Note: ADH unit do not have outdoor ambient sensor installed, the defrost cycle only based on the
outdoor coil sensor. Therefore, “100”, “101”, “110” and “111” do not apply to ADH units.
T-----------Outdoor ambient temperature
t-----------Accumulation of compressor running time
T1----------Initiation Coil Temperature
T2---------Termination Coil Temperature
The factory default setting is “0 0 0”. After the compressor consecutively runs for 30 minutes, the
defrost cycle will be initiated if the sensor detects the coil temperature ≤ 32F for consecutive 1 minute.
The defrost cycle will be terminated either the coil temperature reach 68F or the defrost cycle reach 15
minutes.
Defrost Cycle:when the system running in heat pump mode, after the compressor has been
running for “t” minutes continuously, the defrost cycle start if the defrosting temp sensor has been in T1
degree or under T1 degree for 1 minute continuously. During the defrost cycle, the reversing valve is
energized, the outdoor fan stops running and the auxiliary electric heating is energized. The defrost
cycle will be terminated if defrost cycle reach 15 minutes or the coil sensor detects the coil temperature
over T2 degree.
Manually Defrost Cycle
There is a Manually Defrost Button located on the Defrost Control PCB, by press this button , the
system will go to defrost cycle right away to melt the ice on the coil.
STEP 11 —Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub--through or
wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all
panels and covers.
3. Tighten service valve stem caps to 1/12--turn past finger tight.
4. Leave Users Manual with owner. Explain system operation and periodic maintenance requirements
outlined in manual.
5. Fill out Dealer Installation Checklist and place in customer file.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment failure, periodic maintenance
must be performed on this equipment. Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications.
Without Outdoor Ambient Sensor
installed With Outdoor Ambient Sensor Installed
Dip Switch
Setting 000 001 010 011 100 101 110 111
T - - - - >26F <26F >26F <26F >26F <26F >26F <26F
t 30 min 44 min 60min 90min 30min 60min 44min 60min 60min 90min 90min 120min
T1 32F 28F 32F 32F 28F 14F 28F 14F 28F 5F 28F 5F
T2 68F 68F 68F 68F 68F 60F 68F 60F 68F 60F 68F 60F