consult a qualified installer, service agency or
the gas supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
Cleaning and Maintenance ................................ 31
be performed by a qualified
installer, service agency or the
gas supplier.
WARNING: This product
contains and/or generates
chemicals known to the State
of California to cause cancer or
birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon Monoxide
poisoning may lead to death.
www.fmiproducts.com
111986-01K2
SAFETY
Continued
This replace complies with the National Safety Standards and is listed and tested by PFS
Corporation to ANSI Z21.50/CSA 2.22 standard as vented gas replace.
NOTICE: Decorative product not for use as a heating appliance.
This replace must be installed by a qualied (certied or licensed) service person. It has
a sealed gas combustion chamber that uses a coaxial pipe (pipe within a pipe and having
the same center) venting system. It brings in fresh air for combustion through the outer pipe
and combustion gases are exhausted through the inner pipe. If the glass door assembly
and venting pipe are not properly seated, connected, and sealed, carbon monoxide leakage
(spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the u,
with headaches, dizziness, or nausea. If you have these signs, the replace may not have been
installed properly. Get fresh air at once! Have replace inspected and serviced by a qualied
service person. Some people are more affected by carbon monoxide than others. These include
pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol,
and those at high altitudes.
Propane/LP and Natural Gas: Propane/LP and natural gases are odorless. An odor-making
agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this replace.
WARNING: Any change to this replace or it’s controls can be
dangerous. Do not modify this replace under any circumstances.
Any parts removed for servicing must be replaced prior to operating replace.
WARNING: This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for
use with other gases unless a certied kit is used.
WARNING: Do not use a blower insert, heat exchanger insert or
other accessory not approved for use with this replace.
WARNING: Do not allow fans to blow directly into the replace.
Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the
appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other ammable material.
111986-01K3
www.fmiproducts.com
SAFETY
Continued
This replace reaches high temperatures. Keep children and
adults away from hot surface to avoid burns or clothing ignition.
Fireplace will remain hot for a time after shutdown. Allow surface
to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with replace.
Keep the area around your
replace clear of combustible
materials, gasoline and other
ammable vapor or liquids. Do
not run replace where these
are used or stored.
1. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier's instructions
• if you cannot reach you gas supplier, call
the re department.
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects
can make contact with the replace front
• in high trafc areas
www.fmiproducts.com
4. Turn appliance off and let cool before
servicing, installing or repairing. Only a
qualied service person should install,
service or repair this replace. Have replace inspected annually by a qualied
service person.
5. You must keep control compartments,
burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust
from carpeting, bedding material, etc.
Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually
by a qualied service person. If needed,
have venting system cleaned or repaired.
See Cleaning and Maintenance, page 31.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace.
8. This appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
codes, with the National Electrical Code,
ANSI/NFPA 70.
9. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
10. Do not operate replace if any log is
broken.
11. Do not operate replace with glass door
removed, cracked or broken.
12. Provide adequate clearances around air
openings.
111986-01K4
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes,
use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54* (USA).
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
PRODUCT
IDENTIFICATION
Upper Louver
Panel
Nailing
Flange
Glass Door
Assembly
Glowing
Embers
Piezo
Ignitor
Lower
Louver
Panel
Control
Valve
Grate
Assembly
ON/OFF/
REMOTE
Switch (Optional
Installation)
Figure 1 - Direct-Vent Fireplace with
Millivolt Ignition
Flue Collar
Log Set
Lava Rock
Blower Switch
(Optional
Installation)
PRODUCT FEATURES
These are a few facts that can help you understand and enjoy your direct-vent replace:
• The venting system may be routed to the
outside of your home in several ways. It may
vent through the roof (vertical) or it may vent
to an outside/exterior wall (horizontal). The
vent pipe installation is very important to
allow for proper operation. You must follow
the venting instructions very carefully for
either vertical or horizontal applications.
• This replace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
• This replace does not require electricity
to operate.
• Only the blower requires electricity if in-
stalled and if you plan to install the blower
at a later date, do not forget to wire the
outlet at the bottom of the replace when
framing.
• A piezo ignitor and ceramic electrode cre-
ate spark to ignite the pilot light. It does not
require any matches, batteries or any other
sources of ignition to light the pilot.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20
minutes of operation.
• Your direct-vent gas fireplace system
(replace and venting) is a balanced and
sealed gas operating unit. It requires ap-
proximately 10-20 minutes of operating
time before the ame pattern stabilizes.
111986-01K5
www.fmiproducts.com
D
RW
FW
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efcient location for your FMI PRODUCTS, LLC direct-vent
replace. Make sure that rafters and wall
studs are not in the way of the venting system.
Choose a location where the heat output is
not affected by drafts, air conditioning ducts,
windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and
precautions before deciding the exact location
for your replace and termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible ma-
terial other than wood, it must be installed
on a metal or wood panel extending the
full width and depth of the replace. See
Figure 3.
• Your replace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your replace, except where standoff spacers
are integrally attached. If standoff spacers
are attached to your replace, these spacers
can be placed directly against wall or framing
material. See framing details on page 7.
• If you plan on installing a television or
entertainment center recessed above
your replace, it is recommended that you
maintain a minimum 18" above top of louver
opening.
• When locating termination cap, it is important to observe the minimum clearances
shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with 450º
F (232º C) heat-resistant paint to coordinate
www.fmiproducts.com
with the exterior nish.
• There must not be any obstruction such
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
of the termination cap.
• Do not locate termination cap where excessive snow or ice build up may occur. Be sure
to clear vent termination area after snow falls
to prevent accidental blockage of venting
system. When using snow blowers, do not
direct snow towards vent termination area.
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 2 - Common Fireplace Locations
22 1/2"
16 5/8"
34 3/8"
Figure 3 - Fireplace Bottom Dimensions
111986-01K6
PRE-INSTALLATION
C
B
A
D
E
F
G
Top of Louver
Opening
3
2
1
4
5
6
7
Wall
A
B
E
F
G
H
D
C
Nailing Tabs
PREPARATION
Continued
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top of Standoffs 0"
Vent (See venting instructions for
specic venting clearances.)
Combustible material with a maximum thickness of 5/8" may be ush with the top front of
replace.
* For back and sides of replace, do not pack
with insulation or other materials. 0" clear-
ance to combustible materials are for framing
purpose only.
NOTICE: This replace is intended for use as supplemental
heat. Use this replace along
with your primary heating system. Do not install this replace
as your primary heat source.
If you have a central heating
system, you may run system’s
circulating blower while using
replace. This will help circulate
the heat throughout the house.
In the event of a power outage,
you can use this replace as a
heat source.
323/8"
345/8"
19"
Figure 4 - Framing Clearances for
Installation Against an Exterior Wall
135/8"
91/2"
393/8"
281/2"
97/8"
343/8"
345/8"
541/8"
Nailing
Tabs
Figure 5 - Framing Clearances for Corner
Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation.
All minimum clearances must be met.
