reference Guide
Battery Precautions
There are no user-serviceable parts to the Compaq Pro UPS 500. Do not open the UPS for any reason. Contact an authorized Compaq service provider.
WARNING: There is a risk of personal injury from the hazardous energy levels associated with UPS batteries. The maintenance and replacement of batteries must be carried out by qualified service personnel who understand the procedures, hazards, and precautions involved.
WARNING: The UPS contains a sealed lead-acid battery. To reduce the risk of fire or chemical burns, Compaq authorized service personnel must take the following precautions:
Set the UPS on a flat, level surface and unplug the UPS.
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Do not attempt to recharge the battery.
Battery replacement is to be performed only by a Compaq authorized
service provider using the Compaq spare designated for this product.
Do not disassemble, crush, puncture, short external contacts, or dispose of
the battery in fire or water.
Charging the Battery
The UPS automatically charges the battery while the UPS is connected to utility power at nominal voltage levels. No user intervention is required while the UPS is in use.
For information on keeping the battery charged while the UPS is in extended storage, see “Care and Storage of Batteries,” in this chapter.
Page 56
When to Replace the Battery
If the BATTERY LOW/REPLACE indicator () illuminates during a self-test, the UPS may require service. The indicator will be accompanied by an audio alarm.
Figure 5-1. BATTERY LOW/REPLACE indicator ()
Battery Maintenance 5-3
1
Verify that battery replacement is required by allowing the UPS to charge the battery for 12 hours, then initiate a confirming self-test. For more information on initiating a self-test, see Chapter 3, “Operation.”
NOTE: Depending on usage and environmental conditions, the battery should last three to six years.
Pre-Failure Battery Warranty
The Pre-Failure Battery Warranty, standard on all Compaq Uninterruptible Power Systems (UPS), extends the advantage of a Compaq two-year limited warranty by applying warranty coverage to the battery before the battery actually fails. Specifically, the Pre-Failure Battery Warranty ensures that when customers receive notification from Compaq Power Manager Pro UPS software that the battery may fail, the unit is replaced free of charge under the warranty.
Page 57
5-4 Compaq Pro UPS 500 Operation and Reference Guide
Compaq maintains the highest standards in the industry, as evidenced by the Compaq Pre-Failure Battery Warranty. The Pre-Failure Battery Warranty is beneficial in at least two significant ways:
Reduced total cost of ownership
Reduced downtime
Obtaining a New Battery
Contact an authorized Compaq service provider when the BATTERY LOW/REPLACE indicator (
indicating that a new battery will be required.
Care and Storage of Batteries
To maximize the life of the battery:
Minimize the amount of time the UPS is using battery power.
Keep the area around the UPS clean and dust-free. If the environment is
very dusty, clean the outside of the UPS regularly with a vacuum cleaner.
Maintain the ambient temperature at 25
) illuminates during the confirming self-test,
o
C (77oF).
If storing a UPS for an extended period, recharge the battery every six
months:
Connect the UPS to utility power.
Allow the UPS to charge the battery for 12 hours.
Disposing of Used Batteries
Replacement equipment includes the instructions and packaging required to return used batteries/units to the appropriate location for disposal.
Do not dispose of used batteries with general office or household waste. Return the used module for proper disposal to either:
Compaq, authorized Compaq Partners, or their agents.
A recycling center that meets all local environmental
standards.
Page 58
Troubleshooting
This chapter provides information on the following topics:
Troubleshooting during UPS start
Troubleshooting after UPS start
Repairing the UPS
Chapter 6
Page 59
6-2 Compaq Pro UPS 500 Operation and Reference Guide
Troubleshooting During UPS Start
If problems occur when starting the Compaq Pro UPS 500, select the appropriate symptom for possible causes and suggested actions.
Troubleshooting Guide (UPS Start)
Symptom Possible Cause Suggested Action
UPS power cord disconnected. Connect power cord.Indicators:
none
Alarm: none
No utility power. Contact a qualified
Table 6-1
electrician to check power at the utility power receptacle.
If desired, the UPS can be used as a stand-alone power source. See “Start­On-Battery Operation” in Chapter 3.
Indicators: BATTERY LOW/REPLACE
LINE STATUS
Alarm: none
Battery voltage is low because the UPS has been stored for an extended period of time without charging.
