Comfort Glow Owner's Operation And Installation Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
For more information, visit www.desatech.com
For more information, visit www.desatech.com
CF26NR
CF26PR
19,000 to 26,000 Btu/Hr
Remote Control Ready
VENT-FREE GAS
BAY FRONT FIREPLACE
OWNER’S OPERATION AND
INSTALLATION MANUAL
Patent Pending
AUTO
OFF
ON
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
Fireplace Shown
With Optional
Bay Front Mantel
WARNING: Improper installation,
adjustment, alteration, service, or
maintenance can cause injury or
property damage. Refer to this
manual for correct installation and
operational procedures. For assistance or additional information
consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented
gas-fired heater. It uses air (oxygen) from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to
Combustion and Ventilation
Air for
sec-
tion on page 4 of this manual.
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
2
SAFETY INFORMATION
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
CLEANING AND MAINTENANCE ............................................ 20
SAFETY INFORMATION
WARNINGS
WARNING ICON G 001
IMPORTANT: Read this owner’s manual carefully
and completely before trying to assemble, operate, or
service this fireplace. Improper use of this fireplace
can cause serious injury or death from burns, fire,
explosion, electrical shock, and carbon monoxide
poisoning.
ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 26
WARRANTY INFORMATION...................................... Back Cover
WARNING: Do not allow fans to blow directly into
the fireplace. Avoid any drafts that alter burner flame
patterns. Ceiling fans can create drafts that alter
burner flame patterns. Altered burner patterns can
cause sooting.
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If
you have these signs, the fireplace may not be installed or working
properly. Get fresh air at once! Have fireplace inspected and
serviced by a qualified service person. Some people are more
affected by carbon monoxide than others. These include pregnant
women, people with heart or lung disease or anemia, those under the
influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor-making
agent is added to each of these gases. The odor helps you detect a gas
leak. However, the odor added to these gases can fade. Gas may be
present even though no odor exists.
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this fireplace.
WARNING: Any change to this heater or its controls
can be dangerous.
WARNING: Do not use a blower insert, heat
exchanger insert, or other accessory not approved
for use with this heater.
Do not place clothing or other flammable material on
or near the appliance. Never place any objects in the
fireplace or on logs.
Fireplace front and screen become very hot when
running heater. Keep children and adults away from
hot surface to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow
surface to cool before touching.
Carefully supervise young children when they are in
the room with fireplace. When using the hand-held
remote accessory, keep selector switch in the OFF
position to prevent children from turning on burners
with remote.
You must operate this fireplace with a fireplace screen
in place. Make sure fireplace screen is closed before
running heater.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors
and liquids.
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
109774
SAFETY INFORMATION
AUT
O
OFF
ON
Continued
SAFETY INFORMATION
PRODUCT IDENTIFICATION
UNPACKING
3
3
2.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building.
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
3.Do not place propane/LP supply tank(s) inside any structure.
Locate propane/LP supply tank(s) outdoors.
4.This fireplace shall not be installed in a bedroom or bathroom.
5.Do not use this fireplace as a wood burning fireplace. Use only
the logs provided with the fireplace.
6.Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could
fall into the control area of fireplace.
7.This fireplace is designed to be smokeless. If logs ever appear
to smoke, turn off fireplace and call a qualified service person.
Note:
During initial operation, slight smoking could occur due
to log curing and fireplace burning manufacturing residues.
8.To prevent the creation of soot, follow the instructions in Clean-ing and Maintenance, page 20.
9.Before using furniture polish, wax, carpet cleaner, or similar
products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or
on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run properly . This
fireplace has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the fireplace if not enough
fresh air is available. See Air for Combustion and Ventilation,
pages 4 through 6. If fireplace keeps shutting off, see Trouble-shooting, pages 21 through 23.
11. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or to burn paper or other
solid fuels.
13. Do not use fireplace if any part has been under water. Immediately call a qualified service technician to inspect the room
fireplace and to replace any part of the control system and any
gas control which has been under water.
14. Turn fireplace off and let cool before servicing, installing, or
repairing. Make sure the selector switch is in the OFF position. Only a qualified service person should install, service or
repair fireplace.
15. Make sure the selector switch is in the OFF position when you
are away from home for long periods of time.
16. Operating fireplace above elevations of 4,500 feet could cause
pilot outage.
17. Do not operate fireplace if any log is broken. Do not operate
fireplace if a log is chipped (dime-sized or larger).
18. T o prevent performance problems, do not use propane/LP fuel
tank of less than 100 lbs. capacity (propane/LP gas only).
19. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Fireplace
Cabinet
Brick
Liner
Logs
Screen
Heater Controls
(Inside Door)
Figure 1 - Vent-Free Gas Compact Fireplace
UNPACKING
1.Remove and fireplace from carton.
2.Remove all protective packaging applied to fireplace for
shipment.
3.Make sure your fireplace includes one hardware packet.
