Compact CP 30SC E, CP 30 E, CP 45 E, CP 70 E, CP 120 E Service Manual

SERVICE MANUAL
SELF CONTAINED UNITS WITH TIMER
CP 30SC E
CP 30 E CP 45 E CP 70 E
CP 120 E
Ice Machines UK Ltd
Unit 10, LDL Business Centre, Station Road West, Ash Vale, Surrey, GU12 5RT
www.icemachines.co.uk e-mail: info@icemachines.co.uk
LEV1FG-296
ICE CUBES MAKERS
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
INDEX
1. HOW IT WORKS 1
1.A. REFRIGERATION SYSTEM 1
1.A.a. Freezing cycle 2
1.A.b. Defrost cycle (harvest) 2
1.A.c. Air cooling 2
1.A.d. Water cooling 2
1.B. WATER SYSTEM 4
1.B.a. Freezing cycle 4
1.B.b. Defrost cycle (harvest) 4
1.B.c. Ice storage bin 4
1.C. ELECTRICAL SYSTEM 5
1.C.a. Water cooled models 8
2. INSTALLATION 9
2.A. CONNECTIONS 9
2.B. SET-UP 9
2.B.a. Air cooled condenser units 9
2.B.b. Water cooled condenser units 10
3. START-UP & TEST 10
3.A. START-UP 10
3.B. TEST 11
4. CLEANING 11
4.A. CONDENSER CLEANING 11
4.B. INTERNAL CLEANING & SANITIZING 12
4.B.a. Cleaning - To remove lime scale or other mineral deposits 12
4.B.b. Sanitizing - To remove algae or slime 13
5. GENERAL INFORMATION 14
5.A. WEIGHTS & DIMENSIONS 14
5.B. CUBE SIZE 15
5.C. MODEL NUMBER BREAKDOWN 15
5.D. GENERAL DATA 16
5.E. PRODUCTION 17
5.E.a. Theoretical daily ice production - N. of cubes/24h 17
5.E.b. Theoretical daily ice production - kg/24h 18
5.F. WATER VALVE & FLOW REGULATOR CHART 19
5.F.a. Air cooled 19
5.F.b. Water cooled 19
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.1
1. HOW IT WORKS
The system is very simple and efficient. The evaporator is built up connecting together a series of reversed cups with a cooling coil. The refrigerant flows into the tubes while the pump sprays water into the cups. Thus inside each cup, an ice cube grows layer by layer. When the cubes are ready, harvest starts : hot gas flows through cooling coil of the evaporator and fresh water enters on top of evaporator. This melts the outer surface of the cubes which fall into the bin. A new freezing cycle then begins. When the bin is full of ice, the unit stops production. When a quantity of ice is taken away, the unit restarts production.
1.A. REFRIGERATION SYSTEM
REFRIGERATION TUBING SCHEMATICS
C
VG
V
F
PT
B
S
E
230V
T
CD
mod. CP70 - CP120
TE
AIR COOLED
C
Compressor
V
Fan motor
VG
Hot gas valve
T
Capillary tube
CD
Air cooled condenser
PT
Pressure switch CP70, CP120 only
F
Molecular sieve
E
Evaporator
B
Receiver
S
Heat exchanger
TE
Evaporator thermostat
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.2
1.A.a. Freezing cycle
1. The compressor C pumps the refrigerant to the condenser CD or CA when the hot gas valve
VG
is closed.
2. The liquid line reaches the evaporator E through the molecular sieve F and the capillary tube T.
3. In the evaporator the refrigerant expands, thus producing the freezing effect.
4. The refrigerant goes back to the compressor through the receiver/tank B and suction line/heat exchanger S.
5. The freezing cycle ends when the evaporator thermostat TE reaches the set temperature thus starting the TIMER; when the time is over, the refrigeration cycle ends and the VG hot gas valve is opened.
1.A.b. Defrost cycle (harvest)
1. When the hot gas valve VG open, refrigerant flows directly from the compressor C to the evaporator E and back to the compressor through S.
2. Duration of harvest is fixed by the timer. There is a delay in starting the TIMER in the defrost period. The TIMER is energized when the evaporator thermostat TE reaches the preset high 'IN' temperature; for this reason the motor of the TIMER is connected directly with the COMMON contact of the evaporator thermostat. When the harvest ends, the timer is de­energized, the hot gas valve VG is closed and a new freezing cycle begins.
