ComAp, a.s.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT Plus, SW version 1.5, ©ComAp – October 2013 1
InteliNano-NT-Plus-1.5-Fast User Guide.pdf
CAN INTERFACE
MAINS / GENERATOR
VOLTAGE
MEASUREMENT
T20 = Neutral
T21 = Phase 1
T22 = Phase 2
T23 = Phase 3
GENERATOR CURRENT
MEASUREMENT
T16 = k
T17 = l
USB interface
L
COM
H
INTPUT TERMINALS
T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog input – Low Fuel Level
T14 = binary/analog input – Coolan Temperature
T15 = binary/analog input – Oil Pressure
OUTPUT TERMINALS
T04 = binary output – Starter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)
T08 = binary output (500 mA)
T09 = binary output (500 mA)
POWER SUPPLY, D+
T01 = BATT T02 = D+
T03 = BATT +
GENERATOR VOLTAGE
MEASUREMENT
T18 = Neutral / Phase 1
T19 = Phase 1 / Phase 2
InteliNano NT
Plus
Fast User Guide
Typical wiring diagram
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off).
If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press ▲ button and then Auto .
If you have already created your own init screen then press and hold Stop button and then briefly press ▲, the custom init screen will appear, keep holding the Stop
button. Then press ▼ to switch LCD to default init screen, and then press Auto.
To move up and down in the setup menu use ▲ and ▼ buttons. Press Start button to select or Stop button for exit.
Engine parameters and protections
AMF(Auto Mains Failure) settings
T04 , T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
T04, T05, T06, T07, T08, T09
Normally Open Contact – output
Normally Open Contact - input
button
Normally Closed Contact – output
Normally Closed Contact – output
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13,T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
T07, T11, T12, T13, T14, T15
Coolant Temperature Analog
T07, T11, T12, T13, T14, T15
Dimensions
Case dimensions: 118mm x108mm x 40mm
Panel Cutout: 96mm x 96mm
WARNING!
If D+ is not used, connect this terminal to battery positive!

ComAp, a.s.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT Plus, SW version 1.5, ©ComAp – October 2013 2
InteliNano-NT-Plus-1.5-Fast User Guide.pdf
Setpoints
Use ▲ and ▼ buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back.
Mono Phase (1), SplitPhase (2),
3Ph3Wire (3), 3Ph4Wire (4)
Metric unit format (1), US unit
format (2)
Generator Overvoltage Shutdown
Generator Undervoltage Shutdown
Generator Overfrequency Shutdown
Generator Underfrequency Shutdown
Generator Short Circuit Shutdown
Generator Short Circuit Delay
Engine parameters and protections
Coolant Temperature Shutdown
Oil Pressure Starter Disengagement
Minimal Stabilization Time
AMF(Auto Mains Failure) settings
To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.
Alarms and Events
Island Operation Warnings
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.
Technical data
Power supply drop-out immunity
Zero Power Mode consumption
6 A (long term) / 10 A (short term) (L≤500mH)
10 A (long term) / 16 A (short term) (L≤500mH)
Charging alternator preexcitation circuit
95 % non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel)
IP65 with GASKET 4x405 only
Generator/Mains measurements
1ph gen. voltage,1ph current, 3ph mains voltage

ComAp, a.s.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT Plus, SW version 1.5, ©ComAp – October 2013 3
InteliNano-NT-Plus-1.5-Fast User Guide.pdf
Typical wiring diagram of AMF application
G
ECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fuel Solenoid
Battery
Sarter
Fuel Level Analog
Coolant Temperature Analog
Oil Pressure Analog
D+
-
+
GCB MCB
GCB
MCB
Alarm
Ready To Load
Fuel Solenoid
Starter
COM
Remote Start And Load
Emergency Stop
CAN
L COM H
USB
Battery +
Battery -
D +
PC
L1
L2
L3
N
k l
Typical wiring diagram of MRS application
G
ECU
DIESEL / GASOLINE ENGINE GENERATOR
LOAD
Fuel Solenoid
Battery
Sarter
Fuel Level Analog
Coolant Temperature Analog
Oil Pressure Analog
D+
-
+
Ready To Load
Fuel Solenoid
Starter
COM
Remote Start And Load
Emergency Stop
CAN
L COM H
USB
Battery +
Battery -
D +
L1
L2
L3
N
k l
Alarm
PC