CommPact Control system Installation Manual

Page 1
Installation Manual
For quick installation information please refer to the CommPact
Quick Start Installation Guide provided on our website: www.electronics-line.com
Page 2
ii
Table of Contents
1. Introduction ................................................................................................................................................................................ 1
1.1. Documentation Conventions ................................................................................................................................... 1
1.2. Specifications .......................................................................................................................................................... 2
1.3. System Overview .................................................................................................................................................... 3
1.4. Hardware Layout ..................................................................................................................................................... 4
2. System Installation ..................................................................................................................................................................... 7
2.1. Pre-Installation Planning ......................................................................................................................................... 7
2.2. Installation Procedure ............................................................................................................................................. 8
2.3. Back Tamper ........................................................................................................................................................ 12
2.4. Internet Communication Setup ............................................................................................................................. 12
3. Basic System Operation .......................................................................................................................................................... 14
3.1. Front and Back Panel Layouts .............................................................................................................................. 14
3.2. Front Panel System Status LEDs ......................................................................................................................... 15
3.3. Front Panel Keypad .............................................................................................................................................. 15
3.4. LCD Display .......................................................................................................................................................... 16
3.5. Audible Notification ............................................................................................................................................... 17
3.6. Setting and Unsetting ............................................................................................................................................ 18
3.7. Additional Setting Options ..................................................................................................................................... 21
4. Advanced System Operation ................................................................................................................................................... 23
4.1. Menu Navigation ................................................................................................................................................... 23
4.2. Cancel Report ....................................................................................................................................................... 24
4.3. Zone Omitting ....................................................................................................................................................... 24
4.4. User Codes ........................................................................................................................................................... 24
4.5. Follow-Me .............................................................................................................................................................. 27
4.6. Event Log .............................................................................................................................................................. 27
4.7. Service Menu ........................................................................................................................................................ 28
5. Telecontrol and Two-Way Audio ............................................................................................................................................. 34
5.1. Incoming Calls ...................................................................................................................................................... 34
5.2. Outgoing Calls....................................................................................................................................................... 36
6. PGM Control.............................................................................................................................................................................. 38
6.1. Keyfob Control ...................................................................................................................................................... 38
6.2. Telephone Control ................................................................................................................................................ 38
7. Devices ...................................................................................................................................................................................... 39
7.1. Device Descriptors ................................................................................................................................................ 39
7.2. Wireless Devices .................................................................................................................................................. 39
7.3. Zones .................................................................................................................................................................... 41
7.4. Keyfobs ................................................................................................................................................................. 45
7.5. Wireless Keypads ................................................................................................................................................. 46
7.6. Repeaters ............................................................................................................................................................. 47
7.7. Wireless Sounder ................................................................................................................................................. 47
8. Entry/Exit Timers and System Tones ...................................................................................................................................... 49
8.1. Entry/Exit Delay ..................................................................................................................................................... 49
8.2. Set on Exit ............................................................................................................................................................. 49
8.3. Supplementary Entry Delay ................................................................................................................................... 49
8.4. Entry Deviation ...................................................................................................................................................... 50
8.5. Setting Tones ........................................................................................................................................................ 50
8.6. System Trouble Tones .......................................................................................................................................... 51
Page 3
iii
8.7.
Tones Options ....................................................................................................................................................... 52
9. System Options ......................................................................................................................................................................... 53
9.1. Code Lockout ........................................................................................................................................................ 53
9.2. Set/Unset Options ................................................................................................................................................. 53
9.3. Panic Alarm ........................................................................................................................................................... 54
9.4. AC Loss Delay ...................................................................................................................................................... 55
9.5. Display Options ..................................................................................................................................................... 55
9.6. PGM Output Options ............................................................................................................................................. 56
9.7. "No Set" Indication ................................................................................................................................................ 58
9.8. Jamming Detection ............................................................................................................................................... 58
9.9. "No Motion" Time .................................................................................................................................................. 58
9.10. Vocal Messages .................................................................................................................................................... 59
9.11. Engineer Access ................................................................................................................................................... 59
9.12. Daylight Savings .................................................................................................................................................... 59
9.13. Entry/Exit Trouble .................................................................................................................................................. 59
9.14. Report Fail Trouble ............................................................................................................................................... 60
9.15. Immediate Setting from WUApp ........................................................................................................................... 60
10. Communications ....................................................................................................................................................................... 61
10.1. System Reporting .................................................................................................................................................. 61
10.2. Report Cycles ........................................................................................................................................................ 63
10.3. Vocal Message Dialer ........................................................................................................................................... 63
10.4. Remote Programming ........................................................................................................................................... 65
10.5. Service Call ........................................................................................................................................................... 67
10.6. Communications Options ...................................................................................................................................... 67
10.7. GSM Options ......................................................................................................................................................... 70
10.8. TWA Event Report Options................................................................................................................................... 72
10.9. Event Options for Central Station Reporting ......................................................................................................... 74
10.10. Vocal Message Dialer Event Options ............................................................................................................... 75
11. Internet Options .......................................................................................................................................................................... 77
11.1. ELAS Connection Parameters .............................................................................................................................. 77
11.2. Control System Parameters .................................................................................................................................. 77
11.3. GPRS Network Parameters .................................................................................................................................. 78
12. System Initialization ................................................................................................................................................................. 79
12.1. Initialization ............................................................................................................................................................ 79
12.2. Default Program Restore ...................................................................................................................................... 79
12.3. Clear User Codes.................................................................................................................................................. 79
12.4. Clear Wireless Transmitters ................................................................................................................................. 79
Appendix A: Menu Structure ............................................................................................................................................................. 80
Appendix B: Transmitter Installation ................................................................................................................................................ 87
PIR Detectors (EL-2645/EL-2645PI) .................................................................................................................................. 87
Directional PIR (EL-2650XL) .............................................................................................................................................. 90
Wireless PIR (EL-2652SR) ................................................................................................................................................ 95
Magnetic Contact (EL-2601) .............................................................................................................................................. 99
Universal Transmitter (EL-2602) ...................................................................................................................................... 101
Glassbreak Detector (EL-2606) ....................................................................................................................................... 102
Vibration Detector (EL-2607) ........................................................................................................................................... 106
Smoke Detector (EL-2703) .............................................................................................................................................. 108
Keyfobs (EL-2711M / EL-2711P / EL-2614E and EL-2714) ............................................................................................. 116
1-Way Wireless Keypad (EL-2620) .................................................................................................................................. 117
Wireless Indication Keypad (EL-2621) ............................................................................................................................. 118
Page 4
iv
Flood Detector (EL-2661) ................................................................................................................................................ 120
Gas Leak Detector (EL-2762) .......................................................................................................................................... 122
Carbon Monoxide Detector (EL-2764) ............................................................................................................................. 125
Outdoor Sounder and Strobe (EL-2626AC) ..................................................................................................................... 130
Repeater (EL-2635) ......................................................................................................................................................... 133
Transmitter Specifications................................................................................................................................................ 136
Appendix D: Event Table ................................................................................................................................................................. 139
Appendix E: Zone Types ................................................................................................................................................................. 142
Page 5
1 Introduction
CommPact Installation Manual
1
1. Introduction
This manual is designed to help you install the CommPact Control System1. We strongly urge you to read through this manual, in its entirety, before beginning the installation process so that you can best understand all that this security system has to offer. This manual is not intended for end user use. End users are encouraged to read the user manual provided with the system. If you have any questions concerning any of the procedures described in this manual please contact Electronics Line 3000 Ltd. at (+972-3) 963-7777.
1.1. Documentation Conventions
Throughout the manual, we have tried to include all of the operating and programming functions using a similar structure and order as they appear in the menu. A detailed explanation of how to navigate the Control System’s menu is included in p. 23, 4.1 Menu Navigation. In order to simplify the procedures that appear in the rest of this manual, the following conventions are used:
Table 1-1: Documentation Conventions
Item
Description
Select
Use the arrow keys to scroll through the options and press '
√'
From the Event Log Menu, select Clear Log.
Enter the main menu by pressing 3 and entering your user code. Using the arrow keys, navigate until you reach Event Log and press √. Using the arrow keys,
navigate until you reach Clear Log and press '
√'.
From the Service menu, select Time/Date, Set Date.
The same as above only this time you are navigating through three menu levels.
[7012] The shortcut to a specific menu item from the main menu. In this case, this is the
shortcut for Set Date. These appear in the procedures as an additional aid to menu navigation.
[#5] A shortcut to a specific item in a sub-menu. For example, [#5] is the shortcut to Bell
enable disable in the sub-menu that is opened once you have selected the detector you want to program.
The symbol on a key that appears on the Front Panel keypad
5. Interface Test The text that actually appears on the CommPact LCD display (bold).
Due to the occurrence
Important note, please pay attention.
The CommPact Control
System is
Caution: description of a potentially hazardous situation.
Warning Do not test
with flame!
Warning: description of a potentially hazardous situation that is a threat to human life.
1
The terms Control System, Control Panel, and CP refer to the same notion.
Page 6
1 Introduction
CommPact Installation Manual
2
1.2. Specifications
General
Zones: 32 wireless zones (1 transmitter per zone), 1 hardwire zone (Zone 33). Wireless Keyfobs: 19 (Controlled or Non-controlled) Wireless Keypads: up to 4, including one way or two­way Repeaters: 4 Wireless Sounder: 1 (2-way) User Codes: 32 Setting Methods: Full, Part or Perimeter. Event Log: 1022 event capacity, time and date stamped Weight: 1.350g Dimensions: 210x153x40 mm
Communications
Event Reporting Accounts: up to 6, including Central Station, Follow-Me, and Voice. Telephone Numbers: 6 event reporting accounts, RP Callback, Service Call. Communication Interface Options: GPRS, GSM, PSTN.
Receiver
Type: Super-heterodyne, fixed frequency Frequency: 418MHz, 868.35 or 433.92 (optional). Data Encryption: SecuriCode™
Electrical
*
Power Input: 230VAC, 50Hz, 120VAC, 60Hz/9VAC, 15VA (Model 1332) AC Current Consumption: 30mA (alarm), 17mA (standby) DC Current Consumption: 280mA (alarm), 130mA (standby) Maximum Auxiliary Output Current Rating : 50mA Battery low: below 7.15V Backup Battery Pack: 4.8V 1.3Ah Part No. BT3021 (4 x 1.2 NiMH, size AA, rechargeable cells,) The maximum charging current for the BT-5780 is 1.8 Ah Fuse Ratings: 63mA/250V for 230VAC – Part No. EF1063, PGM Relay Output Contact Rating: 100mA (max. load) Built-in Sounder: 93dB @ 10ft Tamper Switch: N.C. Operating Temperature: -10°C to 55°C (14°F to 131°F)
*
The measurements are with fully charged battery. AC current was measured on fuse F1 and DC current was measured
on fuse F2.
!
Power connection to the unit should be according to the national electrical code for
permanent installation. The power supply should be fed from a readily accessible disconnect device. If the unit is permanently wired to the mains power, use a 2-pole disconnect device (15A max.) and the wires should be min. 0.75mm
2
in a conduit of at least 16mm. If the mains power is connected with a plug, the plug should be indicated as the disconnecting device and the socket shall be max. 2m from the Control System. Batteries shall be provided by a distributor and replaced by authorized service personnel. The backup battery pack should be replaced every five years. Batteries should be stored in a cool, dry place.
Page 7
1 Introduction
CommPact Installation Manual
3
1.3. System Overview
The CommPact Control System is a full-featured wireless Control System that is expected to provide a solution to the needs of most residential installations. This system has been developed based upon a design concept geared towards easy installation and use. With this in mind, the user interface is based on a simple, menu-driven model that suits the essential requirements of both the user and engineer alike. You can program the CommPact Control System on-site using the Front Panel keypad or PC, or off-site via a PC using local programming option of the Remote Programmer.
The system offers GPRS network connectivity, providing high-speed central station reporting via a GPRS interface.
The Electronics Line Application Server (ELAS) handles all communication between the system, service providers and web users enabling monitoring and control to be performed via the Web. Backup communication is carried out via PSTN or GSM.
Central station communication and remote parameters programming and maintenance employ GPRS, GSM or standard PSTN communication. SMS messaging provides an innovative method used for both central station and Follow-Me user monitoring. Additionally, SMS messages can be sent to the Control System enabling the user to send commands to the system from anywhere on the planet.
Figure 1-1 shows the components that make up the system and the system’s interaction with external communication networks for all the available configurations.
Page 8
1 Introduction
CommPact Installation Manual
4
Figure 1-1: System Architecture
1.4. Hardware Layout
The aim of this section is to acquaint you with the circuit boards that make up the system. The CommPact Control System housing has two PCBs: the Main Board and the Power Supply and Connections Board.
Page 9
1 Introduction
CommPact Installation Manual
5
1.4.1. Main Board
The Main Board is the brain of the system. It coordinates all the Control System activity. The Main Board (see Figure 1-2) enables GSM and GPRS communication that allows reporting
events to the Central Station send or receive SMS messages, implement cellular Two-Way Audio and remote software update.
This Board also has a standard dialer for communication via the Public Switched Telephone Network (PSTN). Backup communication with event reporting, and Two-Way Audio (TWA) are also available via PSTN.
The Main Board also has connectors to the Built-in Sounder and the Speaker. Additionally, the Main Board includes a USB port for PC programming.
Figure 1-2: Main Board
1. Built-in Sounder Connector
2. Buzzer
3. LCD Contrast Control
4. USB Port
5. SIM-Card Holder
6. Speaker Connector
7. Flat-Cable Interface Connector to the Power Supply and Connections Board
8. Sounder Strength Control Jumper (JP1)
Table 1-2: Main Board Jumper Settings
JPI Sounder Strength
(see Figure 1-2, Main Board)
Installed: 105dB Removed: 85dB
Do not use VoIP phone lines for communication to the central monitoring station. In certain cases the system may not transmit alarm signals successfully over the VoIP network.
To reduce the risk of fire, use only No. 26AWG or larger telecommunication wire. Flat cable (8) is not Removable!
Page 10
1 Introduction
CommPact Installation Manual
6
1.4.2. Power Supply and Connections Board
As the name suggests, the Power Supply and Connections Board has the AC and battery connectors, power connection fuses, and the transformer. This Board also serves as the interface to the PGM programmable output, the Hardwire Zone, Telephone, Telephone Line, and Back Tamper. On the rear side of the Board, there is a battery switch that allows applying battery power at first installation.
Figure 1-3: Power Supply and Connections Board
1. AC Power Connector (N=Neutral, L=Live)
2. AC Fuse
3. Terminal Block
4. Back Tamper Connector
5. AC to AC Transformer
6. Front Tamper Switch
7. Flat-Cable Interface Connector to the Main Board
8. Battery Connector
9. PGM Control Jumper (JP1)
Table 1-3: Jumper Settings
JPI PGM (see Figure 1-3, Power Supply
and Connections Board)
Installed: Open Collector Removed: Dry Contact
Page 11
2 System Installation
CommPact Installation Manual
7
2. System Installation
The following chapter explains how to install the system and provides guidelines and tips on how to optimize the installation.
It is recommended that you familiarize yourself with the various circuit boards that make up the system – see p. 4, 1.4 Hardware Layout.
2.1. Pre-Installation Planning
Before starting the installation procedure, it is worthwhile to draw a rough sketch of the building and determine the required position for the Control System and each wireless device.
When deciding on the placement for installation, consider the following:
Mount the Control System in a location with easy access to telephone and power
connections.
Mount the Control System in a location that provides easy connection to the router.
For best performance of the GPRS Communication, the Control System should be
mounted in a position where the GSM signal is strong.
Refer to the following section in order to choose the optimal location for wireless
devices in relation to the Control System.
2.1.1. Wireless Installation Guidelines
In order to optimize wireless communication, consider the following guidelines:
Whenever possible, mount the Control System centrally in relation to wireless
detectors.
Avoid installation in close proximity to sources of high noise or radio frequency
interference. For example, metal air conditioner/heater ducts and circuit breaker boxes.
Minimize the distance between the Control System and transmitters.
Minimize the number of obstacles between the Control System and transmitters.
Figure 2-1: Minimizing Obstacles
Metal based construction materials, such as steel reinforced concrete walls, reduce the
range of radio transmissions.
Figure 2-2: Considering Construction Materials
Page 12
2 System Installation
CommPact Installation Manual
8
The reduction of the RF signals’ strength is directly proportional to the thickness of
the obstacle, assuming that the obstacles are of identical material.
Figure 2-3: Considering Thickness of Obstacles
2.2. Installation Procedure
The CommPact Control System Kit consists of:
Control System
Quick Start Installation Guide
Quick User Guide
Mounting Guide
Plastic bag with Cable Clamp, Cable Clamp screw, Housing Screw,
After unpacking the kit and making certain that you have all the necessary equipment, it is recommended that you install the system as follows:
STAGE 1: Temporarily power up the system and install the SIM card. STAGE 2: Selecting language and defaults STAGE 3: Register the transmitters. STAGE 4: Test the chosen mounting location. STAGE 5: Program the relevant Internet options. STAGE 6: Permanently Install the Control System and Transmitters
2.2.1. Stage 1 – Temporarily Power Up the System
In order to register and test transmitters, it is necessary to temporarily power up the Control System before permanently installing it.
1. Insert a screwdriver between the front and back panels of the housing; carefully twist it to release the tabs (see p. 8, Figure 2-4).
Figure 2-4: Opening the Housing
2. Thread the Power AC cable through the hole in the back cover. Connect it to the AC cable connector on the PCB and secure it by Cable Clamp (see p. 9, Figure 2-5).
The Control System is supplied without AC cable. Please use Standard Two-Pin European Plug cable only. For the Cable Clamp, use the screw and the washer supplied in your kit to replace the PCB screw.
Page 13
2 System Installation
CommPact Installation Manual
9
3. Open the SIM card holder on the Main Board; insert the SIM card* (see p. 5, Figure 1-2 ).
4. Close the Housing.
5. Plug the Power AC cable into the wall outlet.
In five minutes since power-up, the sounder will sound. To silence the sounder, press your user code (default user code is 1234).
At this stage, do not connect the backup battery. Ignore any trouble conditions that may appear on the LCD Display (e.g. Low Battery).
Figure 2-5: Main Board Wiring Scheme
2.2.2. Stage 2: Selecting Language and Defaults
The Control System supports several languages. Language and defaults settings must be defined before any configuration parameters are set or any transmitters registered.
Setting language and defaults automatically initializes the Control System. This means that all prior configuration settings are reset to the default settings and all previously registered transmitters are deleted from the Control System.
To select language and defaults:
1. Press '√ʹ.
2. Enter your Engineer code (the default Engineer code is 1111).
3. From the Programming menu, select Devices [971].
4. Select default and press '√ʹ.
5. Select language (Voice + LCD display) and press '√ʹ.
6. Press '√ʹ once more to initialize the Control System
2.2.3. Stage 3 – Register the Transmitters
For the Control System to recognize a device, its transmitter must be registered. In general terms, transmitter registration means sending two transmissions from a device when the Control System is in Registration mode.
