Parts Central...................................................... 39
Warranty Information ............................ Back Page
WARNING: Improper installation, adjustment, al-
teration, service or maintenance can cause in-
jury or property damage.
Refer to this manual for
correct installation and
operational procedures.
For assistance or additional information con-
sult a qualied installer,
service agency or the gas
supplier.
WARNING: This appliance
is for installation only in a
solid-fuel burning masonry
or UL127 factory-built replace or in a listed ventless rebox enclosure. It is
design-certied for these
installations in accordance
with ANSI Z21.11.2. Exception: Do not install this
appliance in a factory-built
replace that includes instructions stating it has
not been tested or should
not be used with unvented
gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 5
of this manual.
This appliance may be in-
stalled in an aftermarket,*
per man ent ly loc ate d,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.desatech.com
113097-01H2
SAFETY INFORMATION
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
be f o r e trying to a s s e mble,
operate or service this heater.
Improper use of this heater can
cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon
monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs,
the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people
are more affected by carbon monoxide than others.
These include pregnant women, people with heart
or lung disease or anemia, those under the inuence
of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent
is added to the gas. The odor helps you detect a gas
leak. However, the odor added to the gas can fade.
Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved
for use with this heater.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This appliance is not convertible for use with other
gases.
2. Do not place propane/LP supply tank(s) inside
any structure. Locate propane/LP supply
tank(s) outdoors (propane/LP units only).
3. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 lb.
capacity (propane/LP units only).
113097-01H3
www.desatech.com
SAFETY INFORMATION
Continued
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighb or’ s phone. Fo ll ow the gas
supplier’s instructions
• if you cannot reach your gas supplier, call
the re department
5. This heater shall not be installed in a bedroom
or bathroom unless installed as a vented appliance (Variable Manually-Controlled Models
Only) (see Installing Damper Clamp Acces-sory for Vented Operation, page 11). This
gas log set may not be installed as a vented
appliance in a bedroom or bathroom in the
Commonwealth of Massachusetts.
6. Before installing in a solid fuel burning
replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and loose
paint by a qualied chimney cleaner. Creosote
will ignite if highly heated. A dirty chimney
ue may create and distribute soot within
the house. Inspect chimney ue for damage.
If damaged, repair ue and rebox before
operating heater.
7. Do not burn solid-fuel in a masonry or UL127
factory-built replace in which a vent-free
room heater is installed.
8.
If replace has glass doors, never operate this
heater with glass doors closed. If you operate
heater with doors closed, heat buildup inside replace will cause glass to burst. Make sure there are
no obstructions across openings of replace.
9.
This log heater is designed to be smokeless. If
logs ever appear to smoke, turn off heater and
call a qualied service person. Note: During
initial operation, slight smoking could occur
due to log curing and heater burning manufacturing residues.
10.
To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 23.
11. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ventilation
to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system.
The ODS shuts down the heater if not enough
fresh air is available. See Air for Combustion and Ventilation, page 5. If heater keeps shutting
off, see Troubleshooting, page 25.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn
paper or other objects.
15. Do not use heater if any part has been exposed
to or under water. Immediately call a qualied
service technician to inspect the room heater
and to replace any part of the control system and
any gas control which has been under water.
16. Do not operate heater if any log is broken. Do
not operate heater if a log is chipped (dimesized or larger).
17. Turn heater off and let cool before servicing.
Only a qualied service person should service
and repair heater.
18. Operating heater above elevations of 4,500
feet could cause pilot outage.
19.
Provide adequate clear ances around a ir
openings.
LOCAL CODES
Install and use heater with care. Follow all local
codes. In the absence of local codes, use the lat-
est edition of The National Fuel Gas Code, ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
Note: Where listed vented decorative logs are
required, thermostat operation is not permitted.
State of Massachusetts: The installa-
tion must be made by a licensed plumber
or gas fitt er in the Common we alth of
Massachusetts.
Sel lers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
www.desatech.com
113097-01H4
PRODUCT
IDENTIFICATION
Log Set
Burner
Piezo
Ignitor
Control Knob
Base
Grate
Figure 1 - Vent-Free Gas Log Heater
(Logs May Vary by Model, Seasonal Oak
Single Burner Model Shown)
UNPACKING
CAUTION: Do not remove
the data plates from the grate assembly. The data plates contain
important product information.
1. Remove logs and heater base assembly from
carton. Note: Do not pick up heater base assembly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied to
logs and heater for shipment.
3. Check all items for any shipping damage. If
damaged, promptly inform dealer where you
bought heater.