Battery voltage is low because UPS supported a load (and performed shutdown) during a blackout.
Allow the UPS to charge the battery for 12 hours. Initiate a self-test. If indicators illuminate again, replace the battery.
Page 60
Troubleshooting After UPS Start
For problems that occur after the UPS has gone through the startup self-test sequence, these suggested actions address possible causes.
Table 6-2
Troubleshooting Guide (After Start)
Symptom Possible Cause Suggested Action
Troubleshoo ting 6-3
Indicators: LINE STATUS (flashing)
Alarm: 1 per minute (can be silenced)
Indicators: ON BATTERY
BATTERY LOW/REPLACE
Alarm: continuous (cannot be silenced)
Indicators: UPS LOAD
Alarm: none
Output: none
UPS in STANDBY mode. Press and hold the ON/STANDBY
button for 2 seconds until you hear a beep, indicating to switch UPS to ON mode.
Battery voltage is low. Automatic shutdown is imminent.
Extreme overload condition existed. Battery-protected devices are exceeding the UPS power rating. The UPS has automatically shut down.
Immediately shut down connected equipment.
1. Remove excess load as quickly as possible.
2. Press TEST/ALARM RESET button to initiate self-test and reset the UPS.
continued
Page 61
6-4 Compaq Pro UPS 500 Operation and Reference Guide
Table 6-2 Troubleshooting Guide (After Start)
Symptom Possible Cause Suggested Action
continued
Indicators: UPS LOAD (flashing)
ON BATTERY (continuous)
Alarm: 1 per 10 seconds (can be silenced)
Output: available
Indicators: LINE STATUS
BATTERY LOW/REPLACE
Alarm: none
Indicators: LINE STATUS
BATTERY LOW/REPLACE (flashing)
Alarm: 1 per 10 seconds (can be silenced)
Battery-protected devices are loaded to the maximum UPS power rating.
Battery voltage is low, but line power is present and the battery is charging.
Battery has failed a UPS self-test, indicating low voltage or a weak battery.
Reduce load on UPS as quickly as possible until indicators extinguish.
No action is required.
1. Press TEST/ALARM RESET
button to silence alarm.
2. Allow battery to charge for
12 hours, then initiate a second self-test. If BATTERY LOW/REPLACE indicator illuminates again, arrange for battery replacement.
Repairing the UPS
The UPS has no user-serviceable parts. All repairs to the UPS, including battery replacement, must be carried out by Compaq or a Compaq authorized service provider.
Page 62
Regulatory Compliance Notices
Federal Communications Commission Notice
Part 15 of the Federal Communications Commission (FCC) Rules and Regulations has established Radio Frequency (RF) emission limits to provide an interference-free radio frequency spectrum. Many electronic devices, including computers, generate RF energy incidental to their intended function and are, therefore, covered by these rules. These rules place computers and related peripheral devices into two classes, A and B, depending upon their intended installation. Class A devices are those that may reasonably be expected to be installed in a business or commercial environment. Class B devices are those that may reasonably be expected to be installed in a residential environment (that is, personal computers). The FCC requires devices in both classes to bear a label indicating the interference potential of the device as well as additional operating instructions for the user.
Appendix A
All Compaq Pro UPS 500 models are Class B devices.
Class B Equipment
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
Page 63
A-2 Compaq Pro UPS 500 Operation and Reference Guide
instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
Consult the dealer or an experienced radio or television technician for
help.
Declaration of Conformity for Products Marked with the FCC logo - United States Only
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
For questions regarding your product, contact:
Compaq Computer Corporation P. O. Box 692000, Mail Stop 530113 Houston, Texas 77269-2000
or call 1-800-652-6672 (1-800-OK-COMPAQ
1
).
For questions regarding this FCC declaration, contact:
Compaq Computer Corporation P. O. Box 692000, Mail Stop 510101 Houston, Texas 77269-2000
or call (281) 514-3333.
To identify this product, refer to the part, series, or model number found on the product.
1
For continuous quality improvement, calls may be recorded or monitored.
Page 64
Modifications
The FCC requires the user to be notified that any changes or modifications made to this device that are not expressly approved by Compaq Computer Corporation may void the user's authority to operate the equipment.
Cables
Connections to this device must be made with shielded cables with metallic RFI/EMI connector hoods in order to maintain compliance with FCC Rules and Regulations.