To register a device:
1. Press '√ʹ.
2. Enter your Engineer code.
3. From the Programming menu, select Devices [91].
4. Select the type of transmitter you want to register. For example, if you want to register a wireless detector to a zone, select Zones.
*
optional feature
Page 14
2 System Installation
CommPact Installation Manual
10
5. Select the specific device you want to register (for example, Zone 4); the system initiates Registration mode. During Registration mode, the system waits for two transmissions from the device.
If a device has already been registered at the selected location, the system will not initiate Registration mode. If the device has already been registered at another location, attempts to register it are ignored by the system. Zones 1-32 are intended for wireless detectors
6. Register the device – refer to each device’s installation instructions in Appendix B for further details.
7. When two transmissions have been received, Save? is displayed. Press '√ʹ to confirm registration.
8. Continue entering other parameters for the chosen device.
9. Press Χ to exit menu mode.
2.2.4. Stage 4 – Test the Chosen Mounting Location
Once all of the transmitters are registered, it is recommended that you test the chosen mounting locations before permanently mounting the Control System and wireless devices. You can test the transmitter signal strength using the TX Test feature.
To test transmitter signal strength:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [7072] (Service, Transmitters, and TX Test) to initiate TX Test mode.
4. Activate the transmitter you wish to test; the transmitter’s details appear on the Control System’s LCD. Additionally, between one and four tones are sounded to indicate the transmitter’s signal strength. If four tones are sounded, the transmitter is in the best possible location – see p. 30, 4.7.7 Transmitters for further information.
5. After you have tested each transmitter, press Χ to exit TX Test mode.
When using GPRS and/or GSM communication, test the GSM signal strength. To test the GSM signal strength:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [7091] (Service, RF & GSM level, GSM Signal); RF RSSI level measured by the system's receiver – see p. 31, 4.7.9 GSM Signal Strength for further information.
Check the RF RSSI (Received Signal Strength Indication) level using the system’s RSSI meter. To view the RF RSSI level reading:
Enter [7092] (Service, RF & GSM level, RF RSSI Level); the RF noise measured by the
system's receiver is displayed – see p. 32, 4.7.10 RF RSSI level for further information.
Page 15
2 System Installation
CommPact Installation Manual
11
2.2.5. Stage 5 – Program Internet Options
The Electronics Line Application Server (ELAS) handles all communication between the system, service providers and web users, enabling monitoring and control to be performed via the Web. Internet settings are mostly pre-programmed in the Control System’s default settings. The only settings you need to program are the Control System’s connection settings and control system parameters (provided by the ELAS administrator). The following procedures explain how to program the Control System’s ID (CPID) and Password. For further information regarding other Internet options and settings, see p. 77, 11 Internet Options.
To program the ELAS IP Address and Port:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9571] (Programming, Communications, Internet, and XMP Proxy ID).
4. Enter the IP address of the ELAS and press '√ʹ.
5. Enter the XML port of the ELAS and press '√ʹ.
For MyELAS, define the IP address as 195.219.118.21 and the Port as 33000.
If the end user is to perform the self registration on-line then the following CPID and CP Password steps are not required.
To program the CPID:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9573] (Programming, Communications, Internet, and CPID).
4. Enter an ID using the alphanumeric keypad. The ID length must be six up to sixteen characters. The ID must begin with a letter.
5. Press '√ʹ.
To program the Control System’s password:
1. Press '√ʹ.
2. Enter your Engineer code.
3. Enter [9574] (Programming, Communications, Internet, and CP Password).
4. Enter a password using the alphanumeric keypad. The password length must be six up to sixteen characters. The password must begin
with a letter.
5. Press '√ʹ.
2.2.6. Stage 6 – Permanently Install the Control System and Transmitters
Having chosen and tested the mounting location of the Control System and each transmitter, you are now ready to permanently install the system.
To permanently install the transmitters, refer to each device’s installation instructions in Appendix B of this manual or to those supplied individually with each product.
To install the Control System:
1. Place the drilling template against the wall and mark the mounting holes.
Page 16
2 System Installation
CommPact Installation Manual
12
2. Install 2 wall anchors and screws leaving 2-3mm out of the wall.
The Control System must be mounted so that it shall withstand a force of at least three times its own weight.
3. Disconnect (unplug) AC power from the Control System.
4. Open the housing (see p. 8, Figure 2-4).
5. Thread any required cables through the hole in the back cover.
6. Connect the optional Telephone Line, Telephone, Wired Zone, and PGM to their connectors on the Main Board terminal block – see p. 9, Figure 2-5.
7. Plug the AC power cable into the outlet.
Always connect AC power before connecting the battery pack. Batteries are supplied uncharged. When you first connect the battery, it is probable that the system will display a Low Battery condition. Allow the battery to charge for at least 18 hours before use.
8. Connect the Backup Battery to its connector on the Main Board – see p.6 Figure 1-3.
9. Mount the Control System to the wall by hanging the back cover onto the screws.
Make sure that the back tamper is closed.
10. Close the housing making sure that the front and back covers click shut. Apply the housing screw at the bottom of the panel.
2.3. Back Tamper
The Back Tamper switch is an optional feature that provides an extra safeguard in the event that the Control System is removed from the wall.
The Back Tamper switch is located on the rear side of the Control System’s housing and is constantly depressed while the panel is hanged tightly on the screw.
2.4. Internet Communication Setup
After you have powered up the system, the GPRS startup sequence is initiated. During this sequence, the parameters programmed in the Control System's Internet Options (see – p. 77, 11 Internet Options) are activated. After the startup sequence is complete, the Control System attempts to connect to the ELAS GPRS Proxy.
If the Control System is having difficulty connecting to ELAS, a trouble message is displayed. The following table summarizes the trouble messages for this case.
Table 2-1: ELAS Connection Trouble Message
LCD Display
Trouble condition Restored by
SIM CARD TROUBLE SIM card not recognized or incorrectly
programmed
Insertion of recognized SIM card
or correct programming. MEDIA LOSS GSM Cellular network down Cellular network restore DEVICE TROUBLE GSM Faulty GSM/GPRS module Replacement of faulty module MEDIA LOSS GPRS
MODULE
Wrong GPRS settings (APN, Password etc.) or loss of GPRS service
Correct GPRS settings or restored
GPRS service XML FAIL Control panel fails to communicate with the
XML Proxy
Successful communication with
XML Proxy
In this case, check that the Control System’s Internet Options are correctly programmed. If you still experience problems, the IP Protocol and GPRS settings must be checked.
Page 17
2 System Installation
CommPact Installation Manual
13
To check the IP Protocol and GPRS settings:
1. Open the PCB Compartment and make sure a SIM Card with GPRS support is on the PCB – see p. 14 Figure 3-2.
2. Close the housing and enter your Engineer code.
3. Enter [95112] (Programming, Communications, Accounts, Account 1, and Protocol). If the setting is correct, you will see "IP Protocol".
4. Exit this menu and Enter [95113] (Programming, Communications, Accounts, Account 1, Interface). If the setting is correct, you will see "GPRS".
When using a SIM card with a PIN code, the engineer has to make sure that the PIN code programmed in the Control System is the same as the SIM card's PIN code – see p. 8,
10.7.2 PIN Code.
Page 18
3 Basic System Operation
CommPact Installation Manual
14
3. Basic System Operation
3.1. Front and Back Panel Layouts
The front panel provides a detailed interface for operating and programming the system. The following diagram will familiarize you with the various elements of the front panel.
Figure 3-1: Front Panel
Next diagram shows the Control System's back panel that provides access to the SIM card, the USB Connector and the battery power switch used at first installation – see Figure 3-2 below.
Figure 3-2: Back Cover
Alphanumeric
Keypad
Setting
Keys
LCD
Display
OK LED
Arm
Status
LED
Menu Navigation Keys
Page 19
3 Basic System Operation
CommPact Installation Manual
15
3.2. Front Panel System Status LEDs
The two LEDs, OK and Set Status, provide essential information on the status of the system.
Table 3-1: OK LED Indication
OK LED Status
Meaning
Off Both AC and Battery power are disconnected. Green On System Power Status is OK and there is no System Trouble. Green Flashing Open Zone. Check that the windows and doors are closed and no movement is
detected by the detectors within the protected area. Yellow On System Trouble. Yellow Flashing (slow) Backup battery low or low battery from transmitters. Yellow Flashing (fast) AC loss. Yellow Intermittent
On/Off
System Trouble in addition to AC loss/Low Battery.
Table 3-2: Set Status LED Indication
LED Status
Meaning
Off The system is unset. Green On The system is set. Red Flashing An alarm has occurred. Alarm indication is cleared the next time you set the
system or view the relevant setting event in the event log.
Alarm indication is not displayed after a silent panic alarm.
3.3. Front Panel Keypad
The alphanumeric keypad on the front panel enables you to perform various operation and programming tasks. Apart from Full, Part, and Perimeter setting, the front panel keypad offers a number of special functions.
Table 3-3: Front Panel Keypad Functions
Key
Symbol used in
the text of this manual
Special function
1
Used to enter symbols in descriptor editing.
0
Used to enter symbols in descriptor editing.
Χ Used to cancel the current selection.
Used to return to the previous menu level.
Used to enter Menu mode.
Used to select the current menu item. Used to signify the end of an entered value. Toggles status in Zone Omit/Un-omit function.
Page 20
3 Basic System Operation
CommPact Installation Manual
16
In descriptor editing, used to insert a space before the current character In phone number editing, used to enter "T", ",", "P", "+", "*", "#". In account number editing, used to enter Hexadecimal digits (A-F). Toggles item descriptors and default names. In the event log, toggles the time/date stamp. Toggles AM and PM when setting the time in 12hr format. In descriptor and phone number editing, used to delete the current
character
Used to scroll backwards in the current menu level. For Global Chime and Message Center features, used to access
shortcuts.
+ (Global Chime shortcut) + Χ (Record Message shortcut, front panel keypad only) + √ (Play Message shortcut, front panel keypad only)
Used to scroll forwards in the current menu level. During standby, used to scroll through the list of system trouble
conditions.
3.4. LCD Display
The LCD display provides you with a detailed interface for operation and programming.
3.4.1. Standby Mode
Standby mode can be defined as the state the system is in when it is unset and not in Menu mode. In Standby mode, the set status, system status, or banner is displayed. If system status is normal, the current time is displayed.
Table 3-4: Set Status
Item
Description
UNSET The system is unset. FULL SET
The system has been set using the displayed setting method.
PART SET PERIMETER SET PART SET INST
The system has been set using the displayed setting method with the Instant set feature activated.
PERIM SET INST FULL SETTING
The system is in the process of setting (displayed during exit delay).
PART SETTING PERIMETER SETTING
Page 21
3 Basic System Operation
CommPact Installation Manual
17
Item
Description
PART SETTING INST
The system is in the process of setting with the Instant set feature activated.
PERIM SETTING INST
Table 3-5: System Status
Item
Description
ZONES IN ALARM Zones have been violated. TAMPER ALARM The system has been tampered with. 56 TO EXIT The exit delay is counting down (56 seconds remaining). 11 TO UNSET The entry delay is counting down (11 seconds remaining). SYSTEM NOT READY The system is not ready to set, check that all doors and windows are closed. KEYPAD LOCKED Five unsuccessful attempts were made to enter a user code; the keypad is locked for
30 minutes.
SYSTEM TROUBLE A trouble condition has been detected, press  for further details.
3.5. Audible Notification
The following table is a summary of tones that audibly notify system status.
Table 3-6: Audible Notification
Status
Tones Description
Positive Acknowledge
1 long tone. The preceding action was accepted.
Negative Acknowledge
5 low tones. The preceding action was not accepted (e.g. an
incorrect user code entry).
Exit Delay/ Entry Delay
External Sounder: 4 tones. Built-in Sounder: 4 tones or
Continuous tones. Continuous tones quicken
when there are 15 seconds remaining and quicken again when there are 5 seconds remaining.
The exit/entry delay is counting down. The number of tones sounded during each delay is
determined in programming – see The number of tones sounded during each delay is – see
p. 50 8.5 Setting Tones.
Chime 2-tone modulated sequence
(similar to a doorbell).
A zone with the Chime option enabled has been opened – see p. 43 7.3.5 Chime .
Set 3-tone modulated sequence
(low to high) sounded twice
The system has been set using any of the setting methods.
Unset 3-tone modulated sequence
(high to low).
The system has been unset.
System Trouble 4 rapid tones sounded once
per minute.
A trouble condition has been detected, press for further details. For Fire Trouble Tones, there is a programmable option to repeat fire-related trouble tones until the problem has been taken care of – see p. 51, 8.6.3 Fire Trouble Tones.
3.5.1. System Trouble Tones
In the event of system trouble, the CommPact Control System sounds a series of tones to alert the user. To silence these tones, press and scroll through the system trouble list displayed on the LCD. When the trouble condition is restored, it is removed from the system trouble list.
Page 22
3 Basic System Operation
CommPact Installation Manual
18
For this feature to function, Trouble Tones must be enabled in programming – see p. 51,
8.6.1 System Trouble Tones.
System trouble tones are not sounded from 10:00pm to 7:00am so as not to disturb household members who may be asleep. However, you can program the system to immediately annunciate telephone trouble at all times – see p. 51 8.6.2 Telephone Trouble Tones.
3.5.2. Vocal Message Annunciation
Certain versions of the CommPact Control System hardware support vocal annunciation of system status. If this feature is enabled in programming (see p. 59, 9.10 Vocal Messages), the system plays short messages to indicate setting, unsetting, omitted zones, system trouble, message waiting, and water alarm.
The availability of the Vocal Message annunciation feature is hardware dependent.
3.5.3. Alarm Sounding Patterns
The following table summarizes the system’s various alarm patterns.
Table 3-7: Alarm Patterns
Alarm
Alarm Pattern Description Sounding
Device
Burglary ON (continuously) Sounder Fire ON - ON - ON, 1.5-second pause, ON - ON – ON... Sounder Gas ON - ON - ON - ON (short bursts), 5 second pauses, ON - ON - ON -
ON...
Sounder
Medical ON (continuously) – only applicable for Medical alarm from zone Sounder Flood/ Environmental
4 rapid tones sounded once per minute (same as Trouble tones) Buzzer
3.6. Setting and Unsetting
The following section explains how to set and unset the Control System using the front panel keypad or Wireless Keypad:
3.6.1. Setting
You have three setting modes available: full, part, and perimeter. Figure 3-3 illustrates the three setting modes. In each diagram, the protected area is shaded.
Full Set Part Set Perimeter Set
Figure 3-3: Setting Modes
The setting options are entirely flexible. You can program each detector to be included in any combination of the three setting modes – see p. 42, 7.3.2 Set. Additionally, each setting mode has a separate exit and entry delay.
Page 23
3 Basic System Operation
CommPact Installation Manual
19
Below you can see another, more complicated example of how can the premises be divided. In this example, the garage is included in full + part + perimeter setting, the house perimeter zones are included in full + perimeter setting, and the house interior zones, in full setting only. So, part setting allows the user to set the garage, perimeter setting is used to secure the house perimeter at nights, and the full setting is used when leaving the house. Figure 3-4 illustrates this example. In each diagram, the protected area is shaded.
Full set Part set Perimeter set
Figure 3-4: Setting Modes: Garage Example.
3.6.2. Setting Keys
The Setting keys enable you to set the system using any of the three setting methods: -- Full, Part and Perimeter.
Front Panel Wireless Keypad EL-2620
Figure 3-5: Setting Keys
3.6.3. Full Setting
Full setting is designed for when the occupant vacates the premises. To fully set the system using the front panel keypad or Wireless Keypad:
1. Check if the system is ready to set.
2. Press the Full setting key on the keypad.
3. If One-Key Setting is disabled, enter your user code.
3.6.4. Part Setting
Part setting is designed for when the occupant intends to remain inside one part of the premises and secure another part.
To partially set the system using the front panel keypad or Wireless Keypad:
1. Check if the system is ready to set.
2. Press the Part setting key on the keypad.
3. If One-Key Setting is disabled, enter your user code.
Page 24
3 Basic System Operation
CommPact Installation Manual
20
3.6.5. Perimeter Setting
Perimeter setting is designed for when the occupant intends to remain inside the premises and secure the perimeter.
To set the system’s perimeter using the front panel keypad or Wireless Keypad:
1. Check if the system is ready to set.
2. Press the Perimeter setting key on the keypad.
3. If One-Key Setting is disabled, enter your user code.
3.6.6. Combination Setting
The system allows you to activate a combination of two setting methods. If you Perimeter set the system, you may also activate Full or Part setting. Likewise, you can Perimeter set the system after activating Full or Part setting. It is not important which setting mode you choose first.
You can activate the second setting mode only during the exit delay of the first setting mode. When the first exit delay expires, you cannot activate a second setting mode.
For combination setting, perform the following procedure:
1. Check if the system is ready to set.
2. Activate the first setting mode.
3. If One-Key Setting is disabled, enter your user code.
4. While the exit delay of the first setting mode is counting down, activate the second setting mode.
5. If One-Key Setting is disabled, enter your user code.
It is not possible to activate Full and Part setting modes simultaneously. It is
necessary to unset first when changing from one setting mode to another setting mode.
The exit delays of the two setting modes are entirely independent. The moment a setting mode is activated, its exit delay begins to count down. The entry delay depends on which detector was tripped first. For example, if the detector is included in Full setting, the entry delay for Full setting counts down – see p.42, 7.3.2 Set. If the detector is included in both activated setting modes, the entry delay for Perimeter setting counts down.
Unsetting cancels both active setting modes.
3.6.7. Unsetting
When an entry/exit detector is tripped, the entry delay counts down; each setting method has its own entry delay.
To unset the system:
Enter a valid user code, the system is unset.
You can only unset all the active setting modes.
Page 25
3 Basic System Operation
CommPact Installation Manual
21
3.7. Additional Setting Options
3.7.1. Forced Setting
Forced setting enables you to set the system when the system is not ready. For example, if a door protected by a magnetic contact is open, you may set the system on condition that the door will be closed by the end of the Exit delay. If the door is still open after the exit delay expires, an alarm is generated.
Two conditions enable you to perform Forced setting:
Forced setting is enabled – see p. 53, 9.2.1 Forced .
The detector that is causing the System Not Ready condition is Force Set enabled – see
p.43, 7.3.6 Force .
3.7.2. Instant Setting
Instant setting is a feature that allows you to cancel the entry delay after Part or Perimeter setting the system. For this feature to function, it must be enabled in programming – see p. 54, 9.2.4 Instant
To instantly set the system.
1. Check if the system is ready to set.
2. Press the Part or Perimeter setting key on the keypad and enter your user code if One-Key Setting is disabled.
3. Press and hold down on your keypad until the message Instant Setting, OK? is displayed
4. Press '√ʹ; the entry delay for the current setting period is canceled.
3.7.3. Remote Setting/Unsetting via SMS
You can set and unset the system remotely by sending the SMS commands from a cellular phone. Additionally, you can check the set status of the system by sending an Set Status request message.
