ComAp InteliLite NT AMF 25, InteliLite NT MRS 16 Operator's Manual

Page 1
InteliLite NT
®
Operator Guide
December 2008 Copyright © 2007 ComAp s.r.o. Written by Adela Prochazkova Prague, Czech Republic
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 246 316 647 E-mail: info@comap.cz, www.comap.cz
Page 2
Operator Interface AMF
GEN-SET CONTROL BUTTONS
POSITION BUTTON DESCRIPTION
1
START button. Works in MAN mode only. Press this button to initiate the start sequence of the engine.
2
STOP button. Works in MAN mode only. Press this button to initiate the stop sequence of the gen-set. Repeated pressing or holding the button for more than 2s will cancel current phase of stop sequence (like ramping the power down or cooling) and next phase will continue.
3
FAULT RESET button. Use this button to acknowledge alarms and deactivate the horn output. Inactive alarms will disappear immediately and status of active alarms will be changed to "confirmed" so they will disappear as soon as their reasons dismiss.
4
HORN RESET button. Use this button to deactivate the horn output without acknowledging the alarms.
5
MODE LEFT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed.
NOTE:
This button will not work if the controller mode is forced by one of binary inputs Remote OFF, Remote MAN, Remote AUT, Remote TEST.
IL-NT Operator Guide ©ComAp – December 2008 2
Page 3
6
MODE RIGHT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed.
NOTE:
This button will not work if the controller mode is forced by one of binary inputs Remote OFF, Remote MAN, Remote AUT, Remote TEST.
7
GCB button. Works in MAN mode only. Press this button to open or close the GCB manually. Note that certain conditions must be valid otherwise GCB closing is blocked.
8
MCB button. Works in MAN mode only. Press this button to open or close the MCB manually.
CAUTION!
You can disconnect the load from the mains supply with this button! Be sure you know well what you are about to do!
GEN-SET OPERATION INDICATORS
POSITION INDICATOR DESCRIPTION
9
Gen-set failure. Red LED starts flashing when gen-set failure occurs. After FAULT RESET button is pressed, goes to steady light (if an alarm is still active) or is off (if no alarm is active).
10
Gen-set voltage OK. Green LED is on if the generator voltage is present and within limits.
NOTE:
The limits for the generator voltage and frequency are given by setpoints in the Gener Protect group.
11
GCB ON. Green LED is on, if GCB is closed. It is driven by GCB CLOSE/OPEN output (AMF 8/9) or by GCB feedback signal (AMF 20/25).
12
MCB ON. Green LED is on, if MCB is closed. It is driven by MCB CLOSE/OPEN output (AMF 8/9) or by MCB feedback signal (AMF 20/25).
13 Mains voltage OK. Green LED is on, if mains is present and within limits.
14
Mains failure. Red LED starts blinking when the mains failure is detected and after the gen-set has started and connected to the load it lights permanently until the mains failure disappears.
E
N
DISPLAY AND CONTROL BUTTONS
POSITION BUTTON DESCRIPTION
15 Graphic B/W display, 128x64 pixels
16
PAGE button. Use this button to switch over display pages. See Display Screens and Pages Structure chapter below this table for more details.
17
UP button. Use this button to move up or increase a value.
18
DOWN button. Use this button to move down or decrease a value.
19
ENTER button. Use this button to finish editing a setpoint or moving right in the history page.
IL-NT Operator Guide ©ComAp – December 2008 3
Page 4
Operator Interface MRS
GEN-SET CONTROL BUTTONS
POSITION BUTTON DESCRIPTION
1
START button. Works in MAN mode only. Press this button to initiate the start sequence of the engine.
2
STOP button. Works in MAN mode only. Press this button to initiate the stop sequence of the gen-set. Repeated pressing or holding the button for more than 2s will cancel current phase of stop sequence (like ramping the power down or cooling) and next phase will continue.
3
FAULT RESET button. Use this button to acknowledge alarms and deactivate the horn output. Inactive alarms will disappear immediately and status of active alarms will be changed to "confirmed" so they will disappear as soon as their reasons dismiss.
4
HORN RESET button. Use this button to deactivate the horn output without acknowledging the alarms.
5
MODE LEFT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed.
NOTE:
This button will not work if the controller mode is forced by one of binary inputs Remote OFF, Remote MAN, Remote AUT.
IL-NT Operator Guide ©ComAp – December 2008 4
Page 5
6
MODE RIGHT button. Use this button to change the mode. The button works only if the main screen with the indicator of currently selected mode is displayed.
NOTE:
This button will not work if the controller mode is forced by one of binary inputs Remote OFF, Remote MAN, Remote AUT.
7
GCB button. Works in MAN mode only. Press this button to open or close the GCB manually. Note that certain conditions must be valid otherwise GCB closing is blocked.
GEN-SET OPERATION INDICATORS
POSITION INDICATOR DESCRIPTION
8
Gen-set failure. Red LED starts flashing when gen-set failure occurs. After FAULT RESET button is pressed, goes to steady light (if an alarm is still active) or is off (if no alarm is active).
