Comet MS5, MS5D Instruction Manual

MONITORING, DATA LOGGING AND
CONTROL SYSTEM
MS5, MS5D
Basic Part
SYSTEM s.r.o.
2 ie-ms2-MS5-02
CONTENT: page
INSTRUCTION MANUAL........................................................................................................... 1
INTRODUCTION ............................................................................................................................. 3
1. GENERAL SAFETY PRECAUTIONS ........................................................................................ 5
2. WIZARD for INSTALLATION and CONFIGURATION of DATA LOGGER.......................... 5
3. RULES for MOUNTING and CONNECTION of DATA LOGGER...........................................7
3.1. Mechanical location of data logger and the way of cable routing...................................... 7
3.2. Data logger interface connectors......................................................................................11
3.3. Mounting and connection of output relays module MP018............................................. 13
3.4. Mounting and connection of external terminal with display............................................ 14
3.5. Connection of data logger to the computer ...................................................................... 14
3.6. Wiring of data logger with supported SMS messages...................................................... 20
3.7. Connection of data logger to power ................................................................................. 21
4. USER PROGRAM and CONFIGURATION OF DATA LOGGER ......................................... 21
4.1. Program features............................................................................................................... 21
4.2. Installation of program..................................................................................................... 21
4.3. Setting of communication with data logger ..................................................................... 21
4.4. Basic items in menu program........................................................................................... 26
5. DESCRIPTION of CONFIGURATION and DATA LOGGER MODES .................................. 27
5.1. Bookmark Common.......................................................................................................... 27
5.2. Bookmark Communication............................................................................................... 28
5.3. Bookmark Profile............................................................................................................. 29
5.4. Bookmark Ch.. Identity & Calculations........................................................................... 30
5.5. Bookmark Ch.. Measuring & recording .......................................................................... 31
5.6. Bookmark Ch..Conditions............................................................................................... 33
5.7. Bookmark Ch..Alarms and indication............................................................................. 38
6. CONTROL and INDICATION COMPONENTS of DATA LOGGER...................................... 40
7. APPLICATION NOTES.............................................................................................................. 45
7.1. Processes and how to work with ...................................................................................... 45
7.2. Configuration Profiles and how to work with.................................................................. 46
7.3. SMS message and how to work with ................................................................................ 46
7.4. Possibilities of setting Logging interval........................................................................... 46
7.5. Identification of person, who deactivated alarm.............................................................. 47
7.6. Way of entering PIN code from data logger keyboard..................................................... 47
7.7. Sharing of Display mode on several computers together with automatic storing of data
on network.................................................................................................................................... 47
7.8. How to ensure alarm report, in case of power failure..................................................... 48
7.9. Back-up of data logger configuration and its restoring................................................... 48
7.10. Other possibilities in data logger configuration.............................................................. 48
7.11. What to do if data logger does not work .......................................................................... 48
7.12. Self test error.................................................................................................................... 48
7.13. Problems with correct measurement................................................................................ 48
7.14. Problems in communication with computer..................................................................... 49
8. RECOMMENDATION FOR OPERATION AND MAINTENANCE...................................... 50
9. TECHNICAL DESCRIPTION AND PARAMETERS OF DATA LOGGER ........................... 52
Note: Manual Appendixes are available in electronic pdf format.
ie-ms2-MS5-02 3
INTRODUCTION
Data loggers are designed for measurement, record, evaluation and consequent processing of input electrical signals, characterized by relatively slow changes (>1s). Together with proper transmitters and transducers are suitable for monitoring of physical values.
Device enables:
to measure and process 1 to 16 input signals
to acquire autonomous time record of measured values
create alarm states
to perform other actions based on created alarms (audible, visual indication, controlling of
relay outputs, sending SMS message, controlling of telephone dialer etc.)
to monitor on-line measured values and states
The basic model is data logger MS5. Data logger MS5D is equipped on the top of it with and display and simple keyboard.