Each SMS command contains the following elements:
SMS Command Descriptor (up to 43 characters of free text) # (delimiter – separates the descriptor from the actual command) User Code (4 digits) Command (120=Unset, 121=Full Set, 122=Part Set, 123=Perimeter Set, 124=Full + Perimeter Set, 125=Part +
Perimeter Set, 200 = Set Status)
The following example shows the format of an SMS command for setting the system:
FU L L SET#1234121
While the SMS Command Descriptor is optional, you must start the SMS command with the # symbol for the system to accept the command.
After an SMS command is executed by the system, you can program the system to return a confirmation message to the sender – see p. 72, 10.7.5 SMS Confirmation.
3.7.4. Set Status Reply
On receiving an Set Status request message, the system returns a status message to the sender. This message includes the system status and the descriptor of the user or the device used to set/unset the system.
Page 26
3 Basic System Operation
CommPact Installation Manual
22
The following example shows an Set Status Reply message reporting that the system was fully set by Master User.
F U L L S E T -MAST ER US E
R
3.7.5. Remote Setting/Unsetting via DTMF
Using the Telecontrol feature, you can set and unset the system via the telephone with DTMF commands. For further information on the Telecontrol features, see p. 35, 5.1.5 Set/Unset DTMF Commands.
3.7.6. Remote Setting/Unsetting via WUAPP
You can set and unset the system remotely using the WUAPP (Web User Application) – see p. Error! Bookmark not defined., Error! Reference source not found..
3.7.7. Alarm Activation
In the event of an emergency, the user can generate three kinds of alarms from the front panel keypad, wireless keypad, or keyfobs.
To activate an SOS Panic alarm from the Keyfob EL-2714E:
Press B1 and B2 buttons
simultaneously.
Figure 3-6: SOS Panic Alarm Activation (EL-2714E)
To activate an SOS Panic alarm from the front panel keypad:
Press and hold down both SOS
buttons simultaneously.
Figure 3-7: SOS Panic Alarm Activation (Front Keypad)
To activate a Fire alarm from the front panel keypad:
Press and hold down buttons 1
and 3 simultaneously.
Figure 3-8: Fire Alarm Activation
To activate a Medical alarm from the front panel keypad :
Press and hold down buttons 4
and 6 simultaneously.
Figure 3-9: Medical Emergency Alarm Activation
Page 27
4 Advanced System Operation
CommPact Installation Manual
23
4. Advanced System Operation
Besides the basic setting functions described in the previous chapter, you can access additional functions via the menu. This chapter describes these functions and the menu navigation procedure.
4.1. Menu Navigation
Figure 4-1: On-Board Keypad Layout
The Front Panel's friendly, menu-driven interface is designed to facilitate operation and provide a gentler learning curve for first-time users. You can navigate through the menus using the arrow navigation keys (/) and make simple yes/no decisions using the 3 and 7 keys.
For example, perform the following procedure to navigate to Service, Interface Test.
1. Press '√ʹ to enter Menu mode.
2. Enter an authorized user code; the first menu item, 1. Cancel Report is displayed.
3. Press until 7. Service is displayed.
4. Press '√ʹ to enter the Service menu.
5. Press until 5. Interface Test is displayed.
6. Press '√ʹ to choose the displayed function.
Press Χ to return to the previous menu level. Press this key when you are in the main menu to exit Menu mode.
As an alternative to scrolling through menu options, you may enter a function’s shortcut once you have entered Menu mode. Shortcut numbers appear in square brackets in the procedures throughout this manual.
4.1.1. Menu Mode Timeout
Menu mode automatically terminates at a predefined amount of time after the last keystroke. The duration of this timeout depends upon which code is used to enter the menu. Usually the Menu Mode Timeout is two minutes but if you enter menu mode using the Engineer code, the timeout is extended to fifteen minutes.
Menu Navigation Keys
Service Call Key
A
lphanumeric
Keypad
Page 28
4 Advanced System Operation
CommPact Installation Manual
24
4.2. Cancel Report
This feature allows the user to cancel false alarms. Cancel Report behavior depends on time when it is performed. If the user selects Cancel Report:
…before the alarm/restore message is sent, all the pending alarm or restore messages
in the queue are aborted and marked "Cancelled" in the event log.
…within 5 minutes since an alarm, a Cancel Report event and the user number are
sent to the Central Station;
…at the moment when the event is being reported (communication in progress), the
event reporting is not cancelled;
Non-alarm events (system trouble, set/unset etc.) are not aborted by Cancel Report.
To activate cancel report:
From the main menu, select Cancel Report. [1].
4.3. Zone Omitting
When a detector is omitted, it is ignored by the system and does not generate an alarm when triggered.
To omit a detector:
1. From the Omit Zones menu, select Omit [21].
2. Using the arrow keys, scroll to the detector you want to omit
3. Press '√ʹ to change the omit status.
4. Press ‘Χ’; Save Changes? is displayed.
5. Press '√ʹ to confirm the changed omit status. To un-omit all detectors:
1. From the Omit Zones menu, select Un-omit All [22].
2. Press '√ʹ; all detectors are un-omitted.
All omitted zones are automatically un-omitted when the system is unset.
A Fire zone cannot be omitted.
4.4. User Codes
The Control System supports up to 32 individual user codes. Each of these codes is four digits long. Most system operations require you to enter a valid user code. The ability to perform an operation is defined by your user code’s authorization level. These authorization levels are pre-defined for each code as explained below.
Codes 1-29 can be edited only by the Master code.
The Engineer code and the Central Station TWA Code can be edited only by the engineer.
Page 29
4 Advanced System Operation
CommPact Installation Manual
25
Code 1: Master Code
The Master code is the highest user authorization level. With the Master code, you can edit all other user codes except the Engineer code, the Guard code and the Central Station TWA Code. Additionally, the Master code grants access to the Event Log, and the Service menu. The Master code is a "controlled" code. Setting and unsetting using this code causes the Control System to notify the central station with an Set/Unset event message*.
The default Master code is 1234. Change this code immediately after installing the system!
Codes 2-19: Controlled Codes*
When you use a controlled user code for setting and unsetting, the Control System notifies the central station with an Set/Unset event message.
Codes 20-25: Non-controlled Codes
Non-controlled codes do not cause the Control System to send Set/Unset event messages to the central station. The Control System sends a Unset message only if you use this code to unset the system after an alarm occurrence.
Codes 26-27: Limited Codes
A Limited code enables the user to issue a code that is valid for one day only. This code automatically expires 24 hours after it has been programmed. These codes are "controlled" in that their use for Set/Unset is notified to the central station.
Code 28: Duress Code
The Duress code is designed for situations where the user is being forced to operate the system. This user code grants access to the selected operation, while sending a Duress event message to the central station.
Code 29: Telecontrol Code
The Telecontrol code is designed to enable the user to perform a number of tasks via their telephone using DTMF commands. Using this code, the user can call their system to set and unset, activate and deactivate the PGM output, cancel sounder activation or establish Two-Way Audio communication.
Code 30: Central Station TWA Code
The Central Station TWA code is designed to enable the central station operator to establish Two­Way Audio communication with the Control System after an alarm. This code is valid for use for the first ten minutes after an alarm has occurred. This code can only be used for this specific purpose and does not grant access to any additional system functions such as unsetting.
Code 31: Guard Code
Guard Code is an option that allows a security guard to check the premise in case of an alarm.
*
Only if arm/unset event group is enabled in System Programming
*
Only if arm/unset event group is enabled during System Programming
Page 30
4 Advanced System Operation
CommPact Installation Manual
26
Code 32: Engineer Code
The Engineer code grants access to the Programming menu and the Service menu. Additionally, this code enables you to view and clear the Event Log.
The default Engineer code is 1111. Change this code immediately after installing
the system!
4.4.1. Editing User Codes
To edit a user code:
1. From the main menu, select User Codes [4].
2. Select the code you want to edit.
3. From the code’s sub-menu, select Edit Code [#1]; the 4-digit code is displayed with the cursor flashing on the first digit.
4. Edit the code.
5. Press '√ʹ; the new code is stored in the memory.
If you enter a code that is identical to an existing user code, the Control System sounds an error tone and the new code is not accepted.
4.4.2. Deleting User Codes
To delete a user code:
1. From the main menu select, User Codes [4].
2. Select the code you want to delete.
3. From the code’s sub-menu, select Edit Code [#1]; the 4-digit code is displayed with the cursor flashing on the first digit.
4. Enter 0000.
5. Press '√ʹ; the code is deleted.
The Engineer and Master codes cannot be deleted.
4.4.3. User Code Descriptors
Each user code can be assigned a 16-character descriptor. These descriptors help to identify users in the event log and in SMS Follow-Me messages.
To edit a code descriptor:
1. From the main menu, select User Codes [4].
2. Select a code.
3. From the code’s sub-menu, select Descriptor [#2].
4. Edit the descriptor using the alphanumeric keypad.
5. Press '√ʹ when you have finished editing.
Page 31
4 Advanced System Operation
CommPact Installation Manual
27
4.5. Follow-Me
The Follow-Me feature is designed to notify the user that certain events have occurred. The events that are sent to the Follow-Me telephone number are those events that the user is authorized to view in the event log; events that can be viewed only by the engineer are not sent to the Follow-Me number – see p. 139, Appendix D: Event Table. If using the TWA Follow-Me feature, the audio channel is opened after alarm events only.
To edit the Follow-Me number:
1. From the main menu, select Telephone, Follow-me Number # [5].
2. Enter a telephone number for Follow-Me communication. If using the SMS Follow-Me feature, this number must be for a cellular phone with the capability to receive SMS messages.
You may only access Follow-Me programming if the protocol for Account 3 is programmed as SMS or TWA Follow-Me.
4.6. Event Log
The event log records the last 1022 events the system has undergone. The log uses the FIFO (First In, First Out) method, automatically erasing the oldest event when the log is full.
To view the event log:
1. From the Event Log menu, select View Log [61]; a summarized version of the most recent event is displayed. Press the key to view the time/date stamp or the device/user number on the second row of the display.
2. Use the arrow keys to scroll through the events.
3. When you have finished viewing, press ‘Χ ‘ to exit the log.
The event log displays the following information for each event:
The event descriptor – a brief description of the event that occurred.
The zone where the event occurred.
Time/date stamp – the exact time the event occurred.
Report details – a single character indicating whether the event was reported to the
central station. The options available are R: Report Sent, F: Report Failed, C: Report Canceled, N: No Report, or D: Disabled.
Figure 4-2 shows the detailed event log entry for a Fire alarm on November 14
th
2008. The event
was successfully reported to the central station.
Figure 4-2: Detailed Event Log Display
Page 32
4 Advanced System Operation
CommPact Installation Manual
28
4.6.1. Event Log Authorization Levels
Every event that occurs is recorded in the event log. However, certain events are intended for the engineer only. Those events include various service messages that are of little interest to the regular user. The View Log function requires you to enter either the Master or Engineer code. The events that are displayed depend on which code you use to enter the log – see p.139, Appendix D: Event Table.
4.6.2. Clearing the Event Log
The Clear Log function erases all events from the log. After performing this function, a Clear Log event is recorded in the log. The Clear Log function is accessible using the Engineer code only.
To clear the event log:
1. From the Event Log menu, select Clear Log [62]; the OK? confirmation message is displayed.
2. Press '√ʹ; the log is cleared -- See p.139, Appendix D: Event Table.
For certain versions of the CommPact Control System software, the Clear Log function may be disabled.
4.7. Service Menu
The Service menu is accessible using either the Engineer or Master code. This menu includes various functions that enable you to test the system effectively.
4.7.1. Set Time & Date
The time and date are used to time stamp events in the event log. Additionally the time is also displayed on the LCD display.
To set the time:
1. From the Service menu, select Set Time/Date, Set Time [7011].
2. Enter the current time.
3. Press '√ʹ; the time is modified.
To set the date:
1. From the Service menu, select Set Time/Date, Set Date [7012].
2. Enter the current date.
3. Press '√ʹ; the date is modified.
The format of the time and date is defined in the System Options – see p.56, 9.5.3 Time/Date
Format. If you are setting the time in 12hr format, use the
key to toggle between AM
and PM.
Page 33
4 Advanced System Operation
CommPact Installation Manual
29
4.7.2. Message Center
The CommPact Control System Message Center is designed to allow the user to record a short message that may be played back later by another user. After a message is recorded, Message Waiting is displayed on the LCD until the message is played back. If the Vocal Message option is enabled, the Message Waiting vocal message is sounded.
Recording a new message automatically overwrites the previous messages in the Message Center.
To play back a recorded message:
From the Service menu, select Messages, Play Message [7021].
To record a message:
1. From the Service menu, select Messages, Record Message [7022].
2. Press '√ʹ to start recording the message.
3. Record your message. The message may be up to twenty seconds long. Time left out of the 20 seconds' timeout is displayed on the LCD.
4. Press '√ʹ to stop recording; the message is automatically played back and OK? Is displayed.
5. Press '√ʹ to save your recording.
To delete a message:
1. From the Service menu, select Messages, Delete Message [7023]; OK? Is displayed.
2. Press '√ʹ, the message is deleted.
The Record and Play options can also be accessed via a convenient shortcut without needing to enter a valid user code.
To play back a recorded message via a keypad shortcut:
From Standby mode, press then '√ʹ.
To record a message via a keypad shortcut:
From Standby mode, press, ‘Χ‘ then '√ʹ.
4.7.3. Wireless Sounder Test
To test the wireless sounder:
From the Service menu, select WL Sounder Test [703]; the external sounder is
sounded briefly.
4.7.4. Sounder Test
To test the Control System’s Built-In Sounder:
From the Service menu, select Sounder Test [704]; the Control System’s Built-In
Sounder is sounded briefly.
4.7.5. Interface Test
The Interface test enables you to check if the speaker, LEDs and LCD are functioning correctly. To test the system interface:
From the Service menu, select Interface Test [705]; a short sequence of chimes are
sounded from the speaker, all LEDs flash and the LCD Display is tested.
Page 34
4 Advanced System Operation
CommPact Installation Manual
30
4.7.6. Walk Test
To initiate Walk Test mode:
1. From the Service menu, select Walk Test [706]; a list of registered detectors appears.
2. Trigger each detector; when the system receives a successful transmission from a detector, the detector is removed from the list.
3. When all the detectors are removed from the list, End Walk Test is displayed.
4. Press ‘Χ‘ to exit Walk Test mode.
4.7.7. Transmitters
The Transmitters menu offers two utilities that serve as a valuable aid during installation. The first utility, TX List, is a scrollable inventory of all registered transmitters and their last reported
status. To view the TX list:
1. From the Service menu, select Transmitters, TX List [7071]; the first transmitter on the list is displayed.
2. Using the arrow buttons, scroll through the transmitter list.
3. When you have finished viewing, press ‘Χ ‘to exit the list.
The TX list displays the following information for each transmitter:
The zone descriptor.
The signal strength of the last received transmission.
An abbreviation indicating the last received status of the transmitter – see Table 4-1.
Table 4-1: Transmitter Status Abbreviations
Item
Description
OK The transmitter is functioning correctly TA Tamper condition BT Battery low OS The transmitter is out of synchronization NA The transmitter is inactive (Supervision Loss) – see p. 40, 7.2.3 Supervision Time
Press
Figure 4-3: TX List Display
In most cases, an "out of synchronization" condition indicates that an unauthorized attempt at grabbing the transmission has occurred – i.e. a previous transmission has been recorded and sent by somebody trying to violate the system.
Page 35
4 Advanced System Operation
CommPact Installation Manual
31
The second utility, TX Test, enables you to identify transmitters and test their signal strength. In TX Test mode, each time a transmission is received, the activated transmitter is displayed. If you enter this function using the Master code, a chime is sounded every time a transmission is received. If you enter this function using the Engineer code, a sequence of tones is sounded indicating the transmitter’s signal strength – see Table 4-2. This feature helps you to determine the best location to install a transmitter.
The lowest recommended signal strength for any installed transmitter is 5. If the received signal strength is lower than 5, relocate the transmitter.
Table 4-2: Signal Strength Tones
Signal Strength
Strength Tones
0-2 1Tone 3-5
2 Tones
6-7
3Tones
8-9
4 Tones
To initiate TX Test mode:
1. From the Service menu, select Transmitters, TX Test [7072].
2. Activate a transmitter; the transmitter’s details are displayed.
3. When you have finished, press ‘Χ‘ to exit TX Test mode.
4.7.8. Audio Volume
To adjust the sensitivity of the microphone and the volume of the speaker:
1. Establish a two-way audio connection – see 5.1.4 Telecontrol Call Procedure.
2. From the Service menu, select Audio Volume [708].
3. Using the arrow keys on the Front Panel keypad, adjust the setting according to the following table.
Table 4-3: Voice Level Adjustment
Key
Function
1 Increases microphone sensitivity 4 Reduces microphone sensitivity
3
Increases speaker volume
6
Reduces speaker volume
4. Press '√ʹ; the new settings are stored in the memory.
4.7.9. GSM Signal Strength
You can measure the GSM signal strength. This function and the RF RSSI level (see below) enable you to calculate the optimal location to install the Control System.
To view the GSM signal strength reading:
From the Service menu, select RF & GSM level, GSM Signal [7091]; the signal strength
of the cellular network is displayed.
In severe cases of low GSM signal consider using external GSM antenna.
Page 36
4 Advanced System Operation
CommPact Installation Manual
32
4.7.10. RF RSSI level
You can measure the RF RSSI level (RF noise measured by the systems' receiver) using the system’s RSSI (Received Signal Strength Indication) meter. The Control System will start measuring the RSSI level of the receiver every second, and it will display the result in levels from 1 to 9 – similar to the level of detector transmitter's signal strength. It is recommended that the gap between the RF noise level and the TX signal strength be at least 2. For example, if the RF RSSI level is 5 and the TX signal strength is 6, consider relocation of the Control System or its peripherals – see p. 7 2.1.1 Wireless Installation Guidelines.
The menu will have timeout of 5 minutes. If the engineer doesn't exit the menu within 5 minutes of its entry, the Control System will exit all menus.
To view the RF RSSI level reading:
From the Service menu, select RF & GSM level, RF RSSI level [7092]; the RF RSSI level
of the Control System's receiver is displayed.
4.7.11. Display Version
To display the system’s software and hardware versions:
From the Service menu, select Version [710]; the software (SW) versions is displayed.
4.7.12. Enable Programming
The Enable Programming command enables a user with Master code authorization to grant access to system programming. This feature is relevant only if the Engineer Access and/or the RP Access options are programmed as "User Initiated" – see p. 59, 9.11 and p. 66, RP Access Options.
To grant access to the engineer or Remote Programmer:
From the Service menu, select Enable Prog. [711]; a 30-minute time window is opened
during which the Engineer Code is valid or RP communication may be established.
Page 37
4 Advanced System Operation
CommPact Installation Manual
33
4.7.13. Global Chime
The Chime feature causes the Control System’s Built-In Sounder to ring when specific zones are triggered. Using the Global Chime option, you can enable or disable this feature for all zones that are defined as Chime enabled – see p.43, 7.3.5 Chime.
