COMBAT CUHA, CUHB, CUHA/A, CUHC, CUHB/A Installation, Commissioning, Service & User Instructions

...
SUITABLE FOR: GB, IE, IT & ES
UNIT HEATERS
Installation, Commissioning,
Service & User Instructions
Models
CUHA, CUHB, CUHC & CUHD
60 to 240 (Manual Ignition)
60 to 380 (Automatic Ignition)
October 1999
Part No. X404C
Price £5.00
Page 1
UNIT HEATER
T
hese appliances have been tested and certi fied as complying with the
essential requirements of the Gas Appliance Directive, The Low Voltage Directive, The Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and L.P.G. gas when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the following countries: Ireland (IE), Spain (ES), Italy (IT) & United Kingdom (GB ). Appliances designed for other countries are available on request.
This A ppliance must be installed in accordance with the rules in force and used only in a sufficiently ventilated space, as specified in these instructions.
Before installation, check that the local distri bution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
Page 2
UNIT HEATER
CONTENTS
The parts of this manual are numbered by section, clause and sub-clause. Hence 1:2:3 refers to Section 1, clause 2, sub clause 3. Figure numbers also follow this notation, hence Fig.2:3 is Section 2, Fig. 3.
SECTION
1. General Specification
2. Technical Data
3. Heater Installation
4. Commissioning of the Air Heater
5. Wiring Diagram
6. Servicing Instructions
7. Removal and Replacement of Parts
8. Fault Finding Charts
9. User Instructions
10. Conversion between natural gas and L.P.G
11. Parts List
12. Commissioning Data Sheet
THESE AIR HEA TERS ARE FOR USE WITH NATURAL GAS OR L.P.G ONLY AS ST ATED ON THE HEA TER DAT A PLATE
(Conversion between gasses must be carried out in accordance with section
10 of these instructions)
THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR NEAR THE HEATER
Note: Every eff ort is made to ensure that the information contained in this Manual is accura te. Howe ver,
Combat Engineering Ltd. reserves the right to alter specifications without prior notice.
Combat shall not be liable to rectify any defects or damage caused by any modifications made or attempted to be made to the heating units by the customer, his servants, agents or employees.
WARRANTY: The Heat Exchanger has a ten year W arranty (subject to terms and conditions).
Page 3
UNIT HEATER
Section 1. GENERAL SPECIFICATION- CUH RANGE
l.l Basic Information
There are eight types of heater in the CUH... range covered by these instructions.
1. CUHA 60 to CUHA 240 Manual ignition with axial fans.
(22.5kW (76770 Btu/hr) to 89kW (303668 Btu/hr) Gross heat input)
2. CUHB 60 to CUHB 240 Manual ignition with centrifugal fans.
(22.5kW (76770 Btu/hr) to 89kW (303668 Btu/hr) Gross heat input)
3. CUHC 60 to CUHC 240 Manual ignition as CUHB but with the fans encased to allo w inlet ducting .
(22.5kW (76770 Btu/hr) to 89kW (303668 Btu/hr) Gross heat input)
4. CUHD 60 to CUHD 240 Manual ignition without fan for installing into ducting.
(22.5kW (76770 Btu/hr) to 89kW (303668 Btu/hr) Gross heat input)
5. CUHA/A 60 to CUHA/A 380 Automatic ignition axial fans.
(22.5kW (76770 Btu/hr) to 140kW (477680 Btu/hr) Gross heat input)
6. CUHB/A 60 to CUHB/A 380 Automatic ignition ,with centrifugal fans.
(22.5kW (76770 Btu/hr) to 140kW (477680 Btu/hr) Gross heat input)
7. CUHC/A 60 to CUHC/A 380 as CUHB/A but with the fans encased to allow inlet ducting.
(22.5kW (76770 Btu/hr) to 140kW (477680 Btu/hr) Gross heat input)
8. CUHD/A 60 to CUHD/A 380 Automatic ignition, without fans for installing into ducting .
(22.5kW (76770 Btu/hr) to 140kW (477680 Btu/hr) Gross heat input)
Combat CUH... ranges of unit Air Heaters are type B11 appliances for vertical flue whi ch are designed to be suspended or shelf mounted.
These heaters are Cat II
2H3+
appliances for use with natural gas or L.P.G. as stated on the heater data
plate, and are intended for indoor installation only.
They must be installed in accordance with local regulations and the requirements of Section 3 of these Instructions.
A permanent electrical supply of 230 volts 50 Hz, single phase is required for all models and all models must be earthed.
ON/OFF, temperature and time control may be obtained by use of the Combat range of control consoles, or by the use of individual controls as per the circuit diagrams in Section 5.
Page 4
UNIT HEATER
1.2 Heater Operation
1.2.1 Automatic Ignition Burner
Combat CUH.../A range warm air heaters are fitted with an automatic ignition control which ignites the gas and monitors for the safe operation of the burner each time the exter nal controls call for the heater to operate.
1.2.2 Manual Ignition
Combat CUH... range heaters are fitted with a permanent pilot w hi ch requires manual ignition. Once ignited the pilot remains alight so long as the thermocouple is detecting a flame. i.e. the multifunctional control or isolating gas valve is not turned off and the electrical power supply is not interrupted.
1.2.3 Common Operation - All Heater Types
When the external controls call for heat, the burner operates to supply heat to the heat exchanger . After approximately 2 or 3 minutes the air delivery fan will start to run, supplying warm air to the b uilding.
When the external controls are satisfied they will turn off the burner leaving the fan running to cool down the heat exchanger. When cool enough the fan thermostat will turn off the fan.
Note: F or CUHD... versions supplied without a fan, for installation in ducting with a customer supplied fan unit, it is essential that the control of the f an incorporates a system for allowing the fan to run on at close down of the burner as described above.
WARNING
The electrical isolator should only be used in an emergency and should not be used for
closing down the burner, as this switches off the fan prematurely and may damage the heat
exchanger invalidating the warranty and causing a potential fire hazard.
Operating the electrical isolator on a CUH... manual ignition heater will also
turn off the pilot burner.
Page 5
UNIT HEATER
Fig 2.1 Dimensions etc. CUHA... 60 to 300
Gas Connection
Access to Second
Limit Thermostat
WARNING !
Isolate Before
Removing Cover
Electrical Connections
for Main Fan, Gas
Valve and Interrupter
Relay
Lighting
Instructions
Data Plate
Electrical Supply via Cable
Gland
Pilot viewing
via cut out
Combustion
Air Slots
Honeywell
Combination Fan/
Limit Stat.
Burner
Compartment
Air Deflection
Grille
Model
Ref.
60 80 100 120 140 160 180 200 240 280 300
A Width
mm
(ins)
519
(20½)
519
(20½)
589
(23)
589
(23)
729
(28½)
729
(28½)
869
(34)
869
(34)
1009
(39¾)
1219
(48)
1219
(48)
B Support
Spacing
mm
(ins)
479
(18)
479
(18)
549
(21¾)
549
(21¾)
689
(27¼)
689
(27¼)
829
(32¾)
829
(32¾)
969
(38¼)
1179
(46½)
1179
(46½)
C Flue Dia.
mm
(ins)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
229
(9)
229
(9)
254
(10)
254
(10)
254
(10)
Weight kg 91 91 110 110 130 130 150 150 190 200 200
Page 6
UNIT HEATER
Fig 2.2 Dimensions etc. CUHA... 340 to 380
Air Deflection GrilleBurner Compartment
WARNING !
Isolate Before
Removing
Cover
Lighting
Instructions
Electrical Supply
via Cable Gland
Access to Second
Limit Thermostat
Combustion
Air Slots
Data Plate
Gas
Connection
Pilot viewing
via cut out
Electrical
Connections for
Main Fan, Gas
Valve and
Interrupter Relay
Flue
Connections
Assembled on Site
Honeywell
Combina-
tion Fan/
Limit Stat.
Model
Ref.
340
380
A Width
mm
(ins)
1359
(53½)
1499
(59)
B Support
Spacing
mm
(ins)
1319
(52)
1459
(59)
C Flue Dia.
mm
(ins)
305
(12)
305
(12)
Weight kg 210 210
Page 7
UNIT HEATER
Fig 2.3 Dimensions etc. CUHB... 60 to 300
Burner
Compartment
Electrical Supply
via Cable Gland
Access to Second
Limit Thermostat
Data Plate
Combustion
Air Slots
Lighting
Instructions
Pilot viewing
via cut out
Gas
Connection
Electrical
Connections for
Main Fan, Gas
Valve and
Interrupter Relay
WARNING !
Isolate Before
Removing
Cover
Honeywell
Combina-
tion Fan/
Limit Stat.
Air Deflection
Grille
Model
Ref.
60 80 100 120 140 160 180 200 240 280 300
A Width
mm
(ins)
519
(20½)
519
(20½)
589
(23)
589
(23)
729
(28½)
729
(28½)
869
(34)
869
(34)
1009
(39¾)
1219
(48)
1219
(48)
B Support
Spacing
mm
(ins)
479
(18)
479
(18)
549
(21¾)
549
(21¾)
689
(27¼)
689
(27¼)
829
(32¾)
829
(32¾)
969
(38¼)
1179
(46½)
1179
(46½)
C Flue Dia.
mm
(ins)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
229
(9)
229
(9)
254
(10)
254
(10)
254
(10)
Weight kg 111 111 130 130 150 150 170 180 220 270 270
Page 8
UNIT HEATER
Fig 2.4 Dimensions etc. CUHB... 340 to 380
Air Deflection GrilleBurner Compartment
Electrical
Supply via
Cable Gland
WARNING !
Isolate
Before
Removing
Cover
Combustion
Air Slots
Access to Second
Limit Thermostat
Data
Plate
Lighting
Instructions
Gas
Connection
Pilot viewing
via cut out
Electrical
Connections for
Main Fan, Gas
Valve and
Interrupter Relay
Honeywell
Combina-
tion Fan/
Limit Stat.
Model
Ref.
340
380
A Width
mm
(ins)
1359
(53½)
1499
(59)
B Support
Spacing
mm
(ins)
1319
(52)
1459
(59)
C Flue Dia.
mm
(ins)
305
(12)
305
(12)
Weight kg 276 276
Flue
Connections
Assembled on Site
Page 9
UNIT HEATER
Fig 2.5 Dimensions etc. CUHC... 60 to 300
Air Deflection
Grille
Burner
Compartment
WARNING !
Isolate
Before
Removing
Cover
Access to Second
Limit Thermostat
Combustion
Air Slots
Honeywell
Combina-
tion Fan/
Limit Stat.
Electrical Supply via
Cable Gland
Lighting
Instructions
Data
Plate
Gas
Connection
Pilot viewing
via cut out
Electrical
Connections for
Main Fan, Gas
Valve and
Interrupter Relay
Model
Ref.
60 80 100 120 140 160 180 200 240 280 300
A Width
mm
(ins)
519
(20½)
519
(20½)
589
(23)
589
(23)
729
(28½)
729
(28½)
869
(34)
869
(34)
1009
(39¾)
1219
(48)
1219
(48)
B Support
Spacing
mm
(ins)
479
(18)
479
(18)
549
(21¾)
549
(21¾)
689
(27¼)
689
(27¼)
829
(32¾)
829
(32¾)
969
(38¼)
1179
(46½)
1179
(46½)
C Flue Dia.
mm
(ins)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
229
(9)
229
(9)
254
(10)
254
(10)
254
(10)
E Duct
Spigot Width
mm
(ins)
438
(17¼)
438
(17¼)
508
(20)
508
(20)
648
(25½)
648
(25½)
788
(31)
788
(31)
928
(36½)
1137
(44¾)
1137
(44¾)
Weight kg 128 128 148 148 169 169 191 201 243 295 295
Page 10
UNIT HEATER
Fig 2.6 Dimensions etc. CUHC... Models 340 to 380 Range
WARNING !
Isolate
Before
Removing
Cover
Electrical Supply
via Cable Gland
Honeywell
Combina-
tion Fan/
Limit Stat.
Access to
Second
Limit
Thermostat
Combustion
Air Slots
Air Deflection GrilleBurner Compartment
Data
Plate
Lighting
Instructions
Gas
Connection
Pilot viewing
via cut out
Electrical
Connections
for Main Fan,
Gas V alve and
Interrupter
Relay
Model
Ref.
340 380
A Width
mm
(ins)
1359
(53½)
1499
(59)
B Support
Spacing
mm
(ins)
1319
(52)
1459
(59)
C Flue Dia.
mm
(ins)
305
(12)
305
(12)
E Duct
Spigot Width
mm
(ins)
1277
(50¼)
1417
(55¾)
Weight kg 303 304
Flue
Connections
Assembled
on Site
Page 11
UNIT HEATER
Fig 2.7 Dimensions etc. CUHD 60 to 300
Burner
Compartment
25mm Mez. Flange
Duct Connection Spigot
Electrical Supply via
Cable Gland
Honeywell
Combina-
tion Fan/
Limit Stat.
WARNING !