FCC Part 68 Notice
If the Fax Modem Protector causes harm to the telephone network, the Telephone Company may temporarily discontinue your service. If possible, they will provide advance notification. If advance notice is not practical, notification will be provided as soon as possible. You will be advised of your right to file a complaint with the FCC. The Telephone Company may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If the Telephone Company does, advance notice will be given to provide an opportunity to maintain uninterrupted service. If trouble with this equipment is experienced, Fax Modem Protector, please contact Compaq for repair/warranty information. The Telephone Company may request that the equipment be disconnected from the network until the problem has been corrected or until the equipment is not malfunctioning. There are no repairs that can be made by the customer to the Fax Modem Protector. This equipment may not be used on coin service provided by the Telephone Company. Connection to party lines is subject to state tariffs. (Contact the state public utility commission or corporation commission for information.)
Regulatory Compliance Notices A-3
Canadian Notice (Avis Canadien)
Class B Equipment
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Page 65
A-4 Compaq Pro UPS 500 Operation and Reference Guide
European Union Notice
Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low Voltage Directive (73/23/EEC) issued by the Commission of the European Community.
Compliance with these directives implies conformity to the following European Norms (in brackets are the equivalent international standards):
EN55022 (CISPR 22) - Electromagnetic Interference
EN50082-1 (IEC801-2, IEC801-3, IEC801-4) - Electromagnetic
Immunity
EN60950 (IEC950) - Product Safety
Japanese Notice
July 14 version
Page 66
China Taiwan Notice
Battery Replacement Notice
Your UPS is provided with a Sealed Lead Acid battery. There is a danger of
explosion and risk of personal injury if the battery is incorrectly replaced or mistreated. Battery replacement is to be performed only by a Compaq authorized service provider using the Compaq spare designated for this product.
For more information about battery replacement or proper disposal, contact your Compaq authorized reseller or your authorized service provider.
WARNING: The UPS contains a sealed lead-acid battery. To reduce the risk of fire or chemical burns, Compaq authorized service personnel must take the following precautions:
Set the UPS on a flat, level surface and unplug the UPS.
Remove watches, rings, or other metal objects.
Regulatory Compliance Notices A-5
Use tools with insulated handles.
Do not attempt to recharge the battery.
Battery replacement is to be performed only by a Compaq authorized
service provider using the Compaq spare designated for this product.
Do not disassemble, crush, puncture, short external contacts, or dispose of
the battery in fire or water.
Batteries, battery packs, and accumulators should not be disposed of together with the general household waste. In order to forward them to recycling or proper disposal, please use the public collection system or return them to Compaq, your authorized Compaq Partners, or their agents.
Page 67
Appendix B
Specifications
This appendix provides specifications that apply to the Compaq Pro UPS 500:
Physical specifications
Input specifications
Output specifications
Battery specifications
Environmental specifications
Page 68
B-2 Compaq Pro UPS 500 Operation and Reference Guide
Physical Specifications
Physical Specifications – 120VA, 100VA, and 230VA models
Feature U.S. Metric
Dimensions Width 5.1 in 12.95 cm
Weight 16 lb 7.25 kg
Input Specifications
Input Specifications – Per Model
Table C-1
Height 8.4 in 21.34 cm
Depth 7.1 in 18.03 cm
Table C-2
UPS Model Nominal Input Voltage /
Frequency
500 (120VA)* 120VAC
60 Hz
500 (100VA)* 100VAC
50/60 Hz, auto-sensing
500 (230VA)** 230VAC
50/60 Hz, auto-sensing
Note: * Non-detachable cord with NEMA 5-15 plug