For available accessories for this replace,
see Accessories on page 42. If you are using
a separate combustible mantel piece, refer to
Figure 6 for proper installation height. You can
install noncombustible mantels at any height
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
A
A = 6" (15.2 cm)
V
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
B
J
V
X
A
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
111986-01K8
VENTING INSTALLATION
NOTICE: Read these instructions completely before attempt-
NOTICE: Failure to follow these in-
structions will void the warranty.
ing installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations.
The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or ue system serving a
separate solid fuel or gas burning appliance.
A direct-vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following guidelines:
• When venting system terminates horizontally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which
could cause a re.
• Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the
horizontal sections, which requires 2" clearance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Snorkel terminations are required when
minimum clearance to grade cannot be
met (see Figure 16 on page 12).
• Have replace and selected vent compo-
nents on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall restops when penetrating
walls and restops when penetrating ceil-
ings or attic spaces.
• If using a venting conguration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
111986-01K9
www.fmiproducts.com
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• Installation of any damaged venting component
• Unauthorized modication of the venting
system (Do not cut or alter vent components)
• Installation of any component part not
manufactured or approved by FMI PROD-
UCTS, LLC.
• Installation other than as instructed by
these instructions
WARNING: This gas replace
and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving a separate solid fuel burning
appliance. Each direct-vent gas
appliance must use a separate
vent system. Do not use common vent systems.
WARNING: Vent pipe air
space clearances to combustibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances
from the top of the pipe. Where
the termination cap penetrates
a combustible wall, 1" air space
clearance is required.
VENTING INSTALLATION
(Framing
Detail)
10"
10" Inside Framing
10"
7 3/4"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
INSTALLATION PLANNING
There are two basic types of direct-vent
installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop.
Horizontal installations using round termination require exterior portion of wall restop
available only in vent kit HTK (see Figure
14, page 12).
1. Set replace in its desired location and determine the route your horizontal venting
will take. Do not secure replace until all
venting has been installed. Some instal-
lations require sliding replace in and out
of position to make nal venting connec-
tions. Figures 14 through 18 on pages 12
through 14 show different congurations
for venting with horizontal termination that
will help you decide which application best
suits your installation. Check to see if wall
studs or roof rafters are in the path of your
desired venting route. If they are, you may
want to adjust location of replace.
2. Direct vent pipe sections and components
are designed with special twist-lock connections.
Twist-Lock Procedure: Female ends of
pipes have locking lugs (indentations).
These lugs will slide straight into matching slots on male ends of adjacent pipes.
Push pipe sections together and twist
one section clockwise approximately onequarter turn until sections are fully locked
(see Figure 8). Note: Horizontal runs of
vent must be supported every three feet.
Use wall straps for this purpose.
3. Use a 45° elbow to connect venting system to replace ue collar. The elbow is
designed to be twist-locked onto the ue
collar as described in step 2.
IMPORTANT: Do not attempt to alter
conguration of elbow by cutting, twisting,
bending, etc.
4. Assemble desired combination of pipe
and elbows to replace ue collar. If there
are long portions of venting run, preassembled pipe sections may be installed
as subassemblies for convenience.
Continued
5. Carefully determine the location where
vent pipe assembly will penetrate outside
wall. The center of hole should line up with
center line of horizontal vent pipe. Mark
wall for a 10" x 10" square hole. Cut and
frame square hole in exterior wall where
vent will be terminated. If wall being pen-
etrated is constructed of noncombustible
material, such as masonry block or concrete, a 7 3/4" hole with zero clearance is
acceptable (see Figure 9).
Figure 8 - Vent Pipe Connections
Figure 9 - Vent Opening Requirements
www.fmiproducts.com
Male
Slots
Female
Locking Lugs
Center of
Hole
111986-01K10
VENTING INSTALLATION
Continued
WARNING: Do not recess
vent termination into any wall.
This will cause a re hazard.
6. Noncombustible Exterior Wall: Posi-
tion horizontal vent cap in the center of 7
3
/4" round hole and attach to exterior wall
with four wood screws provided. Before
attaching vent cap to exterior wall, run a
bead of non-hardening mastic (pliable
sealant) around outside edges to make a
seal between it and outside wall.
Note: The four wood screws provided
should be replaced with appropriate fasteners for stucco, brick, concrete or other
types of sidings.
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between vent
cap and exterior wall. The siding standoff
prevents excessive heat from damaging
siding materials. Siding material must be
cut to accommodate standoff. Bolt vent
cap to standoff. Apply non-hardening
mastic around outside edge of standoff.
Position standoff/cap assembly in the
center of the 10" square hole and attach
to exterior wall with wood screws provided
(see Figure 11). Siding standoff must sit
ush against exterior fascia material.
7. Combustible Exterior Wall Only: Slide
wall restop over vent pipe before connecting horizontal run to vent cap (see
Figure 12).
8. Carefully move replace, with vent assembly attached, toward wall and insert
vent pipe into horizontal termination. Pipe
overlap should be a minimum of 1 1/4" (see
Figure 13, page 12).
9. Combustible Exterior Wall Only: Slide
wall restop against interior wall surface
and attach with screws provided. See Figure 13, page 12, for horizontal termination
details.
10. Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure
unit in place. IMPORTANT: Make sure re-
place is level before securing. If replace
is not level it will not work properly.
Apply Mastic to
All Four Sides
Vent Cap
Wood Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
Cut Siding Away to
Fit Standoff
Standoff
Apply Mastic to
All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Vent Cap
(Horizontal
Termination)
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Screws
Screw
Wood
Screw
Vent
Cap
Interior Wall
Surface
Wall
Firestop
Horizontal
Vent Pipe
111986-01K11
www.fmiproducts.com
VENTING INSTALLATION
Continued
Minimum Pipe
Overlap 11/4"
Direct-Vent
Pipe
Wall
Firestop
Siding Standoff
Screws
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square
termination (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
Horizontal
High Wind
Square
Termination
Adjustable
Pipe 12" Max.
45° Elbow
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Penetrating a Wall
10" x 10" Framed
Opening
Exterior Wall with Vinyl Siding
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
Horizontal Termination Congurations
Figures 14 through 18 show different congurations and alternatives for venting with horizontal
termination. Each gure includes a chart with
critical minimum and maximum dimensions
which MUST be met. IMPORTANT: If using
a venting configuration of only horizontal
venting with no vertical run, a 1/4" rise for
every 12" of run toward the termination is
required.
High Wind
Termination
Apply
Mastic to
Outside
Edge of
Standoff
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a re. Operation of
improperly installed and maintained venting system could
result in serious injury, property
damage or loss of life.
Wall Firestop
Square Termination
Vertical (V) Horizontal (H)
29" min. 17" Max.
Exterior Portion
45° Elbow
Wall
Firestop
* If installing this replace at altitudes of
4000 feet and above, it is recommended
that an additional vertical height of 6" be
added to the vent system.