Drawing (MS5D):
Items marked Accessory are not included in delivery and it is necessary to order separately.
4 ie-ms2-MS5-02
Architecture of measuring system with data logger MS5:
ie-ms2-MS5-02 5
1.GENERAL SAFETY PRECAUTIONS
The following list of precautions serves to reduce risk of injury or damage of described instrument. To prevent injuries use instrument accordingly with rules in this manual.
Follow rules specified in part Not allowed manipulations and notice
Service should be performed only by qualified person.
Use suitable power source. Use only source with power voltage recommended by the
manufacturer and approved in accordance with proper standards. Pay attention, the source has undamaged cables or cover.
Connect and disconnect correctly. Do not connect and disconnect cables, if device is under
electrical voltage.
Do not use instrument without covers.
Do not use instrument, if it does not work correctly. If you mean instrument does not correctly,
let it check by qualified service person.
Do not use instrument in environment with danger of explosion.
2.WIZARD for INSTALLATION and CONFIGURATION of DATA LOGGER
2.1.1
Mounting of data logger and its accessory
Select suitable location for placing data logger – pay attention to parameters of ambient
environment, minimize the number of cables, avoid sources of interference
Mounting of sensors and routing of cables – pay attention to rules of theirs installation, use
recommended working positions, avoid devices and distribution of power electricity
Check proper connection – before first switching on. If data logger controls other actuating
devices of regulation, it is recommended to put them out of operation before configuration of data logger.
Detailed rules for mounting of data logger including different ways of connection to the computer are described in chapter RULES for MOUNTING and CONNECTION DATA
LOGGER.
2.1.2
Basic activation of data logger
Connection of data logger to power - connect data logger to power and visually check its
function (indication of power, optionally the display and keyboard)
Installation of software - install user program to the PC (see part PROGRAM for DATA
LOGGER)
Configuration of data logger communication with computer – in user SW in part
Configuration-Setting of communication configure and test the data logger connection to computer. Detailed description of Setting of communication interface is in chapter
RULES for MOUNTING and CONNECTION of DATA LOGGER.
Program enables to work simultaneously with several data loggers, that are connected to the
computer in different ways.
2.1.3
Configuration of data logger – read and change the data logger configuration by means of
the SW in part Configuration – Configuration of data logger (icon i). Detailed description of data logger configuration is in
part DESCRIPTION of CONFIGURATION and MODES of
DATA LOGGER.
set data logger Name, Date and Time in data logger
!
6 ie-ms2-MS5-02
assign names to each measured point and optimize the display for your requirements (signal
conversions, decimal point position etc.)
switch on each input channel needed and set record function:
- on channels where recorded value with fixed interval is required, use Continuous record
with fixed interval.
- if record with fixed interval only under certain conditions is required, use Conditional
record.
- if only values and time under defined conditions are required, use Sampled record
- each type of record can be limited in time
- different record modes can be combined
if needed set alarm functions
- first define conditions for consequent actions
- assign to each alarm conditions for creation of alarm
- assign to each alarm actions to be performed in alarm creation (lightening of LED diode
on data logger panel, activation of ALARM OUT output, activation of audible indication, sending SMS message, sending e-mail etc.)
- maximum four conditions and two different alarm actions on one channel can be
defined; if there is a need for one channel to link several alarms (maximum four), it is enabled to use available alarms from different channels
- activity of output ALARM-OUT can be cancel by the user directly from data logger or
remotely, at the same time it is possible to record it (including information on way of canceling)
- changes of state for each alarms can be recorded separately
if there is a need during data logger operation to describe from its keyboard parts of record
with predefined notes, it is enabled by means of Processes.
if there is a need during data logger operation to change entire data logger configuration from
its keyboard, it is enabled by means of storing several configuration Profiles.
if it is required to secure data transfer and access to data logger and program functions,
system of passwords and access rights can be used
2.1.4
Usual work with data logger
reading, viewing, archiving and print/export recorded data from selected data logger or from
file on disk
on-line viewing of measured values – Display mode, enables to watch simultaneously all
connected data loggers
Display mode can be shared simultaneously on several computers in the network
Instructions for regular check and maintenance of data logger are specified in part
RECOMMENDATIONS for OPERATION and MAINTENANCE.
ie-ms2-MS5-02 7
3.RULES for MOUNTING and CONNECTION of DATA LOGGER
3.1. Mechanical location of data logger and the way of cable routing
Location of data logger must match the operating conditions and not allowed manipulations.