** IEC-320 jumper cord to replace device power cord
Input
Current
10A
10A -20% to +23% of nominal input voltage
5.3A -30% to +22% of nominal input voltage
On Line Voltage Range
-30% to +22% of nominal input voltage
Page 69
Output Specifications
Battery-and-Surge-Protected Output Specifications - Per Model
Specifications B-3
Table C-3
Model
500 (120VA) 500 / 300 3 x 5-15R 3 x 5-15R
500 (100VA) 500 / 300 3 x 5-15R 3 x 5-15R
500 (230VA) 500 / 300 2 x IEC-320 (10A) 1 x IEC-320 (10A)
Capacity
(VA/Watts)
Surge-Protected
Output Receptacles
Battery-and-
Surge-Protected
Table C-4
Output Current Specifications - Per Model
Output Current
Model
500 (120VA) 2.5A 7.25A
500 (100VA) 3A 5.6A
500 (230VA) 1.3A 7.25A
Battery-and-Surge-Protected
Receptacles
Surge-Protected Receptacles
Page 70
B-4 Compaq Pro UPS 500 Operation and Reference Guide
Output Specifications (continued)
Output Specifications - 120VA, 100VA, and 230VA models
Source of Power Regulation
Table C-5
Automatic voltage regulated output during on line operation
Battery power output
Feature Specification
Other Features On-line efficiency 96%
Transfer time 2-4 ms (typical)
Voltage wave shape Simulated sine wave
Surge suppression Up to 6,000V spikes at current levels
Noise filtering Full time EMI/RFI noise suppression
Phone/Fax Surge Protection
(Available on select models)
Output is increased by 14% in the following voltage ranges: 83V to 104V (120VA model); 80V to 91V (100VA model); 159V to 199V (230VA model)
±5% RMS
up to 27,000A. Spike suppression starts at voltages above nominal peak line values. Handles up to 240 joules (120VA and 100VA models) or 340 joules (230VA model). Clamping response time: less than 1 ns. Spike suppression in all three modes: Hot to Neutral, Hot to Ground, and Neutral to Ground
Meets the requirements of UL 1449 and ANSI C62.41 Category B (formerly IEEE 587)
with attenuation exceeding 40dB at 1MHz
Clamping voltage: 235V peak ±10%. Response time: 5 ns. Peak transient input voltage: 6Kv 10 ms. Single-line modem/fax protection covers center two wires of RJ11 connection
Page 71
Battery Specifications
Battery Specifications - 120VA, 100VA, and 230VA models
Feature Specification
Type Sealed lead-acid; maintenance-free
Voltage Internal batteries - 12 VDC
Specifications B-5
Table C-6
Battery Recharge Rate (discharged with 50% load)
Environmental Specifications
Environmental Specifications - 120VA, 100VA, and 230VA models
Feature Specification
Operating temperature 0o to 40oC (32o to 104oF)
Relative humidity 0% to 95%; non-condensing
Operating altitude Up to 3000 m (10,000 ft) above sea level
Audible noise Less than 45 dBA
2 to 4 hours
Table C-7
UL-tested at 25
o
C (77oF)
Page 72
A
alarm See audio alarm
Automatic Shutdown
mode 3-6
audio alarm
ability to disable 3-9 Battery Operate mode 3-5 features 3-9 how to respond 6-3 silencing 3-3, 3-9
requirement to address alarm
condition 3-9
Automatic Shutdown mode 3-5
alarm 3-6 explained 3-5
B
battery
care and storage See care and
storage of batteries
changing
warning on risk of personal
injury 5-2
warning to use qualified service
personnel 5-2
warnings on risk of fire or
burns 5-2
charging 5-4

Index

disposing See disposing of
used batteries
maintaining
care and storage 5-4 warning on risk of personal
injury 5-2
warning to use qualified service
personnel 5-2
warnings on risk of fire or
burns 5-2
new
when to obtain 5-4
when to replace See when to
replace battery
BATTERY LOW/ALARM
indicator 3-11
Automatic Shutdown
mode 3-5 illuminated 3-5 troubleshooting alarm
conditions 6-2
Battery Operate mode 3-5
explained 3-5 ON BATTERY indicator 3-5
Battery-and-Surge-Protected
receptacles
features 2-8 illustrated 2-8 plugging in equipment 2-8 warning against connecting
laser printers 2-7
Page 73
2 Compaq Pro UPS 500 Operation and Reference Guide
C
care and storage of batteries 5-4
ambient temperature 5-4 charging stored batteries 5-4
preventive maintenance 5-4 changing battery 5-1 charging the battery
after installation 2-14
in storage 5-4 communications port