Isolate
Before
Removing
Cover
Combustion
Air Slots
Access to Second
Limit Thermostat
Lighting
Instructions
Data
Plate
Pilot viewing
via cut out
Gas
Connection
Electrical Connec-
tions for Gas Valve
and Interrupter
Relay
Rear Honeywell
Combination Fan/
Limit Stat.
Model
Ref.
60 80 100 120 140 160 180 200 240 280 300
A Width
mm
(ins)
519
(20½)
519
(20½)
589
(23)
589
(23)
729
(28½)
729
(28½)
869
(34)
869
(34)
1009
(39¾)
1219
(48)
1219
(48)
B Support
Spacing
mm
(ins)
479
(18)
479
(18)
549
(21¾)
549
(21¾)
689
(27¼)
689
(27¼)
829
(32¾)
829
(32¾)
969
(38¼)
1179
(46½)
1179
(46½)
C Flue Dia.
mm
(ins)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
178
(7)
229
(9)
229
(9)
254
(10)
254
(10)
254
(10)
D Duct
Spigot Width
mm
(ins)
438
(17¼)
438
(17¼)
508
(20)
508
(20)
648
(25½)
648
(25½)
788
(31)
788
(31)
928
(36½)
1137
(44¾)
1137
(44¾)
Weight kg 82 82 92 99 104 114 124 134 154 180 180
Page 12
UNIT HEATER
Fig 2.7 Dimensions etc. CUHD 340 to 380
Access to Second Limit
Thermostat
Data
Plate
Lighting
Instructions
Honeywell
Combina-
tion Fan/
Limit Stat.
Combustion
Air Slots
WARNING !
Isolate
Before
Removing
Cover
Rear
Honeywell
Combination
Fan/Limit Stat.
Burner
Compartment
25mm Mez. Flange
Duct Connection Spigot
Gas
Connection
Pilot viewing
via cut out
Electrical
Connections
for Gas Valve and
interrupter relay
Electrical Supply
via Cable Gland
Model
Ref.
340 380
A Width
mm
(ins)
1359
(53½)
1499
(59)
B Support
Spacing
mm
(ins)
1319
(52)
1459
(59)
C Flue Dia.
mm
(ins)
305
(12)
305
(12)
D Duct
Spigot Width
mm
(ins)
1277
(50¼)
1417
(55¾)
Weight kg 190 190
Flue
Connections
Assembled
on Site
Page 13
UNIT HEATER
Table 2.1 General Technical Data - All Models
ECNEREFERLEDOM0608001021041061081002042082003043083
EGNAR'A'
-daoLlacirtcelElatoT
sttaW
1911911918.7228.7224444442.4832.4838.8488.8488.8488.848
epyTnaF
nafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiSnafiS
GMPGMPGMPGMPGMPGMPGMPGMPGMPGMPGMPGMPGMP
101-14053101-14053101-14053101-14093101-14093101-14024101-14024101-14053101-14053101-14024101-14024101-14024101-14024
dettiFsnaFforebmuN
1111111222222
fµroticapaC
5.25.25.23344 5.2x25.2x24x24x24x24x2
sttaW-gnitaR
071071071012012081081071071081081081081
spmA-tnerruCnuR
7.07.07.068.068.08.18.145.145.165.365.365.365.3
spmA-tnerruCtratS
9.19.19.13.23.24.34.32.42.47.67.67.67.6
rh/³M-wolFriA
0962096200330283440460743834065405360139013967396739
nim/³tf-wolFriA
3851385124918422083207720852486273730845084591559155
gk-thgieW
1919011011031031051051091002002012012
SEGNAR'C'&'B'
-daoLlacirtcelElatoT
sttaW
00900900210021571157110571002200420042004200530053
dettiFsnaFforebmuN
FFO1FFO1FFO1FFO1FFO1FFO1FFO2FFO2FFO2FFO2FFO2FFO3FFO3
epyTnaF
072-072NIROT072-072NIROT072-072NIROT072-072NIROT072-072NIROT072-072NIROT142-142NIROT142-142NIROT072-072NIROT072-072NIROT072-072NIROT072-072NIROT072-072NIROT
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
EVIRDTCERIDEVIRDTCERID
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
TCERID
EVIRD
sliateDrotoM
sttaWeziS
055x1055x1055x1055x1055x1055x1055x2055x2055x2055x2055x2055x3055x3
DEEPSTESLAMRON
WOLWOLMUIDEMMUIDEMMUIDEMMUIDEMWOLMUIDEMMUIDEMMUIDEMMUIDEMMUIDEMMUIDEM
-tnerruCnuRlamroN
spmA
9.39.32.52.51.51.55.74.93.013.013.015151
-tnerruCtratSlamroN
spmA
8.48.44.64.6663.96.118.21277.21277.216.816.81
deepShgiHtasmumixaM
spmA-tnerruCnuR
1.61.69.69.61.51.54.114.117.317.317.319.719.71
spmA-tnerruCtratS
88 6.86.877 6.316.311.711.711.711.221.22
tuohtiwdesuebottoN
tabmoCotecnerefer
rh/³M-wolFriA
0052006200130023052306230844007500260076008600490049
nim/³tf-wolFriA
1741035152813881319191917362553394633493200433553355
gkthgieW-egnaR'B'
111111031031051051071081022072072672672
gkthgieW-egnaR'C'
131131051051071071591502542003003603603
EGNAR'D'
deriuqeR
rh/³mwolFriAmuminiM
0052006200130023052306233834065400260086008667396739
nim/³tf
1741035152813881319191910852486294632004200491559155
taehssorcassolerusserP
riaderiuqertaregnahcxe
wolf
rabm
34.034.034.034.034.034.034.034.034.034.034.034.034.0
gkthgieW-egnaR'D'
28282999401411421431451081081002022
eziSnoitcennoCsaG
egnaRnoitingIlaunaM
½RA/NA/NA/NA/N
egnaRnoitingIcitamotuA
½R
Page 14
UNIT HEATER
Table 2.2 Technical Data CUHA, CUHB, CUHC and CUHD
Manual Ignition Range
Appliance Category II
2H3+
Propane Gas Inlet pressure 37 mbar (25 - 45)
Natural gas inlet pressure 20 mbar (17 - 25) Butane gas Inlet pressure 29 mbar (20 - 35)
ONLEDOMNOITINGILAUNAM0608001021041061081002042
Wk-vcssorGtupnItaeH
5.225.92733425955.664798
rh/utB-vcssorGtupnItaeH
07767456001442621617641424771803102898622884252866303
Wk-vcteNtupnItaeH
3.026.623.337.839.642.359.957.662.08
rh/utB-vcteNtupnItaeH
0719698609647311191231958951973181534402294722506372
Wk-tuptuOtaeH.xorppA
87.7113.3232.9279.3380.1416.6445.2564.8513.07
rh/utB-tuptuOtaeHxorppA
846067159733799609511561041330951942971664991898932
srenruBforebmuN
4456789 0121
SAGLARUTAN
ezisrotcejnI
49.x749.x749.x749.x749.x749.x749.x749.x749.x7
kramdna
048048048048048048048048048
rabm-erusserPrenruB
9.5016.017.0121215.218.219.41
GWsni-erusserPrenruB
4.242.43.48.48.40.51.50.6
rh/³M-etaRsaG
41.218.235.301.469.426.543.650.784.8
rh/³tf-etaRsaG
7.573.995.4217.4410.5715.8918.3220.9425.992
EPYTEVLAVSAG
avoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.S
450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0
oNTRAP
134L134L134L134L134L134L134L134L134L
SAGGPL
eziSrotcejnI
A/N45.x745.x745.x745.x745.x745.x745.x745.x7
kramdna
A/N052052052052052052052052
rabm-erusserPtelnIenaporP
A/N7300.737300.737300.737373
GWsnI-erusserPtelnIenaporP
A/N8.4108.418.4108.418.4108.418.418.41
rh/³MetaRsaGenaporP
A/N11.193.126.169.122.205.297.253.3
rh/gketaRsaGenaporP
A/N11.246.270.327.322.457.492.563.6
rabm-erusserPtelnIenatuB
A/N9200.929200.929200.929292
GWsnI-erusserPtelnIenatuB
A/N6.1106.116.1106.116.1106.116.116.11
rh/³MetaRsaGenatuB
A/N48.060.132.194.196.109.121.255.2
rh/gketaRsaGenatuB
A/N51.296.231.387.392.448.493.584.6
EPYTEVLAVSAG
A/NavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.S
A/N450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0450.028.0
)ROTALUGERON()ROTALUGERON()ROTALUGERON()ROTALUGERON()ROTALUGERON()ROTALUGERON()ROTALUGERON()ROTALUGERON(
oNTRAP
134L134L134L134L134L134L134L134L
Page 15
UNIT HEATER
Table 2.3 Technical Data CUHA/A, CUHB/A, CUHC/A and CUHD/A
Automatic Ignition Range
Appliance Category II
2H3+
Propane Gas Inlet pressure 37 mbar (25 - 45)
Natural gas inlet pressure 20 mbar (17 - 25) Butane gas Inlet pressure 29 mbar (20 - 35)
NOITINGICITAMOTUA
ECNEREFERLEDOM
06A/08A/001A/021A/041A/061A/081A/002A/042A/082A003A/043A/083A/
Wk-vcssorGtupnItaeH
5.225.92733425955.664798301011521041
rh/utB-vcssorGtupnItaeH
07767456001442621617641424771803102898622884252866303634153023573005624086774
Wk-vcteNtupnItaeH
3.026.623.337.839.642.359.957.662.088.291.996.2111.621
rh/utB-vcteNtupnItaeH
0719698609647311191231958951973181534402294722506372446613361833772483093034
Wk-tuptuOtaeH.xorppA
87.7113.3232.9279.3380.1416.6445.2564.8513.0773.1809.6857.8906.011
rh/utB-tuptuOtaeH.xorppA
846067159733799609511561041330951942971664991898932436772305692539633763773
srenruBforebmuN
4456789 012141517191
SAGLARUTAN
ezisrotcejnI
49.x749.x749.x749.x749.x749.x749.x749.x749.x749.x749.x749.x749.x7
kramdna
048048048048048048048048048048048048048
rabm-erusserPrenruB
7.56.92.01016.015.015.015.015.015.015.010.114.11
3.28.31.40.42.42.42.42.42.42.42.44.46.4
rh/³M-etaRsaG
41.218.235.301.469.426.543.650.784.818.984.0119.1143.31
rh/³tf-etaRsaG
7.573.995.4217.4410.5715.8918.3220.9425.9926.6432.0736.0241.174
EPYTEVLAVSAG
.T.I.S.T.I.S.T.I.S.T.I.S.T.I.ST.I.ST.I.ST.I.ST.I.ST.I.ST.I.SnosnhoJnosnhoJ
mednaTmednaTmednaTmednaTmednaTavoNavoNavoNavoNavoNavoN
0402MG
1009
0402MG
1009
330.038.0330.038.0330.038.0330.038.0330.038.0711-228-0711-228-0711-228-0711-228-0711-228-0711-228-0
oNTRAP
114L114L114L114L114L124L124L124L124L124L124L950L950L
SAGGPL
eziSrotcejnI
A/Nmm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7mm45.0x7
kramdna
A/N052052052052052052052052052052052052
ENAPORP
rabm-erusserPtelnI
A/N737373737373737373737373
GWsnI-erusserPtelnI
A/N8.418.418.418.418.418.418.418.418.418.418.418.41
rh/³M-etaRenaporP
A/N11.193.126.169.122.205.297.253.388.341.407.472.5
rh/gk-etaRenaporP
A/N11.246.270.327.322.457.492.563.663.768.739.810.01
rh/rtLdiuqiL-etaRenaporP
A/N1.42.50.63.73.83.94.014.214.414.515.716.91
ENATUB
rabm-erusserPtelnI
A/N929292929292929292929292
GWsnI-erusserPtelnI
A/N6.116.116.116.116.116.116.116.116.116.116.116.11
rh/³M-etaRenatuB
A/N48.060.132.194.196.109.121.255.259.251.385.310.4
rh/gk-etaRenatuB
A/N51.296.231.387.392.448.493.584.605.700.801.991.01
rh/rtLdiuqiL-etaRenatuB
A/N47.396.454.506.684.734.893.992.1160.3159.3168.5167.71
EPYTEVLAVSAG
T.I.ST.I.ST.I.ST.I.ST.I.S
A/NmednaTmednaTmednaTmednaTavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SavoN.T.I.SnosnhoJnosnhoJ
020.038.0020.038.0020.038.0020.038.0711-228-0711-228-0711-228-0711-228-0711-228-0711-228-0
0402MG
1009
0402MG
1009
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oN(
)rotalugeR
oNTRAP
314L314L314L314L124L124L124L124L124L124L950L950L
Page 16
UNIT HEATER
2.1 Gas Controls - Automatic Ignition
The heaters may be fitted with one of two types of gas control v al ves dependent upon the model, each giving the same control elements as follows (see Section 4).
2.1.1 Main Gas Burner
The multifunctional main gas val ve contains a gas regulator and two automatic shut off va lves. When set up as defined in Section 4 the valves will have a step opening operation on the main gas to give smooth lighting. Settings of the valves are given in Section 4 and tables in Section 2.