To enable or disable Global Chime:
1. From the Service menu, select Global Chime [712].
2. Select either Enabled or Disabled.
Though the Service menu is accessible to the Master and Engineer only, Global Chime can also be accessed via a convenient shortcut without needing to enter a valid user code. To access the Global Chime option from Standby mode, press then.
4.7.14. Remote Firmware Update
The Remote Firmware Update command enables a user with Master code authorization to initiate the update. This feature is relevant only if the Remote Firmware Update mode is programmed as "User Initiated" – see p. 73, 10.8.4 Remote Firmware Update
To grant access to Remote Firmware Update:
From the Service menu, select, SW Update [713]; a 24-hours time window is opened
during which the Remote Firmware Update may be performed.
4.7.15. System Reset
System Reset feature can be accessed with Engineer and Master Code. When accessed with Engineer Code, reset message is registered in the log.
To Reset the System:
From the Service menu, select System Reset [714]; the OK? confirmation message is
displayed.
Page 38
5 Telecontrol and Two-Way Audio
CommPact Installation Manual
34
5. Telecontrol and Two-Way Audio
The CommPact Control System offers a range of Telecontrol features that provide remote access via the telephone. These features include Two-Way Audio, remote setting/unsetting and cancel sounder activation. This chapter explains these features and their operating procedures.
Telecontrol features can be separated into two fundamental groups; incoming and outgoing calls. These groups differ in their associated features.
5.1. Incoming Calls
The Control System can receive incoming calls from either the user or central station operator. Users may use this feature as a convenient way of contacting their family, operating their system or to check their home when they are away. Additionally, the monitoring service can contact the user in the event of an emergency or use this feature for listen-in alarm verification.
For any of the incoming Telecontrol features to function, Telecontrol must be enabled in the Communication Options section of the Programming menu – see p. 69, 10.6.9 Incoming Calls.
5.1.1. User Code Verification
To prevent unauthorized attempts to connect with the Control System, there are two user codes designed for use with the Telecontrol features. The Telecontrol code enables the user to establish communication with the Control System at any time. Additionally, the Central Station TWA Code is used exclusively for Two-Way Audio alarm verification and is only valid for a ten-minute period following an alarm.
5.1.2. Incoming Calls via PSTN
In the case of PSTN communication, the Control System often shares a line with regular telephone handsets, an answering machine or a fax machine. It is therefore important that the Control System distinguish between calls so that it knows when to pick up the relevant call. For this purpose the CommPact Control System employs a double call method.
To connect to the Control System using the double call method:
1. Dial the telephone number of the line connected to the Control System.
2. Wait for two or three rings and hang-up.
3. Wait at least five seconds and dial the number again; on the second ring, the Control System picks up and sounds two DTMF tones.
5.1.3. Incoming Calls via a Cellular Network
The Control System has its own individual telephone number and therefore, the double call method is not needed. In this case, the user or central station operator may call the Control System directly.
5.1.4. Telecontrol Call Procedure
The following procedure explains how to make a Telecontrol call. The conditions and procedure differ when using PSTN or Cellular Communication. For further information, see the entire section
5.1 Incoming Calls.
To make a Telecontrol call:
1. Call the Control System either using the double call method (PSTN) or directly (Cellular); when the Control System picks up, two DTMF tones are sounded.
2. Enter the Telecontrol code (Code 29) on your telephone within 15 seconds.
Page 39
5 Telecontrol and Two-Way Audio
CommPact Installation Manual
35
Do not enter your user code until you hear the two DTMF tones. Any digits entered before the tones are sounded are disregarded by the system.
3. A DTMF tone is sounded to indicate that the system is ready to receive commands. The following DTMF commands are available:
o Press "2" for Two-Way Audio.
If the TWA mode is defined as "Simplex" (see 70, 10.6.11, TWA Mode.), the audio channel opens in Listen mode (microphone active/speaker mute). To switch to Speak mode, press "1" on your telephone. To switch back to Listen mode, press "0" on your telephone.
During the TWA session, you can adjust the speaker volume using the arrow buttons.
o Press "3" to fully set the system. o Press "430" to activate PGM output (Unit 30) o Press "530" to deactivate PGM output (Unit 30) o Press "6" to unset the system. o Press "9" to cancel the sounder.
Set/Unset, PGM on/off, and Sounder Canceling can also be executed at any time during a Two-Way Audio session.
Error beeps (three tones) sound in case of a wrong command.
To clear the last command, press "*" or "#".
o The duration of the call is determined by the TC/VM Timeout -- see p.70, 10.6.10
Telecontrol/Vocal Message Timeout. Ten seconds before the timeout expires, two short DTMF tones are sounded. To extend the call, press "7" on your telephone. This command restarts the timeout.
4. To disconnect before the end of the timeout, press "*" then "#" on your telephone.
5.1.5. Set/Unset DTMF Commands
During a Telecontrol call, you can set and unset the system remotely using the DTMF commands 3" (set) and "6" (unset). When setting the system in this way, the system is set immediately without an exit delay.
5.1.6. PGM DTMF commands
During a Telecontrol call, you can activate and deactivate PGM using the DTMF commands "430" (PGM On) and "530" (PGM Off).
5.1.7. Sounder Cancel ("Bell Cancel")
The sounder is muted during Two-Way Audio communication. At the end of the call, the sounder is re­activated (if the Sounder Cut-Off has not yet expired). During the call, pressing "9" on your telephone cancels the re-activation of the sounder.
5.1.8. Central Station Two-Way Audio
Central Station Two-Way Audio is an alarm verification feature that enables the central station operator to establish Two-Way Audio communication with the Control System within ten minutes of an alarm.
Page 40
5 Telecontrol and Two-Way Audio
CommPact Installation Manual
36
To make a Central Station TWA call:
1. Call the Control System either using the double call method (PSTN) or directly (Cellular); when the Control System picks up, two DTMF tones are sounded.
2. Enter the Central Station TWA code (Code 30) on your telephone within 15 seconds.
Do not enter your user code until you hear the two DTMF tones. Any digits entered before the tones are sounded are disregarded by the system.
3. If the TWA mode is defined as "Simplex"(see p.70, 10.6.11 TWA Mode), the audio channel opens in Listen mode (microphone active/speaker mute). To switch to Speak mode, press "1" on your telephone. To switch back to Listen mode, press "0" on your telephone.
4. The duration of the call is determined by the TC/VM Timeout -- see p. 70, 10.6.10 Telecontrol/Vocal Message Timeout. Ten seconds before the timeout expires, two short DTMF tones are sounded. To extend the call, press "7" on your telephone. This command restarts the timeout.
5. To disconnect before the end of the timeout, press "*" then "#" on your telephone.
5.2. Outgoing Calls
The CommPact Control System can make Two-Way Audio calls to the user or central station in the event of an alarm. This feature is designed for medical, panic alarms, and for alarm verification.
5.2.1. Service Call
The Service Call feature enables the user to establish a two-way audio connection with the central station operator. For further information on how to program this feature, see p. 67 , 10.5 Service Call.
To initiate a Service Call:
Press the up arrow key press and hold Service Call key for a few seconds.
The Control System starts to dial.
5.2.2. TWA Alarm Reporting
In the event of Burglary, Fire and Medical alarms, the Control System is able to report the events and then stay on the line after acknowledgment is received (ACK 2). This allows the operator to verify the alarm or provide assistance in the event of an emergency.
For this feature to function, you must enable Two-Way Audio for both the account and the event group.
The sequence for Two-Way Audio during alarm reporting is as follows:
1. An alarm event is sent to the central station and acknowledgment is received (ACK 2).
2. If Two-Way Audio is enabled for the account and event group, the Control System stays on the line and opens the audio channel.
3. If the TWA mode is defined as "Simplex" (see p.70, 10.6.11 TWA Mode), the audio channel opens in Listen mode (microphone active/speaker mute). The operator may switch to Speak mode, by pressing "1" on their telephone. Pressing "0" switches back to Listen mode.
4. The duration of the call is determined by the TWA/VM Timeout. Ten seconds before the timeout expires, two short DTMF tones are sounded. To extend the call, the operator presses "7" on their telephone. This command restarts the timeout.
5. To disconnect before the end of the timeout, the operator presses "*" then "#" on their telephone.
Page 41
5 Telecontrol and Two-Way Audio
CommPact Installation Manual
37
If multiple events are sent, the Control System sends all the events before opening the audio channel.
When using the SIA protocol for event reporting, this feature functions in "listen-in"
mode only.
5.2.3. Two-Way Audio after Vocal Messages
If Two-Way Audio is enabled for a Vocal Message account, the user can open the audio channel by pressing "2" on their telephone after the system has played all of the event messages.
The sequence for Two-Way Audio after a vocal message is as follows:
1. An event occurs and the Control System calls the telephone number of the first Voice Report Account chosen.
2. When the user answers the call, the Home ID message and the relevant event message are played.
3. If Two-Way Audio is enabled for the Voice Report account, the user presses "2" on their telephone to open the audio channel.
4. The duration of the call is determined by the TWA/VM Timeout. Ten seconds before the timeout expires, two short DTMF tones are sounded. To extend the call, the user presses "7" on their telephone. This command restarts the timeout.
5. To disconnect before the end of the timeout, the user presses "*" then "#" on their telephone.
5.2.4. TWA Follow-Me
The TWA Follow-Me feature is designed to establish a Two-Way Audio connection with the user in the event of an alarm. For this feature to function, the account’s protocol must be defined as TWA Follow-Me.
The sequence for a Two-Way Audio Follow-Me call is as follows:
1. An alarm occurs.
2. The Control System dials the programmed telephone number and sounds two DTMF tones when you pick up the call.
3. Press "2" on your telephone; the Control System opens the audio channel.
If you press "9" to answer the call, the Control System simultaneously cancels the sounder when opening the audio channel.
4. If the TWA mode is defined as "Simplex", (see p. 68, 10.6.11 TWA Mode), the audio channel opens in Listen mode (microphone active/speaker mute). To switch to Speak mode, press "1" on your telephone. To switch back to Listen mode, press "0" on your telephone.
5. The duration of the call is determined by the TWA/VM Timeout. Ten seconds before the timeout expires, two short DTMF tones are sounded. To extend the call, press "7" on your telephone. This command restarts the timeout.
6. To disconnect before the end of the timeout, press "*" then "#" on your telephone.
Page 42
6 PGM Control
CommPact Installation Manual
38
6. PGM Control
The purpose of this chapter is to explain the various methods used to control PGM output. PGM is a programmable output that is triggered according to specific system status conditions, or by remote command sent via PSTN, GSM, keyfobs explained below.
6.1. Keyfob Control
You can control PGM using any of the four button keyfobs registered to the system. For further information on how to assign keyfob B2 button to PGM, see p. 45, 7.4.2 PGM Assignment.
6.2. Telephone Control
You can send On and Off commands to PGM output by SMS messages sent from a cellular phone to the Control System. Alternatively, PGM can be controlled by DTMF commands during Telecontrol call (either cellular or landline). For this feature to function correctly, Telephone control must be enabled for PGM – see p.56, 9.6.1 Output Trigger.
6.2.1. DTMF Command
Using the Telecontrol feature, you can turn on and off PGM output via the telephone with DTMF commands. For further information on the Telecontrol features, see p. 35 5 Telecontrol and Two- Way Audio and PGM DTMF commands.
6.2.2. SMS Command Format
Each SMS command for PGM control must contain the following elements:
SMS Command Descriptor (Optional, up to 43 characters of free text)
User Code (4 digits)
Delimiter # (Mandatory, separates the descriptor from the actual command)
Command (0=Off, 1=On)
Device Number (30 for PGM output)
The following example shows the format of an SMS command to switch PGM On.
P G M ON#1234130
While the SMS Command Descriptor is optional, you must start the SMS command with the # symbol for the system to accept the command.
6.2.3. SMS Confirmation Message Format
After an SMS command is executed, the system can return a confirmation SMS message to the sender. This message includes the PGM descriptor and the command that was sent. For further information on how to enable this feature, see p. 72, 10.7.5 SMS Confirmation.
This message is sent when the parameter ‘SMS Confirm’ (Programming, Communications, Comm. Options, GSM Options, SMS Confirm [954135]) is Enabled.
The following example shows the confirmation message the sender receives for the sample command from the previous section:
PGM ON
Page 43
7 Devices
CommPact Installation Manual
39
7. Devices
This chapter explains how to register devices to the system and the programming options for each device. For further information, please refer to the installation instructions included with each device.
7.1. Device Descriptors
You can assign a 16-character descriptor to each device except the Wireless Sounder. These descriptors help identify the devices when you operate and program the system.
To edit a device descriptor:
1. From the Programming menu, select Devices [91].
2. Select a device type.
3. From the device’s sub-menu, select Descriptor.
4. Edit the descriptor using the alphanumeric keypad.
5. Press '√ʹ when you have finished editing.
7.2. Wireless Devices
7.2.1. Registering Wireless Devices
For the system to recognize individual devices, each device must be registered to the system. For example, if the device is a wireless transmitter, registration enables the system to identify the source of a received transmission. Each device has an individual encrypted ID code. Registering the device to the system familiarizes the system with this code.
To register a device to the system:
1. From the Programming menu, select Devices [91].
2. Select the type of transmitter you want to register. For example, if you want to register a wireless detector to a zone, select Zones.
3. Select the specific device you want to register (for example, Zone 4); the system initiates Registration mode. During Registration mode, the system waits for two transmissions from the device.
If a device has already been registered at the selected location, the system will not initiate Registration mode. If the device has already been registered at another location, attempts to register it are ignored by the system. Zones 1-32 are intended for wireless detectors by default.
4. Register the device – refer to each device’s installation instructions in Appendix B for further details.
5. When two transmissions have been received, Save? is displayed.
6. Press '√ʹ to confirm registration.
7.2.2. Deleting Wireless Devices
When you want to remove a device from the system, you have to delete the device. It is important to delete unused devices for two reasons. Firstly, you have to delete a device before you can register a new transmitter in its place. Secondly, if the device is a wireless detector, it is important to delete the device so that the system will not react to the transmitter’s failure to send supervision signals.
Page 44
7 Devices
CommPact Installation Manual
40
To delete a device:
1. From the Programming menu, select Devices, [91].
2. Select the specific device you want to delete.
3. From the device’s sub-menu, select Delete.
4. Press '√ʹ to confirm; the device is deleted.
7.2.3. Supervision Time
The detectors in Electronics Line 3000’s supervised wireless range send a supervision signal approximately 20 minutes after its last transmission. If the system does not receive supervision signals from a specific transmitter, the transmitter is regarded as inactive.
The amount of time after which a transmitter is considered inactive is called the Supervision Time. There is a separate supervision time for general transmitters and devices that are registered to Fire zones.
To program the Supervision Time for general transmitters:
1. From the Programming menu, select Devices, Superv. Time, General [9161].
2. Enter a supervision time between 02:00 and 23:59 hours. To program the Supervision Time for transmitters registered to Fire zones:
1. From the Programming menu, select Devices, Superv. Time, Fire [9162].
2. Enter a supervision time between 02:00 and 23:59 hours.
7.2.4. Re-Synchronization
Transmissions that are out of synchronization are rejected by the system. For example, it is not possible to set or unset the system using a keyfob that is out of synchronization. In the event that a transmitter is out of synchronization, it is possible to re-synchronize the transmitter and restore normal operation.
To re-synchronize transmitters:
From the Programming menu, select Devices, TX Re-synch [917]; a 10-minute time
window is opened. During the 10-minute time window, if a transmission is received that is out of
synchronization, the transmitter is re-synchronized.
Page 45
7 Devices
CommPact Installation Manual
41
7.3. Zones
The CommPact Control System supports Electronics Line 3000’s supervised wireless range of transmitters that includes various PIR detectors, magnetic contacts and smoke detectors. All these transmitters send supervision signals to the Control System's receiver in order to indicate that the transmitter is functional.
Control System includes 33 security zones. Zones 1-32 are intended for wireless detectors by default. Only one detector can be registered to each zone.
Zone 33 is an on-board hardwire zone. This zone is programmed in the same way as the wireless zones with the exception of registration and deletion.
This section explains the programming exclusive to detectors. For information on registration, descriptor editing, and deletion, see p. 39, 7.1, 7.2.1, 7.2.2. The zone menu is displayed according to the zone type (see below).
Most of the programming options are identical for hardwire and wireless zones with the following exceptions:
Wireless Zones
Register (see: p. 39, 7.2.1 Registering Wireless Devices)
Delete (see: p. 39, 7.2.2 Deleting Wireless Devices)
Repeater (see: p. 44, 7.3.7 Repeater)
Figure 7-1: Wireless Zone Menu
Wired Zone 33
Loop Type (see p. 44, 7.3.8, Loop Type)
Figure 7-2: Wired Zone Menu
Page 46
7 Devices
CommPact Installation Manual
42
7.3.1. Zone Type
The zone type defines the type of alarm the system generates when the detector is tripped. To program a zone type:
1. From the Programming menu, select Devices, Zones [911].
2. Select the detector you want to program.
3. From the detector’s sub-menu, select Zone Type [#02].
4. Select one of the following zone types:
Normal
Entry/Exit
Follower
Panic
Medical
Fire
24H
24Hr-X (future option)
Gas
Flood
Environmental
No Motion
Not Used
For a detailed explanation on the function of each zone type, see p. 139, Appendix D: Event Table.
7.3.2. Set
The Set option allows you to define the setting methods in which the zone is included. Each zone can be assigned to Full Setting and/or to Part and/or to Perimeter Setting in any
combination. The following table summarizes set options:
Table 7-1: Set Options
Set
Description
1 (F) The zone is included in Full setting. 2 (P) The zone is included in Part setting. 3 (PE) The zone is included in Perimeter setting.
To program the Set option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Set [#03]; the zone’s current Set setting is displayed.
4. Use the keys 1, 2 and 3 to toggle the current setting.
It is not necessary to program this option for Panic, Medical, Emergency, Fire, 24Hr and Gas, Flood and Environmental zones.
7.3.3. Descriptor
For information on device descriptor editing, see p. 39, 7.1 Device Descriptors
Page 47
7 Devices
CommPact Installation Manual
43
7.3.4. Bell (Sounder)
Each zone can be programmed to activate the sounder when triggered or to generate a silent alarm where only a message is sent to the central station.
To program the Bell option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Bell [#05]; the zone’s current Bell setting is displayed.
4. Select either Enabled or Disabled.
Fire zones always activate the sounder regardless of what is programmed for this
option.
If the bell is disabled for Panic zones, this also disables all forms of alarm indication
from the on-board keypad in the event of a Panic alarm.
If the Bell option is enabled for Environmental or Flood zones, the system sounds trouble tones from the keypad.
7.3.5. Chime
When Chime is enabled, triggering the zone when the system is unset causes the Built-In Sounder to chime.
To program the Chime option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Chime [#06]; the zone’s current Chime setting is displayed.