Working position of data logger:
data logger lies on horizontal nonflammable surface
data logger is fixed by means of mounting consoles on the wall from nonflammable
material or at low current switchboard – working position is with input connectors downward
The way of mounting of consoles to data logger and mounting holes dimensions:
data logger is fixed by means of the holder on DIN rail at low current switchboard -
working position is with input connectors downward
The way of mounting the holder to data logger:
8 ie-ms2-MS5-02
Mechanical drawing (without cables and connectors):
Connection terminals and connectors can be protected by magnetically fixed side covers MP027.
Recommendations for mounting:
do not mount data logger near sources of interference (data logger must not be
mounted directly to power switchboard nor to its nearness. Also do not mount data logger near power contactors, motors, frequency converters and other sources of strong interference).
In cable routing follow rules of standards for installation of low current distribution (EN
50174-2), especially it is necessary to pay attention to avoid electromagnetic interference intrusion to the leads, transmitters, transducers and sensors. Do not locate cabling near sources of interference.
!
ie-ms2-MS5-02 9
Do not use leads in parallel with power distribution network leads
Do not use outdoor leads without corresponding protection against effects of static
electricity
if not necessary, do not connect system with other circuitry
fundamentally use shielded cables - e.g. SYKFY n pairs x 0.5, shielding at data logger side
connect properly
do not create earth loops - it concerns both measuring circuits and cable shielding.
do not create hidden earth loops - do not connect cable shielding at end device side, if these
device do not have terminal designed for shielding. Shielding must not be connected to outer metal parts of the device nor with other devices. Do not use shielding as a signal lead.
10 ie-ms2-MS5-02
Do not use common leads for several channels
It is recommended to earth data logger at one point – there is a special terminal on power
terminal. This earthing will work correctly, if system would not be grounded at other point at the same time.
ie-ms2-MS5-02 11
3.2. Data logger interface connectors
Connectors
Each signal is connected to self-locking terminal WAGO located on the side of the case. Insert flat­bladed screwdriver to rectangle terminal hole and push screwdriver towards away from you - contact is released. Connect wire to released terminal (circular hole behind the rectangular one) and close the terminal by removing the screwdriver. Connect positive pole of dc voltage of input signal to terminal IN, negative to COM, shielding to GND.
Notice: The entire input terminal block is possible to remove from data logger by pulling it up from the connector.
Connection of leads:
Connection of transducers with current output powered by current loop
In case of connection of channels with current loop powered from data logger (inputs A0) it is possible to insert other devices (panel meters, measuring computer cards, etc.) to current loop. In this case it is necessary to consider, if undesirable current coupling will not
cause measurement inaccuracy. All inserted devices must be galvanic isolated from other circuits. In case, it is not possible to ensure this, use galvanic isolated inputs A1G and power loops from external source. Connection of input part of the module A0 including connection to two-wire probes is described in appendix 2.
!
12 ie-ms2-MS5-02
Connection of thermocouple probes
For connection of thermocouples use appropriate extension cable. Continuity of material of thermocouple wire should be kept along the line up to data logger connector. Extension (compensation) cable for thermocouples type S (PtRh-Pt) is used from different materials (due cost reasons).