Figure 14 - Horizontal Termination
Conguration for Square and Round
Terminations
of Wall Firestop
(Round
Termination
Only)
Slide Ring
Over Elbow
to Complete
Connection
Round
Termination
Cap
Round Termination
(Kit HTK Shown)
www.fmiproducts.com
111986-01K12
VENTING INSTALLATION
Continued
CORNER AND ALTERNATE INSTALLATION
Recommended Applications:
• Corner ground oor installation
•
Ground oor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
•
Basement installation where one foot clear-
ance from ground to termination is possible
Not to Exceed (H) Limits
Square
Termination
Wall
Firestop
45° Elbow
Figure 15 - Horizontal Termination Conguration for Corner Installation Using One
90° Elbow
As Required
for (V), See
Chart for
Pipe Section
Required
* Ground Floor Corner Venting
90° Elbow
SNORKEL TERMINATION INSTALLATION
Recommended Applications:
• Installations requiring a vertical rise on building exterior
• Any installation using snorkel termination to achieve one foot above ground
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If
installing snorkel termination below grade, you must provide proper drainage to prevent water from entering
snorkel termination (see Figure 16). Do not back ll around snorkel termination.
Figure 18 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
with Termination at 90° with Fireplace
www.fmiproducts.com
111986-01K14
VENTING INSTALLATION
Continued
INSTALLATION FOR VERTICAL
TERMINATION
Note: Vertical restrictor must be installed in
all vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct the venting
system, consider an offset (see Figure 19)
to avoid cutting load bearing members.
Note: Pay special attention to these instal-
lation instructions for required clearances
(air space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with insulation. Also note maximum vertical rise of the venting system and any
maximum horizontal offset limitations.
2. Set the replace in desired location. Drop
a plumb line down from the ceiling to the
position of the replace exit ue. Mark the
center point where the vent will penetrate
the ceiling. Drill a small locating hole at
this point.
Drop a plumb line from the inside of the
roof to the locating hole in the ceiling.
Mark the center point where the vent will
penetrate the roof. Drill a small locating
hole at this point.
Roof Flashing
Flat Ceiling Installation
1.
Cut a 10" square hole in the ceiling using
the locating hole as a center point. The
opening should be framed to 10" x 10"
inside dimensions, as shown in Figure 9
on page 10 using framing lumber the same
size as the ceiling joists. If the area above
the ceiling is an insulated ceiling or attic
space, nail restop from the top side. This
prevents loose insulation from falling into
the required clearance space. If the area
above the ceiling is a living space, install
restop below the framed hole. The restop
should be installed with no less than three
nails per side (see Figure 20).
2. Assemble the desired lengths of pipe
and elbows necessary to reach from the
replace ue up through the restop. Be
sure all pipe and elbow connections are
fully twist-locked (see Figure 8, page 10).
3. Cut a hole in the roof using the locating
hole as a center point. (Cover any exposed
open vent pipes before cutting hole in roof.)
The 10" x 10" hole must be measured on
the horizontal; actual length may be larger
depending on the pitch of the roof. There
must be a 1" clearance from the vent pipe to
combustible materials. Frame the opening
as shown in Figure 9, page 10.
4. Connect a section of pipe and extend up
through the hole.
If area above is an attic or insulated area,
install restop above framed hole.
Wall Strap
If area above is a living space, install
45° Elbow
Ceiling Firestop
Figure 19 - Offset with Wall Strap and 45°
111986-01K15
Elbows
www.fmiproducts.com
restop below framed hole.
Figure 20 - Installing Firestop
VENTING INSTALLATION INSTRUCTIONS
Continued
Note: If an offset is needed to avoid
obstructions, you must support the vent
pipe every 3 feet. Use wall straps for this
purpose (see Figure 19, page 15). Whenever possible, use 45° elbows instead of
90° elbows. The 45° elbow offers less
restriction to the ow of the ue gases
and intake air.
5. Place the ashing over the pipe section(s)
extending through the roof. Secure the
base of the ashing to the roof and framing with roong nails. Be sure roong
material overlaps the top edge of the
ashing as shown in Figure 19, page 15.
There must be a 1" clearance from the
vent pipe to combustible materials.
6. Continue to add pipe sections until the
height of the vent cap meets the minimum
building code requirements described in
Figure 7 on page 8.
Vertical Termination Congurations
Figures 21 through 24 show four different
congurations for vertical termination.
Note: You must increase vent height for
steep roof pitches. Nearby trees, adjoining
rooines, steep pitched roofs and other
similar factors may cause poor draft or
down-drafting in high winds. Increasing
the vent height may solve this problem.
7. Twist-lock the vent cap onto the last section of vent pipe.
Note: If the vent pipe passes through any oc-
cupied areas above the rst oor, including
storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclosure with standard construction material.
Make sure and meet the minimum allowable
clearances to combustibles. Do not ll any of
the required air spaces with insulation.
Venting with One 90° Elbow
Vertical (V)Horizontal (H)
not install fireplace. See retailer where you
purchased the replace for proper replace
according to your gas type or to purchase gas
conversion kit (see Accessories, page 42). A
conversion kit is supplied with the CHDV32NR.
INSTALLING OPTIONAL BLOWER
ACCESSORIES
NOTICE: If installing blower in
an existing replace with gas
connections, shut off gas supply
and disconnect replace from
gas supply. Contact a qualied
service person to do this.
WARNING: If there is a duplex
electrical outlet installed in the
right side of the bottom of the
replace base area, be sure that
the electrical power to the outlet is
turned off before proceeding with
blower installation. Failure to do
this may result in serious injury.
6. While supporting speed control, secure
control shaft with lock nut by pushing and
turning lock nut with pliers clockwise until
it is tight against front panel. Place control
knob provided on shaft.
7. Turn on power to duplex outlet if previously
turned off per the warning in column 1.
8. Plug in blower power cord.
a. If your rebox is installed as a free-
standing unit with an accessory mantel, determine whether power cord will
exit left side or right side of rebox.
Route power cord through exit hole
and plug power cord into a wall receptacle near rebox.
b. If your rebox installation is recessed
and/or pre-wired, plug power cord into
duplex outlet provided. Refer to your
rebox owner’s manual for instructions
on wiring duplex outlet.
CAUTION: Never touch the
blower wheel while in operation.
Blower
Location
Magnetic
Strips
Side View
Lower Firebox
Cavity
Spade
Terminals
Exhaust
Port
Model BK Installation
Follow all instructions provided in blower
accessory kit.
1. Attach power cord to blower motor by
rmly pushing two female terminals at end
of power cord onto two spade terminals
on blower motor (see Figure 25).
2. Attach green ground wire from power cord
to blower housing using screw provided
(see Figure 25). Tighten screws securely.
3. Place blower against lower rear wall of
rebox outer wrapper with exhaust port
directed upward. The blower will t inside
back opening and be held in position against
back wall by magnets (see Figure 25).
4. Be certain that all wire terminals are
securely attached to terminals on blower
motor and screw retaining green ground
wire is tight.
5. Mount speed control box to switch bracket
by placing plastic control shaft forward
through opening in switch bracket (see
Figure 26).