connecting to the host
computer 2-4
caution against using other
communications cables 2-4
connecting to the host
computer, illustrated 2-4 features 1-6 overview 1-6
Compaq Power Management
software
configuration 4-3
Compaq Power Manager Pro UPS
software
obtaining information on
installation
requirements 2-2, 2-14
Compaq Pro UPS 500
features 1-6 front panel 1-3
illustrated 1-3 models 1-2 rear panels 1-4, 3-12
illustrated 1-4, 3-12
connecting
devices to the UPS 2-7 Phone/Fax Surge
Protector 2-5
RS-232 communications
cable 2-4
serial communications
cable 2-4 UPS to utility power 2-10 UPS/computer interface
cable 2-4
controls and indicators
front panel See front panel,
indicators
converting Watts to VA 2-6
D
disposing of used batteries
instructions 5-4 precautions to be observed 5-4
F
features 1-6 front panel
display See front panel,
indicators
indicators 3-10, 3-13
illustrated 1-3, 3-3
front panel display See front panel,
indicators
indicator colors 3-13
front panel indicators
meaning of colors 3-10
G
guarantee See warranties
I
indicators See front panel,
indicators
installing a UPS
checking the load 2-7 completing the
installation 2-14
connecting the communications
port 2-4
caution against using other
communications cables 2-4
illustrated 2-4
connecting the devices
turning equipment off 2-7 warning concerning laser
printers 2-7
Page 74
Index 3
connecting the Phone/Fax
Surge Protector 2-5
requirements
hardware 2-2 software 2-2 tools 2-2
starting the UPS 2-7
L
LINE STATUS indicator 3-10 load
calculating total load
(VA) 2-6
overload 2-6
M
mode of operation
Automatic Shutdown
mode 3-5
Automatic Voltage Regulation
(Boost mode) 3-6 Battery Operate mode 3-5 ON mode 3-5 STANDBY mode 3-5
O
ON BATTERY indicator 3-10
Battery Operate mode 3-5 illuminated 3-5
ON mode 3-5 Operating mode
selecting 3-3
operating the UPS
BATTERY LOW/ALARM
indicator illuminated 3-5 ON BATTERY indicator
illuminated 3-5 warning on earth leakage
hazards 3-2 warning on operating while
disconnected from utility
power 3-2
overload
conditions and indicator 3-11 starting a UPS Start-On-Battery
load 3-7
overview
battery maintenance 5-1 installation 2-1 operating the UPS 3-1 troubleshooting 6-1 UPS 1-1
P
PBX
connecting to a digital
PBX 2-5
Phone/Fax Surge Protector
connecting 2-5 features 1-7, 3-14
plug
always using three prong
grounded plug 2-7
precaution against use of
adapters 2-7
power cord
cords shipped with the
UPS 2-10
requirement for additional
cord 2-11, 2-13 shipped with the UPS 2-2 solution for additional
cord 2-11, 2-13
powering down the UPS 3-4 problems See troubleshooting
R
rear panels
features 1-4, 3-12 illustrated 1-4, 3-12
reference material
Compaq Power Manager Pro
UPS software installation
instructions 2-2
Page 75
4 Compaq Pro UPS 500 Operation and Reference Guide
Compaq Power Products
Software Reference Guide 2-2
Compaq Pro UPS 500
Operation and Reference
Guide 2-2 repairing the UPS 6-4 RJ11 Phone/Fax Surge
Protector See Phone/Fax Surge Protector
S
self-test
audio alarm 3-8 BATTERY LOW/ALARM
indicator 3-8
initiating 3-8 use of battery backup 3-8
software
configuration 4-3 functions explained 4-2 overview 4-1 using the UPS communication
port 2-4 STANDBY mode 3-5
power supplied when utility
power returns 3-7 Start-On-Battery 3-6
starting 3-7
storage See care and storage of
batteries
surge protectors, external
precaution against use 2-7
Surge-Protected receptacles
features 2-9 illustrated 2-9 plugging in equipment 2-9
T
TEST/ALARM RESET button
initiating a self-test 3-8
troubleshooting
after start 6-3 during start 6-2
turning OFF the UPS 3-4
U
UPS
turning OFF 3-4
UPS kit contents
hardware 2-2 reference material 2-2 software 2-2
UPS/computer interface cable
connecting from the UPS to the
host computer 2-4
V
VA rating
UPS and devices 2-6
W
warranties
$25,000 Computer Load
Protection Guarantee 1-8 applicability 1-8 limited warranty 1-8 pre-failure battery 1-8, 5-3 two-year limited 1-8
when to replace battery 5-3 Error! Cannot open file referenced
on page 5
Loading...