Marking of subminiature thermocouple connectors and wires manufactured by OMEGA (in
accordance with US standard):
Type of thermocouple
Connector color + wire color - wire color
K (NiCr-Ni) Yellow Yellow Red J (Fe-Co) Black White Red S (Pt10%Rh-Pt) Green Black Red B (Pt30%Rh-Pt) White Black Red T (Cu-CuNi) Blue Blue Red
If there are more thermocouple inputs in data logger not galvanic isolated, avoid thermocouples to be mutually connected. If hazard of current leakage exists (mostly between thermocouple welded point and surrounding metal framework), thermocouple probes with galvanic isolated weld from outer probe shield or galvanic isolated input modules should be used. In other case high measuring errors can appear. It is recommended to use shielded thermocouple cables for longer distance (depending on possible interference sources).
Connection of temperature resistance transducers
data logger enables only two-wire connection
choose wires of maximum diameter and minimum length. In Appendix 6 additional errors
caused by leads resistance are specified.
measurement error caused by wire resistance can be compensated by suitable configuration
of data logger
Connection of transmitters with digital output RS485 to RP input
For connection of RS485 link for input module RS use e.g. shielded cable 2x2x0.5 mm2,
where one pair can be used for power of transducers and second pair for link RS485.
It is recommended to terminate the link by resistor 120 at the beginning and end of the
cable.
ATTENTION - it is recommended to connect to one RP module only devices communicating with the same communication speed and the samem communication protocol!
Connection of output ALARM OUT
This output is dual:
switching-over galvanically isolated relay contact
voltage (galvanically connected to data logger)
The output is set from the manufacturer, that in case of selected alarm voltage appears at the output
and simultaneously relay closes. It is enabled to set opposite behavior in data logger configuration
(service menu).
Activity of this output can be cancelled from data logger keyboard by the user or remotely from the
PC. It is enabled to identify by proper data logger configuration, who cancelled the alarm.
It is possible to connect to this output:
!
ie-ms2-MS5-02 13
External audio indication unit - use shielded cable up to 100m from data logger. Connect
terminal ALARM OUT and GND on data logger with the audio unit in corresponding polarity. Connector CINCH of audio indication unit has positive pole on its central lead.
Telephone dialer – in case of alarm telephone dialer dials specified telephone number and
announces voice message. In dialer configuration first select user mode, then store phone number (or numbers) and record voice message. Then it is recommended to set delay of transmitting after activation at least 10 seconds (Function 4 1). After completing of all settings connect dialer to phone line and check the function.
Simultaneously galvanically isolated contact relay can be used for control of other devices.
If indication controls external circuitry, it is recommended to set delay after activation at least 10 seconds to prevent possible false alerts.
3.3. Mounting and connection of output relays module MP018
Module contains 16 output relays with switching-over contact, which can be used for control of external devices (see parameters of relay and not allowed manipulations precautions). It is possible to assign any number of relays to any alarm to be closed if alarm appears. Relay are identified by numbers 1 to 16. Each relay has three self-locking terminals (switching-over contact). Activity of relay can be checked visually on assigned LED diodes.
Mounting:
Relay module is designed for mounting to switchboard with corresponding protection. Fix module (140x211 mm) by means of DIN rail holder MP019 or screw by means of side wall holders MP013 with four suitable screws (mounting holes are identical as for data logger with wall holders MP013, see figure above).
Connection:
Connect module to data logger with special cable MP017 (wiring diagram is specified in Appendix 10). Plug one cable end to corresponding connector on relay module, second end to data logger, connector Ext. Display & Relays (upper or lower connector half can be used, both parts are connected identically). Connect slave device on output terminals of relay. Pay attention to necessary safety (depending on the character of connected device).
Configuration:
Activate relay module function for proper operation in service menu of user SW. If data logger is delivered together with relay module, this function is activated already from the manufacturer.
Relay module layout:
14 ie-ms2-MS5-02
3.4. Mounting and connection of external terminal with display
External terminal with display is designed for visualization of measured values, alarms and for data logger controlling from point up to maximum 50 m from data logger. Its function is identical with internal built-in display of MS5D (keyboard and display work in parallel).