2.1.2 Start Gas Burner
There is one solenoid valve to contr ol the pilot burner gas supply which is designed to operate at inlet pressure and therefore does not need a regulator.
2.2 Gas Controls - Manual Ignition
The multifunctional gas valve contains a main gas regulato r, a safety gas valve controlled by the thermocouple, and a solenoid valve to operate the main gas. The manual control knob and Piezo electric igniter incorporated in this control allow for the safe manual ignition of the pilot and selection for automatic oper ation of the main burner.
2.3 Main Fan
The main air moving fan(s) fitted to these heater s are operated automatically by the fan thermostat within the Honeywell combination fan/limit thermostat. When suitably connected to site wiring (see Section 5) the fan(s) may also be used for distributing unheated air.
2.4 Limit Thermostats
There are two limit thermostats on these heaters to protect them from overheating, should the fan fail for any reason. One is within the Honey well combination thermostat and the second is situated on the side of the heater towards the rear. Note: on models 340 and 380 B & C versions there is an extra secondary limit thermostat protecting the third fan unit.
2.4.1 Honeywell Combination Fan/Limit Thermostat
The combination fan/limit thermostat is a dual function control and safety device (see Fig. 2.7). There are two of these fitted to CUHD versions, the second one on the inlet spigot at the rear of the heater.
Page 17
UNIT HEATER
2.4.2 Second Limit Thermostat
This is a manual reset device - see Figs. 2. 1 to 2.7. Note: On CUHB and CUHC models 340 and 380 there are two of these fitted.
To reset this thermostat:
a) Remove the screw on cover of the thermostat where it protrudes from the cabinet side.
b) Push in the button in the centre of the thermostat. Note: the heat exchanger must be cooled to
allowthis to happen.
c) Replace the cover.
Fan Thermostat
The fan thermostat controls the operation of the main fan during the heater operating cycle. This control also ensures that the main fan continues to run after the burner tur ns of f to dissipate the residual heat from the heat exchanger.
The white button on the fan thermostat should be pulled to its “out” position for normal operation. In the “pushed in” position the fan will run continuously. However, when connected to CD100 type control consoles this feature is catered for b y the fan on position of the control switch.
Limit Thermostat
The limit thermostat operates in overheat conditions caused by insufficient air passing over the heat exchanger. T his is a manual reset de vice and is reset by pressing in the red reset button on the thermostat. Note the heat exchanger must have cooled to below the operating temperature for reset to be possible.
Fig. 2.8 Combination Fan/Limit Thermostat
WARNING: IT IS ESSENTIAL THAT THE BREAK OFF LINK SHOWN IS REMOVED
IN THE EVENT OF THERMOSTAT REPLACEMENT
Page 18
UNIT HEATER
2.5 Thermocouple Interrupter Relay
All manual ignition heater s are fitted with a thermocouple interrupter relay to interface between the limit thermostats and the thermocouple. This r elay is fully encapsulated and if faulty must be replaced with the same type as it is specially produced to operate with burner thermocouples.
For normal operation the limit thermostats provide a constant voltage to the coil connections making the relay permanently energ ised unless the limit thermostats operate or the electrical supply is interrupted. In the event of interruption of the electrical supply to the interrupter relay then the contact opens and the safety valve of the m ultifunctional gas va lve closes. The pilot will then need to be manually relit.
2.6 Automatic Ignition - Burner Control Box
2.6.1 DESCRIPTION OF SATRONIC TFI 812 2B Mod 10 CONTROL BOX
The fully automatic gas burner fitted to all CUHA/A, CUHB/A, CUHC/A and CUHD/A models is controlled by a Satronic TFI 812 2B Mod 10 plug-in control box. This control ensures the safe start and stop sequence and also monitors the safe presence of a flame.
Fig 2.9 Satronic TFI 812 Control Box Sequence
Page 19
UNIT HEATER
2.6.2 Sequence of Events
With the external controls on and calling f or heat, the control box will self check and then begin a start sequence.
Electric Ignition ON
Start Gas Valve Energises
The start gas valve opens and once a flame has been established this remains on until close down. The flame probe is now continuously monitoring for the safe presence of flame.
Electric Ignition Off
Five seconds later the electric ignition turns off, leaving the start gas flame to be proved as stable.
Main Gas Valve Energises
Following a short delay the main gas valves ener gise and the main flame cross lights from the start gas. The control is now in its normal run position.
Close Down
When the external controls are satisfied the control box turns of f all outputs simultaneously and returns to rest position for the beginning of the next sequence.
2.6.3 Fault Conditions
If at any stage the flame fails the control will go to ‘lockout'. The red light will glow and the control will need to be manually reset before any further start attempt can be made.
Minimum flame probe current 1 µA DC. Typical flame probe current 3-5 µA DC
2.7 External Control s
CUH... range heaters may be operated from external controls or consoles supplied by Combat Engineering Ltd. which ar e described in their own instructions book.
The wiring diagrams for the external controls are shown in Section 5.
Page 20
UNIT HEATER
Section 3. HEATER INSTALLATION
3.1 Required Standards
It is important that all gas appliances are installed by competent persons, in accordance with the relevant requir ements of the local laws and regulations. Failure to install gas appliances correctly could lead to prosecution.
THE RELEVANT REGULATIONS ARE:
Gas Safety (Installations and Use) Regulations 1984;
BS 6230 Specification for the Installation of Gas Fired Forced Convection Air Heaters for Commercial and Industrial Space Heating of Rated input Exceeding 60kW;
BS 6891 Insatallation of Low Pressure Pipes up to 28mm (R1) or Institute of Gas Engineers Documents IGE/UP/1 and IGE/UP/2 as appropriate;
BS 5588 Parts 2 and 3 Fire Precautions In the Design and Construction of Buildings;
Building Regulations; The I.E.E Regulations; The Health and Safety at Work etc. Acts; Any Requirements of the Local Authority, Fire Officer and Insurance Company.
The installation will be similar to the one shown in Figure 3.1.
WARNING:
AIR HEATERS SHOULD NOT BE INSTALLED IN CORROSIVE ATMOSPHERES
i.e. NEAR PLATING OR DEGREASING PLANTS OR IN AREAS WHERE THERE IS A
FIRE RISK.
CONSULT LOCAL REGULATIONS FOR FURTHER INFORMATION ON
HAZARDOUS AREAS.
Page 21
UNIT HEATER
3.2 General
All models must be installed with the base level and may be suspended from above or from specially prepared wall brackets of sufficient strength to adequately support the weight of the hea ter as listed in Section 2. Data Tables. Drop r ods should be a minimum of 10 mm diameter mild steel. The four hanging brackets are located on top of the heater, for all models. All heaters may be mounted on a shelf of NON combustible mate rial.
Heaters will normally be installed at between 2.75m and 3.75m above the floor.
Clearances around the heater as indicated in Fig. 3. 1 must be maintained to ensure adequate access for servicing and to ensure that the temperature of combustib le materials does not exceed 65°C.
It is important to ensure that at all times there is adequate air circulation around the heater to supply air for combustion ,ventilation and distribution.
Consideration should also be given when siting a heater to allo w for the proper location of the flue .
It is important that the gas supply pipe and the electrical connections do not support any of the heaters weight
Fig 3.1 Typical Installation
C le ara nc e s fo r ins ta llation a ll mo d e ls
CUHA.... CUHB... CUHC... CUHD...
"A " Re ar o f fan to wa ll 0.6 M 0.6 M Se e B e low Se e B e low
"B " C le a r an c e at si de s 0.8 M 0.8 M 0 .8 M 0.8 M
"C" He ight to base 2.75 to 3.0 M 2.75 to 3.75 M N/A N/A
Clearance in front of heater See Below See Below
"D " T o re m o ve b ur ne r 1.1 M 1.1 M 1.1 M 1.1 M
"E" From combustible mater ial 3.0 M 3.0 M N/A N/A
"F" Clea r a n c e ab o ve h e ate r 0.6 M 0.6 M 0.6 M 0.6 M
CUHC & CUHD inlet and outlet ducts Dime n sion "A" Minimum le ng th o f inle t d uct 2 x large st dimension Minimum le ng th of o utlet duct 1.1 m or 2 x largest dimen sion whichever is gre ater.
Page 22
UNIT HEATER
3.3 Gas Supply
General
The installation must compl y with local laws and re gulations, and the complete installation including the meter where fitted, must be purged and tested for soundness. The gas supply must be via metal pipes and terminate at the heater with a service gas cock and union as in Fig. 3.1 to facilitate servicing.
The gas supply pipes must be sized to supply the correct amount of gas to the heater at the specified inlet pressure under all load conditions. It will generall y be required to use installation pipes of a larger diameter than the hea ter inlet connection. On suspended heaters it is recommended that an approved metal flexible connection is used betwe e n the service cock and the heater.
Note: Due to the design of flexible connectors it is usually needed to use at least one pipe size larger than the supply gas pipe to reduce the pressure loss through the connector.
Natural Gas
The gas meter and service must be checked by the local gas supply undertaking to ensure that it is adequate to deal with the total connected load of the completed installation.
L.P.G.
For L.P.G. applica tions each heater must be provided with g as with the inlet pressure closely controlled to 37 mbar for Propane (G31) or 29 mbar for Butane (G30). T his is best provided by the installation of a suitable re gulator controlling the inlet to each heater to ensure tha t variations in system pressure are not transferred to the individual heaters.
3.4 Flue
Each heater must be fitted with at least one metre of an individual and correctly sized stainless steel flue (see Section 2 Tables) .which is designed to carry the products of combustion outside of the building in accordance with B.S. 6230 or B.S.5440 Part 1 as appropriate.
Suitable flue may be supplied by Combat Engineering Ltd.
A separate draught div erter is not required as the heaters have one b uilt in. No other appliance may be connected to the flue.
Page 23
UNIT HEATER
Models 340 and 380 only
The models 340 and 380 heaters are provided with two outlet spigots on top of the heater and a flue assembly as shown in Fig 3.2 to combine these two flue outlets into a single vertical flue for the appliance.
The combination piece is supplied in three pieces for ease of transportation and must be assembled on site.
The same assembly is used for both Model 340 and 380 units.
T o assemble the flue combination piece on site the two bends provided must be secured to the branch arms of the centre section as shown in Fig 3.2 using 'Monel' blind rivets or sheradised PK screws. T o do this offer the female end of each bend in turn to the branch arm and secure to the tw o components together ensuring that the dimension "F" shown on Fig 3.2 is correct. Also ensure that when the assembly is standing on a flat surface the central flue section is exactly vertical.
The assembled unit is then fitted to the heater. Ensure that the combination flue is sealed into the two heater spigots using heat resistant rope and fire cement.
The remainder of the vertical flue is then installed from the spigot at the top of the combination assembly in accordance with the instructions for all other models.
All Models
The flue must be terminated at least one metre higher than the section of the roof it intersects (see Fig
3.1). Furthermore if the point of intersection with the roof is within 2.5m of a nearby structure the terminal must be at least 1m above that structure.
It is important that flues are designed to pre vent the adv erse ef fects of down draughts which cause the products of combustion to spill from the draught diverter and it is essential that the spilla ge test in Section 4.6 is carried out. If spillage is occurring then it is recommended that the flue is terminated at least one metre above the highest point of the roof or any close obstruction.
If the flue extends more than 2 M above the roof it should be adequately supported by guy wires (see Fig. 3.1).
The top of flues with a diameter of 200mm or less should be fitted with an approved ter minal and flues of larger diameter should be fitted with a "Rain Cap". 90º bends and horizontal pipe must not be used in flues. As a guide, if 135º bends are used to offset the flue, then at least one metre of vertical flue must be added to the minimum height to overcome the resistance of each 0.33 m of none vertical flue or each two 135º bends.
Flues should be assembled with their sockets facing upwards inside of the building up to the rain collar, and with their sockets facing downwards outside of the building above the rain collar. T he sections should be secured together using "Monel" blind rivets or sheradized P.K. screws and be supported so that the heater does not carry the weight of the flue.
Page 24
UNIT HEATER
Fig 3.2 Flue assembly of models 340 and 380 only
3.5 Air Supply
It is important to ensure that there is adequate air supply at all times for both combustion and heating requirements. Particular attention must be paid to this point when the heater is installed in a separate room. Ventilation should prevent the Plant r oom temperature exceeding 32°C and any negative air pressure within the room containing the heate r.
Any plant room containing air heaters will require permanent air v ents direct to outside air in compliance with BS 6230.
Most traditional building constructions will provide air changes of at least 0.5/h without the need for ventilation openings. In the case of a building having an air change rate less than 0.5/h, low level ventilation will be necessary in accordance with B.S.6230.
If the flue passes through a wall or ceiling of combustible mate rial it must be enclosed by a sleeve of noncombustible material and be separa ted from the sleeve by at least a 25 mm air ga p. The temperature of any combustible ma terial near the flue or heater must not exceed 65°C when the heater is in oper ation.
The flue must be at least 50 mm from any other comb ustible material.
The joints between the flue and the roof or wall must be made good to prevent water ingress.
The joint between the flue and the female spigot of the heater must be sealed using a heat resistant rope and fire cement.