4. Select either Enabled or Disabled.
7.3.6. Force Set
Force setting enables you to set the system when the system is not ready. For example, a door that is protected by a magnetic contact is open. You may set the system on condition that the zone is defined as Force Set enabled. This door must be closed by the end of the Exit delay otherwise an alarm is generated. If the magnetic contact’s zone is defined as Force Set disabled, the system will not be ready to set until you close the door.
To program the Force Set option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Force Set [#07]; the zone’s current Force Set setting is displayed.
4. Select either Enabled or Disabled.
For the Force Set feature to function, you must also enable Force Setting in System
Options -- see p. 53, 9.2.1 Forced .
Page 48
7 Devices
CommPact Installation Manual
44
7.3.7. Repeater (Wireless Zones Only)
The EL-2635 repeater is an additional module that extends the range of the wireless transmitters. For a detector to use the repeater to relay transmissions to the system, you must define the Repeater option for its zone as "Use Repeater".
To program the Repeater option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Repeater [#09]; the zone’s current Repeater setting is displayed.
4. Select either No Repeater or Use Repeater.
Do not register the same transmitter to more than one repeater.
7.3.8. Loop Type (Wired zone 33 only)
This option enables you to determine the zone’s loop type. The Control System supports the following Loop Types:
Normally Closed (N.C.) – alarm on open, restore on close
Normally Open (N.O.) – alarm on close, restore on open
End of Line Resistor (E.O.L.R.) – alarm on short, alarm on open, restore on close
Double End of Line Resistor (D.E.O.L.R) – alarm on short, alarm on open, restore on
close, and tamper alarm on tamper.
The zone Loop Types must be defined accordingly at each zone’s programming parameters.
Figure 7-3: Loop Types
To program the Loop Type option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Loop [#01]; the zone’s current Loop type setting is displayed.
4. Select N.O., N.C., or E.O.L.R, or D.E.O.L.R.
Page 49
7 Devices
CommPact Installation Manual
45
7.4. Keyfobs
The CommPact Control System supports four types of keyfob transmitter, EL-2711M, EL-2711P, EL­2614E and EL-2714. You can register up to 19 keyfobs to the system. Figure 7-4 illustrates two of these transmitters and the functions assigned to their buttons. For information on registration and deletion, see p. 39, 7.2. Wireless Devices. For descriptor editing, see p. 39, 7.1 Device Descriptors.
EL-2714 EL-2711M/P
Figure 7-4: Keyfob Button Assignments
The following sections explain the programming options exclusive to the EL-2714 and EL-2614E keyfob transmitters. These programming options are not relevant to the EL-2711M and EL-2711P.
For panic Alarm activation with the keyfob, see p. 22, 3.7.7, Alarm Activation.
7.4.1. Keyfob Type
You can define each registered keyfob as Controlled or Non-controlled. A Controlled keyfob causes the system to send set/unset event messages to the central station. Non-controlled keyfobs never send set messages and send a unset message only if the system is unset after an alarm occurrence.
To program a keyfob type:
1. From the Programming menu, select Devices, Keyfobs [912].
2. Select the keyfob you want to program.
3. From the keyfob sub-menu, select Type [#2]; the current setting is displayed.
4. Select Controlled or Non-controlled.
7.4.2. PGM Assignment
The EL-2714 and EL-2614E allows programming B2 button to control PGM. When PGM Assign function is enabled, B2 is used for PGM control; when PGM Assign is disabled, B2 is used for Perimeter setting.
To program B2 button:
1. From the Programming menu, select Devices, Keyfobs [912].
2. Select the keyfob you want to program.
3. From the keyfob sub-menu, select PGM Assign [#4].
4. Select Enable for PGM Operation or Disable for Perimeter Set.
Medical/Panic Emergency
Perimeter Set
or PGM
Part Set or PGM
Full Set
Unset
Page 50
7 Devices
CommPact Installation Manual
46
7.5. Wireless Keypads
The system supports up to four wireless keypads: 1-Way Wireless Keypad (EL-2620) and Wireless Indication Keypad (EL-2621).
Figure 7-5: EL-2620 Keypad Layout
Figure 7-6: EL-2621 Keypad Layout
Keypad SOS Panic Alarm Activation
Using any of the wireless keypads, you can activate an SOS Panic alarm by pressing the Full and Perimeter setting keys simultaneously. Figure 7-7 illustrates how to activate an SOS Panic alarm on the EL-2620 wireless keypad.
Figure 7-7: SOS Panic Alarm Activation (EL-2620/2621)
Numeric
Keypad
Setting/ SOS
Keys
Arm and Alarm Status LEDs
Cancel
Setting/ SOS
Keys
Cancel
Numeric
Keypad
Battery Status LEDs
Page 51
7 Devices
CommPact Installation Manual
47
7.6. Repeaters
Repeaters are designed to extend the wireless range of the Control System. Up to four repeaters may be registered to the system with a maximum of 32 transmitters associated with each receiver. For information on registration, deletion, and descriptor editing, see p. 133.
7.7. Wireless Sounder
The Control System sends alarm and set status information to the wireless sounder’s receiver. This requires that you register the Control System to the wireless sounder’s receiver.
To register the Control System to the wireless sounder’s receiver:
1. Set the wireless sounder’s receiver to Registration mode – refer to the sounder’s installation instructions for further information.
2. Activate the sounder using the WL Sounder Test feature – see p.29, 4.7.3 Wireless Sounder Test.
3. Activate the sounder again; the Control System is registered to the sounder’s receiver.
2-way sounders must be registered to the Control System. For information on registration and deletion, see p. 39, 7.2.1 Registering Wireless Devices, and p. 39, 7.2.2 Deleting Wireless Devices.
7.7.1. Wireless Sounder Type
The Control System supports 2-way wireless sounders. For this feature to function correctly, you must define the wireless sounder type in programming.
The following options are available:
2-Way Sounder – if using the EL-2626AC wireless sounder.
2-Way Sounder/Kpd – if using the EL-2626AC wireless sounder and EL-2621 wireless
indication keypad.
To program the wireless sounder type:
1. From the Programming menu, select Devices, Sounder and WL Sounder Type [9152].
2. Select a sounder type or No WL Sounder if no sounder is installed.
7.7.2. Wireless Sounder Delay
The Wireless Sounder Delay is the period of time during which the wireless sounder is not sounded after an alarm is triggered by Normal, Follower or 24Hr zones. This feature is implemented only when the system is not fully set. During the Wireless Sounder Delay, the Control System’s built-in sounder is sounded but the alarm report is not sent until the delay has expired. This gives the user enough time to unset in the event that the alarm was accidentally triggered during Part or Perimeter setting. If the user unsets the system during the Sounder Delay, an alarm event is not reported to the central station.
To program the Wireless Sounder Delay time:
1. From the Programming menu, select Devices, Sounder and WL Sounder Delay [9153].
2. Enter a Sounder Delay time (00-63 seconds), then press '√ʹ.
Page 52
7 Devices
CommPact Installation Manual
48
7.7.3. Sounder Cut-Off
The Sounder Cut-Off is the period of time the sounders are activated after an alarm has occurred. You may program a Sounder Cut-Off time in the interval between ten seconds to twenty minutes.
To program the Sounder Cut-Off time:
1. From the Programming menu, select Devices, Sounder, Cut-Off [9154].
2. Enter a Sounder Cut-Off time MM:SS (00:10 - 20:00), then press '√ʹ.
7.7.4. Wired Sounder
When the system generates an audible alarm, both the wired Built-In Sounder and the wireless sounder are sounded. This option allows you to disable the alarm from the Control System’s Built­In Sounder. If disabled, the Control System’s built-in sounder may still be used to sound arm/unset and entry/exit tones.
To program the Wired Sounder option:
1. From the Programming menu, select Devices, Wired Sounder [9155].
2. Select Enabled or Disabled.
Page 53
8 Entry/Exit Timers and System Tones
CommPact Installation Manual
49
8. Entry/Exit Timers and System Tones
This chapter explains how to program the time of the Entry/Exit delays and the tones sounded by the Built-In Sounder and wireless sounder during Exit/Entry Delays, setting, unsetting, and when a trouble condition is present.
8.1. Entry/Exit Delay
The Entry/Exit delay timers determine the amount of time the user has to set or unset the system before an alarm is activated.
You can program separate Entry and Exit delays for each setting method. To program Exit delay timers:
1. From the Programming menu, select Entry/Exit, Exit Delays [921].
2. Select the Exit delay you want to program: Full [#1], Part [#2] or Perimeter [#3]
3. Enter a delay time (000-255 seconds), then press '√ʹ.
To program Entry Delay timers:
1. From the Programming menu, select Entry/Exit, Entry Delays [922].
2. Select the Entry Delay you want to program: Full [#1], Part [#2] or Perimeter [#3]
3. Enter a delay time (000-255 seconds), then press '√ʹ.
8.2. Set on Exit
The Set on Exit feature cancels the unnecessary remainder of the Exit delay that continues to count down after the user has vacated the premises. This feature automatically sets the system when an Entry/Exit zone is closed during the Exit delay.
To program the Set on Exit option:
1. From the Programming menu, select Entry/Exit, Set On Exit [923].
2. Select Enabled or Disabled.
8.3. Supplementary Entry Delay
The Supplementary Entry Delay is a pre-alarm feature that is employed in the event that the system is not unset during the entry delay. When the entry delay expires, the Control System’s Built-In Sounder is sounded during an additional entry delay period. At the end of the supplementary entry delay, the system generates a full alarm condition; the wireless sounder is sounded and an alarm event is reported to the central station.
To program the Supplementary Entry Delay setting:
1. From the Programming menu, select Entry/Exit, Supp. Ent. Delay [924].
2. Select Enabled or Disabled.
Page 54
8 Entry/Exit Timers and System Tones
CommPact Installation Manual
50
8.4. Entry Deviation
Entry Deviation is a pre-alarm feature employed in the event that a detector defined with the Normal zone type is opened during the entry delay. In this case, the Control System’s Built-In Sounder is sounded until the end of the entry delay period. Failure to unset by the end of the entry delay causes the system to generate an alarm.
To program the Entry Deviation setting:
1. From the Programming menu, select Entry/Exit, Ent. Deviation [925].
2. Select Enabled or Disabled.
8.5. Setting Tones
Setting tones are the tones sounded by the Control System’s Built-In Sounder and/or the wireless sounder when setting and unsetting the system. Each set of tones can be enabled or disabled according to the requirements of the installation.
8.5.1. Exit Delay Tones
To program tones sounded by the wireless sounder during the Exit delay:
1. From the Programming menu, select Tones, Exit Tones, WL Sounder [9311].
2. Select Enabled or Disabled. To program tones sounded by the Built-In Sounder during the Exit delay:
1. From the Programming menu, select Tones, Exit Tones and Sounder [9312].
2. Select No Tones, Four Tones or Continuous Tones.
8.5.2. Entry Delay Tones
To program tones sounded by the wireless sounder during the Entry Delay:
1. From the Programming menu, select Tones, Entry Tones, WL Sounder [9321].
2. Select Enabled or Disabled. To program tones sounded by the built-in sounder the Entry Delay:
1. From the Programming menu, select Tones, Entry Tones and Sounder [9322].
2. Select No Tones, Four Tones or Continuous Tones.
8.5.3. Setting Tones
To program tones sounded by the wireless sounder on setting:
1. From the Programming menu, select Tones, Set Tones, WL Sounder [9331].
2. Select Enabled or Disabled. To program tones sounded by the Built-In Sounder on setting:
1. From the Programming menu, select Tones, Set Tones and Sounder [9332].
2. Select Enabled or Disabled.
Page 55
8 Entry/Exit Timers and System Tones
CommPact Installation Manual
51
8.5.4. Unsetting Tones
To program tones sounded by the wireless sounder on unsetting:
1. From the Programming menu, select Tones, Unset Tones, WL Sounder [9341].
2. Select Enabled or Disabled.
To program tones sounded by the Built-In Sounder on unsetting:
1. From the Programming menu, select Tones, Unset Tones and Sounder [9342].
2. Select Enabled or Disabled.
8.6. System Trouble Tones
System trouble tones are sounded to provide an audible indication that a system trouble condition exists. On hearing these tones the user is then able to determine which trouble condition is present from the front panel keypad. For additional information, see p. 17, 3.5.1 System Trouble Tones.
8.6.1. Trouble Tones
The Trouble Tones option allows you to enable or disable audible trouble annunciation. To program the Trouble Tones option:
1. From the Programming menu, select Tones, Trouble Tones [936].
2. Select Enabled or Disabled.
8.6.2. Telephone Trouble Tones
Most trouble tones are not sounded between 10:00pm and 7:00am so as not to disturb the user late at night. Telephone trouble, however, may be an attempt to sabotage the system by cutting the telephone wires. For this reason, you can program telephone trouble tones to sound at all times.
To program the Telephone Trouble Tones option:
1. From the Programming menu, select Tones, Tel. Trb. Tones [937].
2. Select Immediate or Delayed.
8.6.3. Fire Trouble Tones
The Fire Trouble Tones option is a feature designed to repeat fire-related trouble tones until the problem has been taken care of. If this feature is enabled, fire trouble tones will be repeated 3½ hours after the user has manually silenced the tones if the trouble condition has not been restored.
To program the Fire Trouble Tones option:
1. From the Programming menu, select Tones, Fire Trb. Tones [937].
2. Select Enabled or Disabled.
It is not possible to program the Telephone Trouble Tones and Fire Trouble Tones
options if the Trouble Tones option is programmed as disabled.
Page 56
8 Entry/Exit Timers and System Tones
CommPact Installation Manual
52
8.7. Tones Options
8.7.1. Tones Output
The Tones Output option enables you to determine whether the tones sounded when setting and unsetting are sounded by the Control System’s Built-In Sounder or its built-in speaker.
To program the Tones Output option:
1. From the Programming menu, select Tones, Tones Options, Tones Output [9381].
2. Select Sounder or Speaker.
8.7.2. Speaker Volume
The Speaker Volume option determines the volume level of the tones sounded by the speaker. To program the Speaker Volume option:
1. From the Programming menu, select Tones, Tones Options, Speaker Vol. [9382].
2. Select High or Low.
It is not necessary to program the Speaker Volume option if "Sounder" is selected for the Tones Output option.
Page 57
9 System Options
CommPact Installation Manual
53
9. System Options
As the name suggests, System Options are settings that affect the entire system. This chapter offers explanations and programming instructions for each of these options.
9.1. Code Lockout
The Code Lockout option locks the keypad for 30 minutes if five unsuccessful attempts are made to enter the user code.
To program the Code Lockout setting:
1. From the Programming menu, select System Options, Code Lockout [9401].
2. Select Enabled or Disabled.
During the 30-minute lockout period, you can still set and unset the system using
keyfobs. If one key setting is enabled, you may still set the system using the keypads.
9.2. Set/Unset Options
The options offered in this section relate to setting and unsetting the system.
9.2.1. Forced Set
Forced setting enables you to set the system when the system is not ready. This option allows you to enable or disable Forced setting for the entire system. Additionally, you can enable or disable Forced setting for each individual zone. For further information, see p. 43, 7.3.6 Force .
To program the Forced Set:
1. From the Programming menu, select System Options, Set/Unset and Forced Set [94021].
2. Select Enabled or Disabled.
9.2.2. One-Key Setting
You can set the system by pressing any of the three setting keys on the keypad. If One-Key Setting is enabled, the system does not prompt you for a user code.
To program the One-Key Setting:
1. From the Programming menu, select System Options, Set/Unset, and One-Key Setting [94022].
2. Select Enabled or Disabled.
9.2.3. Supervised Set
The Supervised Set option is a feature designed to supervise a wireless device activity before you set the system. If the system has not received a transmission from a detector during the interval defined for this option, all setting methods that include that detector will not be available. Medical, Panic, Fire, Gas, Flood, and Environmental zones are not included in this supervision and do not affect the system’s ability to set.
Press  to check which detector is causing the "System Not Ready" condition. To make the required setting method available, activate the detector. PIR detectors have a three-
minute delay between transmissions.
Page 58
9 System Options
CommPact Installation Manual
54
If activating the detector does not help, there may be a problem with the detector. You can omit the faulty detector’s zone to allow system setting until the problem is remedied – see p. 24, 4.3 Zone Omitting.
Zone omitting is valid for one setting period only. All omitted zones are automatically un-omitted when the system is unset.
To program the Supervised Set interval:
1. From the Programming menu, select System Options and Set/Unset, Superv. Set [94023].
2. Enter a Supervised Set interval (001-255 minutes or 000 to disable the Supervised Set option).
Do not program a Supervised Set interval that is less than the detector’s supervision time
9.2.4. Instant Setting
Instant setting is a feature that allows you to cancel the entry delay after setting the system – see p. 21, 3.7.2 Instant . The feature is designed for use in situations where the system’s perimeter is set and nobody is expected to enter the premises from outside during the set period.
To enable/disable the Instant Set option:
1. From the Programming menu, select System Options, Set/Unset, and Instant Setting [94024].
2. Select Enabled or Disabled.
9.2.5. Keyfob Unset
The Keyfob Unset option enables you to determine whether it is possible for the user to unset the system using their keyfob at all times or during the entry delay only.
This feature can be applied only after the system has been fully set.
1. From the Programming menu, select System Options, Set/Unset and KF Unset [94025].
2. Select Always or On Entry.
9.2.6. Supervised Set Mode
For the Supervised Set option, you can choose whether the Control System waits for a transmission of all the devices included in this supervision, or from at least one of them – see p. 53, 9.2.3 Supervised .
To program the Supervised Set mode:
1. From the Programming menu, select System Options, Set/Unset, and Super Set Mode [94026].
2. Select All Reg. Devices or Any Reg. Devices.
9.3. Panic Alarm
SOS Panic alarms generated from the front panel, keypads or keyfobs can be defined as either audible or silent.
To program the Panic Alarm setting:
1. From the Programming menu, select System Options, Panic Alarm [9403].
2. Select Audible or Silent.
Page 59
9 System Options
CommPact Installation Manual
55
9.4. AC Loss Delay
The AC Loss Delay is the amount of time that has to elapse before an AC Loss report is sent to the central station. If AC power is restored before the event message is sent, the event message is cancelled and will not be sent. You can program an AC Loss Delay to be between 1 and 255 minutes after the system first senses the AC loss condition. Alternatively you can program a random AC Loss Delay.
The AC Restore message is also sent using the same method described above. AC Restore is reported only if the AC Loss report was sent.
To program the AC Loss Delay:
1. From the Programming menu, select System Options, AC Loss Delay [9404].
2. Enter a delay time (001-255 minutes) or enter 000 if you require the system to choose a random AC Loss Delay, and then press '√ʹ.
9.4.1. Random AC Loss Delay
In the event of AC loss, an event message is sent to the central station between 15 and 30 minutes after the AC loss condition is sensed. The system chooses this delay at random in order to prevent the central station being inundated by simultaneous AC Loss reports in the event of a regional power cut.