1.A.c. Air cooling
1. Models with air cooled condenser, have a fan motor V which is always energized (mod. CP30, CP45) or is switched on and off by the pressure switch PT, (mod.CP70, CP120) which senses condensing pressure.
2. Pressure switch PT is factory set. After sale service is
not allowed
to make adjustments for any
reason.
1.A.d. Water cooling
1. Models with water cooled condenser, have a fan motor V which is always energized.
2. Water inlet to condenser is regulated by the pressure switch PT, which senses condensing pressure and energizes or not the condenser water inlet solenoid valve VC.
3. The safety thermostat
TSA
feels condensing temperature, too. In case of excessive temperature, due e.g. to water shortage, valve failure etc., it shuts down the unit. When temperatures decreases, it starts again.
4. Condenser thermostats and pressure switch are factory set. After sale service is
not allowed
to
make adjustments for any reason.
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.3
REFRIGERATION TUBING SCHEMATICS
C
VG
V
F
PT
VC
B
S
E
CA
230V
⇐⇐⇐⇐
⇒⇒⇒⇒
T
1
2
TSA
TE
WATER COOLED
C
Compressor
V
Fan motor
VG
Hot gas valve
VC
Condenser water valve
TSA
Safety thermostat
T
Capillary tube
CA
Water cooled condenser
PT
Pressure switch
TE
Evaporator thermostat
F
Molecular sieve
E
Evaporator
B
Receiver
S
Heat exchanger
c
Water inlet
d
Water drain
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.4
1.B. WATER SYSTEM
P
Pump(s)
SB
Spray bar(s)
WT
Water tank
VA
Inlet water valve
E
Evaporator
OF
Overflow
c
Water inlet
d
Bin overflow drain
e
Tank overflow drain
1.B.a. Freezing cycle
1. The pump P takes water from the water tank WT through a suction pipe and sends it to the spray bar SB (two pumps and two spray bars for mod. CP120).
2. The water sprayed by the nozzles reaches the cooled cups on the evaporator E. A quantity of water freezes and the excess falls again into the water tank.
3. The water inlet valve VA is closed.
1.B.b. Defrost cycle (harvest)
1. The water inlet valve VA is open. Fresh water goes up on top of evaporator, helping defrost.
2. From the top of the evaporator, water falls into the water tank and refills it.
3. Excess water is discharged by the overflow control OF.
4. Water pump(s) is not working.
1.B.c. Ice storage bin
1. Water from melted ice is drained separately, and does not enter again into the water system.
E
WT
OF
P
SB
c
d
e
mod. CP30 - CP45
CP70
SB
VA
⇐⇐⇐⇐
1
⇒⇒⇒⇒
3
P
OF
WT
P
E
⇒⇒⇒⇒
2
mod. CP 120 only
F.A.G. SRL
SELF CONTAINED UNITS WITH TIMER
ME-CPT1-199 COMPACT SERVICE MANUAL
PAG.5
1.C. ELECTRICAL SYSTEM
Compressor is always ON. Fan motor is regulated by the pressure switch
PT
only in models
CP70 & CP120. In models CP30sc, CP30 & CP45 fan motor is always ON.
The bin thermostat
TB
opens, when the ice-feeler is in contact with ice. The unit then stops.
WIRING DIAGRAM
air cooled
T
TB
PT
C
V
P
VG
VA
C
TE
2
4
TIMER
C
C
NC
NO
3
4
B
B
B
B
B
B
B
BM
M
M
M
M
M
V
V
R
R
R
RV
P
A
CP70 - CP120
a
b
A) Start of freeze cycle
C
compressor
ON
V
fan motor
ON (PT)
P
pump
ON
T
timer
OFF
a
micro a
C-NO
b
micro b
C-NO
VG
gas valve
OFF
VA
water valve
OFF
TE
evaporator thermostat
WARM (C-4)
TB
bin thermostat
closed
A) Start of freeze cycle.
The pumps spray water to the cups on the evaporator which is freezing.
The evaporator thermostat TE has not reached set-point. It is in WARM position.
M
Brown
B
Blue
V
Green
R
Red -
A
Orange
P