4.Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
109774
For more information, visit www.desatech.com
For more information, visit www.desatech.com
LOCAL CODES
4
PRODUCT FEATURES
OPTIONAL REMOTE CONTROL ACCESSORIES
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence
of local codes, use the latest edition of The National Fuel Gas Code,
ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS/pilot is a required feature for ventfree room fireplaces. The ODS/pilot shuts off the fireplace if there is
not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches,
batteries, or other sources to light fireplace.
AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a
confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuelburning appliances in your home.
Today’s homes are built more energy efficient than ever. New
materials, increased insulation, and new construction methods help
reduce heat loss in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out and the warm air
in. During heating months, home owners want their homes as
airtight as possible.
While it is good to make your home energy efficient, your home
needs to breathe. Fresh air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
OPTIONAL REMOTE
CONTROL ACCESSORIES
There are two optional remote controls that can be purchased
separately for this log heater:
• hand-held ON/OFF remote
• hand-held thermostat remote
See Accessories, page 25.
The following are excerpts from National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a.walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retarder with a rating
of one perm (6 x 10
openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
-11
kg per pa-sec-m2) or less with
and
and
For more information, visit www.desatech.com
For more information, visit www.desatech.com
109774
AIR FOR COMBUSTION AND
VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation (Cont.)
Determining Fresh-Air Flow For Fireplace Location
5
5
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between
wall panels, at penetrations for plumbing, electrical,
and gas lines, and at other openings.
If your home meets all of the three criteria above, you
must provide additional fresh air. See
From Outdoors
, page 6
.
Ventilation Air
If your home does not meet all of the three criteria above,
proceed to
Location
Determining Fresh-Air Flow For Fireplace
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating
of all appliances installed in that space and an unconfining space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR
FIREPLACE LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
can support)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater_____________ Btu/Hr
Vent-free heater+ _____________ Btu/Hr
Total= _____________ Btu/Hr
4.Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See V entilation Air Fr omInside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-
confined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.
51,200 Btu/Hr (maximum the space can support)
56,000 Btu/Hr (actual amount of Btu/Hr used)
30,000
26,000
56,000
WARNING: If the area in which the heater may be
operated is smaller than that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3
or applicable local codes.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
109774
AIR FOR COMBUSTION AND VENTILATION
6
Ventilation Air
INSTALLATION
AIR FOR COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 5, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Ventilation
Grills
into Adjoining
Room,
Option 1
Do not provide openings for inlet or outlet air into
12"
Ventilation Grills
Into Adjoining Room,
Or
Remove
Door into
Adjoining
Room,
Option 3
12"
Option 2
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors Shown with Optional
Mantel
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this heater as your primary heat source.
WARNING: A qualified service person must install fireplace. Follow all local codes.
Note:
Your fireplace is designed to be used in zero clearance
installations. Wall or framing material can be placed directly against
any exterior surface on the fireplace, except where standoff spacers
are integrally attached. If standoff spacers are attached to your
fireplace, these spacers can be placed directly against wall or
framing materials.
Use the dimensions shown for rough openings to create the easiest
installation (see Built-In Fireplace Installation, page 8).
Figure 2 - Ventilation Air from Inside Building Shown with
Optional Mantel
For more information, visit www.desatech.com
For more information, visit www.desatech.com
109774
INSTALLATION
Continued
INSTALLATION
Check Gas Type
Installation Items
Locating Fireplace
7
7
CHECK GAS TYPE
Use only the correct type of gas (natural or propane/LP). If your gas
supply is not the correct gas type, do not install fireplace. Call dealer
where you bought fireplace for proper type fireplace.
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed
below.
• external regulator (propane/LP gas only) (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• test gauge connection*
* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase
the optional CSA design-certified equipment shutoff valve from
your dealer. See Accessories, page 25.
Note:
If desired, purchase a four-sided brass trim kit for built-in
installations. See Accessories, page 25.
LOCATING FIREPLACE
WARNING: Maintain the minimum clearances
shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
You can recess firebox into the wall. You can also position fireplace
in the optional cabinet mantels.
cabinet mantels specified in this manual. Purchase the optional
mantel from your dealer (see Accessories, page 25).
WARNING: Never install the fireplace
• in a bedroom or a bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the
front, top, or sides of the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
IMPORTANT:
Only use optional
CAUTION: This fireplace creates warm air currents. These currents move heat to wall surfaces next
to fireplace. Installing fireplace next to vinyl or cloth
wall coverings or operating fireplace where impurities (such as, but not limited to, tobacco smoke,
aromatic candles, cleaning fluids, oil or kerosene
lamps, etc.) in the air exist, may discolor walls or
cause odors.
IMPORTANT:
Vent-free fireplaces add moisture to the air. Although
this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Airfor Combustion and Ventilation, pages 4 through 6.
CAUTION: If you install the fireplace in a home
garage
• fireplace pilot and burner must be at least 18
inches above floor.
• locate fireplace where moving vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspection, and service.
• in coldest part of room.
An optional blower kit is available from your dealer. See Accesso-
ries, page 25. If planning to use blower, locate fireplace near an
electrical outlet.