9.5. Display Options
The following options relate to the information the system displays on the front panel keypad.
9.5.1. Set Status Display
The Set Status Display includes the current set status and any trouble conditions that may exist within the system. You can program the system to display this information at all times, only for two minutes, or only for 30 seconds after setting or unsetting the system.
To program the Set Status Display options:
1. From the Programming menu, select System Options, Display, and Set Status [94051].
2. Select Display Always, Display 2 Min, or Display 30 sec.
9.5.2. Banner
The Banner is the 16-character text that you can program to appear on the top row of the LCD display. This text replaces the set status if it is programmed to display for two minutes or 30 seconds only – see p.55, 9.5.1 Set Status Display.
To edit the Banner text:
1. From the Programming menu, select System Options, Display, and Banner [94052].
2. Edit the Banner text using the alphanumeric keypad, then press '√ʹ.
The system never displays the Banner text if the Set Status Display option is
programmed as Always.
Page 60
9 System Options
CommPact Installation Manual
56
9.5.3. Time/Date Format
This option determines the format in which the time and date are displayed. The following options are available:
DD/MM/YY, 24Hr
DD/MM/YY, 12Hr
MM/DD/YY, 24Hr
MM/DD/YY, 12Hr
To program the Time/Date format:
1. From the Programming menu, select System Options, Display, and Time Format [94053].
2. Select the required format from the options available.
9.5.4. Supervision Loss Indication
This option enables you to select whether the system trouble display will indicate transmitter supervision loss to the user.
To program the Supervision Loss Indication setting:
1. From the Programming menu, select System Options, Display, and SV Loss Ind. [94054].
2. Select Enabled or Disabled.
9.6. PGM Output Options
The PGM is a programmable output that is triggered according to specific system status conditions, or by remote command sent via PSTN, GSM, keyfob, RP, or via Internet (ELAS versions 321 and above).
9.6.1. Output Trigger
The Output Trigger option determines the conditions that activate and deactivate the PGM output. To program the Output Trigger:
1. From the Programming menu, select System Options, PGM Options, and Output Trigger [94061].
2. Select an Output Trigger option from the following table.
Table 9-1: PGM Output Trigger Options
Trigger Option
Activated by Deactivated by
PGM Not Used
The PGM output is disabled
Full Set System "Full" set
System unset or PGM Cut-off
Perimeter Set System "Perimeter" set Part Set System "Part" set Set Status Any setting method Power
Trouble
AC Loss or Low Battery conditions AC restore or Battery restore
Tel. Line Trouble
Telephone line supervision trouble Telephone line restore
System Trouble
System trouble condition System trouble restore
Medical Medical alarm
Any setting method, system unset or PGM Cut-off
Burglary Burglary alarm
Page 61
9 System Options
CommPact Installation Manual
57
Trigger Option
Activated by Deactivated by
Fire Alarm Fire alarm
Zone Status
*
Open zones (steady) Omitted zones (pulsing)
All zones closed and no zones omitted
Entry/Exit Entry/Exit delay follower Sounder Built-In Sounder follower WL Sounder Wireless sounder follower
Telecontrol
Remote PGM activation (PSTN/GSM/keyfob/RP, or via Internet in ELAS versions 321 and above)
For certain trigger options, deactivation may be determined by the PGM Cut-off -- see p. 58, 9.6.4 PGM Cut-off. If the PGM Cut-off is programmed as 000 (continuous activation), the PGM output shall remain activated until it is toggled by the relevant change in system status.
9.6.2. Output Type
The Output Type option determines whether the PGM output produces a steady or pulsed output. To program the Output Type:
1. From the Programming menu, select System Options, PGM Options, and Output Type [94062].
2. Select Steady or Pulsed.
The Zone Status, Sounder and WL Sounder trigger options have a fixed Output Type;
there is no need to program an Output Type for these options.
9.6.3. Polarity
You can determine the polarity of the PGM output from the following two options:
Active High: The output is normally off and is switched on when activated.
Active Low: The output is normally on and is switched off when activated.
To program the Polarity:
1. From the Programming menu, select System Options, PGM Options, and Polarity [94063].
2. Select Active High or Active Low.
*
Zone Status functions only when the system is unset.
Page 62
9 System Options
CommPact Installation Manual
58
9.6.4. PGM Cut-off
The PGM Cut-off is the duration for which the PGM is activated. Certain Output Trigger types are deactivated after the PGM Cut-off time has expired– see p. 56, Table 9-1. For those Output Trigger types that are not affected by the PGM Cut-off, there is no need to program this option.
If, for example, Output Trigger option is set to Full Set, and PGM Cut-off time is 060 seconds; then PGM is activated by Full Setting and deactivated by unsetting or by PGM Cut-off Time, whichever comes first. If this option is set to "000" (Continuous activation), PGM is activated by Full Setting, and deactivated by unsetting.
To program the PGM Cut-off time:
1. From the Programming menu, select System Options, PGM Options, and PGM Cut-off [94064].
2. Enter a PGM Cut-off time (001-255 seconds or 000 for continuous activation), then press '√ʹ.
9.7. "No Set" Indication
The "No Set" indication is a feature designed to inform the central station that the system has not been set for a specified period of time.
To define the "No Set" indication interval:
1. From the Programming menu, select System Options, No Set Ind. [9408].
2. Select 1 Week, 2 Weeks, 3 Weeks, 4 Weeks or Disabled.
The No Set event message is an unclassified event. This means that it does not belong to any event group. If the No Set option is programmed with any option other than "Disabled", the event message will be sent.
9.8. Jamming Detection
The system is able to detect RF Jamming that is usually caused by an intruder attempting to compromise the security system.
To program the Jamming Detection setting:
1. From the Programming menu, select System Options, Jamming Det. [9409].
2. Select Enabled or Disabled.
9.9. "No Motion" Time
The No Motion feature is designed to monitor the activity of disabled or elderly people. If a detector defined as No Motion (see p. 35, 7.3.1 Zone Type):
When the system is unset, and the detector has not been triggered within a pre-
defined period of time (00:00 to 72:00 hours), a No Motion event message is sent to the central station.
When the system is set, this zone behaves as Normal.
The No Motion zone must be included in this setting mode – see p. 42, 7.3.2 Set.
To program the No Motion time:
1. From the Programming menu, select System Options, No Motion [9410].
2. Enter the No Motion time value between 00:00 and 72:00. To disable the No Motion feature, enter 00:00. press '√ʹ.
Time counter is reset each time the system is unset.
Page 63
9 System Options
CommPact Installation Manual
59
9.10. Vocal Messages
The Vocal Messages option allows you to enable/disable vocal annunciation of system status. When this feature is enabled, the system plays a short message to announce events such as setting and unsetting.
To program the Vocal Messages option:
1. From the Programming menu, select System Options, Vocal Message [9411].
2. Select Enabled or Disabled.
The availability of the Vocal Message annunciation feature is hardware dependent.
9.11. Engineer Access
The Engineer Access option determines if the Engineer code can access the system at all times or only after the Master code provides authorization with the Enable Programming command – see p 32, 4.7.12 Enable Programming.
To program the Engineer Access option:
1. From the Programming menu, select System Options, Instal. Access [9412].
2. Select Always or User Initiated.
9.12. Daylight Savings
Using the Daylight Savings option, the system is able to automatically adjust its clock twice a year according to the national adjustment to Daylight Saving Time.
Two options are available:
Europe – the clock is adjusted forward 1hr on the last Sunday in March at 1am, the
clock is adjusted back 1hr on the last Sunday in October at 1am.
USA– the clock is adjusted forward 1hr on the second Sunday in March at 2am, the
clock is adjusted back 1hr on the first Sunday of November at 2am.
To program the Daylight Savings option:
1. From the Programming menu, select System Options, Daylight Savings [9413].
2. Select Europe, USA or Disabled.
9.13. Entry/Exit Trouble
If this function is enabled, the system can't be set when the Exit Delay expires, if one of the following conditions is present:
An entry/exit zone is open;
Tamper Alarm from a zone during exit (if not restored before the exit delay expires);
Zone Active when Exit Delay expires.
The event is then sent to the central station account. To program the Entry/exit Trouble option:
1. From the Programming menu, select System Options, Entry Exit TR [9415].
2. Select Enabled or Disabled.
Page 64
9 System Options
CommPact Installation Manual
60
9.14. Report Fail Trouble
If the Report Fail Trouble option is enabled, failure to report an event displays System Trouble on the LCD display. Report Fail Trouble is displayed after the Control System has exhausted all message attempts and report cycles when trying to report the event. To restore a System Trouble condition caused by failure to report, press until you have scrolled through the entire system trouble list. If the Report Fail Trouble is disabled, failure to report an event does not cause a system trouble condition.
To program the Report Fail Trouble option:
1. From the Programming menu, select System Options, Rep. Fail Trb. [9416].
2. Select Enabled or Disabled.
9.15. Immediate Setting from WUApp
If immediate setting from WUApp is enabled, all WEB Set commands received are executed immediately regardless of the programmed Exit Delay – see p. 49 8.1 Entry/Exit Delay. If disabled, the SET commands will be executed with the programmed Exit Delay.
1. From the Programming menu, select System Options, WEB Immed. Set [9417].
2. Select Enabled or Disabled.
Page 65
10 Communications
CommPact Installation Manual
61
10. Communications
This section explains how to determine the way the Control System communicates by GPRS, GSM, and PSTN to the Central Station and to the user.
10.1. System Reporting
The Control System supports six report accounts for central station and user reporting. Each account has its own telephone number and communications options.
The first account is always primary, every other account (that is not a voice report) may be chosen as primary or backup. Each primary account may have one, several, or no backup accounts at all. The order of calling is the following:
1. First, the Control System calls all the primary accounts, in ascending order. In case a primary account report fails, the Control System calls the backup accounts.
2. After that, the system calls the Voice Report accounts – see p. 63, 10.3 Vocal Message Dialer.
If account is set as Backup after Voice Report account, reports to this account will be discarded. It is Engineer responsibility to program primary and backup accounts in proper order. To ensure proper functionality, Engineer will not be able to set Account 1 as Voice Report or Backup.
10.1.1. Telephone Number
To edit an account’s telephone number:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (1-6).
3. From the account’s sub-menu, select Phone Number [#1].
4. Enter up to 16 digits. Use the key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ.
10.1.2. Protocol
To program an account’s communication protocol:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (1-6).
3. From the account’s sub-menu, select Protocol [#2].
4. Select a protocol from the options available.
Set account 1 to IP protocol if you use GPRS communication. Account number 3 is designed for use with the Follow me feature. It is the only telephone number that can be programmed by the user.
Page 66
10 Communications
CommPact Installation Manual
62
10.1.3. Communication Interface
For each account, you can choose whether the system employs PSTN, GSM, or GPRS communication, provided that it is available in your control system configuration.
To program an account’s communication interface:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program account (1-6).
3. From the account’s sub-menu, select Interface [#3].
4. Select PSTN, GSM, or GPRS (GPRS is used only for the first account).
10.1.4. Two-Way Audio
The Two-Way audio option determines whether Two-Way Audio is enabled for the account. For further information, see p. 36, 5.2.2 TWA Alarm Reporting.
To program the Two-Way Audio option for an account:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (1-6).
3. From the account’s sub-menu, select Two-Way Audio [#4].
4. Select Enabled or Disabled.
10.1.5. Account Number (Not Relevant for Voice Report)
To edit an account number:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (1-6).
3. From the account’s sub-menu, select Account Number [#5].
4. Enter up to eight digits. Enter leading zeros for account numbers of less than eight digits. Use the key to enter hexadecimal digits. Press '√’.
If the programmed protocol is Contact ID, "A" is not a valid entry in the account number.
10.1.6. Call Attempts (Not Relevant for Voice Report)
The Call Attempts option determines the number of times the system tries to call a telephone number before moving on to the next number in sequence.
To program the number of call attempts for an account:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (1-6).
3. From the account’s sub-menu, select Call Attempts [#6].
4. Enter a value between 01 and 15. Press '√ʹ.
Page 67
10 Communications
CommPact Installation Manual
63
10.1.7. Account Type (Not Relevant for Voice Report)
To program the number of call attempts for an account:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (2-6).
3. From the account’s sub-menu, select Account Type [#7].
4. Select Primary or Backup.
Account 1 is a primary account.
10.2. Report Cycles
The system’s attempts to report events are organized in cycles. A report cycle is a set of call attempts – see p. 62, 10.1.6 Call Attempts (Not Relevant for Voice Report). If the system does not succeed in sending a report to any of the telephone numbers, it tries to dial the entire report cycle again until it sends a successful report. You can determine the number of times the system attempts to dial this sequence by programming the Report Cycle option.
To program the number of Report Cycles:
1. From the Programming menu, select Communications, Accounts, Report Cycles [9517].
2. Enter a value between 01 and 15. Press '√ʹ. In the example illustrated in Figure 10-1, Account 1 is programmed with 2 call attempts, Account 2
is programmed with 3 call attempts and the number of report cycles programmed is 3.
Figure 10-1: Typical Report Cycle Sequence
10.3. Vocal Message Dialer
The Vocal Message Dialer is a feature that calls the user’s telephone number when specific events occur and plays pre-recorded messages. These calls are made after the system has reported the events to the central station. Additionally, in the event of an alarm, the user is able to establish a Two-Way Audio connection on receiving the vocal message in order to check the premises.
The system supports up to five Voice Report accounts. Each account has its own telephone number, communication interface and Two-Way Audio options.
Page 68
10 Communications
CommPact Installation Manual
64
The event types reported using the Vocal Message Dialer feature are determined in VM Event Options see p.75, 10.10 Vocal Message Dialer Event Options. If one of these events occurs, the Control System dials the phone numbers of the Voice Report Account.
The sequence for a vocal message call is as follows:
1. An event occurs and the Control System calls the telephone number of the first Voice Report Account chosen.
2. When the user answers the call, the Home ID message and the relevant event message are played.
3. The user presses 1 on their telephone; if there are additional events to report the next message is played. Otherwise, "No Further Messages" is announced.
-Or­If Two-Way Audio is enabled for the Voice Report account, the user may open the
audio channel by pressing 2 on their telephone. If the user does not want to open the audio channel they may press "*" then "#" on their telephone to hang up.
If the call is not answered or the TC/VM Timeout (see p. 70, 10.6.10 Telecontrol/Vocal Message Timeout) expires before the message is acknowledged by the user pressing 1, the Control System calls the next Voice Report Account telephone number.
The availability of the Vocal Message Dialer feature is hardware dependent.
10.3.1. Telephone Number
To edit a Voice Report Account account’s telephone number:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (2-6).
3. From the account’s sub-menu, select Phone Number [#1].
4. Enter up to 16 digits. Use the key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ when you have finished editing.
10.3.2. Protocol
To program voice report protocol:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (2-6).
3. From the account’s sub-menu, select Protocol [#2].
4. Select Voice Report.
10.3.3. Communication Interface
For each Vocal Message account, you can choose whether the system employs cellular or PSTN communication, provided that it is available in your control system configuration.
To program a Voice Report Account’s communication interface:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (2-6).
3. From the account’s sub-menu, select Interface [#3].
4. Select GSM or PSTN.
Page 69
10 Communications
CommPact Installation Manual
65
10.3.4. Two-Way Audio
The Two-Way audio option determines whether Two-Way Audio is enabled for the Voice Report Account. For further information, see p. 37, 5.2.3 Two-Way Audio after Vocal Messages.
To program the Two-Way Audio option for a Voice Report Account:
1. From the Programming menu, select Communications, Accounts [951].
2. Select the account you want to program (2-6).
3. From the account’s sub-menu, select Two-Way Audio [#4].
4. Select Enabled or Disabled.
10.3.5. Home ID
The Home ID is a short message that is played at the beginning of a vocal message call in order to identify the system to the user. For example, at the beginning of the vocal message call, the message "Michael’s House" will be played before the event messages.
To play back the Home ID message:
From the Programming menu, select Communications, Accounts, Home ID, and Play
Message [95181].
To record a Home ID message:
1. From the Programming menu, select Communications, Accounts, Home ID, and Record Message [95182].
2. Press '√ʹ to start recording the message.
3. Record your message. The message may be up to ten seconds long.
4. Press '√ʹ to stop recording; the message is automatically played back and OK? is displayed. Press '√ʹ to save your recording.
10.4. Remote Programming
Electronics Line 3000’s Remote Programmer (RP) and WEB Remote Programmer software enable you to operate and program the system from a PC either on-site or from a remote location. The software provides a comprehensive interface to the CommPact Control System designed to facilitate programming. There are 3 access levels available: Supervisor (full access), Technician (limited access to the program, a technician is not able to view or change user codes or the RP access code), and Operator (access to user operations, such as setting and unsetting the system).
10.4.1. Remote Programmer
PC to Control System Connection Methods
You can connect to the Control System from a PC using one of three methods:
Direct Call: The RP calls the site, the system picks up and RP communication is
established.
Callback: The RP calls the site, the system picks up then hangs up. The system then
calls the Callback telephone number to establish a connection.
Serial Connection: The RP connects directly via the Main Board's USB port.
Page 70
10 Communications
CommPact Installation Manual
66
The following programming options relate to the method in which the Remote Programmer software connects with the system.
Callback Telephone Number
RP Callback is a security feature that helps ensure that remote programming is only performed by authorized personnel. When the Remote Programmer contacts the Control System, the Control System hangs up and calls the Callback telephone number.
To edit the Callback telephone number:
1. From the Programming menu, select Communications, Remote Prog., Call-Back # [9521].
2. Enter up to 16 digits. Use the key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ when you have finished editing.
If there is no Callback telephone number programmed, RP Callback is disabled and the system connects to the Remote Programmer software using the "direct call" method.
RP Passcode
The RP passcode is a six-digit code that grants access to remote programming. When establishing an RP connection, the passcode programmed in the RP customer file on the PC must be identical to the system’s RP passcode.
To edit the RP passcode:
1. From the Programming menu, select Communications, Remote Prog., RP Passcode [9522].
2. Enter six digits, and then press '√ʹ.
RP Communication Interface
For remote programming, the CommPact Control System can employ GPRS, GSM, or PSTN communication, provided that it is available in your control system configuration.
To program the RP communication interface:
1. From the Programming menu, select Communications, Remote Prog., RP Interface [9523].
2. Select PSTN or GSM (GPRS is relevant for the WEB RP only).
RP Access Options
Options are available to enable, disable or limit access to remote programming. To program RP Access Options:
1. From the Programming menu, select Communications, Remote Prog., RP Access [9524].
2. Select an RP access option from the following table.
Table 10-1: RP Access Options
Access option
Description
Always Enable
Up/downloading is always possible.
During Unset
The system must be unset in order to establish a connection.
Disable Up/downloading is disabled. User
Initiated
The user must perform Enable Programming from the Service menu in order to establish a connection – see p.32, 4.7.12 Enable Programming.