PRODUCT FEATURES
OpERATION
This heater is clean burning. It requires no outside
venting. There is no heat loss out a vent or up a
chimney. Heat is generated by realistic dancing,
yellow ames. This heater is designed for vent-free
operation with ue damper closed. It has been
tested and approved to ANSI Z21.11.2 standard
for unvented heaters. State and local codes in some
areas prohibit the use of vent-free heaters. This
heater may also be operated as a vented decorative
(ANSI Z21.60) product by opening the ue damper
(non-thermostat operation only).
SAFETY pILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room
heaters. The ODS/pilot shuts off the heater if there
is not enough fresh air.
pIEzO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries or other sources to
light heater.
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a conned
space or unusually tight construction unless provisions are
provided for adequate combustion and ventilation air. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
While it is good to make your home energy efcient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
113097-01H5
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
Exhaust fans, replaces, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
pROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is dened
as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 7.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow for Heater Location.
-11
kg per pa-sec-m2) or
www.desatech.com
Conned and Unconned Space
National Fuel Gas Code, ANSI Z223.1/NFPA
54 denes a conned space as a space whose
volume is less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate input
rating of all appliances installed in that space and
an unconned space as a space whose volume is
not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m3 per kw) of the aggregate input rating of
all appliances installed in that space. Rooms communicating directly with the space in which the
appliances are installed*, through openings not
furnished with doors, are considered a part of the
unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills
between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have a
conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x
width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free replace __________ Btu/Hr
Gas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + ________ Btu/Hr
Total = ________ Btu/Hr
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
113097-01H6
AIR FOR COMBUSTION
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills
Into Adjoining
Room,
Option 1
12"
12"
AND VENTILATION
Continued
Example:
Gas water heater ____________ Btu/Hr
Vent-free replace + ___________ Btu/Hr
Total = ___________ Btu/Hr
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
_________
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space
can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space because
the actual Btu/Hr used is more than the maximum
Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconned
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an unconned space. You will need no additional fresh
air ventilation.
WARNING: If the area in
which the heater may be operated is smaller than that dened
as an unconned space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
40,000
39,000
79,000
the two spaces (see options 1 and 2, Figure 2). You
can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12"
of the oor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining
unconned space, you must provide two permanent openings: one within 12" of the ceiling and
one within 12" of the oor on the wall connecting
113097-01H7
Figure 3 - Ventilation Air from Outdoors
www.desatech.com
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using log heater. This will
help circulate the heat from your
log heater throughout the house.
In the event of a power outage,
you can use this heater as your
primary heat source.
WARNING: Never install the
heater
• in a bedroom or bathroom
unless installed as a vented
appliance (Variable ManuallyControlled Models Only) (see
page 11)
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 42" from
the front, top or sides of the
heater
• in high trafc areas
• in windy or drafty areas
WARNING: A qualied service person must install heater.
Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appliance in a vented conguration.
Check your state or local codes.
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
house. Inspect chimney ue and
rebox for damage. If damaged,
repair ue and rebox before
operating heater.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is benecial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5.
CHECK GAS TYpE
Use the correct gas type (natural or propane/LP)
for your unit. If your gas supply is not correct, do
not install heater. Call dealer where you bought
heater for proper type heater.
WARNING: This appliance
is equipped for natural or propane/LP gas. Field conversion
is not permitted.
www.desatech.com
113097-01H8
INSTALLATION
Continued
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from oor, ceiling and adjoining
wall.
Carefully follow the instructions below. This will
ensure safe installation into a masonry, UL127listed manufactured replace or certied vent-free
rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the
replace opening (see Figure 4).
Note: When installing your gas logs into
a man uf actur ed fireb ox , foll ow fir ebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace open-
ing to the ceiling should not be less than 42".
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel, page 10. If not using a mantel, follow the
information below.
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible
material must extend at least 8" up (for all models). If noncombustible material is less than 12",
you must install the replace hood accessory (24"
and 30" models only). See Figure 5, page 10 for
minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
ue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.
113097-01H9
www.desatech.com
INSTALLATION
Heat Resistant
Material
(A)
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
12"
8"
(A)
18"8"20"
14"
22"
17"
24"
20"
All minimum
distances
are in inches
Log Set
24"/30"
Models
18" Model
2
1
/2
"
6"
8"
10"
Continued
If Using Mantel
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible
material must extend at least 8" up (for all models).
If noncombustible material is less than 12", you
must install the replace hood accessory (24" and
30" models only). Even if noncombustible material
is more than 12", you may need the hood accessory to deect heat away from your mantel shelf.