Dimension E = 405
Dimension F = 372
Page 25
UNIT HEATER
For buildings with a design air chang e rate 0.5/h or greater and where the v olume of the heated space is greater than 4.7 m
3
per kilowatt of total rated heat input, as appropriate, additional high and low le vel
ventilation will not be required.
Where natural ventilation is used for compartment/plant r ooms, suitable permanent openings at low and high level, communicating directly with the outside air, must be provided.
Where mechanical ventilation is used, it must be by mechanical inlet and with either natural or mechanical extraction. Systems of ventilation employing mechanical extraction and natural air inlet must not be used.
Automatic means, such as interlocks, must be provided for installations where equipment failures can lead to hazardous situations developing.
3.6 Building Ventilation
Air must be taken from an outside point w h ere it is not likely to be contaminated, for example with smells, road vehicle exhausts, dry cleaners exhausts, solvents etc.
The minimum quantity of outside air required for ventilation must be a t least that required for personnel within the building.
Where the heaters are located in the heated space the air supply requirement is not necessarily the sum of the individual requirements for combustion, v entilation and dilution air, and fresh air , but the gre ater individual requirement.
Where there are any open flued appliances in the room and where outside air is supplied mechanically and there is mechanical extraction, the design extr act rate must be 5% to 10% less than the design inlet rate so that the room will be at a higher pressure than outside air.
3.7 Distribution Ductwork CUHC and CUHD Heaters
CUHD range heaters are supplied with inlet and outlet duct spigots for mounting the heater into a customer designed duct system .
CUHB range heaters may be supplied to special request with the outlet flanged for connecting to customer designed duct systems.
CUHC range heaters are as CUHB range but with the fans enclosed so that the heater may be connected to inlet ducting.
It is important when ducted systems are required that only the flanges made and fitted at the factory are used at the heater to ensure that the integrity of combustion zone and draught diverter is not impaired. Also it isimportant that the lower front and rear panels remain accessible for burner routine maintenance and repairs. The burner may only be removed from the front lower panel and the rear lower panel needs to be removed to do this.
Provision should be made so that the complete heater may be removed from the duct system.
Page 26
UNIT HEATER
It is recommended that f lexible duct connectors are used to reduce duct born noises.
The dimensions of the connecting ducts must be maintained to those of the heater spigot for at least twice the major duct dimensions. T his should ensure that adequate air flow will pass ov er the whole of the heat exchanger cross sectional area. Also there must be a duct length of at least 1.2m in front of the heater before any downward vertical turn in the ducting to ensure that the burner may be withdrawn from the front of the heate r.
All joints between the heater and the ductwork should be made as air tight as possible.
When installing a CUHB or CUHC heaters onto ducting it is possible for the duct installation to change the natural convected air flow through the heater before the fan is turned on. Under these condition it is sound practice to use an electrical design (such as a 60 second time delay relay) to force the fan to run and not rely on the fan thermostat to turn it on (see suggested scheme in Section 5). Any such de vice must be in parallel with the fan thermostat so that the fan run-on operation will still take place. CUHD heaters are fitted with tw o combination thermostats, at the front and in the rear inlet spigot to cater for this effect.
Contact Combat Engineering Limited Design Department for advice regarding duct resistance and design.
3.7.1 CUHD Heaters
For CUHD heaters it is essential that the airflow in the duct system is at least that specified in the Dat a Sheets in Section 2 and in the correct direction across the heat e xchanger as indicated by the ar row on the heater. Higher air flows are acceptable but it should be remembered that as the air flow rises the temperature rise across the heat exchanger will fall. It is recommended that the fan is positioned to blow the air through the heat exchanger.
It is important that the duct is designed as described in 3.7 a bove to ensure that there is a homogenous air flow across the whole of the heat exchanger . F ailure to provide a suita ble air flo w properly distributed across the heat exchanger will cause heat exchanger failures.
The fan motor or its control should contain a method of overload protection and be supplied via a local electrical isolator if it is installed remote from the heater. Where such a local isolator is installed it should be positioned and labelled to prevent inadvertent operation
3.8 Electrical Supply
A constant 230 volt 50 Hz single phase supply is required for all heater models connected to terminals L, N & Earth. It is important that the "L & N " polarity is correct, particularly for automatic ignition heaters as incorrect polarity will prevent the burner control box from operating correctly. It is also important on these heate rs that the voltage between N and Earth does not exceed 15v.
All heaters and controls must be correctly earthed.
All external wiring must comply with the relevant IEE regulations and be carried out by a qualified electrician.
Page 27
UNIT HEATER
3.9 Remote Controls
Burner Controls
The heaters are designed to be operated by controls installed remote from the heater. Any controls intended to operate the burner must be voltage free contacts connected between terminals 2 & 3 of the main terminal block on the side of the heater.
Fan Controls
The fan is designed to operate automatically providing there is a constant 230v supply to the main terminals. However, a switch wir ed between terminals L & 1 in the terminal block at the side of the heater will provide for summer running of the fan/s. It is acceptable for the fan to operate continuously from an external control, with the burner c ycling on and off, providing that the fan run-on at close down is not impared.
3.9.1 Siting of Combat Control Consoles or Room Thermostats
The Combat control consoles or room thermostats should be mounted on a wall or column at a height of approximately 1.5 metres from the floor of the building being heated. It is important for both comfort and fuel economy that the control or thermostat is sited where it will monitor an average room temperature i.e. keep clear of cold draughts from door s, windows etc., similarly it should be kept out of the direct path of warm air from the heater. Areas of little air movement e.g. corners, should also be avoided.
Where CD100 type controls are fitted these also need to have the same constant 230v 50Hz.
An isolator with a contact separation of at least 3 mm on all poles should be installed adjacent to, but not fixed to the heater to disconnect all supplies to the heater and where necessary to isolate any remote control.
The final connection to the heater should be made in metal sleeved flexible cable or flexible conduit to the main terminal block on the side of the heater using 1 sq. mm cable on all models.
A fuse size of 5 Amp must be used for all models CUHA and CUHA/A up to and including model 240, and 10 Amp for all remaining CUHA , CUHA/A ,CUHB, CUHC,CUHB/A and CUHC/A models except for models CUHB… CUHC … 340 and 380 where the fuse size should be 20 Amp.
CUHD and CUHD/A models must have the external fan, or its control connected to Terminal 1 so that the fan run on function at close down operates correctly.
Page 28
UNIT HEATER
3.9.2 Remote Room Thermostat
A remote room thermostat may be connected to terminals 2 & 3 in the main terminal block on the side of the heater (see Section 5).
3.9.3 Remote Frost Thermosatat
Where a remote frost thermostat is required to override the operation of a time switch during its "off" periods, this may be connected to terminals 2 and 3 in the main terminal block on the side of the heater. It should be sited within the heated space adjacent to the most vulnerable equipment that requires protection.
Page 29
UNIT HEATER
Section 4. COMMISSIONING THE HEA TER - ALL TYPES
Before starting to commission a heater read this section through and fully understand its contents. Only competent engineers should carry out the work.
4.1 Pre Commission Checks
Checks before lighting the unit heater
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply that they are being connected to.
4.1.1 Electrical Checks
A preliminary electrical check should be carried out by a qualified engineer, after completion of the installation and before commissioning the heater as follows:-
Check that all site wiring is connected in accordance with the appropriate wiring diagram of Section 5.
Check the correct fuse size is fitted; 5 Amp must be used for all models CUHA and CUHA/A, and 10 Amp for CUHB, CUHC, CUHB/A and CUHC/A models, except for models 340 and 380 where th e fuse size should be 20 Amp. This must be connected in the live conductor (see Polarity Test below).
Earth Continuity Test
The appliance earthing must be tested using a suitable method according to local regulations. The resistance of the earth circuit from the heater to the earth connection must be 0.1 ohm or less.
Polarity Test
Connect one lead of a suitable voltmeter to earth and connect the other lead to the live supply terminal at the heater.
Turn on power to heater. A reading of approximately 230 volts AC 50Hz should be found.
The same result should be obtained by connecting the test leads from live to neutral.
Connecting the voltmeter between Neutral ‘N’ and Earth should give a reading of 0 v olts. If these tests do not conform to the above there is a fault whi ch must be rectified before progressing further with the commission. An electrician should be consulted to carry out this work.
Note: For Automa tic Ignition models the burner control box will not operate with a neutral to earth voltage above 15v and may be unreliable at any reading other than 0.
Page 30
UNIT HEATER
4.2 Gas Supply
The whole of the gas installation including the meter should be inspected, tested for soundness and purged in accordance with local regulations.
It will be necessary to ensure that the air is fully purged from the heater inlet pipe up to the main gas val ve inlet test nipple before the start gas burner will ignite.
4.3 Mechanical checks
1. Check that the fan(s) are free to run and delivery louvres are turned to give required air deflection.
2. Check that the flue is installed in accordance with these instructions and local regulations.
3. Check that the Settings of the Combination Fan/Limit thermostat are correct - see below . Note: The limit thermostat is preset and sealed a t the works and will need no adjustment.
To set the combination fan/limit thermostat first remove the co ver by releasing the co ver fixing screw and pulling off the cover. The three hands from left to right should be set approximately as follows subject to site conditions:- See Fig. 2.8.
Front combination thermostat (All Models) Rear thermostat on CUHD ... Only
HAND 1 FAN OFF SET TO 38°C SET TO 30ºC HAND 2 FAN ON SET TO 57°C SET TO 55ºC HAND 3 LIMIT SET TO 95°C SET TO 90ºC
Always refit the cover and tighten the cover scr ew after adjustments.
To continue with the Commissioning follow 4.4 f or Automatic Ignition models or 4.5 for Manual Ignition models. Then continue with 4.6 for all appliance types
4.4 Automatic Ignition Unit Heaters
4.4.1 Carry Out a “Dry Run”
To ensure that all the controls are in safe working order it is advisable to operate the fully automatic controls for the first time with no main gas.
To do this unplug the electrical plug from the main gas valves (there are two plugs for Nov a automa tic valves). Now, using the installed external control turn on the burner.
The automatic sequence will now begin as described in Section 2. The electric ignition will be heard and the spark may be observed via the gas inlet port in the rear panel.
The start gas flame will then ignite on the opening of the start gas valve. If the flame does not ignite then the control will go to the “lockout” condition.Wait one minute, then press in the control box reset button, or the remote reset button if fitted and repeat until the start gas flame ignites.
Page 31
UNIT HEATER
Note: At the first firing of the heater it may be necessary to repeat several times whilst purging the remaining air from the gas train.
There is no adjustment for the start gas burner.
Once the start gas flame has ignited it will be monitored by the flame probe and should remain on until the controls turn it off.
Turn off the burner at the external control and refit the electrical plug/s to the main gas val ve.
Inlet Pressure
Step Opening adjustment
Electrical connection
Fig. 4.1 S.I.T. Tandem 0.830.033 Gas Valve (Natural gas)
0.830.020 valve (L.P.G)
Burner Pressure
Regulator adjusting screw under cover. (Note: on L.P.G. heaters this is a throughput adjuster and must be fully open )
Gas Outlet
Page 32
UNIT HEATER
Inlet Pressure "E"
Burner Pressure "A"
Manual control knob
Regulator adjusting screw
Thermocouple interrupter relay connections
Thermocouple connection
Pilot Gas pipe connection
Electrical connection
Gas Outlet
Pilot gas outlet of valve Blanked off
Fig. 4.2 S.I.T. Nova 0.822.177 Automatic Ignition Gas Valve
Fig. 4.3 S.I.T. Nova 0.820.054 Manual Ignition gas Valve
Burner pressure
Inlet Pressure
Regulator (under cover)
Page 33
UNIT HEATER
2
3
1
Dungs MBDLE 405 BO1 Main gas valve
Johnson GM 2031 0240 Main gas valve
4
5
The main gas control valve used on all versions of the models CUHA/A, CUHB/A, CUHC/A and CUHD/A 340 and 380 is the Johnson GM 240 9001 combination gas valve or alternative Dungs MBDLE 405 BO1 (see Fig 4.4). These controls contain two main safety shut off valves and burner pressure regulator.
1. Pressure regulator under swivel cover
2. Slow opening adjustment
3. Throughput adjuster (Always fully open)
4. Inlet flange with inlet pressure test point
5. Outlet flange with outlet pressure test point
Fig 4.4 Main gas valves for Models 340 and 380
Page 34
UNIT HEATER
4.4.2 Commissioning the Gas Valves - Natural Gas
Depending on the model of the heater there will be an S.I.T Tandem valve, an S.I.T Nova va l ve or a Johnson controls gas valve (see Data Table in Section 2 and Figs 4.1 to 4.4).
Connect a manometer to the outlet (burner) pressure test point of the g as val ve after f irst removing its screw cover.
To set the burner pressure remove the regulator cover and, with the burner firing, turn the regula tor adjustment screw to set the required burner pressure as stated in the data tables in Section 2.
Note: If any difficulty is found in obtaining the correct burner pressure then check that there is a sufficient inlet pressure available to the valve, with the bur ner firing.
Under no circumstances should a regulator be set to a pr essure ov er that wher e the pressure is no longer being changed.