Page 71
10 Communications
CommPact Installation Manual
67
10.4.2. WEB Remote Programmer (Relevant only when using ELAS connection)
Electronics Line 3000's WEB-based Remote Programmer (WEB RP) allows the engineer or service provider to operate and program the system via the WEB using ELAS database to get the list of supported Control Systems. To access WEB RP, the engineer must enter user name and password.
10.5. Service Call
The Service Call feature is designed to enable the user to call the monitoring service at the push of a button. When the user presses the up arrow key button and then presses and holds down the Service Call button for a few seconds, a two-way audio connection with the central station is established.
10.5.1. Service Call Telephone Number
To edit the Service Call telephone number:
1. From the Programming menu, select Communications, Service Call, Phone Number [9531].
2. Enter up to 16 digits. Use the key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ when you have finished editing.
10.5.2. Service Call Interface
For the Service Call feature, you can choose whether the system employs cellular or PSTN communication, provided that it is available in your control system configuration.
To program the Service Call interface:
1. From the Programming menu, select Communications, Service Call, Interface [9532].
2. Select either GSM or PSTN.
10.6. Communications Options
10.6.1. Line Monitor
The Line Monitor feature monitors the PSTN telephone line. If a problem is detected with the line, a Media Loss event is registered in the log.
To program the Line Monitor setting:
1. From the Programming menu, select Communications, Comm. Options, and Line Monitor [95401].
2. Select Enabled or Disabled.
Page 72
10 Communications
CommPact Installation Manual
68
10.6.2. Periodic Test Interval
The Periodic Test is a test transmission the system sends to notify the central station that its reporting capability is fully functional.
Two options are available for the Periodic Test:
You can program the system to send a Periodic Test message according to a chosen
time interval. This time interval can be between 1 and 254 hours (approximately 10 days).
The system calculates automatically the time the Periodic Test is sent according to the
last four digits of the account number. Automatically calculated tests can be sent daily, weekly or monthly according to the Auto Interval option – see p. 68, 10.6.4 Auto Interval. This feature is designed to avoid overflow of test reports to the central station at any given time.
The Periodic Test event message is an unclassified event. This means that it does not belong to any event group. If the Periodic Test Interval is programmed with any value other than 000, the event message will be sent.
To program the Periodic Test Interval:
1. From the Programming menu, select Communications, Comm. Options, and Test Interval [95402].
2. Enter the test interval (001-254 hours) or 255 for an automatically calculated test interval, then press '√ʹ.
To disable the Periodic Test:
Program the Periodic Test Interval as 000.
10.6.3. First Test
If the Periodic Test Interval is programmed as 001-254 hours, you must also program the time that the first Periodic Test is sent.
To program the First Test Time:
1. From the Programming menu, select Communications, Comm. Options, and First Test [95403].
2. Enter a time (HH:MM), then press '√ʹ.
10.6.4. Auto Interval
The Auto Interval option determines the frequency of automatically calculated periodic test messages.
To program the Auto Interval:
1. From the Programming menu, select Communications, Comm. Options, and Auto Interval [95404].
2. Select Daily, Weekly or Monthly.
Page 73
10 Communications
CommPact Installation Manual
69
10.6.5. Call Timeout
The Call Timeout is the amount of time the system waits for the first acknowledgement (ACK1) from the central station when reporting using the PSTN. If ACK1 is not received during this time, the system regards the call as a failed dialing attempt.
To program the Call Timeout:
1. From the Programming menu, select Communications, Comm. Options, and Call Timeout [95405].
2. Enter a time (001-255 seconds), and then press '√ʹ.
10.6.6. ACK. Timeout
The ACK Timeout is the amount of time the system waits for the second acknowledgement (ACK2) from the central station when reporting using the PSTN. If ACK2 is not received during this time, the system regards the call as a failed dialing attempt.
To program the ACK Timeout:
1. From the Programming menu, select Communications, Comm. Options, and ACK Timeout [95406].
2. Enter a time (001-255 seconds), and then press '√ʹ.
10.6.7. PSTN Country
In order to meet the requirements of local telecommunications authorities, default telephone line parameters have been chosen for a number of different countries.
To program the PSTN Country:
1. From the Programming menu, select Communications, Comm. Options, and PSTN Country [95407].
2. Select your country from the options available.
Electronics Line 3000 offers custom telephone line parameter settings for countries that do not appear in the list of pre-defined options. If your country does not appear among the available options, select the option Custom Settings.
10.6.8. Dial Tone Wait
This option determines whether the system dials only when the dial tone is present or if the dialing is initiated regardless of the dial tone.
To program the Dial Tone Wait option:
1. From the Programming menu, select Communications, Comm. Options, and Dial Tone Wait [95408].
2. Select Enabled or Disabled.
10.6.9. Incoming Calls
This option determines whether the Control System is able to receive incoming Telecontrol/Two­Way Audio calls.
To program the Incoming Calls option:
1. From the Programming menu, select Communications, Comm. Options, and Incoming Call [95410].
2. Select Enabled or Disabled.
Page 74
10 Communications
CommPact Installation Manual
70
10.6.10. Telecontrol/Vocal Message Timeout
The Telecontrol/Vocal Message Timeout (TC/VM Timeout) determines the duration of a Telecontrol, Two-Way Audio or Vocal Message call. In the case of a Telecontrol or Two-Way Audio call, when the time out expires, the system automatically disconnects unless the call is manually extended by the operator. For Vocal Message calls, if the time out expires and the user has not acknowledged the message, the system attempts to call the next Voice Report account’s telephone number. During a Vocal Message call, the timeout is reset each time a message is acknowledged.
To program the Telecontrol/Vocal Message Timeout:
1. From the Programming menu, select Communications, Comm. Options, and TC/VM Timeout [95411].
2. Enter a time (001-255 seconds), and then press '√ʹ.
10.6.11. TWA Mode
The Two-Way audio features offer a choice of two operation modes:
Duplex – both parties may speak at once just like a regular telephone.
Simplex – one party may speak while the other party listens.
To program the TWA mode option:
1. From the Programming menu, select Communications, Comm. Options, and TWA Mode [95412].
2. Select Duplex or Simplex.
10.7. GSM Options
10.7.1. GSM RX Report
The GSM RX Report is a feature that periodically reads the GSM signal strength of the Cellular Communication – see p.31, 4.7.9 GSM Signal Strength. This reading occurs at the times programmed for the Periodic Test – see p. 68, 10.6.2 Periodic Test Interval, and p. 68, 10.6.3 First Test. This means that each time the periodic test is sent, the system also sends a GSM signal strength report to the central station. The system also enters the GSM signal strength in the event log.
If the Periodic Test is disabled, the GSM RX Report feature will not function. The GSM RX
report belongs to the Peripherals event group – see p. 74,
10.9 Event Options for Central
Station Reporting. If this event group is disabled, the GSM signal strength is still recorded in the event log.
To program the GSM RX Report option:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and GSM RX Report [954131].
2. Select Enabled or Disabled.
Page 75
10 Communications
CommPact Installation Manual
71
10.7.2. PIN Code
The PIN (Personal Identity Number) is a four-digit code that protects the SIM card from unauthorized use if lost or stolen.
When using a SIM card with an activated PIN code, the engineer has to make sure that the PIN code programmed in the Control System is the same as the SIM card's PIN code. The PIN code should be programmed in the system before inserting the SIM card.
To program the PIN code:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and PIN Code [954132].
2. Edit the four-digit PIN code, and then press '√ʹ.
3. Power up the Control System to apply the new PIN Code definition.
The new PIN code takes effect only after the System is powered.
If a wrong PIN code was programmed in the system, a System Trouble is generated, the PIN Code Error message is displayed, and GSM communication of any kind is not available. In this case, the
SIM card must be reactivated. To reactivate a SIM card:
1. Program the correct PIN code in the Control System (see above), then disconnect the Control System from all the power sources.
2. Remove the SIM card from the SIM card Holder on the Main Board (see p. 5, Figure 1-2) and insert it into a cellular phone.
3. Turn on the cellular phone and enter the correct PIN code.
4. Re-install the SIM card into the Control System and apply power.
10.7.3. SMS Center
To edit the SMS Center telephone number:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and SMS Center [954133].
2. Enter up to 16 digits. Use the
key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ when finished.
10.7.4. SMS Command
The SMS Command option enables you to enable or disable the ability to send commands to the system via SMS. For further information on SMS commands, see p. 21, 3.7.3 Remote Setting/Unsetting via SMS and p. 38, 6.2 Telephone Control.
To enable/disable SMS commands:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and SMS Command [954134].
2. Select Enabled or Disabled.
Page 76
10 Communications
CommPact Installation Manual
72
10.7.5. SMS Confirmation
After an SMS command is executed by the system, a confirmation message is returned to the sender’s mobile phone. You can enable or disable this feature using this option.
To enable/disable SMS confirmation:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and SMS Confirm [954135].
2. Select Enabled or Disabled.
10.7.6. GSM Media Loss Time
The GSM Media Loss Time is a feature that is designed to control the amount of GSM media loss events registered in the log and sent to the central station.
If, for a period defined in GSM ML Time parameter, the GSM signal has always been below the lower threshold, a Media Loss event is registered in the log and sent to the central station.
The GSM Media Loss event is sent to the central station via PSTN only. If, for a period defined in GSM ML Time parameter, since GSM media restore is detected, the GSM
signal has always been above the upper threshold, GSM Media Restore is registered in the log and sent to central station.
To disable the GSM Media Loss feature (cancel the GSM Media Loss events) enter 000. To program the GSM Media Loss Time:
1. From the Programming menu, select Communications, Comm. Options, GSM Options, and GSM ML Time. [954136].
2. Enter time (003-255 minutes or 000 to disable), then press '√ʹ.
10.8. TWA Event Report Options
10.8.1. TWA Event Report
The TWA Event Report is an event report that is sent to the central station to indicate that Two-Way Audio communication is about to commence. If enabled, the system sends the Contact ID event code 606000 before establishing Two-Way Audio communication.
This option affects Contact ID only. If using SIA, a TWA event report is always sent together with the TC/VM timeout, regardless of the configuration for this option.
To program the TWA Event option:
1. From the Programming menu, select Communications, Comm. Options, and TWA Event Rept. [95414].
2. Select Enabled or Disabled.
10.8.2. TWA Time Report
If the TWA Time Report option is enabled, the last three digits of the TWA Event Report are replaced with the amount of seconds programmed for the TC/VM Timeout – p. 70, 10.6.10 Telecontrol/Vocal Message Timeout. For example, if the TC/VM Timeout is programmed as 120 seconds, the Contact ID event code to be sent for the TWA Event Report will be 606120.
To program the TWA Time Report option:
1. From the Programming menu, select Communications, Comm. Options, and TWA Time Rept. [95415].
2. Select Enabled or Disabled.
Page 77
10 Communications
CommPact Installation Manual
73
10.8.3. Caller ID Mode and Incoming Number
Incoming number feature allows the engineer to program up to three high-priority telephone numbers so that the user would be able to use Telecontrol/2-way audio over GSM during a GPRS session. If the Control System recognizes the incoming call as a high-priority call, the GPRS session will be suspended. Caller ID Mode option allows selection of the ID Mode applicable to your specific network.
Caller ID Mode option affects PSTN too. There is no Caller ID Fail trouble for the incoming calls over GSM.
To choose the applicable Caller ID Mode option:
1. From the Programming menu, select Communications, Comm. Options, and Caller ID Mode. [95416].
2. Choose the mode applicable to your PSTN network (Bellcore, British Telecom, and Japan). You can also disable Caller ID by choosing Caller ID Disable.
To program/edit the Incoming Number:
1. From the Programming menu, select Communications, Comm. Options, and Incoming #. [95417].
2. Select the telephone number you want to edit (1-3).
3. Enter up to 16 digits. Use the key to enter "*", "#", "," (pause), "T" (switch to DTMF tone dialing), "P" (switch to pulse dialing) or "+" (international code). Use the key to delete one character at a time. Press '√ʹ when you have finished editing.
10.8.4. Remote Firmware Update
Electronics Line 3000’s Remote Firmware Update feature allows the Engineer or service provider to perform firmware update from a remote PC using WEB communication.
Before performing the firmware update, locally unset the system and make sure that there is no AC LOSS or BATTERY LOW conditions.
To setup the firmware update mode:
1. From the Programming menu, select Communications, Comm. Options, and Rem. SW Update [95418].
2. Select the Remote Firmware Update mode from the following table:
Table 10-2: Remote FW Update
Access option Description
Always Enable Update is always possible. Disable Firmware update is not allowed. User Initiated The user must perform SW Update from the Service menu in order to
establish a connection – see p. 33, 4.7.14 Remote Firmware Update.
Page 78
10 Communications
CommPact Installation Manual
74
10.9. Event Options for Central Station Reporting
System events are divided into a number of different event groups. This division allows you to enable or disable reporting or Two-Way Audio for a specific group of events.
The different event groups are as follows:
Burglary [#1]
Fire [#2]
Open/Close (set/unset) [#3]
Service [#4]
Power [#5]
Peripherals [#6]
RF Jamming [#7]
Medical [#8]
10.9.1. Event Reporting
You can enable or disable event reporting per Event Group. This allows you to filter the type of events that are reported to the central station.
To enable/disable reporting for an event group:
1. From the Programming menu, select Communications, Event Options [955].
2. Select an Event Group.
3. From the event group’s sub-menu, select Report [#1].
4. Select Enabled or Disabled.
10.9.2. Restore Reporting
For each event group, you can determine whether restore messages will be sent.
There is no Restore for No Motion event.
To enable/disable restore reporting for an event group.
1. From the Programming menu, select Communications, Event Options [955].
2. Select an event group.
3. From the event group’s sub-menu, select Report Restore [#2].
4. Select Enabled or Disabled.
Page 79
10 Communications
CommPact Installation Manual
75
10.9.3. Two-Way Audio
For Burglary, Fire and Medical event groups, there is an additional option that enables Two-Way Audio for that event group – see p. 36, 5.2.2 TWA Alarm Reporting.
To enable/disable Two-Way Audio for an event group:
1. From the Programming menu, select Communications, Event Options [955].
2. Select an Event Group (Burglary, Fire or Medical).
3. Select TWA [#3].
4. Select Enabled or Disabled.
10.10. Vocal Message Dialer Event Options
Events reported using the Vocal Message Dialer is divided into event groups that correspond with the pre-recorded event messages. This allows you to enable or disable the Vocal Message feature for a specific group of events. For further information on this feature, see p. 63, 10.3 Vocal Message Dialer.
The vocal message event groups and their associated system events are as follows:
Burglary [#1]
o Alarm from Zone (excluding Gas and Environmental zones) o Zone Tamper o Tamper o Duress
Fire [#2]
o Zone Fire Alarm o User Activated Fire Alarm
Panic [#3]
o Zone Panic Alarm o User Activated Panic Alarm
Medical [#4]
o Zone Medical Alarm o Zone Medical Alarm o User Activated Alarm o No Motion
System Trouble [#5]
o Battery Low o Transmitter Low Battery o AC Loss o Media Loss o Device Trouble o Communication Trouble o Transmitter Out of Synch. o Control System Transmitter Out of Synch. o Supervision Loss
Page 80
10 Communications
CommPact Installation Manual
76
o Zone Trouble o FM Jamming
Set [#6]
o Full Set o Part Set o Perimeter Set
Unset [#7]
o Unset o Unset after Alarm
Water [#8]
o Zone Water Alarm (Flood)
To enable/disable the vocal message for an event group:
1. From the Programming menu, select Communications, VM Event Opt. [956].
2. Select an event group.
3. Select Enabled or Disabled.
Page 81
11 Internet Options
CommPact Installation Manual
77
11. Internet Options
The following options concern the configuration of the GPRS. In most cases, the Internet options will be pre-programmed as defaults and you will not be required to change any of the settings apart from the CPID and password for each customer.
11.1. ELAS Connection Parameters
The following parameters, required to connect Control System to ELAS, are set by ELAS administrator.
11.1.1. IP Address
To edit the IP Address:
1. From the Programming menu, select Communications, Internet, XML Proxy IP [9571].
2. Enter the IP address provided by your ELAS administrator. Use the "1" key to enter ".",
key to insert and the key to delete one character at a time. Press '√ʹ when finished.
11.1.2. Port Setting
To edit the Port Setting:
1. From the Programming menu, select Communications, Internet, XML Proxy Port [9572].
2. Enter the port setting provided by your ELAS administrator. Use the "1" key to enter ".",
key to insert and the key to delete one character at a time. Press '√ʹ when finished.
For MyELAS, define the IP address as 195.219.118.21 and the Port setting as 33000.
11.2. Control System Parameters
The following parameters, required to connect Control System to ELAS, should be provided by your ELAS administrator.
If the end user is to perform the self registration on-line then the following CPID and CP Password steps are not required.
11.2.1. CP ID
To edit the Control System ID:
1. From the Programming menu, select Communications, Internet, CP ID [9573].
2. Enter the unique Control System ID provided by your ELAS administrator to connect the Control System to ELAS. Use the "1" key to enter ".", key to insert and the key to delete one character at a time. The ID length must be six up to sixteen characters. Press '√ʹ when finished.
11.2.2. CP Password
To edit the Control System Password:
1. From the Programming menu, select Communications, Internet, CP Password [9574].
2. Enter the Control System Password provided by your ELAS administrator to connect the Control System to ELAS. Use the "1" key to enter ".", key to insert and the key to delete one character at a time. The password length must be six up to sixteen characters. Press '√ʹ when finished.
Page 82
11 Internet Options
CommPact Installation Manual
78
11.2.3. ELAS Connection on/off
To enable/disable ELAS connection option:
1. From the Programming menu, select Communications, Internet, ELAS Connect [9575].
2. Select Enabled or Disabled.
11.3. GPRS Network Parameters
The following parameters, required to program your GPRS connection, should be provided by the cellular provider.
11.3.1. APN
To edit the APN name of your GPRS connection:
1. From the Programming menu, select Communications, Internet, GPRS Options, and APN [95761].
2. Enter the APN name provided by the cellular provider. Use the "1" key to enter ".", key to insert and the
key to delete one character at a time.
11.3.2. User Name
To edit the User name of your GPRS connection (optional setting provided by the cellular provider):
1. From the Programming menu, select Communications, Internet, GPRS Options, and User Name [95762].
2. Enter the User Name provided by the cellular provider. Use the "1" key to enter ".", key to insert and the key to delete one character at a time.
3. Press '√ʹ when you have finished editing.
11.3.3. Password
To edit the Password of your GPRS connection (optional setting provided by the cellular provider):
1. From the Programming menu, select Communications, Internet, GPRS Options, and Password [95763].
2. Enter the Password provided by the cellular provider. Use the "1" key to enter ".", key to insert and the key to delete one character at a time.
11.3.4. GPRS Write TMO
To edit the GPRS Write TMO of your GPRS connection:
From the Programming menu, select Communications, Internet, GPRS Options, and
GPRS Write TMO [95764].
Page 83
12 System Initialization
CommPact Installation Manual
79
12. System Initialization
The Initialization menu offers a number of options that enable you to reset the system. This menu is particularly useful when re-installing a Control System at a new site. The Initialization function clears the entire system. This restores programming defaults, clears the log, user codes and the transmitter register. Options are also available that enable you to clear a specific section of the system’s memory separately.