Built-In Installation
CEILING
Top Of
Right
Side
Mantel Can
Be Flush
With Wall
6"
Minimum
From
Sides Of
Fireplace
Left
Side
42" Minimum
FLOOR
0" Minimum To Top Surface Of Carpeting,
Tile Or Other Combustible Material
Figure 4 - Mounting Clearances As Viewed From Front of
Fireplace
Note:
When installing fireplace directly on carpeting, tile or other
Mantel Installation
Left
Side
CEILING
42"
Minimum
Right
Side
combustible material, other than wood flooring, the fireplace shall
be installed on a metal or wood panel extending the full width and
depth of the fireplace.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 5.
Example:
The face of a mantel, bookshelf, etc. is made of
combustible material and protrudes 3 1/2" from the wall. This
combustible material must be 4" from the side of the fireplace
opening (see Figure 5).
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
C. For mantel clearances, see Figure 9 on page 9.
Example
*
*Minimum 16 inches from Side Wall
Figure 5 - Minimum Clearance for Combustible to Wall
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace
into a framed-in enclosure. This makes the front of fireplace flush
with wall. Follow the instructions below to install the fireplace in
this manner. If installing a built-in mantel above the fireplace, you
must follow the clearances shown in Figure 9, page 9. If using for
built-in installation off of the floor, follow clearances shown in
Figure 4, page 7.
2.An optional blower accessory is available (see Accessories,
page 25). There are two options for connecting blower to electrical source.
Option one: Have a licensed electrician install a properly
grounded, three-prong 120-volt electrical outlet at fireplace
location. Locate outlet inside the framed enclosure. Blower
power cord will plug into this outlet.
Option two:Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace.
If using option one, have electrical outlet installed at this time.
If using option two, do not connect blower to electrical source
at junction box until step 6.
3.Install gas piping to fireplace location. This installation includes
an approved flexible gas line (if allowed by local codes) after
the equipment shutoff valve. The flexible gas line must be the
last item installed on the gas piping.
4.Carefully set fireplace in front of rough opening with back of
fireplace inside wall opening.
5.Attach flexible gas line to fireplace gas regulator. See Con-necting Equipment Shutoff Valve to Heater Control, page 13.
6.If the optional blower has been installed connect blower to
electrical source.
Option one: Route blower electrical cord through side or rear
access door of fireplace. Plug electrical cord into electrical outlet.
Option two: Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace.
1
10
/
2
"
7
26
/
8
"
ActualFraming
Height26"26
Front Width26 3/4"26 7/8"
Depth9
1
/2"10 1/2"
Bottom3/4"3/4"
1.Frame in rough opening. Use dimensions shown in Figure 6
for the rough opening.
If installing in a corner, use dimensions shown in Figure 7 for
the rough opening. The height is 26 1/8" which is the same as
the wall opening above.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
7
/8"
26
7
/
8
"
3/4" Off
The Floor
Minimum
Figure 6 - Rough Opening for Installing in Wall
5
36
/
8
"
7
/
8
"
26
3
/
4
"
51
25
7
/
8
"
Figure 7 - Rough Opening for Installing in Corner
109774
INSTALLATION
Continued
Built-In Fireplace Installation (Cont.)
INSTALLATION
Mantel Clearances for Built-In Installation
Removing Brick Liner Retainer
9
9
7.Bend four nailing flanges on outer casing with pliers (see Figure 8).
8.Attach fireplace to wall studs using nails or wood screws
through holes in nailing flange.
9.Check all gas connections for leaks. See Checking Gas Con-nections, page 14.
IMPORTANT:
When finishing your firebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood,
etc. may be butted up next to the sides and top of the firebox.
Combustible materials should never overlap the firebox front facing. Firebox should not be placed on top of carpet or other kinds of
fibrous material.
WARNING: Do not allow any combustible materi-
als to overlap the firebox front facing.
IMPORTANT:
Noncombustible materials such as brick, tile, etc.
may overlap the front facing, but should never cover any necessary
openings like louvered slots.
WARNING: Do not allow noncombustible materials
to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered
slots on the front of the firebox.
WARNING: Use only noncombustible mortar or
adhesives when overlapping the front facing with
noncombustible facing material.
MANTEL CLEARANCES FOR BUILT-IN
INSTALLATION
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.
If placing mantel above built-in fireplace, you must meet minimum
clearance between mantel shelf and top of fireplace opening.
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the
following:
• raise the mantel to an acceptable height
• remove the mantel
Mantel Shelf
Note:
All vertical
measurements are
from top of fireplace
opening to bottom of
mantel shelf.
Minimum NonCombustible
Material
10"
8"
6"
2 1/2"
13"
16"
19"
21"
Nails or
Wood
Screws
AU
TO
O
FF
ON
Figure 8 - Attaching Fireplace to Wall Studs
For more information, visit www.desatech.com
For more information, visit www.desatech.com
109774
Nailing
Flanges
Figure 9 - Minimum Mantel Clearances for Built-In Installation