If the inlet pressure is too lo w to allow correct burner setting then the problem will be on the installa tion and must be corrected before completing the commission. T he inlet pressure must be 20mbar with the main burner firing.
To set the step opening adjustment, first turn off the burner at the external controls or unplug the electrical connection to the main gas valv e and w ait for one minute for the valve to settle. Turn on the burner again and as the main b urner turns on set the step opening pressure to approximately 2.5 mbar. As the step opening lasts for only a few seconds its setting may need to be checked two or three times to ensure satisfactory starting of the main burner.
Following burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re­check settings. Remove the manometer and refit all covers to the val ve.
Wherever possib le a reading of the gas rate timed through the gas meter should be taken and compared with the nominal rating in the Data Table, Section 2. The burner pressure should be adjusted to give this nominal gas rate.
4.4.3 Commissioning the Gas Valves - L.P .G.
In all cases the gas v alves for L.P.G either have no re gulator or have the regulator put out of action (see Section 10). The heater is therefore set on the inlet pressure to the gas va lve w hich must be maintained at 37 mbar (25 - 45) for G31 (Propane) or 29 mbar (20 - 35) for G30 (Butane).
Note: Although the appliances are tested to operate safely between the minim um and maximum pressures show n, they are designed to give the correct heat input only at th especified inlet pressure.
No further adjustments are necessary.
Page 35
UNIT HEATER
4.5 Manual Ignition Unit Heaters
All CUH manual ignition unit heaters are controlled by an S.I.T No va 0.820.054 multifunctional gas valve (see Fig 4.3).
First remove the electrical plug from the multifunctional gas valve to ensure that main gas cannot be released.
T o ignite the pilot press in the manual control button of the g as valve and turn anticlockwise to the star symbol. Press the button fully in and hold whilst continuously pressing and releasing the Piezo ignition device to create the spark ignition.
Note: IF AT ANY TIME THE PILOT FAILS TO LIGHT OR GOES OUT, EITHER INTENTIONALLY OR UNINTENTIONALLY, WAIT A FULL 3 MINUTES BEFORE ATTEMPTING TO RELIGHT.
Once the pilot flame has been seen to light continue to hold in the control valve b utton for a further 30 seconds, and then release. The pilot flame should now remain on.
Should the pilot flame go out check that the limit thermosta ts have not operated and that there is an electrical supply to the main terminal blo ck. Also ensure that the leads to the thermocouple interrupter relay are connected to their connections on the gas valve (see Fig 4.3). Observe the 3 minute waiting time and retry .
Once the pilot flame has been established it will remain on constantly providing that the gas or electricity supplies are not interrupted and the limit thermostats do not operate.
To Operate the Main Burner
Replace the electrical plug onto the gas valve. Press in slightly and turn the valve control knob a further quarter turn anticlockwise to the "flame" symbol. With the external contr ols in an on position and calling for heat the main burner will now fire
Connect a manometer to the outlet (burner) pressure test point of the gas v a lve after first removing its screw cover (see Fig. 4.3).
To Set the Main Burner - Natural gas
T o set the burner pressure r emove the regulator cov er scre w and with the burner fir ing, turn the regulator adjustment screw to set the required burner pressure as stated in the Data Tables in Section 2.
Note: If any difficulty is found in obtaining the correct burner pressure then check that there is a sufficient inlet pressure available to the valve, with the burner firing.
Under no circumstances should a regulator be set to a pressure over tha t where the pressure is no longer being changed.
If the inlet pressure is too low then the problem will be on the installation and must be corrected before completing the commission. The inlet pressure must be 20mbar with the main burner firing.
Page 36
UNIT HEATER
Wherever possib le a reading of the gas rate timed through the gas meter should be taken and compared with the nominal rating in the Data Table, Section 2. The burner pressure should be adjusted to give this nominal gas rate.
4.5.2 Commissioning the Gas Valves - L.P .G.
In all cases the gas val ves for L.P.G. ha ve the re gulator put out of action. The heater is therefore set on the inlet pressure to the gas valve wh ich must be maintained at 37mbar for G31, (Propane) or 29 mbar for G30 (Butane).
No further adjustments are necessary
4.6 Commissioning Tests - All Heater Types
W ith the main burner opera ting for at least 15 minutes carry out a spillage test on the draught diverter in accordance with BS 5440 Part 1 ensuring that all doors and windows in the area are closed and that any extract f ans are turned ON.
One method is to hold a lighted taper or smoke match just inside of the draught diverter and observe that the smoke or flame is not drawn away from the heater.
Should it be indicated that the products of combustion are continuously entering the b uilding from the draught diverter then correctiv e action MUST be taken before leaving the heater to operate nor mally.
4.7 Combustion Testing - All Heater Types
Although there is no adjustment availa ble to alter the combustion performance of the heater , other than burner pressure, it is advisable to take combustion readings to determine the proper operation of the heater.
T o do this the flue gas is sampled at the test point on the flu e, within 1 metre of the heater and tested for contents of CO2 (carbon dioxide), CO (carbon monoxide) and temperature rise. The values of CO
2
should be between 5.5% and 6.5% . CO should be no more than 0.0015% ( 15 PPM) and the temperature rise of the flue gasses above ambient should be approximately 160°C to 180°C.
Combustion testing must be carried out with all covers etc. fully fitted as designed.
4.8 Pilot Drop-Out Test - Manual Ignition Models
Carry out the Pilot Drop-Out Test as described in Section 6.4 and ensure a positive result.
4.9 Turning Off the Heater - All Heater Types
To turn off the heater operate the external controls to the off position and the main burner will stop. Allow the fans to run on until they are stopped automatically by the fan thermostat. The heater will then be at rest until the controls call for heat once more. For long term closing down for summer etc. then when the fans ha ve stopped automatically, turn off the g as and electrical supplies at the isolator s .
Page 37
UNIT HEATER
WARNING
The electrical isolator should only be used in an emergency and should not be
used for closing down the burner, as this switches off the fan prematurely and may damage
the heat exchanger invalidating the warranty and causing a potential fire hazard.
Operating the electrical isolator on a CUH Manual Ignition heater
will also turn off the pilot burner.
4.10 External Controls
Operate the External Controls as installed which may include time switch, room thermostat and manual switch to ensure that they function correctly. Set the time switch (if fitted) and room thermostat to the users requirements.
See Sections 2 and 9.
4.11 Handing Over
Ensure that all covers are fitted correctly and all test points are properly sealed before leaving the appliance.
When the commission is complete explain to the user the controls of the heater including how to operate the heater and how to turn it of f, using the controls fitted on site. Hand over these instructions to the user.
Ensure that the user is shown and understands the emergen cy instructions in Section 9 of this book.
Page 38
UNIT HEATER
Fig. 5.1 Wiring for CUHA Manual Ignition Range
Section 5. WIRING DIAGRAMS
MANUAL IGNITION
Page 39
UNIT HEATER
Fig 5.2 Wiring for CUHB & CUHC models 60 to 160
MANUAL IGNITION
Page 40
UNIT HEATER
Fig 5.3 Wiring for CUHB & CUHC models 180 to 300
MANUAL IGNITION
Page 41
UNIT HEATER
Fig 5.5 Wiring to CUHD Manual Ignition Range (All models)
MANUAL IGNITION
Page 42
UNIT HEATER
Fig. 5.6 Wiring Diagram for CUHA/A Range of Heaters Models 60 to 240
AUTOMATIC IGNITION
Page 43
UNIT HEATER
Fig. 5.7 Wiring Diagram for CUHA/A Range of Heaters Models 280 to 380
AUTOMATIC IGNITION
Page 44
UNIT HEATER
Fig 5.8 Wiring For CUHB/A & CUHC/A Models 60 to 160
AUTOMATIC IGNITION
Page 45
UNIT HEATER
Fig 5.9 Wiring For CUHB/A & CUHC/A Models 180 to 300
AUTOMATIC IGNITION
Page 46
UNIT HEATER
Fig 5.10 Wiring For CUHB/A & CUHC/A Models 340 to 380
AUTOMATIC IGNITION
Page 47
UNIT HEATER
Fig 5.12 Alternative wiring of external motor for CUHD Range - All Models
Fig 5.11 Wiring of CUHD/A Range - Automatic Ignition - All Models
AUTOMATIC IGNITION
Page 48
UNIT HEATER
Fig 5.13 Individual controls for all CUH Range heaters
Page 49
UNIT HEATER
Section 6. SERVICING INSTRUCTIONS
After commissioning, the heater will require maintenance to be carried out at least once per year to ensure that peak performance and safety are maintained. If the heater is used in a dirty or dusty area, then more frequent maintenance may be necessary.
WARNING
Only competent and Qualified Engineering Personnel should carry out servicing and fault
finding on this equipment.
Before any maintenance is carried out, ensure that both gas and electrical supplies are turned of f as the fan can start automatically at an y time.
NOTE 1: After any maintenance wor k always test fire the heater in the prescr ibed manner to make sure all safety systems are in working order before leaving the heater to run normally.
NOTE 2: Check all pipe joints for gas soundness using an approved method. A n y leaks found must be repaired before leaving the heater to fire normally.
NOTE 3: After routine maintenance , the commissioning procedure Section 4, should be carried out to ensure that peak efficiency and safety is maintained.
Minor faults may be traced by use of the fault finding charts, Section 8.
6.1 Burner Maintenance
Burner maintenance is essentially the same for manual and automatic ignition heate rs. Where there is a significant difference the two types are referred to separately:
1. Remove the Burner Assembly as in 7.1.
2. Check condition of the ignition burner, ignition electrode and flame probe (for automa tic), or thermocouple (manual) as appropriate. Clean off any deposits which may have been formed on the thermocouple or flame probe. Replace as necessary.
3. Check that the ignition gas pipe is clear of any deposits and that all joints are sound (See 7.3)
4. Check condition of ignition electrode and flame probe for erosion and damage to the ceramic insulation (see 7.3). Replace as necessary.
5. Clean any deposits from the main burner paying particular attention to fluf f etc. which may have formed in the injectors or venturi of the burner (See 7.2).
6. Check the condition of the thermal insulation lagging at the bottom of the burner compartment and replace if necessary . Pay particular attention to the condition of the foil face of this insulation which must be complete and unbroken.
Page 50
UNIT HEATER
6.2 Fan/Motor Assembly all Models
The main fan requires very little maintenance as the bearings ar e sealed for life and need no lubrica tion. If the fan blades need cleaning re m ove the fan guards and use a small brush or duster to clean the fan blades from each side of the fan(s).
6.2.1 For CUHB & CUHC Centrifugal Fan Models
CUHB and CUHC models are fitted with thermally protected three speed direct dive fans. The data table indicates the normal number of fans and their standard running speed for each model .They require very little servicing other than cleaning of the fan blades.
It is essential th a t the fans are not operated at higher speeds than the original setting on the heater without prior consultation with Combat Engineering Ltd. Such action may cause the fan motor s to be over loaded. Overloading the motor will cause the built in thermal overload protection device to operate.
Where two or three fans are fitted they must be all operating at the same speed and they will be switched using a fan contactor built into the heater see the wiring diagrams.
The "HIGH" speed option is available to g ive the normal required air f low against higher static pressures and is not intended to be operated free blowing or against low resistance . Use of the fans under these conditions may cause the fan thermal o verload to operate and the f an thermostat to cyc le due to a lower temperature rise.
The three speed winding connections are:
Low speed: White N, Red Live The other two windings are "parked" separately in spare terminals
Medium speed: White N, Blue liv e. The other tw o windings are "parked" separately in spare terminals
High speed: White N, Black liv e. The other two windings are "parked" se parately in spare
terminals
For CUHC models the fans may be accessed via the re movable panels in the top, bottom and sides of the inlet spigot compartment as required.
6.3 Heat Exchanger
The heat exchanger should remain clean unless some problem has de veloped with comb ustion. Howev er, an inspection of the condition of the heat exchanger is w ell worth while especially looking for signs of overheating at the lower edges with may indicate burner over firing or persistently lo w air flows. An y deposits in the heat exchanger may be removed with a small flue brush and vacuum cleaner from the burner compartment after first removing the burner tray.
Page 51
UNIT HEATER
Manual Ignition
There is no regular maintenance required on these devices. To change gas control valves, see Section 7.4.
Pilot Drop Out Test - Manual Ignition Models
During the routine service a check must be made that the flame failure device operates correctly To do this:-
I) With the pilot flame alight and running for at least 10 minutes, turn off the gas isolating
val ve and watch the pilot flame.
II) Measure the time taken from the pilot flame going out until the gas safety valve operates
(can be felt and heard as a dull click). This must be less than 60 seconds.
If the above test fails, replace the thermocouple (see Section 8) with one of the correct type.
Repeat the test to confirm a positive result.
It is not recommended for gas control valves to be repaired or disassembled on site. Any faulty gas valve should be changed for the correct replacement.
6.4 Gas Control Valves
Automatic Ignition
There is no regular maintenance required on these devices. To change gas control valves, see Section 7.4.
Page 52
UNIT HEATER
Section 7. REMOVAL AND REPLACEMENT OF PARTS
See warnings and notes at the start of Section 6 before removing or replacing parts.