12.1. Initialization
The Initialization function clears the entire system and resets factory defaults. To initialize the Control System:
From the Programming menu, select Initialize, Init All [971]; the system prompts you
for confirmation.
Factory programming defaults are restored, the event log is cleared, ser codes and wireless transmitters are deleted.
During system initialization, recorded vocal messages (Message Center and Home ID) are not deleted.
12.2. Default Program Restore
Loading the system’s default program enables you to restore the factory-set programming defaults. To load the default program:
From the Programming menu, select Initialize, Load Defaults [972]; the system
prompts you for confirmation.
12.3. Clear User Codes
Clear User Codes deletes all programmed user codes and restores the default Master and Engineer codes.
To clear user codes:
From the Programming menu, select Initialize, Clear Users [973]; the system prompts
you for confirmation.
12.4. Clear Wireless Transmitters
The Clear Wireless Transmitters function enables you to delete all registered transmitters at once. To clear the transmitter register:
From the Programming menu, select Initialize, Clear Wireless [974]; the system
prompts you for confirmation.
Page 84
Appendix A: Menu Structure
CommPact Installation Manual
80
Appendix A: Menu Structure
Page 85
Appendix A: Menu Structure
CommPact Installation Manual
81
Page 86
Appendix A: Menu Structure
CommPact Installation Manual
82
Page 87
Appendix A: Menu Structure
CommPact Installation Manual
83
Page 88
Appendix A: Menu Structure
CommPact Installation Manual
84
Page 89
Appendix A: Menu Structure
CommPact Installation Manual
85
Page 90
Appendix A: Menu Structure
CommPact Installation Manual
86
Page 91
Appendix B: Transmitter Installation
CommPact Installation Manual
87
Appendix B: Transmitter Installation
PIR Detectors (EL-2645/EL-2645PI)
The EL-2645 and EL-2645PI are Wireless Motion PIR Detector designed for use with Electronics Line supervised wireless range of receivers. All these detectors implement a feature to combat the problem of multiple transmissions, which drastically reduce the life of the batteries. After each transmission, there is a four-minute delay during which further transmissions will not be sent. When batteries need replacing, the detector sends a low battery indication to the Control System. The EL-2645PI is designed for pet installations and provides good immunity to nuisance alarms caused by pets and animals.
Detectors that meet the EN-50131 standard, have a three-minute delay between transmissions.
1. Battery Holder
2. Antenna
3. LED Indicator
4. PCB Screw
5. DIP Switch
6. Tamper Switch
7. Pyro Sensor
8. Back Tamper
Figure B- 1: PIR Detector with Cover Removed – EL-2645/EL-2645PI
Considerations before Installation
Select a location from which the pattern of the detector is most likely to be crossed by
a burglar, should there be a break in.
Do not place bulky objects in front of the detector.
Avoid a location that comes in direct contact with radiators, heating/cooling ducts or
air conditioners.
Do not place the detector in front of windows subject to direct sunlight or drafts.
Pet Immunity Guidelines (EL-2645PI)
It is expected that the EL-2645PI will eliminate false alarms caused by:
Animals up to 36kg/80lbs
Several small rodents
Random flying birds.
The weight of the animal should only be used as a guide; other factors such as the length and color of fur also affect the level of immunity.
Page 92
Appendix B: Transmitter Installation
CommPact Installation Manual
88
For maximum pet immunity the following guidelines are recommended:
Mount the center of the detector at a height of 2.0m.
Do not aim the detector at stairways that can be climbed by an animal.
Avoid a location where an animal can come within 1.8m (6') of the detector by
climbing on furniture, boxes or other objects.
Installation Procedure
To install PIR detectors:
1. Open the housing by removing the front cover. To do so, insert a screwdriver in the release slot (located at the bottom of the detector between the front and back cover). Turn the screwdriver 90º to release the cover.
2. Remove the PCB by turning counter-clockwise and removing the 'PCB Screw'.
Do not touch the face of the PYRO sensor.
3. Apply battery power by removing the isolator that separates the battery from the contacts on the battery holder.
4. From the Programming menu, select Devices, Zones [911] and select the zone to which you want to register the transmitter.
5. Cause a Tamper or Alarm transmission and wait for the receiver to indicate that the transmitter has been registered successfully. When Save? appears on the Control System’s LCD display, press '√ʹ. Write the number of the zone and the transmi$er number (if applicable) on the sticker provided. Affix the sticker inside the front cover for future reference.
Alternatively, the Detector can be registered to the receiver by manually entering the transmitter's serial number.
6. Choose an appropriate mounting height from 2.2 – 2.5 and test the transmitter from the exact mounting position before permanently mounting the unit.
If you choose mounting height other than recommended (which is not advised), please perform a walk test to check the lens coverage. The recommended mounting height is the best in terms of detection area.
7. Knock out the mounting holes and attach the base to the wall.
8. If using the rear tamper switch, insert a screw into the rear tamper mounting hole located in the center of the back cover. When the detector is removed from the wall, the screw causes the tamper release to break away from the back cover and the rear tamper switch is released.
Figure B- 2: Back Tamper Release
9. Mount the PCB on the base cover and replace the PCB Screw.
10. Replace the front cover.
Back tamper mounting hole
Page 93
Appendix B: Transmitter Installation
CommPact Installation Manual
89
DIP Switch Settings
Table B- 1: DIP Switch Settings (EL-2645/EL-2645PI)
Warm-Up Time
The detector will need to warm up for the first 90 seconds after applying power.
Walk Test Mode
A walk test is performed in order to determine the lens coverage pattern of the detector – see Figure B- 3. Walk Test mode cancels the delay time between detections, enabling you to perform an efficient walk test.
To perform a Walk Test:
1. Set DIP 2 to ON.
2. Walk across the scope of the detector according to the detection pattern selected.
3. Confirm that the LED activates and deactivates accordingly. Wait for ten seconds after each detection before continuing the test.
4. After completing the walk test. Set DIP-2 to OFF.
LED Indication
The LED indicator is lit every time a transmission is made. To enable/disable LED indication, refer to DIP Switch Setting section for the appropriate DIP-switch setting
LED should only be disabled after successfully walk testing the detector.
Switch Operation
1
PIR sensitivity *Off: Low On: High
2
Operation mode:
* Off: Normal mode – Every 3 minutes. After each detection the sensor initiates a three-minute delay during which alarm transmissions will not be sent
On: Walk Test mode. An alarm transmission is sent after each detection
3
Supervision Time: Off: As supervision message will be sent to the monitoring station every 15
minutes
* On: As supervision message will be sent to the monitoring station every 65 minutes
4
LED Off: LED disabled
* On: LED enabled
*=Default
Page 94
Appendix B: Transmitter Installation
CommPact Installation Manual
90
Changing Lenses
To change a lens, release the cavity seal using a small screwdriver and fix the new lens into place with the smooth side facing outwards. Verify that the word TOP is located at the top of the lens (alternatively a notch may appear on the bottom edge of the lens) before snapping the cavity seal back into place.
Battery Replacement
In case of a low battery (2.5 V and below), the sensor low battery condition is reported to the Control System and low battery message is displayed
To replace a battery: Open the housing by removing the front cover (see Installation Instructions), replace the battery, and close the front cover.
Close the front cover immediately after each battery replacement.
Figure B- 3: Lens Coverage Diagrams EL-2645 (left) and EL-2645PI (right)
The diagram shows the coverage pattern for the detector fitted with a standard lens.
EL-2645 complies with EN-50131 2-2 Grade 2 Class II Power Supply Type C
Directional PIR (EL-2650XL)
The EL-2650XL is a wireless PIR detector that is able to distinguish between permitted and non­permitted motion. This allows the occupants free movement within the premises while detecting intrusion via doors or windows. The detector implements a feature to combat the problem of multiple transmissions, which drastically reduce the life of the batteries. After a transmission is made, the EL-2650XL initiates a delay of approximately three minutes during which transmissions will not be sent. The detector operates in two selectable modes: Curtain and Directional.
Page 95
Appendix B: Transmitter Installation
CommPact Installation Manual
91
Figure B- 4: EL-2650XL (Cover Off)
Location of Detector
Consider the following before mounting the detector:
Select a location from which the pattern of the detector is most likely to be crossed by
a burglar, should there be a break in.
Avoid a location that comes in direct contact with radiators, heating/cooling ducts or
air conditioners.
Do not place bulky objects in front of the detector.
Do not install the detector above beds, sofas, desks or in any area that people are likely to spend continued periods of time. If the occupant does not move within the delay time, an alarm will be generated when moving away from the protected area.
Figure B- 5: Correct Placement of the Detector
Installation Instructions
1. To open the housing, remove the cover screw and, using a flathead screwdriver, press the locking tab at the side of the unit. Remove the Main Board by unscrewing the PCB screw.
Do not touch the face of the PYRO sensor.
2. Set the receiver to Registration mode. Apply battery power by removing the isolator that separates the battery from the contacts on the battery holder. The detector turns on and sends four transmissions in order to be registered with the system. Wait for the receiver to indicate that the transmitter has been registered successfully. Alternatively, the EL-2650XL can be registered to the receiver by manually entering the transmitter's serial number.
LED
Indicator
PCB Screw
Tamper
Switch
Pyro Sensor
Mode Jumper
Alarm Delay Jumper
Battery
Holder
LED
Jumper
PCB Adjustment Scale
Page 96
Appendix B: Transmitter Installation
CommPact Installation Manual
92
The receiver allocates a transmitter number to each registered unit. Write this number and the number of the zone on the sticker provided. Affix the sticker inside the front cover for future reference.
3. After a warm-up period of 130 sec. indicated by both LEDs' blinking, the detector automatically enters Radio Mode for 4 minutes approximately and sends transmissions every 8 seconds, then it enters Regular mode – see Operation and Adjustment, Selectable Operation Modes below.
4. Knock out the mounting holes and test the transmitter from the exact mounting position before permanently mounting the unit. The EL-2650XL can be wall or ceiling mounted.
The "Alarm" arrow on the PCB (see Figure B- 4 and Figure B- 5) must point inward (i.e. towards the protected area). The recommended height is 2.2 m. If you choose mounting height other than recommended (which is not advised), please perform a walk test to check the lens coverage. The recommended mounting height is the best in terms of detection area.
5. Attach the base to the wall with two screws. If using the Back Tamper switch, insert a screw into the Back Tamper hole (see Figure B- 6) instead of the lower mounting hole. When the detector is removed from the wall, the screw causes the tamper release to break away from the back cover and the Back Tamper switch is released.
Figure B- 6: Back Tamper Release
6. Mount the PCB at the required setting using the horizontal adjustment scale and tighten the PCB screw – see Operation and Adjustment, PCB Adjustment below. Attach the front cover and replace the cover screw.
Operation and Adjustment
PCB Adjustment
PCB adjustment enables you to angle the infrared beams by changing the position of the pyro element in relation to the lens. To adjust the PCB, loosen the PCB screw and slide the PCB to the required position using the PCB adjustment scale as a guide. After adjusting the board, tighten the PCB screw. Slide the board towards -2 to position the beams closer to the wall. Slide the board towards +2 to position the beams further away from the wall. For the correct PCB adjustment, you must take into account the distance of the detector from the wall and the distance of the protected door/window from the detector – see Table B- 2 as illustrated in Figure B- 7 are relevant both to wall and ceiling mounting.
Figure B- 7: EL-2650XL Correct Installation
Back tamper mounting hole
Page 97
Appendix B: Transmitter Installation
CommPact Installation Manual
93
This is a typical installation example where the detector is 5cm from the wall and 2m from the protected window. The top two diagrams show the lens coverage pattern for the detector when incorrectly adjusted to -2 and 0. The bottom diagram shows the PCB correctly adjusted to +2.
Table B- 2: Recommended PCB Adjustment Scale Settings for Wall and Ceiling Mounting
Distance of Detector from Wall (D)
5cm 25cm 50cm
Distance of
Door/Window
from Detector (W)
Up to 2m* +2 0 -1 4m +2 0 -1 6m +2 0 0 8m +2 +1 0 9m +2 +1 0
It is not recommended to mount the unit less than 40cm away from the path of entry protected by the detector.
Walk Test
A walk test determines the coverage pattern of the detector. To perform this test, walk across the scope of the detector according to the detection pattern selected. Confirm that the LEDs activate and deactivate as described in Table B- 5. To launch the Walk Test from the Radio mode, after any transmission indicated by LED blinking, press the tamper switch and hold it until the green LED turns on then off (see Figure B- 8, step 1). Release the tamper switch and wait until the red LED turns on and then off (see Figure B- 8, step 2). Press the tamper switch once again. Both LEDS are lit momentarily (see Figure B- 8, step 3). The detector enters the Walk Test mode for 4 minutes. During the Walk Test, wait for twenty seconds between movements. To launch the Walk Test from the Normal mode: Just open the detector housing: the tamper is triggered and the detector enters the Walk Test mode for 4 minutes. Walk test should be performed weekly.
In Walk Test mode there are no delays.
Figure B- 8: Launching the Walk Test from Radio Mode
Selectable Operation Modes
The detector operates in two operation modes. In Directional Mode, crossing the infrared beams is alarm-protected in one direction only. The protected direction is shown by the arrow printed on the PCB. In case of crossing the beams from the non-permitted side (ALARM), red LED is lit for a second. In case of crossing the beams from the permitted side (NO ALARM), green LED is lit for a second and the Alarm delay (see below) starts to count down. In Curtain mode, crossing the beams is alarm-protected in both directions. The Operation mode (Directional/Curtain) is selected using the Mode Jumper – see Table B-3.
Page 98
Appendix B: Transmitter Installation
CommPact Installation Manual
94
Alarm Delay
The Alarm Delay is a feature designed to allow the occupant to move freely within the protected area without triggering a false alarm. When approaching the protected wall, an alarm is not generated because the detector’s beams are crossed from the permitted direction. After detecting permitted motion, the detector counts down the Alarm Delay time. This timer is re-triggered every time the detector detects motion. During the Alarm Delay, the detector permits motion in both directions. The duration of the alarm delay is selected using the Alarm Delay Jumper – see Table B-4.
LED Indication
The LED indicator turns red to indicate non-permitted motion and green to indicate motion detection in either direction. In the event of an alarm, the LED turns red. To disable the LED, remove the LED Jumper, JP1 located next to the LED indicator – see Table B- 5.
Do not disable the LED until you have successfully walk tested the detector.
PIR Supervision
The circuit operation of the PIR is checked once per hour. In the event of PIR failure the red LED flashes.
Battery Replacement
Open the housing by removing the front cover (see Installation Instructions), replace the battery, and close the front cover.
Close the front cover immediately after each battery replacement.
Table B-3: EL-2650XL's Mode JumperJP3
Table B-4: EL-2650XL's Alarm Delay Jumper JP
Table B- 5: EL-2650XL's LEDs
Mode Jumper JP3
Jumper Position
Alarm Delay
Jumper JP2
Jumper Position
LED Indication
Curtain Removed 1 minute Removed Red Non-Permitted
motion
Directional Installed 4 minutes Installed Green Permitted Motion
Signals and Messages:
In case of a low battery (2.5 V and below), the detector low battery condition is reported to the Control System and low battery message is displayed. When the Back Tamper switch is released, the detector sends a tamper condition to the Control System that generates tamper alarm.
Wall Mounted Ceiling mounted
Figure B- 9: Lens Coverage Pattern (Side View)
Page 99
Appendix B: Transmitter Installation
CommPact Installation Manual
95
Wireless PIR (EL-2652SR)
The EL-2652SR is a wireless PIR detector designed for use with Electronics Line 3000’s supervised wireless range of receivers. The detector is designed for both indoor and external installations and provides good immunity to nuisance alarms caused by pets weighing up to 10kg (22lbs). The EL­2652SR implements a feature to combat the problem of multiple transmissions that drastically reduce the life of the batteries. After each detection the detector initiates a three-minute delay during which transmissions will not be sent.
1. PCB Holding Hooks
2. Transmitter
3. Antenna
4. PIR 1 Pyro Sensor
5. Tamper Switch
6. Battery Holders
7. PIR 2 Pyro Sensor
8. Configuration Jumpers
9. LED Indicator
10. LED Jumper
11. PCB Release Tab
Figure B- 10: EL-2652SR (Cover Off)
Location of Detector
Consider the following before mounting the detector:
Select a location from which the pattern of the detector is most likely to be crossed by
an intruder.
Avoid a location that comes in direct contact with radiators, heating/cooling ducts or
air conditioners.
Do not place the detector in front of windows subject to direct sunlight or drafts.
Do not place bulky objects in front of the detector.
Do not place the detector in an area subject to direct sunlight or objects that may
change temperature rapidly.
If installed in external environment:
Do not place the detector in an area exposed to direct wind or rain.
Refrain from pointing the detector at roads and alleyways within the detector’s range.
Do not point the detector at trees, bushes and other objects that may be caused to
sway by the wind, within the detector’s range.
Page 100
Appendix B: Transmitter Installation
CommPact Installation Manual
96
Pet Immunity Guidelines
It is expected that the detector will eliminate false alarms caused by:
Animals up to 10kg
Several small rodents
Random flying birds
The weight of the animal should only be used as a guide; other factors such as length and color of fur also affect the level of immunity.
For maximum pet immunity the following guidelines are recommended:
Mount the center of the detector at a height of 1.8m.
Set the pulse counter for 3 pulse detection.
Do not aim the detector at stairways that can be climbed by an animal.
Avoid a location where an animal can come within 1.8m of the detector by climbing
on furniture, boxes or other objects.
Installation Instructions
1. Open the housing by removing the front cover. To do so, insert a screwdriver in the release slot (located at the bottom of the detector between the front and back cover). Turn the screwdriver 90º to release the cover.
2. To remove the PCB, carefully push down the release tab and lift the board to pull it away from the holding hooks.
Do not touch the face of the PYRO sensor.
3. Apply battery power by removing the isolators that separate the batteries from their contacts on the battery holders.
4. Place the Mode jumper over pins 2 & 3 (see Table B- 6); the LED flashes.
Install the Mode jumper only after applying battery power.
Table B- 6: EL-26552SR's Mode Jumper
Table B- 7: EL-2652SR's Pulse Count Jumper
Table B- 8: EL-2652SR's LEDs
Mode Jumper Position
Mode
Pulse Count Jumper Position
Pulse Count
LED Jumper Position
LED Indication
Pins 1&2 Walk
Test Mode
Pins 1&2 1 Out Disabled
Pins 2&3 Radio
Mode
Pins 2&3 2 In Enabled
Removed Normal
Mode
Removed 3
5. Set the receiver to Registration mode and wait for the receiver to indicate that the transmitter has been registered successfully. Write the number of the zone and the transmitter number (if applicable) on the sticker provided. Affix the sticker inside the front cover for future reference.
Alternatively, the EL-2652SR can be registered to the receiver by manually entering the transmitter's serial number.
Loading...