Columbia MCB50, MCB75, MCB100, MCB125, MCB150 Installation, Operation & Maintenance Manual

...
MODEL NUMBERS:
MCB50 MCB75 MCB100 MCB125 MCB150 MCB175 MCB200 MCB250 MCB300
MCB SERIES
Cast Iron Gas Fired Boilers
For Forced Hot Water
INSTALLATION, OPERATION &
Columbia Company
Main ofces and Factory: Pottstown, PA
P/N 37612101, Rev. E [05/2012]
H
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Ratings & Data - Natural Gas & Propane Gas ...........3
Dimensions .........................................................4
Installation Procedure ..........................................5
Ventilation & Combustion Air .................................6
Connecting Supply and Return Piping .....................7
Connecting Supply and Return Piping .....................8
Vent Installation ................................................ 12
Vent System Modication .................................... 12
Vent Damper Installation & Instructions ................ 13
Connecting Gas Service ...................................... 14
Electrical Section ............................................... 15
Wiring Diagram - 24V Standing Pilot .................... 16
Wiring Diagram - Intermittent Ignition ................. 17
Lighting Instructions .......................................... 18
Normal Sequence of Operation ............................ 20
General Instructions .......................................... 20
Checking Gas Input Rate To Boiler ....................... 22
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions COMPLETELY before installing!!
WARNING
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room.
Modication, substitution or elimination of factory equipped, supplied or specied components may result in property damage,
!
personal injury or the loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualied installer.
Replacement Parts - Base ................................... 23
Safety Symbols & Warnings
The following dened symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
DANGER
Indicates a hazardous situation which, if
!
not avoided, WILL result in death or serious injury.
WARNING
Indicates a hazardous situation which, if
!
not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not
!
avoided, may result in minor or moderate injury.
TO THE INSTALLER - Leave all instructions with the boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
WARNING
All installations of boilers and venting shall be done only by a qualied expert and in accordance with appropriate manual. Installing or venting a boiler or any other gas
!
appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
C.S.A. Certied
For Natural Gas Or Propane
2
Tested For 100 psi.
ASME
Working Pressure
RATINGS & DATA - NATURAL GAS & PROPANE GAS
Table 1 - Ratings and Capacities
(2)
**
Net Rating
Water
Mbh
37
55
72
90
108
124
143
178
214
No.
of
Burners
1
2
2
3
3
4
4
5
6
Boiler
No.
50
75
100
125
150
175
200
250
300
(1)
Input
Mbh
50
75
100
125
150
175
200
250
299
(1)
Heating
Capacity Mbh
42
63
83
104
124
143
165
205
243
EXPLANATORY NOTES
-- All boilers are design certied for installation on noncombustible oor.
-- For installation on combustible oors use combustible oor kit.
(3)
Recommended
Air Cushion
Tank
15
15
30
30
30
30
30
30
60
Water
Content
(Gals.)
2.4
4.0
4.0
5.6
5.6
7.2
7.2
8.8
10.4
High
Altitude
Input
45,000
67,500
90,000
112,500
135,000
157,000
180,000
225,000
270,000
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
• United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1000 ft (304m) above sea
level.
• Canada, 2000 ft (610m) to 4500 (1350m) above sea level. Reduce input per table.
• Canada, over 4500 ft (1350m) above sea level. Contact Provincial authority having jurisdiction.
(2) Net Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer before
selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit Control, Vent Damper Relay, Theraltimeter Gauge, Circulator With Return Piping To Boiler, Main Gas Burners, Combination 24 Volt Gas Control (Includes Automatic Gas Valve, Gas Pressure Regulator, Automatic Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Automatic Vent Damper. Not Shown Are: Wiring Harness, Thermocouple, Non-linting Safety Pilot.
OPTIONAL EQUIPMENT: Intermittent Electric Ignition Pilot System.
3
DIMENSIONS
Table 2 - Dimensions
Boiler No.
50
75
100
125
150
175
200
250
300
* Propane gas inlet, all units, 1/2"
Natural Gas
Inlet*
½"
½"
½"
½"
½"
½"
½"
¾"
¾"
26
A
11⅛"
15
15
18⅞"
18⅞"
22
¾
22
¾
13
30½"
Dimensions
B
5
½
"
7
½
"
7
½
"
9
½
"
9
½
"
"
"
"
16
11
½
11
½
13¼"
"
"
15¼"
4"
5"
6"
6"
7"
7"
8"
8"
9"
C
D
30¾"
30¾"
30¾"
30¾"
30¾"
30¾"
30¾"
30¾"
30¾"
E
36¼"
37¾"
37¼"
37¼"
37¾"
38¾"
38¾"
40¾"
42¾"
F
6"
6"
6½"
6½"
7"
7"
8"
8"
10"
Pump size Supply &
Return Tappings
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
4
INSTALLATION PROCEDURE
WARNING
Improper installation, adjustment, alteration,
!
service or maintenance can cause injury or property damage.
1.
Installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1.
2.
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically red Boilers, ANSI/ASME CSD-1.
3.
This boiler series is classied as a Category I. Vent installation shall be in accordance with "Venting of Equipment ," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or "Venting Systems and Air Supply for Appliances," of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
4.
This boiler has met safe lighting and other performance criteria with gas manifold and control assembly on the boiler per the latest revision of ANSI Z21.13/CGA 4.9.
5.
The boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near the chimney as possible and centrally located with respect to the heat distribution system as practical.
7.
Allow 24 inches (610mm) at front and right side for servicing and cleaning.
8.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as water heater.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement Parts Section.) Boiler can not be installed on carpeting. Minimum clearances to combustible construction are:
TOP ....................................18 IN. (457mm)
FRONT .........................................ALCOVE *
FLUE CONNECTOR ................. 6 IN. (152mm)
REAR ................................... 4 IN. (102mm)
CONTROL SIDE ..................... 9 IN. (229mm)
OTHER SIDE ........................... 3 IN. (76mm)
HOT WATER PIPING .............. 1/2 IN. (13mm)
NOTE: Greater clearances for access should supersede fire
protection clearances. * Denition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
Minimum Clearances to Combustible
Construction (as seen from above)
4"
3"
9"
BOILER
18"
5
VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
• Engineered Installations. Must be approved by authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if minimum volume not available.
о Standard Method. Cannot be used if known air
inltration rate is less than 0.40 air changes per
National Gas and Propane Installation Code Requires providing air supply in accordance with:
hour. See Table 3 for space with boiler only. Use equation for multiple appliances.
Volume ≥ 50 ft3 x Total Input [Mbh]
о Known Air Inltration Rate. See Table 3 for
space with boiler only. Use equation for multiple appliances. Do not use an air inltration rate (ACH) greater than 0.60.
Volume ≥ 21 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s) communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2 Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides and back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
• Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code for specic air supply requirements for enclosure or structure where boiler is installed, including air
supply openings and ducts.
Table 3
Input Mbh
Standard
Method
0.1 0.2 0.3 0.4 0.5 0.6
50 2500 10500 5250 3500 2625 2100 1750
75 3750 15750 7875 5250 3938 3150 2625
100 5000 21000 10500 7000 5250 4200 3500
125 6250 26250 13125 8750 6563 5250 4375
150 7500 31500 15750 10500 7875 6300 5250
175 8750 36750 18375 12250 9188 7350 6125
200 10000 42000 21000 14000 10500 8400 7000
250 12500 52500 26250 17500 13125 10500 8750
300 15000 63000 31500 21000 15750 12600 10500
Known Air Inltration Rate Method (Air Changes Per Hour)
6
CONNECTING SUPPLY AND RETURN PIPING
WARNING
To avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation, a discharge line shall be installed to relief valve outlet connection.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from oor or allowable safe point of discharge.
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or place any obstruction in discharge line.
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375° F; or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
RELIEF VALVE
DISCHARGE
LINE
Check local
codes for
maximum
distance
from oor
or allowable
safe point of
discharge.
RELIEF VALVE
Check local
codes for
maximum
distance
from oor
or allowable safe point of
discharge.
DISCHARGE
LINE
7
AIR
SEPARATOR
CONNECTING SUPPLY AND RETURN PIPING
IMPORTANT: Circulators in the following illustrations are mounted on the system supply side, but mounting on the system return side is also acceptable practice.
Figure 5 - Circulators Mounted on System Supply
1.
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. See Figure 5.
2.
The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with ow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
3.
Hot water boilers installed above radiation level or as required by authority having jurisdiction must be provided with a low water cut-off device.
4.
When a boiler is connected to a heating system that utilizes multiple zoned circulators, each circulator must be supplied with a ow control valve to prevent gravity circulation.
5.
Hot water boilers and system must be lled with water and maintained to a minimum pressure of 12 psi.
6.
Bypass piping is an option which gives the ability to adjust the supply boiler water temperature to t the system or the condition of the installation. This method of piping, however, is not typically required for base­board heating systems. Typical installations where
bypass piping is used are as follows: A. This method is used to protect boilers from con-
densation forming due to low temperature return water. Generally noticed in large converted grav­ity systems or other large water volume systems.
Figure 6 & 7.
B. These methods are used to protect systems using
radiant panels and the material they are encased in from high temperature supply water from the boiler
and protect the boiler from condensation.
NOTE#1: When using bypass piping, adjust valves V1 & V2 until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping as the supply and return piping.
8
CONNECTING SUPPLY AND RETURN PIPING
Figure 6 - Bypass Piping Automatic Mixing Valve
TO SYSTEM
WATER INLET
EXPANSION
TANK
FROM SYSTEM
CIRCULATOR
SHUT-OFF VALV E
PRESSURE REDUCER VALVE
CHECK VALVE
BOILER
BALL VALVE
3 WAY MIXING VALV E
ALTERNATE
CIRCULATOR
LOCATION
AIR SEPARATOR
HOSE BIB
Figure 7 - Bypass Piping - Fixed Low Temp Only Automatic Mixing Valve
TO SYSTEM
WATER INLET
SYSTEM
CIRCULATOR
EXPANSION
TANK
V2V1
BOILER
FROM SYSTEM
ALTERNATE
CIRCULATOR
LOCATION
CIRCULATOR
SHUT-OFF VALV E
7. Installation using circulators and zone valves are
shown in Figures 8-11. For further piping information refer to I=B=R Installation and Piping Guide.
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
8. Install discharge piping from safety relief valve.
• Use ¾" or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or greater.
PRESSURE REDUCER VALVE
CHECK VALVE
9
BALL VALVE
ZONE VALVE
AIR SEPARATOR
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location protecting user from scalding and properly drain piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
Loading...
+ 19 hidden pages