Compact Electric RUW 130 User Manual

FAST EARTH FAULT-SIGNALLING RELAY
RUW 130
- Monitoring of .........: Earth fault in 3-phase networks
- Response time ......: typ. 30 ms
- No auxiliary voltage required
Operation
The earth fault signalling relay RUW 130 is specially designed for earth fault monitoring in 3-phase networks. The relay measures the residual voltage in usual transformer circuits (fig. 1).
No auxiliary voltage is required, since the residual voltage is used both as characteristic quantity and supply voltage. The power consumption of the relay may be considered as negligible load for usual residual voltage transformers.
The setting value of the relay is continuously adjustable between 20 V AC and 80 V AC. If the residual voltage is below setting value, contacts 2-4 and 8-10 are closed. In case of overvoltage the red LED lights up and the output contacts will be switched (contacts 4-6 and 10-12 are closed).
The relay is also available with a continuously adjustable time delay.
The RUW 130 relay is enclosed in a plastic case which fits into a special 14 pin plug-in socket. The socket (type U or K) provides 14 screw terminals 2 x 4 mm
2
.
Specifications
(other values on request)
Rated voltage ............................. : 100 / 110 VRMS
Operating time:
a) without time delay .............. : 30 ms typ.
b) with time delay ................... : 0.1-3 s, 1-10 s, 2-30 s
please specify operating time range on order
Operating voltage range ..............: 20 - 132 VRMS
Setting range ............................ : 20 - 80 VRMS
continuously adjustable
Disengaging ratio ....................... : 2 - 20 % (Hysteresis)
continuously adjustable
Power consumption .................... : 1.3 VA
Maximum continuous overload ... : 132 V
Nominal frequency ......................: 50 Hz
Nominal frequency Range .......... : 45 - 60 Hz
Ambient operating temperature .. : -5 - +60 °C
Storage temperature ................... : -40 - +85 °
Temperature coefficient .............. : +0.005 % / °C
Frequency coefficient ..................: +0.01 % / Hz
ruw130e.pdf edition 05 / 01
RMS
1100 Vienna, DOERENKAMPGASSE 7 PH.: + 43 / 1 / 815-12-71-0 or + 43 / 1 / 815-51-74-0 FAX.: + 43 / 1 / 813-64-21-21
homepage:
http://www.compactelectric.at
FAST EARTH FAULT-SIGNALLING RELAY
RUW 130
Insulation
test voltage ............................. : IEC 255-5: 2.5 kV
impulse test ............................. : IEC 255-5: 5 kV 1.2/50 µs
Mechanical resistance ............ : IEC 255-21-1 class 1
IEC 255-21-2 class 1 IEC 255-21-3
Operating position ................... : any position
Output Relay (2 changeover contacts) Rated / Max. switching voltage : 250 V / 380 V AC Rated / Max. switching current : 8 A / 8 A AC
Rated switching power ............ : 2000 VA (cos ϕ = 1)
Make-break capacity ............... : 250 V / 8 A AC (cos ϕ = 1)
250 V / 4 A AC (cos ϕ = 0.4) 250 V / 0.4 A DC (6 * 10 30 V / 5 A DC (6 * 10
Electrical endurance ............... : 10
Mechanical endurance ............ : 10
Contact material ...................... : gold flash over silver alloy
5
operating cycles
6
operating cycles
50Hz 1min
RMS
3
operating cycles)
3
operating cycles)
Electromagnetic compatibility EN50082-2 (Industry) IEC 255-22-1 1 MHz disturbance / 2.5 kV IEC 255-22-2 (IEC801-2) ESD / 8 kV IEC 801-3 HF / 10 V/m IEC 255-22-4 (IEC801-4) Burst 2 kV
Radiation emission: EN50081-2
Maximum EMC interference (rated voltage applied):
Set point ............................... : <10%
Delay time ............................ : <10%
Protection degree ................ : IP 40
Case material ....................... : Polycarbonat
Flame retardance ................ : UL 94 V-0
Weight .................................. : 0.3 kg
Installation instruction
1) To ensure specified EMC features keep a minimum distance of 1.5 cm to other equipment or metallic parts.
2) Lock the case on the socket by the two clamping devices (metal spring clips with two notches). To lock the case push down the spring clips with a screwdriver positioned in the notches near the outside of the case. To unlock the case push down the spring clips using the notches near the inside of the case.
Connection diagram
Block diagram
Specifications are subject to change without notice.