7.1 Burner Tray
The burner tray may be remov ed from the heater only from the front.
It may be rem oved complete with the gas valve train assembly or on its own leaving the gas valves in the heater.
These instructions indicate how to remove the burner tray and valves separately.
7.1.1
Remove the front lower cabinet panel. Remove the rear lower cabinet panel.
7.1.2
Dependant on the heater size and if it is manual or automatic ignition the main val ve will be connected to the main burner inlet manifold using a navy union or the angled flange outlet of the valve. The pilot gas supply will be in 4mm OD steel pipe and be connected to the pilot gas valve or pilot port of the main gas val ve using a suitable compression fitting.
Undo the pilot supply compression fitting
Automatic Ignition
Unplug the flame probe lead from its socket and the HT lead from the spark generator.
Manual ignition
Unscrew the thermocouple from its connection with the gas valve and pull off the leads to the thermocouple interrupter relay from their receptacles. Disconnect the main burner gas supply pipe at the union or gas valve flange
7.1.3
Unscrew the two scre ws securing the b urner tray at the fr ont, (Fig .7. 1 ) and pull out the tray forward s from the front of the heate r.
7.1.4
To replace the tray reverse the a bove steps ensuring that the tray is firmly in its correct place with the two fixing screws tight and that the gas pipe work is sound.
Page 53
UNIT HEATER
7.2.2
To remove the burner bars first remove the screws securing the retaining bar at the front end of the burner and pull off the retaining bar (see Fig. 7.1).
Remove the screws securing the burner rear baffle and pull it upwards to remove.
7.2.3
The individual bars may now be removed by pulling up the front end clear of the mounting tray and then pulling the burner forward off its injector.
NOTE: The burners are all the same except the first burner on left from the front (see Fig 7.1). This burner has no cross lighting bracket and has two mounting tongues to prevent misplacement. It will be found easier to remove burners starting from the opposite end of the burner tray.
7.2.4
If the injectors are being removed they ar e now accessible, ea ch one is screwed into its port of the manifold with a soft metal sealing washer and may be remov ed using a 13mm spanner.
7.2.5
On replacing injectors ensure that they seat onto the soft metal washer to effect a tight seal and that the correct one is fitted for gas being burned. See marking stamped onto the injector and ta bles in Section
2. It is recommended that new sealing washers ar e used when replacing injectors to ensure a gas tight
seal.
7.2.6
When re fitting the burner bars start by fitting the No 1 burner (without cross lighting bracket) and ensure that the burner is pushed fully home against the injector and then pushed down to the bottom of its mounting slots.
Repeat for each burner in turn until all the burners are back in place.
Replace the rear burner baffle ensuring that it engages into the slot in the bottom of each burner tube inlet bracket.
Finally replace the retaining bar and its fixing screws.
7.2 Main Burner Bars/injectors
7.2.1
Remove the burner tray as in 7.1.
Page 54
UNIT HEATER
Fig 7.1 Burner Tray Assembly
Fig 7.2 Optional versions of pilot burner
7.3 Ignition Burner Assembly
CAUTION: Do not kink or tightly bend the pilot gas pipe or thermocouple (where fitted).
There are two options to the pilot burners used for the complete range of heaters. These are sho wn belo w in Fig 7.2. Howe v er a different pilot injector is used f or natural g as and L.P.G. The pilot burner for use on natural gas is fitted with an injector marked 34. The pilot burner for use on L.P.G. is fitted with an injector marked 19. The difference between manual and automatic ignition is:
Manual Ignition heaters are controlled with a thermocouple . Automatic ignition are controlled with a flame probe.
Page 55
UNIT HEATER
7.3.1 Removal of pilot burner
i) Remove the rear lower panel of the heater. ii) Unscrew the pilot gas pipe at its compression fitting with the pilot gas valve or main gas v alve as
appropriate.
iii) Unplug the H.T cable from the Piezo electric igniter or spark generator, as appropriate. iv) Either unplug the flame probe from its jack socket or unscrew the thermocouple from the gas
valve.
v) Using a 10mm spanner undo the two set scre ws securing the pilot bracket assembly to the main
burner manifold.
The assembly will now come free by pushing it slightly forward and then allo wing it to drop so that it will pull clear of the main burner .
7.3.2
Using the appropriate spanners undo the thermocouple /flame probe, ignition electrode and gas pipe from the rear of the ignition burner.
7.3.3
To replace directly rever se the above.
All manual ignition models use the S.I.T Nova multifunctional valv e for main gas and pilot g as control. Electrical connection is by a plug on a flying lead. There are also ¼" receptacles for the connection of the thermocouple interrupter.
NOTE: It is important that the correct injector is used and that when assembling the gas pipe to the pilot burner that the injector is fitted onto the special compr ession nut so that as the gas pipe is withdrawn the injector is drawn out of the burner.Failure to fit the injector correctly will cause gas leaks and permanent damage to the injector.
The Ignition electrode has a small tag connector for connecting the H.T/lead and ALWA YS fits into the centre hole of the pilot burner.
The thermocouple or flame probe (with permanently connected P.T . F.E. insulated wire) is fitted in the end hole of the pilot burner
7.4 Gas Control Valves
7.4.1
The gas control valves of all heater types are accessible from the rear of the heater without further disassembly or may be withdrawn as part of the b urner assembly as convenient. These instructions assume that the valves are removed with the burner tray remaining in place. Section 2 tables give details of the gas valve specified for use on the various options available.
IT IS MOST IMPORTANT THAT O NLY THE CORRECT GAS VALVES SPECIFIED FOR EACH MODEL TYPE ARE USED WHEN REPLACING THESE CONTROLS.
Page 56
UNIT HEATER
7.4.2 Removal of Gas Valves - Automatic Ignition
There are two mounting systems used for the automatic ignition gas valves. i) S.I.T Tandem valves
These are connected to the main gas manifold using a navy union. Electrical connection is by a plug on the end of a flying lead.
ii) S .I.T Nova automatic gas valves
These are connected to the main gas manifold using the valve manufacturers angled outlet flange. Electrical connection is by two pre-wired plugs on a flying lead.
The pilot gas valves are supported on the ¼ BSP inlet pipe and the outlet is a 4mm OD compression fitting. Electrical connection is by a small three pin plug.
To remove gas valves
i) Disconnect the pilot gas pipe at the compression fitting at the pilot gas valve. ii) Disconnect the union between the gas supply pipe and the gas valve. iii) Disconnect the electrical plugs to all gas valves. iv) Disconnect the navy union or valve outlet flange between the gas va l ve and the burner.
This allows the gas valves to be removed from the heater
Disassemble gas train for automatic ignition
To separate the start and main gas v alves hold the main gas v alve f irmly in a vice and unscrew the pilot line from the main gas line at the ¼ m & f elbow by ¼ turn. This will allow the pilot or the main gas val ve to be unscrewed from the main gas pipe.
Refitting is a direct re versal of the above.
It is important when refitting gas valves that only a minimum amount of none hardening gas seal is used on the pipe threads so that excess sealant is not carried into the valve mechanisms. It is also important that the val ves are assembled with the marked gas flo w in the correct direction, and that the "O" ring seals are fitted to the inlet and outlet flanges where appropriate. See Section 10 for converting between natural gas and L.P.G.
7.4.3 Removal of gas Valves - Manual Ignition.
All manual ignition models use the S.I.T Nova multifunctional v alve for main g as and pilot gas control. Electrical connection is by a plug on flying lead. There are also ¼" receptacles for the connection of the thermocouple interrupter relay.
To remove gas valves
i) Disconnect the pilot gas pipe at the compression fitting at gas valve pilot port. ii) Disconnect the union between the gas supply pipe and the gas valve. iii) Disconnect the electrical plugs to all gas valves. iv) Unscrew the thermocouple from the valve and pull off the leads to the interrupter relay. v) Disconnect the outlet flange between the gas valve and the burner.
This allows the gas valves to be removed from the heater.
Page 57
UNIT HEATER
7.4.4 Thermocouple
The thermocouple is fitted into the pilot burner body by pushing fully home against the shoulder and then tightening the retaining nut to hand tight plus ¼ turn with a spanner. The thermocouple must be bent gently into its original path being careful not to kink or crack it. The valve end of the thermocouple is connected using the screw nut. This connection is an electrical one and must be clean and without the use of compounds. The Connecting nut must be screwed hand tight plus no more than ¼ turn with a spanner to create a sound electrical connection.
7.4.5 Thermocouple Interrupter Relay
All manual ignition heaters are fitted with a thermocouple interrupter relay to interface betw een the limit thermostats and the thermocouple. This relay is fully encapsula ted and if faulty m ust be replaced with the same type, as it specially produced to operate with burner thermocouples.
It is important that the 230v supply to the relay is provided from the specified terminals in the terminal block, and that following replacement the operation of the limit thermostats is checked to ensure that on operation the pilot is extinguished.
NO ATTEMPT SHOULD BE MADE T O OPERATE THE HEATER WITHOUT THIS RELAY . FAILURE TO COMPLY WILL CAUSE A SEVERE FIRE HAZARD
7.5 CUHA Axial Fan/Guard/Motor Assembly
The Axial fan unit for the CUHA range of heaters is supplied completely assembled and balanced. These components are not replaceable separately
7.5.1 To Remove the Fan Assembly:
Disconnect the electrical cables from the fan terminal box at the rear or side of the heater, carefully noting the colour code of the wires to the fan.
Remove the four screws securing the fan guard to the heater carefully retaining the rubber washers.
7.5.2 To Replace the Fan Assembly:
T o replace the f an assembly re ver se the above procedure ensuring that the rubber washers are fitted to the guard mountings to reduce vibration.
Check that the fan blades are free to rotate without catching before turning on the power to the fan.
It is also most important that the colour code of the fan wires is strictly observed to ensure correct operation.
It is sound practice to replace the fan capacitor when changing a fan.
Page 58
UNIT HEATER
7.6 CUHB & CUHC Centrifugal Fan/Guard/Motor Assembly
The direct drive fan/s for the CUHB & CUHC range is supplied as a complete assembly and therefore does not need to be disassembled. Each fan is fitted to the rear of the cabinet secured with four fixing screws and washers.
7.6.1 To Remove the Fan(s)
Disconnect the electrical connections from the terminal block at the rear of the heater making a careful note of the positions of the connecting wires and identifying the current speed setting.
Remove the fan / motor assembly by removing the fixing screws whilst supporting the weight of the fan (approx. 19 kg) and making a careful note of the fan orientation. For the CUHC versions fitted with an inlet spigot assembly the fan/s may be accessed through the removable covers on the sides, top and bottom of the spigot, as required.
7.6.2 To Refit the Fan(s)
To reassemble reverse the above ensuring that the correct motor connections are used as identified when disconnecting and that new rubber seal is used between the fan flange and the heater rear panel. It is important that the fan is fitted to the rear panel in its correct orientation with the curved surface upwards.
It is most important that the colour code of the fan wires is strictly obser ved to ensure correct operation, and being careful to use the correct neutral connection. The Blue Neutr al is for the main fan; the Blue/ White neutral is for the burner controls and must not car ry the load of the main fan .This is because the burner electr ical supply is protected from mains bourne interference by the use of a special conditioning filter which is not ca pable of carrying the full load of the main fan. Check that the fan blades are free to rotate without catching before turning on the power to the fan.
The three speed winding connections are:
Low speed: White N, Red Li ve The other two windings are "par ked" separately in spare ter minals Medium speed: White N, Blue live. The other two windings are "parked"separately in spare terminals High speed: White N, Black li ve. The other two windings are "parked" separately in spar e terminals
7.7 Combination Fan/Limit Thermostat
7.7.1
To gain access to this thermostat, remove the cover retaining screw and pull of the cover.
7.7.2
Disconnect the electrical connections by pushing in with a small screwdri ver and pulling out the wires. (see Fig. 2.8).
The earth wire is held under a screw connection.
Page 59
UNIT HEATER
7.8 Second Limit Thermostat
7.8.1
Remove the mounting nut securing the thermostat to the heater side.
7.8.2
Remove the heater low er rear panel to gain access to the body of the thermostat and its electrical connections.
Disconnect the push-on electrical connections from the thermostat.
7.8.3
Remove the fan assembly from the heater rear (see 7.5 or 7.6). Note: On models 340 and 380 B & C versions the secondary limit thermostats are mounted on the fan mounting panel. The relevant fan will need to be rem oved to gain access to these thermostats.
7.8.4
Carefully pull the capillary sensing probe through its access hole in the side of the heater heat e xchanger being careful not to damage the capillary tube.
7.7.3
Unscrew two fixing screws and withdraw the unit from the cabinet feeding the cables through the plastic conduit connection.
7.7.4
To refit, reverse the above procedur e reusing the plastic conduit connection and reset as in the commissioning instructions, Section 4.
Note: the new thermostat should have the limit setting sealed by a suitable method to prevent unauthorised adjustment.
WARNING
When replacing a combination thermostat ensure that the link is removed.
(See Fig. 2.7). Permanent damage will be caused by leaving this link in.