9
Gen-set voltage OK. Green LED is on if the generator voltage is present and within limits.
NOTE:
The limits for the generator voltage and frequency are given by setpoints in the Gener Protect group.
10
GCB ON. Green LED is on, if GCB is closed. It is driven by GCB CLOSE/OPEN output (MRS 3/4/10/15) or by GCB feedback signal (MRS 11/16).
DISPLAY AND CONTROL BUTTONS
POSITION BUTTON DESCRIPTION
11
PAGE button. Use this button to switch over display pages. See Display Screens and Pages Structure chapter below this table for more details.
12
UP button. Use this button to move up or increase a value.
13
DOWN button. Use this button to move down or decrease a value.
14
ENTER button. Use this button to finish editing a setpoint or moving right in the history page.
15 Graphic B/W display, 128x64 pixels
IL-NT Operator Guide ©ComAp – December 2008 5
Page 6
Display Screens and Pages Structure
The displayed information is structured into "pages" and "screens". Use PAGE button to switch over the pages.
1. The page
Measurement consists of screens which display measured values like voltages, current, oil pressure etc., computed values like i.e. gen-set power, statistic data and the alarm list on the last screen.
2. The page
Setpoints contains all setpoints organized to groups and also a special group for entering password.
3. The page
History log shows the history log in the order that the last record is displayed first.
Measurement Setpoints History log
Generator L1N 0 L1L2 0V L1N 0 L1L2 0V L1N 0 L1L2 0V Gen freq 0.0Hz
0 0 0 A
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
ECU AlarmList
>EngOil Press
000225 (000E1h)
FC 100 OC 4 FMI 1
AlarmList 1
Emergency Stop
Password
>Basic Settings
Engine Params Engine Protect Gener Protect AutoMains Fail Extension I/O Date/Time
Page
Gen-set Name
>Nominal Power
200 kW
Nomin Current
350 A
CT Ratio
2000 /5A
Gen-set Name
>Nominal Power
250 200 kW
Nomin Current
350 A
CT Ratio
2000 /5A
No. Reason
> 0 Switched On
-1 Fault reset
-2 Emergency Stop
-3 Wrn RA15 Fail
-4 Sprinkler Set
-5 Config Loaded
13:02:17 07/08/2008
Time Date
>13:02:17 07/08/2008
13:00:46 07/08/2008 13:00:46 07/08/2008 13:00:45 07/08/2008 13:00:45 07/08/2008 13:00:43 07/08/2008
0 Switched On
Mode RPM Pwr
> OFF 0 0
OFF 0 0 OFF 0 0 OFF 0 0 OFF 0 0 OFF 0 0
0 Switched On
Page
Page
Page
Page
Page
Page
Page
Enter
Enter
Enter
Enter
Page
Enter
Enter Page
NOTE: History and Setpoints pages are available only when you choose Engineer interface (not User). See Controller Information Screen subchapter below.
History Log is not supported in InteliLite MRS 3, 4, 10, 11 and AMF 8, 9, 20.
IL-NT Operator Guide ©ComAp – December 2008 6
Page 7
Alarms
AlarmList 3 *MCB Fail
*Emergency Stop
Sd Override
Inactive unconfirmed alarm
A
ctive unconfirmed alarm
A
ctive confirmed alarm
Browsing ECU Alarms
IL-NT Operator Guide ©ComAp – December 2008 7
Page 8
Setpoint Change
Entering the Password
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
Password
>Basic Settings
Engine Params Engine Protect Gener Protect AutoMains Fail Extension I/O Date/Time
Enter
Page
Enter
Enter Page
Page
Gen-set Name
>Nominal Power
200 kW
*Nomin Current
350 A
CT Ratio
2000 /5A
Gen-set Name
>Nominal Power
250 200 kW
*Nomin Current
350 A
CT Ratio
2000 /5A
NOTE: Cannot change setpoint?
Setpoints marked with an asterisk are password protected. Enter password as described in the chapter Entering the Password below.
IL-NT Operator Guide ©ComAp – December 2008 8
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
>Password
Basic Settings Engine Params Engine Protect Gener Protect AutoMains Fail Extension I/O Date/Time
>EnterPassword
Changepassword
Enter
Page
Enter
Enter Page
>EnterPassword
0
Changepassword
Page
NOTE: Lost password? Display the
information screen containing the serial number and password decode number as described in the chapter below and send them to your local distributor.
Page 9
Controller Information Screen
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
InteliLite NT
ComAp 2007-2008
IL-NT-x.y Serial:12345678 SW ver: x.y, x.y Appl : AMF25 Branch: Standard
Page
Languages >English
Chinese
Enter + Page
User interface:
User
>Engineer
Serial: 12345678 Pwd. dec.: 1234567890
Page
Page
Enter
Enter
Display Contrast Adjustment
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
Enter +
Enter +
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
OFF MAN AUT TEST !
Not ready MainsFlt PF 0.00 RPM 0 No Timer
0 kW 0
IL-NT Operator Guide ©ComAp – December 2008 9
Loading...