Mounting:
External terminal with display is designed for mounting to suitable case. It can be mounted to low-current switchboard lid where data logger itself is located or to a separate case. Cut rectangular hole 133 x 94 mm to the lid. Insert terminal unit and four screws from the front side and screw by means of metal holders from the back side. Tighten slightly.
Connection:
Connect external terminal to data logger with special cable (wiring diagram is specified in Appendix 10). Follow identical rules for cable routing as for input signals. Plug one cable end to corresponding connector on display unit, second end to data logger, connector Ext. Display & Relays (upper or lower connector half can be used, both parts are connected identically).
Configuration:
Activate display module for proper operation in service menu of user SW. If data logger is delivered together with display module, this function is activated already from the manufacturer. Newer displays are equipped with internal audio indication. Audio indication behaves in the same way as
External audio indication unit
connected to the output ALARM OUT. This function can be enabled or disabled in service menu of the SW.
3.5. Connection of data logger to the computer
Data logger contains for communication with computer one internal communication interface, which is separated to several external interfaces:
ie-ms2-MS5-02 15
Do not connect to these connectors simultaneously more than one device!
3.5.1 Connection of data logger to the computer by means of interface RS232
Application:
only short distance between data logger and master device up to approximately 10 m
2 meters cable is included in delivery (wiring diagram is specified in Appendix 4).
3.5.2 Connection of data logger to computer by means of USB interface
Application:
only short distance between data logger and master device up to approximately 5 m
Use usual USB cable A-B
Before Setting of communication in user SW it is necessary to connect converter physically to
the computer to allow operating system to create virtual communication port. Drivers are installed to your computer during installation of user SW for data logger (valid for Windows 2000 and higher).
!
16 ie-ms2-MS5-02
3.5.3 Connection of data logger to the computer by means of Ethernet interface
Parameters:
Access enabled from different computers also via Internet
Near data logger Ethernet network socket is available. Connection cable is not included in
delivery
data logger configuration and data download is not enabled simultaneously for several
users
3.5.4 Connection of data loggers to the computer by means of interface RS485
Parameters:
ie-ms2-MS5-02 17
designed for long distance communication up to 1200m in indoor environment
enables to communicate via one RS485 link with 32 data loggers
necessary RS485 port in computer or suitable converter to other interface (RS232, USB, Ethernet)
see detailed wiring diagrams of connection cables for recommend types of converters in Appendix
4
recommended cable – shielded twisted two-wire, e.g. cable SYKFY n x 0.5, connect RS485 link
(lead A and B) and cable shielding. Cable shielding is not connected to any circuitry of data logger, only continues on parallel terminal. Ground shielding near converter at the computer side, preferably to the PC frame.
termination resistor - see Appendix 4.
if using several data loggers connected to one RS485 network, then all must be set to the same
communication speed and each unit must have its own address (no data logger in the network with the same address is allowed). This configuration can be changed both from user SW and directly from the data logger keyboard.
do not connect to network of data loggers MS5 RS485 any other device, than data logger MS5,
MS2+, MS3+ or MS4+
18 ie-ms2-MS5-02
Drawing of connection by means of converter RS232/RS485 (recommended type E06D):
Drawing of connection by means of converter USB/RS485 (recommended type: E214):
ie-ms2-MS5-02 19
Drawing of connection by means of converter Ethernet/RS485 (recommended type: UDS100,UDS1000):
3.5.5 Connection of data logger via modem
Parameters:
Computer is far from data logger
In data logger and PC location is covering by GSM signal of the operator
Possible work with SMS messages
Except described GSM connection dialed connection via land line is enabled
Parameters:
at the data logger side and PC side suitable modem must be used (recommended type: Wavecom
M1306B)
WARNING – data logger must be connected first by means of RS232 interface and configured, then
connected to the modem! Detailed description is specified in the following chapter with the description of Configuration of communication.
connect interface RS232 of data logger with modem by cable, delivered with modem !
Used SIM card must enable data transfers (verify at your operator, not every operator
automatically supports).
Loading...
+ 42 hidden pages