Page 60
UNIT HEATER
7.8.5
To refit a thermostat, first carefully straighten the capillary tube, it is important not to kink or crack it. Proceed to replace by rever sing the above pr ocedure ensuring that the sensing bulb at the end of the
capillary tube is positioned against the base of the heat exchanger to w ards the centr e of the fan outlet. (Where there are two fans the position of the sensing bulb should be towards the centre of the fan on the opposite side of the heater from the controls).
Secure the capillary tube re -using the metal bra cket from the original one.
Page 61
UNIT HEATER
Section 8. FAULT FINDING
Following the replacement of parts carry out the Commissioning procedure as in Section 4.
Should these procedures not resolve any problem, please contact Combat Engineering Ltd.
NO NO
Is " Lockout " Check external co ntrols
St art warni n g light are on & supply is sound
Assuming gas & el ectrical ON ?
supp l ies are on
YES
T est bur ner as
in 8.2
NO NO
Does the fan run? Press i n white button Use 8.5 to t est fa n
on com bination
thermostat.
Fan runs now?
YES
S ee sect ion 4.3 to Rep lace com b inat ion
che ck fan s t at ther m o stat
setti ngs
YES
YES NO NO
Do es b urn er sto p after Has burner Check for correct Ch eck operation &
Runnin g for several "Locked out" ? operation of fan setting of minutes ? (wi th the combi nation stat.
c o ntrols still on) YES YES Re p a ir or repla c e
as necessary
NO
Use 8.2 to t est burner
YES
Heater operating
8.1 General for Automatic Ignition
Warning
Fault finding should only be carried out by experienced engineers who fully understand the
operation of the burners.
There is a risk, including that of explosion,when burners are faulty and not repaired
correctly.
Page 62
UNIT HEATER
STAR T
Assuming gas & electrical
supplies are ON
NO NO Do es p ilot f lame l ight when Try ign it ing pil o t with Ensure th at t h ere is a gas gas valve button is pressed a lighted taper & electricity supply.
in & piezo i gniter i s Ensure that the limit
re pe ate dly pressed Y ES the rm ostats have not
opera te d.
YES Se e 8.3
Piezo faulty. Replace
NO
Does pilot remain on when Use 8.3.1 to trace fault
start button is released
YES
NO NO
Do es main b urner come ON C heck all co n t rols ar e ON Use 8.4 to t race f ault
& that the gas val ve knob
YES i s in the BURNER ON
position
NO
Do es f an r un after b u rner Use 8.5 to t race f ault
has run for several minutes ?
YES
Heater Working
8.1.1 General - Manual Ignition
Warning
Fault finding should only be carried out by experienced engineers who fully understand the
operation of the burners.
There is a risk, including that of explosion, when burners are faulty and not repaired
correctly.
Page 63
UNIT HEATER
START
All cont rols O N
Y E S
NO
Is Green light ON ? Check for electr ical su pp ly
o p er ation o f ext ernal con tro ls
Y E S & limit therm os ta t s
YES
Is RED lockout warning Press in reset button on
li ght ON ? con trol bo x or r emote re set
NO
NO NO
Ignition spark operating ? Remove pilot burner as in 7.3 replace spark generator
& i nspect electr o d e and
Y E S H .T. lea d. Rep la ce if faulty
NO YES
Pilot flame igniting Pilot solenoid va lve ope ning ? Ch eck gas is on
and purged of ai r
Y E S NO
NO
Use 8.4 to t est so lenoid v alve C on t rol box fault y
Replace
YES NO
Red "Lockout" li ght Check flam e current i s at Check Inlet pressure of gas
comes ON ? least 1 µ amps DC wh en i s cor rect for gas type.
pilo t lights
YES YES
Remove pilot bu rner as in 7.3
in sp ec t f lame p ro be and
lea d. Rep lace if faulty
NO
Control box faulty
Rep lace wi th correct type .
NO NO
Main burne r fires ? Check for 2 30v at output Control box faulty
from c ontrol box Replace with corre ct type
YES
YES
Use 8.4 to chec k val ves
YES
B urner operating
T o measure flame current, connect a 0 - 50 µA DC meter in series with The flame probe by using the flame probe jack plug. If the meter reads Negative values then reverse the test leads.
WARNING Ignition output fr om the spark generator is 160 kv to earth. Extreme care must be taken
8.2 Fault Finding For Automatic Ignition Burner Systems
Page 64
UNIT HEATER
To measure flame current, connect a 0 - 50 µA DC meter in series with The flame probe by using the flame probe jack plug. If the meter reads Negative values then reverse the test leads.
Maximum fl ame current Mi nimum flame current
with no flame with pilot only
0 to 0.5 µA D.C. 1.0 µA D.C.
Typical flame current
3.0 to 5.0 µA with main Burner ON
Connect a D.C. ammeter i n
ser ies w it h th e flame pro be
using the jack plug provi ded
Turn on all cont rols an d
ensure that there i s a supply
to the burner
Green l i ght ON
YES
Is there a curren t flowing in Repair or r eplace
the flame probe cir cuit I nspect and test the flame probe as necessary
with no flame present and wiring for damaged
insul at ion and short circuits
to earth
NO
YES
Does "l ockout" occur when Check adequate ga s pressure Control box f aulty
there is a flame present ?. Replace flame probe and en sure Replace with correct type
that it is fitted correctly.
Check f ro correct eart hing o f
heater
Check th at live and n eutral
NO polarity are correct
Burner Op erat ing
8.3 Flame Supervision System
8.3.1 Automatic Ignition Systems
Page 65
UNIT HEATER
NO NO
Doe s pilot flame ligh t ? Chec k gas supply a nd pilo t Ch e c k if pilot flame will light
gas pipe for blo ckag e using a taper
YES YES
Che ck piezo i gni ter, lead and ignition electro de for
damage. Replace as
necessary
NO NO
Does pilo t f lame rem ain On Wait 3 minutes Check that t here is power t o
When s t art b utto n is rele a se d Try again .Butt on must be fully c oil term ina ls sup plying the
on gas valve ? depressed in "start " positi on ther mocoupl e interru pt er
and held f or at l east 20 s econds relay.
a ft e r pilo t fla m e ha s lit.
T e s t the thermocou ple Ch ange i nterrupte r
output to the saf e ty valve. relay
there shoul d be 5 to 7 mV between the thermocoup le sheath and the valv e input
terminal
Chang e thermocoup le
Bu rner Operat ing
8.3.2 Flame Supervision Systems - Manual Ignition
8.4 Fault Finding for Solenoid Valves
Note For manual ignition valves the gas will not pass to the main burner until the pilot flame has been lit and accepted and the valve knob has been turned to main flame position.
Sta rt
NO
T est for 230v across val ve Fault elsew here
su pply termin als at the Check all con n ections and
appropriate ti me controls incl uding
lim it the rmosta ts
YES
NO
Test gas pressure at inl et of val ve Fault elsewhere
Test gas pressure at outl et of val ve. NO
Pressure should rise on outlet Sol enoid valve faul ty
when valve energises Replace as necess ary
YES
Valve Work ing
Page 66
UNIT HEATER
8.5 Fault Finding for Main Fan
NO NO
Fan does not run automatically? Check fo r electrical supply Fault elsewhere
230v L to N
YES
NO NO
Press in manual switch o f Test for 230v bet ween terminals Fau lt elsewhere
combination therm o stat 1 a nd N in te rminal block
Fan runs now ?
YES
YES Fan m otor or ca pacitor faulty
R epl ace as necessar y
Check sett ings o f combinat ion
ther mostat
fan now operates
Page 67
UNIT HEATER
Section 9. USER INSTRUCTIONS
The CUHA/A, CUHB/A, CUHC/A & CUHD/A ranges of heaters are fully automatic and operate from the remote controls fitted on site.
The only user controls situated on the heater are:
The burner lockout reset button See 9.3.1 The fan run button See 9.2.1 The limit thermostat reset See 9.2.1 The second limit thermostat reset button See 9.2.2 (there are tw o of these on the models 340 & 380)
The CUHA, CUHB, CUHC & CUHD ranges of heaters are manual ignition of the pilot, but operate automatically from the remote controls fitted on site providing that the pilot flame remains alight.
The user controls on these heaters are:
The main gas valve controls for lighting the pilot and main burner see 9.6.1 and Fig 9.1 The fan run button see 9.2.1 The limit thermostat reset see 9.2.1 The second limit thermostat reset button see 9.2.2 (there are tw o of these on the models 340 & 380)
All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation.
9.1 Heater Operation
When the heater has been switched on by the remote controls installed on site (see Controls Instructions) the main burner will automatically turn on to heat the heat exchanger.
For Automatic ignition heaters the burner control box will control the safe ignition of the pilot and main flame.
For manual ignition the pilot flame must be manually ignited and constantly alight to enable the remote controls to operate the main burner.
When the heat exchanger is suf ficiently heate d, the fan thermostat turns on the main fan(s) and warm air is discharged from the front of the heater.
WARNING:
The electrical isolator must not be used for turning the heater off other than in an emergency.
This will prematurely turn off the distribution fan and will seriously shorten the life of the
heat exchanger, invalidating the warranty.
Such action may also cause a fire hazard.
For manual ignition models interrupting the electrical supply also turns off the pilot flame.
Page 68
UNIT HEATER
9.3.1 Burner Lockout Reset Button
This manual reset button which is built into the burner contr ol box, and will illuminate the red warning light on the elctrical terminal box when the control has gone to safety shut down ‘lockout’.
This may be caused by flame failure.
After lockout has occurred, a waiting time of one minute must be observed before an attempt to reset the control is made by pressing in the reset button on the side of the heater.
Note: On some fully ducted heate rs the fan will come on during the burner firing cycle and not w ait for the temperature rise. This is to ensure that there is always a proper oper ation of the heater under all possible duct conditions.
When the remote controls turn of f the heater, the b urner turns off immediately lea ving the f an(s) to run on to cool the heat exchanger. When cooled sufficiently the fan thermo s tat will turn off the fan(s).
9.2.1 Combination Fan/Limit Thermosatat
This is located on the top right hand side of the heater, see Fig.1.1. This control ensures the heater does not blo w cold air in the normal heating cycle and protects the heat exchanger against overheating.
Fan Thermostat (White Button)
Although it should not be necessary for the user to touch this control, it is worth noting that pressing in the White button on the combination fan limit thermostat causes the main fan(s) to run continuously. For normal operation this button should be pulled to the out position.
Limit Thermostat (Red Button)
If for any reason the main fan should fail or the air flow is reduced the built in limit thermostat will cause the burner to go to safety shut down ‘lockout’. This condition will persist until the fault is corrected and the red manual reset button is operated. The combination fan/limit thermostat is preset during commissioning (see 4.3). Note: the heat exchanger must ha ve cooled for reset to be possible.
9.2.2 Secondary Limit Thermostat
There is also a secondary limit thermostat situated on the heater side panel at the rear .There are two of these thermostats on models 340 and 380 which are sited on the rear panel below the fans. These are hand reset devices designed to fail safe and give further protection against fan failure. To reset this thermostat unscrew the plastic cover and press in the central reset button. Note: the heat exchanger must have cooled for reset to be possible.
9.2 User Controls Common to All Versions
9.3 User Controls Automatic Ignition Versions
Page 69
UNIT HEATER
9.4 Lighting Instructions for Automatic Ignition Heaters Types CUHA/A, CUHB/A, CUHC/A and CUHC/A
(See 9.6. for lighting manual ignition heaters)
9.4.1
Ensure that the electrical and gas supplies to the heater are on. Check that the time switch is in an “ON” period and that the thermostat is set to the required temperatu re (which must be above the ambient temperature for the heater to operate).
9.4.2
Operate the Installed remote controls to the “heat on” position and the automatic firing sequence will begin as described in Section 2 of this manual.
The heater will now operate fully automatically under the control of the time switch and thermostats, as installed.
Following long shut down periods the control may go to “lockout” (indicated by the red “lockout light” being illuminated on the heater). To r eset press in the “lockout reset button” and the sequence will begin again automatically.
“Lockout” should not occur during normal operation of the heater and indicates that there is a fault condition which must be corrected.
WARNING
Do not operate the 'Lockout' reset button more than three times.
Turn off the heater and consult a competent heating engineer to correct the fault.
9.4.3 To Turn the Heater Off (short periods):
Operate the installed remote controls to the “OFF” position. The b urner will tur n off immediately, but the distribution fan will continue to run for a few minutes to dissipate the heat from the heat exc hanger . To restart turn the control used above to “ON”.
9.4.4 To Turn the Heater Off (long periods):
Carry out the operations of 9.4.3. Allow the fan to stop running automatically. Turn off the gas and electrical supplies. To start the heater again, turn on the gas and electrical supplies and reset the time switch as described in the manufacturers instructions. Carry out the operations in 9.4.1.
WARNING
If the control should go to ‘lockout’ again, do not make more than three attempts at
restarting the heater.
The fault must be traced and repaired by a competent person.