See Figure 5 and 6 and Figure 7 on page 11 for
minimum clearances.
Noncombustible Requirements for
Material Safe Installation
Distance (A)
12" or more Noncombust ble material
okay.
Between 8" 24", 30" or 36" Models:
and 12" Install replace hood
accessory (GA6050,
GA6052 or GA6053 see
Accessories, page 38).
18" Model: Noncombus tible material okay.
Less than 8" Noncombustible material
must be extended to at
least 8". See Between 8"
and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between replace opening and mantel shelf. If
you do not meet the clearances in Figure 6 you
will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel
shelf and top of replace opening, a hood is not
required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6 are not met, you
must have a hood. When using a hood there are
still certain minimum mantel clearances required.
Follow minimum clearances shown in Figure 7,
page 11 when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
ue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.
www.desatech.com
Figure 6 - Minimum Mantel Clearances
Without Using Hood
113097-01H10
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18"
All minimum
distances are
in inches
Log Set
20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
14"
Min.
Combustible
Material
Noncombustible
Material
Hearth
5"
Min.
Combustible
Material
INSTALLATION
Continued
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an acceptable height
• remove the mantel
All
Models
(GA6050,
GA6052 and
GA6053)
Figure 7 - Minimum Mantel Clearances
FLOOR CLEARANCES
A. If installing appliance on the oor level, you
must maintain the minimum distance of 14"
to combustibles (see Figure 8).
B. If combustible materials are less than 14" to
the replace, you must install appliance at
least 5" above the combustible ooring (see
Figure 9).
Figure 8 - Minimum Fireplace Clearances
113097-01H
When Using Hood
if Installed at Floor Level
www.desatech.com
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMpER CLAMp
ACCESSORY FOR VENTED
OpERATION
Note: When used as a vented heater, appliance
must be installed only in a solid-fuel burning
replace with a working ue and constructed of
noncombustible material.
For Massachusetts Residents Only: Instal-
lation of this gas log set as a vented appliance in
the Commonwealth of Massachusetts requires the
damper be permanently removed or welded in the
fully open position.
If your heater is a manually-controlled model, you
may use this heater as a vented product. There
are three reasons for operating your heater in the
vented mode.
1. The replace does not meet the clearance to combustibles requirements for vent-free operation.
2. State or local codes do not permit vent-free
operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you
must permanently open chimney ue damper. You
must install the damper clamp accessory (to order,
see Accessories, page 38). This will insure vented
operation (see Figure 10). The damper clamp will
keep damper open. Installation instructions are
included with clamp accessory.
Damper
Clamp
Damper
Masonry
Fireplace
Figure 10 - Attaching Damper Clamp
Damper
Damper
Clamp
Damper
Manufactured
Fireplace
11
INSTALLATION
Continued
See chart below for minimum permanent ue
opening you must provide. Attach damper clamp
so the minimum permanent ue opening will be
maintained at all times.
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access
to heater control panel. This
will insure adequate air ow
and guard against sooting and
controls being damaged. Raise
replace oor with noncombustible material. Make sure material
is secure.
CAUTION: Do not pick up
heater base assembly by the
burner. This could damage
heater. Only handle base assembly by grates.
IMPORTANT: Make sure the heater burners are
level. If heater is not level, heater will not work
properly. For thermostat models, avoid damage
to thermostat bulb. Avoid nicks or sharp bends
in thermostat bulb wire. Keep thermostat bulb
in mounting bracket until ready to mount base
to oor. See Optional Positioning Of Thermostat Sensing Bulb, page 28.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose (not provided) (if
allowed by local codes)
• sealant resistant to propane (propane/LP) gas,
not provided
• electric drill with 3/16" drill bit
• athead screwdriver
1. Apply pipe joint sealant lightly to male threads
of the tting to be threaded into gas regulator.
Connect approved exible gas hose to gas
regulator of heater (see Figure 11).
IMPORTANT: Hold gas regula to r with
wrench when connecting exible gas hose.
2. Locate masonry screws in hardware package.
3. Position heater base assembly in replace.
4. Place logs in their proper position on heater base,
see Installing Logs on page 16.
5. Center heater base and logs front-to-back and
side-to-side in replace.
6. Carefully remove logs without moving heater
base.
Flex ble Gas Hose
(if allowed by local codes)
Heater Gas
Regulator
Fitting
Figure 11 - Attaching Flexible Gas Hose
to Heater Gas Regulator
2
www.desatech.com
113097-01H1
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.