111986-01K19
www.fmiproducts.com
Green
Ground Wire
Figure 25 - Blower Model BK
Control
Knob
Figure 26 - Attaching Speed Control to
Switch
Bracket
Locknut
Screw
Control
Shaft
Firebox
Speed
Control
Blower
Plug-In
Duplex Outlet
(Located underneath rebox oor
against lower right
outside wall)
FIREPLACE INSTALLATION
Continued
9. Check to make sure power cord is completely clear of blower wheel and there are
no other foreign objects in blower wheel.
Turn blower on and check for operation.
Turn blower off by turning knob fully counterclockwise before continuing.
10. Peel off backing paper and stick supplied
wiring diagram decal on rebox bottom
approximately 12" in front of blower (see
Figure 27).
Wiring Diagram
Decal 12" in Front
of Burner
Figure 27 - Location of Wiring Diagram
Decal (Model May Vary from Illustration)
Model BKT Installation
Note: When installing the BKT thermostatical-
ly-controlled blower, you must rst secure the
wiring connections from the thermal switch to
the blower (if it has not already been factory
installed).
1. Attach green ground wire from power cord
to blower housing using screw provided
(see Figure 28, page 21) Tighten screws
securely with a Phillips screwdriver.
2. Connect wire harness and power cord
terminals. Connect the jumper wire to
the blower motor terminal to the terminal
of the thermal switch. Connect one wire
of the thermal switch and one wire to the
other remaining blower motor terminal.
Note: The power cord outer insulation sleeve
may have to be stripped slightly to allow
enough wire length to reach and make all
connections. DO NOT trim excessive length
away. Just enable enough to make all con-
nections securely.
3. Place the blower against the lower rear
wall of the rebox outer wrapper with
the exhaust port directed upward. At-
tach Thermal disc magnetic bracket to
the bottom of the rebox sub-oor. The
thermodisc must be oriented near the
replace bottom as shown in Figure 28,
page 21, in order to sense temperature
and properly operate. The blower will be
held in position against the back wall by
the magnets incorporated onto the blower
housing (see Figure 28, page 21)
4. Be certain that all wire terminals are
securely attached to terminals on blower
motor and that the screw retaining the
green ground wire is tight.
5. Mount speed control box against mounting
plate provided in lower replace cavity by
placing plastic control shaft forward through
round hole (see Figure 26, page 19).
6. While supporting speed control, secure
control shaft with lock nut by pushing and
turning lock nut with pliers clockwise until
it is tight against mounting plate. Place
control knob provided on shaft (see Figure
26, page 19).
7. Check to make sure power cord is completely clear of blower wheel and that no
other foreign objects are in blower wheel.
Also double check all wire leads and make
sure wire routing is not pinched or in a
precarious position. Correct accordingly.
8. Turn on power to duplex outlet if previously turned off per warning in column 1,
page 19.
9. Plug in blower power cord to duplex outlet.
10. Blower will only run when speed control
knob is in ON position and thermal switch
senses temperature after replace begins
to heat up. Blower speed can be adjusted
by rotating control knob. To turn off, turn
knob fully counterclockwise until it clicks off.
If blower is ON and has been running with
replace operating, blower will continue to
run for a short time after replace has been
turned off. As thermal switch cools down,
blower shuts down automatically.
11. Peel off backing paper and stick supplied
wiring diagram decal on rebox bottom
approximately 12" in front of blower (see
Figure 27).
.
www.fmiproducts.com
111986-01K20
Power Cord
FIREPLACE INSTALLATION
Continued
To Blower
Motor Terminal
Magnetic
strips
To Thermal
Switch
Thermal Disc
Magnetic Bracket
Assembly
Phillips
Jumper
Wire
Screw
Route BKT
Blower Through
this Area
Side view Firebox Bottom
Figure 28: Blower Model BKT
Blower Wiring Diagram
CAUTION: Label all wires
prior to disconnection when
servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper
operation after servicing.
Ring
Terminal on
Green Wire
Thermodisc
110/115
V.A.C.
Blower
Location
Off
Black
White
Green
Air Flow
Direction
Magnets
Variable
Fan Switch
1
2
Air Flow
Direction
Black
On
Fan Switch
(N.O.)
Blue
Blower
Motor
Figure 29 - Blower Wiring Diagram for
Thermostat-Controlled Models
111986-01K21
www.fmiproducts.com
FIREPLACE INSTALLATION
INSTALLING GAS PIPING TO
FIREPLACE LOCATION
WARNING: A qualified
service person must connect
replace to gas supply. Follow
all local codes.
CAUTION: For propane/LP
units, never connect fireplace
directly to the propane/LP supply.
This replace requires an external
regulator (not supplied). Install the
external regulator between the
replace and propane/LP supply.
WARNING: For natural gas,
never connect fireplace to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
Continued
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" inside diameter or greater
to allow proper gas volume to
replace. If pipe is too small,
undue loss of volume will occur.
External
Regulator
with Vent
Pointing
Down
CAUTION: Use only new,
Propane/LP
Supply Tank
Installation Items Needed
Before installing replace, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connector (if allowed by local codes)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the equipment shutoff
valve from your retailer.
For propane/LP connection only, the installer
must supply an external regulator. The ex-
ternal regulator will reduce incoming gas
pressure. You must reduce incoming gas
pressure to between 11" and 14" of water. If
you do not reduce incoming gas pressure,
replace regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 30. Pointing the vent down
protects it from freezing rain or sleet.
www.fmiproducts.com
Figure 30 - External Regulator with Vent
Pointing Down (Propane/LP Only)
Installation must include an equipment shutoff
valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook
up. NPT tap must be upstream from replace
(see Figure 31, page 23).
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting
off the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged replace valves.
111986-01K22
FIREPLACE INSTALLATION
Continued
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment
trap/drip leg in supply line as shown in Figure
31. Locate sediment trap/drip leg where it is
within reach for cleaning. Install in piping system between fuel supply and replace. Locate
sediment trap/drip leg where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them
from going into replace gas controls. If sediment trap/drip leg is not installed or is installed
wrong, replace may not run properly.
Approved Flexible
Gas Line
Equipment Shutoff
Valve with 1/8" NPT
Tap*
3" Minimum
Cap Pipe Nipple Tee Joint
Figure 31 - Gas Connection
* The equipment shutoff valve may be supplied with the appliance or you can purchase
it from your retailer.
Natural - From Gas
Meter (5.5" W.C. to
10.5" W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14" W.C.
Pressure)
Sediment Trap/Drip Leg
CONNECTING FIREPLACE TO GAS
SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Open lower louver door panel by gently
pulling forward.
2. Route exible gas line (provided by in-
staller) from equipment shutoff valve to
replace. Route exible gas supply line
through one of the access holes on side
of replace.
3. Attach exible gas line from gas supply to
control valve (see Figure 32).
4. Check all gas connections for leaks. See
Checking Gas Connections.
To Gas Supply (Natural)
To External Regulator
(Propane/LP)
Flexible Gas
Line Do NOT
Kink
Figure 32 - Connecting Flexible Gas Line
to Control Valve
Equipment
Shutoff
Valve
Control
Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open ame to check for a leak.