Page 70
UNIT HEATER
Fig 9.1 Features of the S.I.T. Nova valve for Manual Ignition Versions
9.5 User Controls for Manual Ignition Versions
9.5.1 Multifunctional Gas Valve
The S.I.T.Nov a multifunctional gas v a lve fitted to all man ual ignition unit heate rs is shown in Fig 9.1. and is used to control the gas supply whilst lighting the pilot flame by hand. Follow the instructions in 9.6 to light the pilot and operate the main burner.
WARNING
The electrical isolator must not be used for turning the heater off
other than in an emergency. This will prematurely turn off the distribution fan and will
seriously shorten the life of the heat exchanger, invalidating the warranty.
Such action may also cause a fire hazard.
Press in and hold to light pilot
Press in and turn to start
Press in and turn to run burner
Press in and turn to stop
Press in and turn to stop
OFF Position START Position BURNER RUN
Position
Page 71
UNIT HEATER
9.6 Lighting Instructions for Manual Ignition Heaters
Types CUHA, CUHB,CUHC and CUHD
(See 9.4. for lighting automatic ignition heaters)
9.6.1
Ensure that the electrical and gas supplies to the heater are on. Check that the remote controls are set to “OFF”. All CUH manual ignition unit heaters are controlled by an S.I.T No va 0.820.045 multifunctional gas valve (see Fig 9.1).
TO LIGHT PILOT
T o ignite the pilot press in the manual control button of the g as valve and turn anticlockwise to the star symbol. Press the button fully in and hold whilst continuously pressing and releasing the Piezo ignition de vice to create the spark ignition.
Note: IF AT ANY TIME THE PILOT FAILS TO LIGHT OR GOES OUT, EITHER INTENTIONALLY OR UNINTENTIONALLY, WAIT A FULL 3 MINUTES BEFORE ATTEMPTING TO RELIGHT .
Once the pilot flame has been seen to light (visible through the rear panel of the heater near to the gas pipe to the burner) continue to hold in the control valve button for a further 30 seconds, and then release.The pilot flame should now remain on. Should the pilot flame go out check that the limit thermosta ts have not operated and that there is an electrical supply to the main terminal block. Also ensure that the leads to the thermocouple interrupter relay are connected to their connections on the gas valve (see Fig 4.3).
Observe the 3 minute waiting time and retry.
Once the pilot flame has been established it will remain on constantly providing that the gas or electricity supplies are not interrupted and the limit thermostats do not operate.
To Operate The Main Burner
Press in slightly and turn the valve control knob a further quarter tur n anticlockwise to the "flame" symbol. Operate the remote controls to ON ensuring that the thermostat is set to the required temperature, (which must be above the ambient temperature for the heater to operate).
The main burner will now operate automatically pro viding that the pilot flame remains alight.
WARNING
The electrical isolator must not be used for turning the heater off other than in an
emergency. This will prematurely turn off the distribution fan and will seriously shorten the
life of the heat exchanger, invalidating the warranty.
Such action may also cause a fire hazard.
Interrupting the electrical supply also turns off the pilot flame.
Page 72
UNIT HEATER
9.7 Simple Fault Finding - General
Some possible reasons for the heater not operating are:-
1. Gas supply not turned ON.
2. Electricity supply not turned ON.
3. The installed time and/or temperature controls are not “ON”.
4. One or both of the limit thermostats may have operated. This may be caused by
inadvertent rem oval of the electrical supply or failure of the distribution fan.
Limit thermostat 1 is on the combination thermostat. To reset, press in and release the red reset button (see Figs in Section 1).
Limit thermostat 2 is under the screw on cover on the side or rear of the heater (see Figs in Section 1).
To reset remove the screw on cover and press in the reset button. Replace the cover after use.
If the Limit thermostats persistently operate then there is a fault which must be investigated by a competent engineer.
Any other problem will require the assistance of a Service Engineer.
9.6.2 To Turn the Heater Off (Short Periods):
Operate the remote controls to the “OFF” position. The burner will tur n o ff immediately, but the distr ibution fan will continue to run for a few minutes to cool the heat exchanger before turning off automatically. The heater will then be at rest until the controls are turned on again.
9.6.3 To Turn the Heater Off (Long Periods):
Carry out the operations in 9.6.2 and allow the fan to stop automatically. When the fan has stopped, turn off the gas and electricity supplies at the isolators.
To restart follow from 9.6.1
Page 73
UNIT HEATER
9.7.1 Simple Fault Finding - Automatic Ignition Heaters
5. If under fault conditions the burner fails to ignite for an y reason then it will g o to the
lockout condition this will be indicated b y the red lockout warning light on the heater or remote control
To reset press in and release the lockout reset button after waiting for one minute (see Figs 2.1 & 2.2).
"Lockout" should not occur during normal operation of the heater and indicates ther e is a fault condition which must be corrected.
9.7.2 Simple Fault Finding - Manual Ignition Heaters
Ensure that the pilot flame is alight by following the instructions in 9.6. Ensure that the control knob of the gas valve is turned to the main f lame position.
Should the pilot flame fail regularly ensure that the electrical supply to the heater is not being interrupted. Electrical interruption for ev en a few seconds will cause the interrupter relay to turn off the pilot.
9.8 Service Requirements
This heater will require servicing at least once per year except when operating in a dirty or dusty area, when more frequent service may be necessary. The service should be carried out by a competent engineer in accordance with the requirements of this manual.
For service contact your Heating Supplier.
The heater cabinet may be cleaned using a damp cloth with a little domestic detergent.
Do not use excessive water or abrasives.
WARNING
Do not operate the 'lockout' reset button more than three times.
Turn off the heater and consult a competent heating engineer to correct the fault.
EMERGENCY INSTRUCTIONS
If a gas leak is suspected, turn off the gas supply and extinguish all naked
flames. DO NOT operate any electrical switches or machinery. ventilate the
area and contact your local gas supply undertaking immediately.
DO NOT SEARCH FOR GAS LEAKS WITH ANY NAKED FLAME
Page 74
UNIT HEATER
Section 10. Conversion Between Gasses
10.1 General
Note all versions of models CUH...60 may not be operated on L.P.G
All versions of the heaters use the same main burner bars and pilot burners.
Natural gas
All natural gas versions use the same main burner injectors, marked 840, and pilot injectors marked
34.
The gas valves vary accor ding to the models size and method of control i.e. manual or automatic ignition but in all cases the valve contains a gas pressure regulator to allow for setting of the burner pressure.
L.P.G.
All L.P.G. versions use the same main burner injector, marked 250, and pilot injectors marked 19. The gas valves vary accor ding to the models size and method of control i.e. manual or automatic ignition but in all cases the valve DOES NOT contain a gas pressure regulator. The correct operation of the heater de pends on the close control of the gas inlet pressur e to the appliance.
10.2 Burner Conversion
To convert the burner assembly from one gas to the other is the same for all types of heater.
i) Remove the burner tray as in Section 7 of these instructions and remove all of the main burner
injectors. ii) Replace with the ones for the new gas. iii) Remove the pilot burner assembly retaining the flame monitor , and spark electrode. iv) Fit the new pilot burner injector following the instructions in Section 7.
Fig 10.1 Pilot Burner Options
Page 75
UNIT HEATER
10.3 Gas Valves - Automatic Ignition
There are three type of valve used for this range of heaters (see Data Tables in Section 2 for part numbers and specification numbers). CUH.../A 60 to 140 use the S.I.T. Tandem gas valve. Note: Model CUH.../A 60 heaters only cannot be operated on L.P.G. CUH.../A 160 to 300 use the S.I.T. Nova gas valve. CUH.../A 340 to 380 use the Johnson multifunction gas valve.
10.3.1 T andem Range Valves
T andem range main gas v a lves cannot be con verted between gasses as they are constructed either with or without a governor. These valves must be changed for the correct type as listed in the data tables.
10.3.2 Nova Range Valves
Nova range main valves may be converted to operate with or without a burner gas pressure regulator. Follow the instructions in Section 7 of this manual for removal of gas valves.
To convert Nova valve from Natural Gas to L.P.G. (see Fig 10.2)
i) Remove the cov er of the pressure regulator. ii) Completely unscrew the regulator adjusting screw and remove it complete with its spring. iii) Replace the adjusting screw and original cover with the blanking nut attachment. This device screws fully into the body of the re gulator until it stops and puts the regulator out of action. The step opening feature of the main valve will still operate.
To Convert Nova Valve from L.P.G. to Natural Gas
Reverse the instructions a bove.
Blanking screw Governor spring For L.P.G. assembly
The valve shown is the Nova manual ignition version, however conversion of the automatic ignition version is exactly the same.
Fig 10.2 Conversion of Nova Family Valve
Page 76
UNIT HEATER
10.3.3 Conversion of Johnson Valve to L.P.G.
For the Models 340 and 380 the va lve for use on L.P . G. Propane or Butane is exactly the same Johnson valve as for natural gas however the pressure regulator must be put out of service.
To do this for the Johnson gas valves an ada ptor pipe is fitted to connect the pressure regula tor breather port to one of the valve centre test points (see Fig 10.3). This is achieved by f irst removing the plastic re gulator breather plug by unscrewing it and screwing in one of the compression couplers.
Remove the centre test point that coincides with the adaptor pipe length and again replace with the other compression coupler. Link the two couplers with the adaptor pipe and tighten the compression fittings.
The internal re gulator is now out of action and the heater must be supplied with gas closely contr olled at the correct inlet pressure of 37mbar for Propane or 29mbar for Butane.
Fig 10.3 Conversion of Johnson Gas Valve for L.P.G.
Regulator Breather Port
Pipe Link to Put Regulator Out of Action
Page 77
UNIT HEATER
10.4 Conversion of Manual Ignition Valves
All CUH... range manual ignition unit heaters use an S.I.T Nova multifunctional gas valve.
The Models CUH... 60 only cannot be operated on L.P.G.
Nova Range valves
Nova range main valves may be converted to operate with or without a burner gas pressure regulator. Follow the instructions in Section 7 of this manual for removal of gas valves.
To convert Nova valve from Natural Gas to L.P.G. (see Fig. 10.2)
Remove the cover of the pressure regulator. Completely unscrew the regulator adjusting screw and remove it complete with its spring. Replace the adjusting screw and original cover with the blanking nut attachment. This device screws fully into the body of the re gulator until it stops and puts the regulator out of action. The step opening feature of the main valve will still operate.
To Convert Nova Valve from L.P.G. to Natural Gas
Reverse the instructions a bove.
Page 78
UNIT HEATER
DESCRIPTION P ART NUMBER
Axial Fan S4E 350 A 262
Axial Fan S4E 400 A 263
Axial Fan S4E 420 A 264
Manual ignition gas valve. S.I.T. Nova (All gasses) L 431
Thermocouple L 432
Thermocouple interrupter relay L 434
Automatic ignition gas v alve: S.I.T. T andem (Nat gas) L 411
Automatic ignition gas valve: S.I.T. Tandem (L.P.G gas) L 413
Automatic ignition gas valve: S.I.T. Nova (All gasses) L 421
Exclusion screw for No va valves (All Types) for L.P.G. L 425
Automatic Ignition pilot solenoid valve L 085
Main burner injectors, natural gas B 094
Main burner injectors, L.P.G. gas B 095
Sealing washers for main burner injectors B 210
Pilot burner injector for natural gas B 184
Pilot burner for all gas types B 186
Pilot burner injector for L.P.G. gas B 088
Honeywell combination fan/limit thermostat. K 017
Second limit thermostat K 120
Note: Always quote the model and serial number of the heater when ordering spare parts.
Section 11. PARTS LIST
Parts available from:
Combat Engineering Ltd.
Oxford Street, Bilston, West Midlands
WV14 7EG
SERVICE Service Department Tel: 01902 498733 Fax: 01902 401464
SPARES Trade Counter Tel: 01902 499051 Fax: 01902 492411
SWITCHBOARD Tel: 01902 494425 Fax: 01902 403200
Page 79
UNIT HEATER
INLET GAS PRESSURE mbar
BURNER GAS PRESSURE mbar GAS RATE MEASURED AT METER M
3
/hr (ft3/hr)
AMBIANT TEMPERATURE °C
GROSS STACK TEMPERATURE °C
NET STACK TEMPERATURE °C
CARBON DIOXIDE IN FLUE CO
2
%
CARBON MONOXIDE IN FLUE CO.. P.P.M.
ESTIMATED EFFICIENCY % (State net or gross)
COMMENTS
CUSTOMER
SITE ADDRESS
HEATER LOCATOIN
MODEL SERIAL NUMBER
GAS TYPE NATURAL/L.P.G.
ENGINEER SIGNATURE DATE
Section 12. COMMISSIONING DATA SHEET
Page 80
UNIT HEATER
Page 81
UNIT HEATER
CONTACTS
SERVICE
Tel: 01902 498733
Fax: 01902 401464
SPARES
Tel: 01902 499051
Fax: 01902 492411
MAIN SWITCHBOARD
Tel: 01902 494425
Fax: 01902 403200
Combat Engineering Ltd.
Oxford Street, Bilston, West Midlands WV14 7EG
Tel: 01902 494425 Fax: 01902 403200
e-mail: enquiry@combat.co.uk
www.combat.co.uk
A Roberts-Gordon Company
Loading...