Introduction
*If C4 needs to be assembled, the product consists of 1 main board, 12 screws and 6
supporters
SMART & EFFICIENT NETWORK ACCESS
CONTROLLER
ACCESS CONTROL MANAGEMENT SYSTEM
FLEXIBILITY AND COMPATIBILITY IN SYSTEM
INTEGRATION
•Flexibility in System Integration
•Organic expansion
•Easy management
•Modular based architecture
•Compatibility with 3
rd
party systems
•Integrated central monitoring
•4 reader control
•Unlimited controller integration
•12 inputs & 8 outputs (up to 28 & 24)
•Fast Ethernet & Weigand
•Global Anti-passback
•AES/3DES encrypted communication
•Web server embedded
•Auto detects card formats
•Supports HID products
•Unlimited Clients
•Unlimited access rights
•100,000 users
•256/256 Time schedules/holidays
•Supports FP/Iris biometric readers
•AES/3DES encrypted communication
•Time-attendance & Meal management
•Reporting tool
•Supports Multiple languages
Power supply IDentry-C4
Belden #9409, 18 AWG
2 conductor, unshielded
Belden #9512, 22 AWG
4 conductor, unshielded
Input Device IDentry-C4
Belden #9512, 22 AWG
4 conductor, unshielded
Output Device(Lock/alarm) IDentry-
C4
Belden #9409, 18 AWG
2 conductor, unshielded
UTP Cable CAT5(Category5)
4 screw holes to fix the ACU board to its case
DC +12V max 2A (excluded reader and lock/alarm device power
source)
Output port for lock or alarm devices Form-C Type (NO, COM,
NC)
Ethernet port for communication with PC and among controllers
Wiegand format reader port
Input ports with 2 state of ON/OFF
4 state supervised
input ports
8 inputs monitoring Open loop, Shorted loop, Grounded loop an
d Line fault
Output port for LED displaying power/ACU status/communicatio
n status (output current : 50mA)
Switch to initialize ID/EVENT/network configuration/ other config
uration
Recommended Wire and Cables
IDentry-C4
Quick Manual
December 2015 Ver. 2
For the full version of this manual, please visit COMMAX online
www.commax.com > Customer > Manual and download full manuals for installation and
users.
Access Control IDentry-C4 Installation Manual
http://www.commax.co.kr/boardnew/lib/downfile.php?db=TB_ENGLISH_manual&fnum=128
Access Control IDentry Access Control CAMS-C User Manual
http://www.commax.co.kr/boardnew/lib/downfile.php?db=TB_ENGLISH_manual&fnum=131
*CAMS-C Free version covers up to 8 controllers, please feel free to contact us
identry@commax.com if you would like to purchase full version CAMS-C for more than
8 controllers.
Cable Connection

System Overview Diagram
Cable-Connection
1. Power Connection: Use +12V Power supply (TB21)
2. Reader port connection: It allows to use separated power source for readers (important!
Use common ground among of controller board power and of reader power)
3. Relay port connection (Form-C): In case of Power Fail SECURE Lock(left) and in case of
Power Fail SAFE Lock(right). It is recommended to connect diode on the side of output
devices as shown in the above configuration to protect the control device from possible
damage by reversed power current from Lock or alarm devices.
4. Two state input port connection: 2 stated input ports to monitor controller box status
of AC FAIL, LOW BATTERY, TAMPER ALARM and more NO/NC option.

Cable-Connection
5. Four state supervised input connection: Inputs for sensors of exit buttons, door
contacts, PIR and others. 4 state supervised inputs (ON / OFF / CUT / SHORT) and must
connect 2.2K / 470 ohm resister (over 1/4W) as shown above diagram. To use 2 status
inputs, the resister connection is not necessary. Dry contact signal with NO/NC option.
6. External LED Output Port: Output port for controller monitoring LED on the outside
of controller box. POWER / BOARD STATUS / ETH_TXD / ETH_RXD / ETH_STATUS are
included and Output voltage/current: 5V / 20mA (MAX).
Setup
Device Search
It searches controllers connected in the network.
1. Click search.
2. Once it shows controllers searched, make double click the controller to define on
the upper side list, and then it moves from the upper side list to the bottom.
(*It searches controllers only in the same network. If controllers are in another
network, for initial setting connect the controllers in the same network.)
(*Search by specific IP address can be used only after making network data setting in
a same network. Once set the network data, connect the controller in a network and
input IP address and click search button.)
3. Repeat 2 for each controller setting moving the controllers from upper list to the
bottom.
Device Network Management
Change the controllers’ network data upon its actual network of installation site.
1. Select controller to change network data in the list.
2. Change IP address, Subnet Mask, Gateway and port upon its network of installation
site.
(* Device Type, MAC Address cannot be changed. Web port is a port for a connection
via web browser. Connection Password is a password for the software to make
connection to a C4 controller. Please keep this password since the software cannot
make communication with controllers if the password is not correct. The default
password is set as 12345678. Changing password, it has to be an 8 digit number.)
3. Click Network Setup.
4. Once network data is set, go back to Device Search tap, search the controllers and
register controllers again.
Device Setup
1. Select 2 doors control or 4 door control. In case of 2 doors control, it sets to operate
with 2 IN readers and 2 OUT readers and of 4 doors control, with 4 IN readers.
2. Select 2 doors control or 4 doors control.
3. Click Save. (Depending on the number of controller, it may take long time to save.)
Controller Management
1. Select a controller from device list.
2. Enter detailed data of the controller in controller management tap.
3. Click Save.
4. Once the data for the controller management tap is saved, set door management,
reader management, input device management and output device management in order.
5. Once all the setting is done, click upload button to upload to controllers.
(*Upload can be processed only when the communication module is running.)
COMMAX Co., Ltd.
SmartHome & Security
#531-11, Sangdaewon-dong, Jungwon-gu, Seongnam-city, Kyunggi-do, Korea TEL +82-31-7393-540~550 FAX +82-31-745-2133