Apply a noncorrosive leak detection uid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
111986-01K23
www.fmiproducts.com
FIREPLACE INSTALLATION
Continued
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect replace and its individual
equipment shutoff valve from gas supply
piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage replace gas
regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace, or using
compressed air.
4. Check all joints of gas supply piping system. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Reconnect fireplace and equipment
shutoff valve to gas supply. Check recon-
nected ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 33).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace, or using
compressed air.
3. Check all joints from propane/LP supply
tank or gas meter to equipment shutoff
valve (see Figure 34 or 35). Apply noncorrosive leak detection uid to all joints.
Bubbles forming show a leak. Correct all
leaks at once.
Equipment
Shutoff Valve
Open
Closed
Equipment
Propane/LP
Supply Tank
Figure 34 - Checking Gas Joints for
Gas
Meter
Figure 35 - Checking Gas Joints for
PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 33).
2. Open main gas valve located on or near
gas meter for natural gas or open supply
tank valve for propane/LP gas.
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff
valve to thermostat gas valve (see Figure
34 or 35). Apply noncorrosive leak detection uid to all joints. Bubbles forming
show a leak. Correct all leaks at once.
5. Light replace (see Operation, page 29).
Check all other internal joints for leaks.
6. Turn off replace (see To Turn Off Gas to Appliance, page 29).
Shutoff Valve
Gas Valve
Propane/LP Gas Fireplace
Equipment Shutoff Valve
Gas Valve
Natural Gas Fireplace
Figure 33 - Equipment Shutoff Valve
www.fmiproducts.com
111986-01K24
FIREPLACE INSTALLATION
Continued
INSTALLING OPTIONAL WALL
MOUNT SWITCH - GWMS2
1. Connect one terminal of 25 ft. wire for
wall switch to TPTH terminal on the valve.
Connect remaining wire terminal to the TH
terminal on the valve. Make sure wire ter-
minals are in positions on unit as pictured
in Figure 36. If wires are not connected as
shown, switch will not work.
2. Route 25 ft. wire through openings
provided on sides of burner system to a
convenient location to mount your switch.
3. Connect one bare wire end to each terminal of GWMS wall switch.
4. Install wall switch and cover in the wall.
WARNING: If replace has
been running, turn off and unplug replace. Let cool before
removing glass door or louvers.
Removing Louver Panels
Remove the top and bottom louver panels by
simultaneously pulling both top end spring
latches towards the center of the appliance
until they are disengaged from the locating
holes (see Figure 37). Repeat for bottom
spring latches and pull the louvers outward.
To install or replace items removed, simply
reverse the procedures above.
To Wall
Switch
Accessory
Figure 36 - Connecting Wall Switch to
Control Valve
REMOVING/REPLACING GLASS
DOOR
CAUTION: Do not operate
this replace with a broken glass
door panel or without the glass
door panel securely in place. For
replacement part information
see Replacement Parts, page 37.
CAUTION: Wear gloves and
safety glasses while handling or
removing broken glass. Do not
remove if glass is hot. Keep children and pets away from glass.
111986-01K25
www.fmiproducts.com
Louver
Panel
Spring
Latch
Figure 37 - Removing Louver Panel
Removing Glass Door
If replacement of glass is necessary, the entire
assembly, glass and frame, must be replaced.
If glass is broken, wear gloves and tape the
remaining fragments onto the frame.
1. Remove screen assembly by pushing the
rod either left or right and then down and
forward to remove screen/rod assembly
from the rebox. Set assembly aside.
2. Lift up on latches to unlock. There are two on
top of rebox and two below rebox that hold
glass door in place (see Figure 38, page 26).
3.
While holding glass door to prevent it from
falling and causing injury, remove the ve
screws from the hinge located on the left
side of door frame assembly (see Figure
38, page 26).
4. Remount the new frame at the hinge with
ve new screws before closing door. This
will ensure seating of the gasket.
5. Close glass door frame. Lock latches by
placing the bar under the tab on door and
pushing down and back on latch (see
Figure 38, page 26).
6. Replace screen/rod assembly by revers-
ing step 1.
7. Replace louvers by reversing procedure
under Removing Louver Panels.
Lock
Unlock
FIREPLACE INSTALLATION
Continued
Latch
Screw
Hinge
Glass Frame
Assembly
Figure 38 - Removing/Replacing Glass
Cleaning Glass Door
See Cleaning and Maintenance on page 31.
INSTALLING OPTIONAL BRICK
LINER MODEL BL32D
WARNING: If replace has
been running, turn off and unplug replace. Let cool before
installing brick liner.
This brick liner kit is optional. You may purchase brick liner from your local retailer or see
Accessories, page 42.
CAUTION: Always handle
brick panels with two hands.
Do not force brick panels into
place. Excessive force will break
brick panels.
1. Remove top and bottom louvers to allow
access to door latches.
2. Remove screen, unlock door latches and
open glass door. See Removing/Replac-ing Glass Door, steps 1 and 2, page 25.
3. If installing brick liner in new replace,
go to step 4. If installing brick liner in an
existing replace, carefully remove logs,
lava rock, and ember material.
Door
www.fmiproducts.com
4. Remove three screws from deflector
shield on the inside top of rebox. Set
shield and screws aside.
5. Install rear brick panel rst. Rest bottom
edge of panel on back edge of grate (see
Figure 39).
6. Install left side brick panel by sliding it
between grate and side of rebox (see
Figure 40).
Rear Brick
Panel
Figure 39 - Installing Rear Brick Panel
7. Install the right brick panel using the same
method described
8. Replace deector shield using screws
removed in step 4.
9. Install logs, lava rock, and ember material
see Installing Logs, Lava Rock and Glow-ing Embers, page 27.
10. Close glass door, lock latches on top and
bottom of door and replace screen (see
Removing/Replacing Glass Door, steps 5
and 6, page 25).
11. Close top and bottom louvers.
Left Side
Brick Panel
Figure 40 - Installing Side Brick Panels
111986-01K26
FIREPLACE INSTALLATION
1
3
4
5
6
2
Continued
INSTALLING LOGS, LAVA ROCK
AND GLOWING EMBERS
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with replace.
Open louvers, remove screen, unlock door
latches, and open glass door. See Removing/Replacing Glass Door, steps 1 and 2, page
25. Install logs according to instructions for
replace model numbers.
1. Find and place log #1 (rear log). The log
has a at bottom with a slit cut into it to
sit over the grate ap, (see Figure 41).
Rear Log
Front Log
Metal
Pin
Figure 43 - Installing Log No. 3
4.
Place log #4 (right log) onto the landing on
right side of front log as shown in Figure 44.
Grate Flap
Grate
Slit Cut
Underneath
Log
Figure 41 - Installing Log No. 1
2. Rest log #2 (front log) on pins on front part
of grate (see Figure 42).
Grate
Metal
Pins
3. Place log #3 (crossover log) onto front log.
Make sure it is seated properly on surface
of rear log and pin on front log as shown
in Figure 43.
111986-01K27
Figure 42 - Installing Log No. 2
www.fmiproducts.com
Front Log
Figure 44 - Installing Log No. 4
5. Place log #5 (base log) onto front left part
of grate making sure log ts over metal pin
of grate. See Figure 45.
