IE-SNC-T33(4)19+T73(4)11-09 10
pressure at kPa (depended by device type). For atmospheric pressure correction to altitude setting
there is Users software Tsensor.
Jumper and button
If communication with HWg Poseidon unit is selected, the function of jumper and button is as
follows:
• Jumper opened and button shortly pressed – device goes to Info mode, see chapter „Info
mode“.
• Jumper closed and button pressed for longer than six seconds – causes restoring of
manufacturer setting of communication protocol, i.e. sets Modbus RTU communication
protocol, device address sets to 01h and communication speed to 9600Bd - after button press
there is “dEF” message blinking at LCD display. Six seconds later message “dEF” stays
shown, it means manufacturer setting of communication protocol is done.
Error States of the device
Device continuously checks its state during operation. In case error is found LCD displays
corresponding error code:
Error 0 - first line displays „Err0“. Check sum error of stored setting inside device’s memory. This
error appears if incorrect writing procedure to device’s memory occurred or if damage of
calibration data appeared. At this state device does not measure and calculate values. It is a
serious error, contact distributor of the device to fix.
Error 1 - measured or calculated value except in pressure is over upper limit of allowed full scale
range. There is a reading „Err1“ on LCD display. Value read from the device is +999.9. (for
pressure reading there is +999.9 hPa correct value).
This state appears in case of:
• Measured temperature is higher than approximately 600°C (i.e. high non-measurable
resistance of temperature sensor, probably opened circuit).
• Relative humidity is higher than 100%, i.e. damaged humidity sensor, or humidity
calculation of humidity is not possible (due to error during temperature measurement).
• Computed value – calculation of the value is not possible (error during measurement of
temperature or relative humidity or value is over range).
Error 2 - there is a reading „Err2“ on LCD display. Measured or calculated value is below lower
limit of allowed full scale range. Value read from the device is -999.9.
This state appears in case of:
• Measured temperature is lower than approximately -210°C (i.e. low resistance of
temperature sensor, probably short circuit).
• Relative humidity is lower than 0%, i.e. damaged sensor for measurement of relative
humidity, or calculation of humidity is not possible (due to error during temperature
measurement).
• Measured pressure value with added correction for altitude is outside of range from
300 hPa to 1350 hPa (from 4.351 PSI to 19.580 PSI) or the pressure sensor is damaged.
Please check setting of pressure correction for altitude with User’s software.
• Computed value – calculation of computed value is not possible (error during measurement
of temperature or relative humidity).
Error 3 - there is a reading „Err3“ on LCD display upper line. Error of internal A/D converter
appeared (converter does not respond, probably damage of A/D converter). This error does
NOT affect pressure measurement. Rest values are NOT measured. It is a serious error, contact
distributor of the device.