F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.2
1.A.a. Freezing cycle
1. The compressor C pumps the refrigerant to the condenser CD or CA when the hot gas valve
VG
is closed.
2. The liquid line reaches the evaporator E through the molecular sieve F and the capillary tube T.
3. In the evaporator the refrigerant expands, thus producing the freezing effect.
4. The refrigerant goes back to the compressor through the receiver/tank B and suction line/heat
exchanger S.
5. The freezing cycle ends when the evaporator thermostat TE reaches the set temperature thus
starting the TIMER; when the time is over, the refrigeration cycle ends and the VG hot gas
valve is opened.
1.A.b. Defrost cycle (harvest)
1. When the hot gas valve VG open, refrigerant flows directly from the compressor C to the
evaporator E and back to the compressor through S.
2. Duration of harvest is fixed by the timer. There is a delay in starting the TIMER in the defrost
period. The TIMER is energized when the evaporator thermostat TE reaches the preset high
'IN' temperature; for this reason the motor of the TIMER is connected directly with the
COMMON contact of the evaporator thermostat. When the harvest ends, the timer is deenergized, the hot gas valve VG is closed and a new freezing cycle begins.
1.A.c. Air cooling
1. Models with air cooled condenser, have a fan motor V which is always energized (mod. CP30,
CP45) or is switched on and off by the pressure switch PT, (mod.CP70, CP120) which senses
condensing pressure.
2. Pressure switch PT is factory set. After sale service is
not allowed
to make adjustments for any
reason.
1.A.d. Water cooling
1. Models with water cooled condenser, have a fan motor V which is always energized.
2. Water inlet to condenser is regulated by the pressure switch PT, which senses condensing
pressure and energizes or not the condenser water inlet solenoid valve VC.
3. The safety thermostat
TSA
feels condensing temperature, too. In case of excessive temperature,
due e.g. to water shortage, valve failure etc., it shuts down the unit. When temperatures
decreases, it starts again.
4. Condenser thermostats and pressure switch are factory set. After sale service is
not allowed
to
make adjustments for any reason.