6. Place log #6 (left log) onto pin on left side
of front log, the rear part of log rests over
the log no. 1 (See Figure 45).
Figure 45 - Installing Logs No. 5 and No. 6
Log
Landing
Rear Log
Metal
Pins
FIREPLACE INSTALLATION
Continued
7.
Place lava rock along sides and front of rebox
bottom in areas that are visible only. It is not
necessary to use all of lava rock provided.
NOTICE: Do not put lava rock on
burner or under burner. Placing
lava rock on burner will cause
performance problems.
8. Pull ember material apart into pieces no
larger than a dime. Place these pieces
loosely and sparingly directly onto exposed
section of front burner and along space be-
tween burner and grate prongs (see Figure
46). This will create glowing ember appearance as ame touches ember material. Do
not block air slots by using too much ember
material in one area. It is not necessary to
use all of ember material provided.
Ember Material
Figure 46 - Placing Ember Material on
9. Close glass door, lock door latches,
replace screen and close louvers (see
Removing/Replacing Glass Door, steps
5 through 7, page 25).
WARNING: The glass door must
be securely in place before running
this replace. Do not run this replace
if glass is missing or broken.
Burner
5. Slide other end of adjusting plate/shim in slot
on mitered edge of side trim (see Figure 47).
Set Screws
Side Trim
Adjusting
Plate
Shim
Mitered Edge
Slot
Figure 47 - Assembling Trim
6. While rmly holding edges of trim together,
tighten both screws on the adjusting plate
using a slotted screwdriver.
7. Repeat steps 2 through 6 for other side.
8. Place the assembled trim onto rebox
cabinet. Align hanging notches on trim
with trim hanging shoulder screws (see
Figure 48). Tap trim rmly into place with
palm of hand or rubber mallet by engaging hanging notches around shoulder
screws. Start at one end of the trim and
work around rebox until all notches are
fully engaged.
Assembled Trim
Top Trim
Slot
Trim Hanging
Shoulder Screw
Locations
PERIMETER TRIM KIT (PROVIDED)
1. Remove packaging from three pieces of trim.
2. Locate the two adjusting plates with set
screws and two shims in the hardware
packet.
If any of these pieces are missing or dam-
aged, contact the dealer where you purchased this kit or FMI PRODUCTS, LLC
at 1-866-328-4537 for referral information.
You can also visit FMI PRODUCTS, LLC's
web site at www.fmiproducts.com.
3. Align shim under adjusting plate as shown
in Figure 47.
4. Slide one end of adjusting plate/shim in slot
on mitered edge of top trim (see Figure 47).
www.fmiproducts.com
Hanging
Notches
on Trim
Figure 48 - Attaching Trim to Firebox
111986-01K28
OPERATION
O
F
F
P
I
L
O
T
L
O
I
H
O
N
FOR YOUR SAFETY
READ BEFORE LIGHTING
4. Push in gas control knob slightly and turn
clockwise to OFF.
5. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP! Follow “B”
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights
the pilot. Do not try to light by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don't try to repair it, call a qualied
service technician. Force or attempted
repair may result in a re or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
in the safety information in column 1. If
you don’t smell gas, go to the next step.
6. The pilot is located by the main burner and
should not require accessing for lighting.
7. Turn gas control knob counterclockwise
to PILOT.
8. Push in gas control knob all the way and
hold. Immediately light pilot by repeatedly
pressing piezo spark ignitor until a ame appears. Continue to hold for about 1 minute
after pilot is lit. Release gas control knob
and it will pop back. Pilot should remain lit.
If it goes out, repeat steps 4 through 7.
• If gas control knob does not pop up when
released, stop and immediately call our
service technician or gas supplier.
• If pilot will not stay lit after several tries,
turn gas control knob to OFF and call
your service technician or gas supplier.
9. Turn on all electric power to replace.
10. Turn gas control knob counterclockwise
to ON.
11. This valve is equipped with a HI/LO fea-
ture. Set replace input as desired.
12. To leave pilot lit and shut off burners only,
turn control knob clockwise to the
PILOT position then set selector switch in
the OFF position.
13. Close lower louver panel.
Gas Control
Knob
Piezo
Variable Control Knob
Ignitor
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation
of new replace, burning logs
will give off a paper-burning
smell. Orange ame will also
be present. Open damper or
window to vent smell. This will
1. Open lower louver panel.
2. Set selector switch in the OFF position to
3. Turn off all electrical power to the appli-
only last a few hours.
1. STOP! Read the safety information,
above.
2. Open lower louver panel.
3. Turn off all electric power to replace.
111986-01K29
www.fmiproducts.com
4. Push in gas control knob slightly and turn
5. Close lower louver panel.
6. Close equipment shutoff valve (see
Figure 49 - Control Valve
TO TURN OFF GAS
TO APPLIANCE
prevent draining battery.
ance if service is to be performed.
clockwise to OFF.
Figure 33, page 24).
OPERATION
Continued
MANUAL LIGHTING
PROCEDURE
1. Remove glass door (see Removing/Replacing Glass Door, page 25).
2. Follow steps 1 through 7 under Lighting
Instructions, page 29.
3. Press gas control knob and light pilot with
match.
4. Keep gas control knob pressed in for
30 seconds after lighting pilot. After 30
seconds, release gas control knob. Fol-
low steps 9 through 12 under Lighting
Instructions, page 29.
5. Replace glass door (see Removing/Replacing Glass Door, page 25).
OPTIONAL HAND-HELD
REMOTE OPERATION
Note:
All remote control accessories must be
purchased separately (see Accessories, page 42).
Follow instructions included with the remote control.
NOTICE: You must light the pilot
before using the hand-held remote control unit. See Lighting Instructions, page 29.
After lighting, let pilot ame burn for about
one minute. Turn control knob to ON position.
Adjust ame adjustment knob anywhere between HI and LO. Slide the selector switch to
the REMOTE position (see Figure 50).
Note: The burner may light if hand-held remote was on when selector switch was last
turned off. You can now turn the burner on and
off with the hand-held remote control unit.
Blower Control Knob
(Optional Accessory)
Variable
Control Knob
OPERATING OPTIONAL
BLOWER ACCESSORY
Locate the blower controls by opening the
lower louver panel on the replace. Blower
controls are located on the left side of the
switch bracket to the left just inside the louver
panel.
The BK manual blower and the BKT thermostatically-controlled blower have an ON
setting and an OFF setting. The blower will
only run when the switch is in the ON position. In the OFF position, the blower will not
operate.
Note for BKT Only: If you are using BKT
blower with optional thermostat (wall mounted
or remote control) for the fireplace, your
replace and blower will not turn on and off
at the same time. The replace may run for
several minutes before the blower turns on.
After the fireplace modulates to the pilot
position, the blower will continue to run. The
blower will shut off after the rebox tempera-
ture decreases.
The blower helps distribute heated air from
the replace. Periodically check the louvers of
the rebox and remove any dust, dirt, or other
obstructions that will hinder the ow of air.
OFF
ON
OFF
REMOTE
Selector Switch in
Remote Position
ON
Gas Control Knob in
ON Position
N
O
L
O
T
O
L
I
F
P
I
H
O
F
Figure 50 - Setting the Selector Switch, Gas
Control Knob and Variable Control Knob for
Remote Operation
IMPORTANT: Do not leave the selector switch
in the REMOTE or ON position when the pilot
is not lit. This will drain the battery.
www.fmiproducts.com
111986-01K30
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the proper
ame height. Alterations may have occurred during shipping and handling. Call a qualied service
person to readjust the pilot if necessary.
The height of the thermopile must be 3/8"
to 1/2" above pilot ame as shown if Figure
51. The thermocouple must be at a height of
about 1/8" above the pilot ame. The ame
from the pilot burner must extend beyond both
the thermocouple and thermopile.
If your pilot assembly does not meet these
requirements:
• turn replace off (see To Turn Off Gas to
Appliance, page 29)
• see Troubleshooting, page 33
Thermopile
3/8" to 1/2"
Piezo
Ignitor
Pilot Burner
1/8"
Thermocouple
CLEANING AND
MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep
control areas, burners, and
circulating air passageways of
replace clean. Inspect these
areas of replace before each
use. Have replace inspected
yearly by a qualied service
person. Fireplace may need
more frequent cleaning due to
excessive lint from carpeting,
bedding material, pet hair, etc.
GLASS DOOR
WARNING: Handle glass
door panel with care. Do not
strike, slam, or otherwise abuse
glass. Do not operate replace
with the glass door removed,
cracked, or broken.
Figure 51 - Pilot Assembly
BURNER FLAME PATTERN
Burner ames will be steady; not lifting or oating. Flame patterns will be different from unit
to unit and will vary depending on installation
type and weather conditions.
If the vent conguration is installed incorrectly,
the ames will lift or "ghost". This can be dangerous. Inspect the ames after installation to
ensure proper installation and performance.
Figure 52 shows a typical ame pattern.
If burner ame pattern differs from that described:
• turn replace off (see To Turn Off Gas to Appliance, page 29)
• see Troubleshooting, page 33
Figure 52 - Typical Flame Pattern
111986-01K31
www.fmiproducts.com
WARNING: Do not use abrasive cleaners as this may damage
glass. Use a nonabrasive household glass cleaner to clean glass.
Do not clean glass when hot.
Glass must be cleaned periodically. During
start-up it is normal for condensation to form
on the inside of the glass causing lint, dust,
and other airborne particles to cling to the
glass surface. During initial start-up a slight
lm may form on the glass due to paint curing.
The glass should be cleaned several times
with a non-ammonia, nonabrasive household
cleaner and warm water after the rst two
weeks of operation. Thereafter, clean the
glass two or three times during each heating
season, depending on the usage and circumstances present. Refer to Removing/Replac-ing Glass Door on page 25 of this manual
when removing glass door for cleaning.
CLEANING AND
MAINTENANCE
Continued
WARNING: Only parts supplied by the manufacturer should
be used when replacing broken
or damaged glass door panel
(see Replacement Parts, page
37). This glass door panel is
a complete unit. No substitute
materials may be used.
CAUTION: Wear gloves and
safety glasses while handling or
removing broken glass. Do not remove if glass is hot. Keep children
and pets away from glass.
If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass
Door, page 25). Vacuum all glass pieces with
a shop vacuum.
CAUTION: Do not vacuum if
pieces are hot.
Use only the tempered glass door replacement
intended for this replace (see Replacement Parts, page 37, for detail on ordering). No
substitutions may be made. See Removing/
Replacing Glass Door, page 25, for instructions
for replacing glass door.
LOGS
• If you remove logs for cleaning, refer to
Installing Logs, Lava Rock, and Glowing
Embers, page 27, to properly replace logs.
• Use a vacuum cleaner to remove any
carbon buildup on logs.
• Replace log(s) if broken. See Replacement
Parts on page 37.
•
Replace ember material periodically as needed.
See Replacement Parts on page 37.
VENTING SYSTEM
Conduct annual inspection of the venting
system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced immediately by a qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign
material.
3. Check for evidence of excessive con-
densation. Continuous condensation
can cause corrosion of caps, pipes, and
fittings and can be caused by having
excessive lateral runs, too many elbows,
or exterior portions of the system being
exposed to cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loos-
ened. Check mechanical supports such
as wall straps for rigidity.
WARNING: Do not operate
replace with the glass door
removed, cracked, or broken.
PILOT AND BURNERS
• Remove ember material before cleaning
burners and replace when cleaning is
complete.
• Burner and controls should be cleaned
with compressed air to remove dust, dirt,
or lint.
• Use a vacuum cleaner or small, soft bristled
brush to remove excess dust, dirt, or lint.
www.fmiproducts.com
111986-01K32
TROUBLESHOOTING
WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle, or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When ignitor button is pressed,
there is no spark at pilot
POSSIBLE CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Ignitor cable pinched or
wet
3. Piezo ignitor nut is loose
4. Broken ignitor cable
5. Bad piezo ignitor
6. Ignitor electrode broken
7. Ignitor electrode positioned
wrong
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched
by any metal or tubing.
Keep ignitor cable dry
3. Tighten nut holding piezo
ignitor. Nut is located be-
hind the mounting bracket
4. Replace ignitor cable
5. Replace piezo ignitor
6. Replace pilot assembly
7. Replace pilot assembly
When ignitor button is pressed,
there is spark at pilot but no
ignition
1. Gas supply turned off or
equipment shutoff valve
closed
2. Gas control knob not in
PILOT position
3. Gas control knob not
pressed in while in PILOT
position
4. Air in gas lines when installed
5. Depleted gas supply (propane/LP models only)
6. Pilot is clogged
7. Gas regulator setting is not
correct
1. Turn on gas supply or open
equipment shutoff valve
2. Turn gas control knob to
PILOT position
3. Press in gas control knob
while in PILOT position
4. Continue holding down
control knob. Repeat igniting operation until air is
removed
5. Contact local propane/LP
gas company
6. Clean pilot (see Cleaning
and Maintenance, page 31)
or replace pilot assembly
7. Replace gas control
111986-01K33
www.fmiproducts.com
TROUBLESHOOTING
OBSERVED PROBLEM
Pilot lights but flame goes
out when control knob is
released
Continued
POSSIBLE CAUSE
1. Gas control knob not fully
pressed in
2. Gas control knob not
pressed in long enough
3. Equipment shutoff valve not
fully open
4. Pilot flame not touching
thermocouple, which allows thermocouple to cool,
causing pilot ame to go
out. This problem could be
caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged
pilot
5. Thermocouple connection
loose at control valve
6. Thermocouple damaged
7. Control valve damaged
REMEDY
1. Press in gas control knob
fully
2. After pilot lights, keep gas
control knob pressed in 30
seconds
3. Fully open equipment shutoff valve
4. A) Contact local natural or
propane/LP gas company
B) Clean pilot (see Cleaning
and Maintenance, page 31)
or replace pilot assembly
5. Hand tighten until snug, then
tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
Burner does not light after
pilot is lit
Delayed ignition burner
Burner backring during combustion
Slight smoke or odor during
initial operation
1. Burner orice clogged
2. Inlet gas pressure is too
low
3. Thermopile leads disconnected or improperly connected
4. Thermopile is defective
1. Manifold pressure is too
low
2. Burner porting or orifice
clogged
1. Burner orice is clogged or
damaged
2. Damaged burner
3. Gas regulator defective
1. Residues from manufacturing processes and logs
curing
1. Clean burner (see Cleaning
and Maintenance, page 31)
or replace burner orice
2. Contact local propane/LP or
natural gas company
3. Reconnect leads
4. Replace thermopile
1. Contact local propane/LP or
natural gas company
2. Clean burner (see Cleaning
and Maintenance, page 31)
or replace burner orice
1. Clean burner (see Cleaning and Maintenance, page 31)
or replace burner orice
2. Replace damaged burner
3. Replace gas control
1. Problem will stop after a few
hours of operation
www.fmiproducts.com
111986-01K34
TROUBLESHOOTING
OBSERVED PROBLEM
Fireplace produces a whistling
noise when burner is lit
Continued
POSSIBLE CAUSE
1. Turning gas control knob to
HI position when burner is
cold
2. Air in gas line
3. Dirty or partially clogged
burner orice
REMEDY
1. Turn gas control knob to LO
position and let warm up for
a minute
2. Operate burner until air is
removed from line. Have
gas line checked by local
propane/LP or natural gas
company
3. Clean burner (see Cleaning
and Maintenance, page 31)
or replace burner orice
Glass soots
Fireplace produces a clicking/
ticking noise just after burners
are lit or shut off
Remote does not function
Fireplace shuts off in use
1. Flame impingement on
logs
2. Debris around burner air
mixer
1. Metal expanding while
heating or contracting while
cooling
1. Battery is not installed or
battery power is low
1. High or gusting winds
2. Low line pressure
3. Pilot is partially clogged
4. Inner vent pipe leaking exhaust gasses into system
5. Glass too loose and air
tight gasket leaks in corners
after usage
6. Bad thermopile or thermocouple
7. Improper vent cap installation
1. Adjust log set so that ame
does not excessively impinge on it
2. Inspect opening at base of
burner to see that it is NOT
packed with any type of
material
1. This is normal. If noise is
excessive, contact qualied
service person
1. Replace batteries in receiver
and hand-held remote control
1. Fireplace has been tested
for up to 40 mph winds.
However, extreme condi-
tions may occur. See Lighting Instructions on page 29
2. Contact local propane/LP or
natural gas company
3. Clean pilot (see Cleaning
and Maintenance, page 31)
4. Locate and correct all leaks
(see Checking Gas Connections, page 23)
5. Tighten glass
6. Replace faulty component
7. Check for proper installation
and freedom from debris or
blockage
111986-01K35
www.fmiproducts.com
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Fireplace produces unwanted
odors
Gas odor even when control
knob is in OFF position
Gas odor during combustion
Dark residue on logs or inside
of replace
POSSIBLE CAUSE
1. Gas leak. See Warning
statement above
1. Gas leak. See Warning
statement above
2. Control valve defective
1. Gas leak. See Warning
statement above
1. Improper log placement
2. Air holes at burner inlet
blocked
3. Burner ame holes blocked
4. Improper venting or excessive blockage
5. Excessive amounts of embers and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Connections, page 23)
1. Locate and correct all leaks
(see Checking Gas Connections, page 23)
2. Replace control valve
1. Locate and correct all leaks
(see Checking Gas Connections, page 23)
1.
Properly locate logs (see Installing Logs, Lava Rock, and
Glowing Embers, page 27)
2. Clean out air holes at burner
inlets. Periodically repeat as
needed
3. Remove blockage
4. Have the vent system inspected, including the termination cap. Remove any
restrictions or obstruction
5. Clear excess embers until
a minimum gap of 1/2" remains under the grate
www.fmiproducts.com
111986-01K36
SPECIFICATIONS
CHDV32NR
• Rating: 12,000/18,000 Btu/Hr
• Gas Type: Natural
• Ignition: Piezo
• Manifold Pressure: 3.5" W.C.
• Minimum Inlet Supply Pressure: 5.5" W.C.
• Dimensions (Actual size of rebox. Measurements do no include nailing anges
or standoffs): 32 1/4" x 34 1/2" x 16 5/8"
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call FMI PRODUCTS, LLC at
1-866-328-4537.
When calling, have ready:
• your name
• your address
• model and serial numbers of your replace
• how replace was malfunctioning
• purchase date
Usually, we will ask you to return the part to
the factory.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (propane/LP units only)
You may feel your gas pressure is too low. If
so, contact your local gas supplier.
TECHNICAL SERVICE
You may have further questions about
installation, operation, or troubleshooting.
If so, contact FMI PRODUCTS, LLC at
1-866-328-4537. When calling please have
your model and serial numbers of your
replace ready.
You can also visit our web site at
www.fmiproducts.com.
111986-01K37
www.fmiproducts.com
MODEL CHDV32NR
6
7
21
18
19
10
13
2
12
20
8
22-2
22-6
22-4
22-5
22-3
22-1
1
14
9
11
17
15
4
5
16
3
PARTS
www.fmiproducts.com
111986-01K38
PARTS
MODEL CHDV32NR
This list contains replaceable parts used in your replace. When ordering parts, follow the
instructions listed under Replacement Parts on page 37 of this manual.
KEY
NO. PART NO.DESCRIPTIONQTY.
1**Firebox Assembly1
2**Face Weldment1
3108892-01 Door Assembly1
4108903-01 Top Rolled Louver Assembly1
5108903-02 Bottom Rolled Louver Assembly1
6108895-01 Fireplace Top1
7**Fireplace Top Insulation1
8**Fireplace Surround1
9108885-01 Burner Assembly (Natural)1
10108890-01 Burner Base Gasket1
11108897-01 Rear Refractory Brick Panel (Not Included)1
12109082-03 Heat Shield1
13108901-01 Right Refractory Brick Panel (Not Included)1
14108901-02 Left Refractory Brick Panel (Not Included)1
1511418Push-On Nut2
16108440-01 Screen2
17109479-01 Screen Rod1
1814123Strain Relief1
1921171Gas Knock-Out Cover2
2024353Handy Box Assembly1
2124460Gas Conduit Assembly1
22109222-01 Log Set1
22-1 109403-01 Front Log (Log 2)1
22-2 109404-01 Rear Log (Log 1)1
22-3 109407-01 Base Log (Log 5)1
22-4 109406-01 Crossover Log (Log 3)1
22-5 109405-01 Left Top Log (Log 6)1
22-6 109408-01 Right Top Log (Log 4)1
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of two (2) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance
for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC
who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless
expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner.
All warranty will be voided if this product is used with a thermostat.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to two (2) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
111986-01
Rev. K
04/13
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.