Columbia CDVB-50, CDVB-150, CDVB-125, CDVB-100, CDVB-200 Installation, Operation & Maintenance Manual

CDVB SERIES
Gas Fired Boilers
For Forced Hot Water
INSTALL ATION, OPER ATION &
MAINTENANCE MANUAL
Columbia Company
Main ofces and Factory: Pottstown, PA
P/N 37616101, Rev. F [05/2012]
H
GAS FIRED BOILERS FOR FORCED HOT WATER
Introduction ................................................................................................................................ 3
Boiler Ratings, Capacities & Dimensions .......................................................................................... 4
Ventilation & Combustion Air ......................................................................................................... 6
Connecting Supply & Return Piping ................................................................................................ 7
Applicable Federal Codes .............................................................................................................11
Vent System Modication .............................................................................................................11
Horizontal Vent Pipe Installation Instructions ..................................................................................12
Vertical Vent Pipe Installation Instructions ......................................................................................22
Connecting Gas Service ...............................................................................................................28
Electrical Wiring .........................................................................................................................29
Lighting Instructions ...................................................................................................................31
Sequence Of Operation................................................................................................................32
General Instruction For Seasonal Startup & Maintenance ..................................................................33
Replacement Parts ......................................................................................................................37
KEEP THIS MANUAL NEAR BOILER AND
RETAIN FOR FUTURE REFERENCE.
IMPORTANT: Read the following instructions
COMPLETELY before installing!
SAFETY SYMBOLS
The following dened symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
DANGER
Indicates a hazardous situation which, if
!
not avoided, WILL result in death or serious injury.
WARNING
Indicates a hazardous situation which, if
!
not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not
!
avoided, may result in minor or moderate injury.
Indicates information which should be followed to ensure proper installation and operation.
CAUTION
NOTICE
C.S.A. Certied for
Natural gas or Propane
Tested for 100 psi. ASME
Working Pressure
2
WARNING
1. Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
2. DO NOT obstruct air openings to boiler room.
3. Modication, substitution or elimination of factory equipped, supplied or specied components may result in property damage, personal injury or loss of life.
!
4. To owner: Installation and service of this boiler must be performed by qualied installer.
5. To installer: Leave all instructions with boiler for future reference.
6. Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR when installed in Commonwealth of Massachusettes. This includes, but is not limited to, installation by licensed plumber or gas tter.
INTRODUCTION
7.
Install boiler such that gas ignition system components are protected from water, (dripping, spraying, rain, etc.), during appliance operation and service, (circulator replacement, condensate trap, control
replacement, etc.).
8.
Requirements for Commonwealth of Mas sachusetts: Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which includes but is not limited to installation by licensed
plumber or gas tter.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY. *Boiler must NOT be installed on carpeting.
10.
Minimum clearances to combustible constructions are:
TOP ...........................................18 in.
FRONT ........................................6 in
FLUE CONNECTOR .........................6 in
REAR............................................4 in.
CONTROL SIDE..............................9 in.
OTHER SIDE .................................3 in.
VENT PIPE ....................................6 in.
(457mm)
(152mm)
(152mm)
(102mm) (229mm)
(76mm)
(152mm)
NOTICE
WARNING
Improper installation, adjustment, alteration,
!
service or maintenance can cause injury or property damage.
1.
Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or Natural Gas and Propane Installation Code, CAN/BS149.1
2.
Where required by the authority having jurisdiction, installation must conform to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ ASME No. CSD-1.
3.
This boiler is classied as Category I and III and vent installation shall be in accordance with latest revision of the National Fuel Gas Code, ANSI Z223.1 or applicable provisions of the local building codes.
4.
LOCATE BOILER on level, solid base as near outside wall as possible and centrally located with respect to heat distribution system as practicable.
5.
Allow 24 inches at front and right side for servicing and cleaning.
6.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as a water heater.
• Greater clearances for access should supersede re protection clearances.
* For installation on combustible ooring
Special Base MUST BE USED. (See Replacement Parts Section)
3
All installations of boilers and venting should be done only by a qualied expert and in accordance with
!
the appropriate utica boilers manual. Installing or venting a boiler or any other gas appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
Figure 1 -Boiler Dimensions
BOILER RATINGS, CAPACITIES & DIMENSIONS
WARNING
Table 1- DIMENSIONS FOR NATURAL GAS
Model #
-50
-100
-125
-150
-200
NOTE:
each 1,000 ft. above sea level.
For altitudes above 2,000 ft. ratings should be reduced at the rate of 4% for
Natural
Gas Inlet
½"
½"
½"
½"
½"
Dimensions
A B C D
11¼
15⅛
19
19
22⅞
2⅛
4⅛
6
6
8
3
3
3
4
4
4
6⅜
6⅜
6⅜
6⅜
7
E
27
27
27
27
28
Pump
size
Supply &
Return
Tappings
1¼"
1¼"
1¼"
1¼"
1¼"
BOILER RATINGS, CAPACITIES & DIMENSION
Table 2 - RATINGS AND CAPACITIES
Model #
-50
-100
-125
-150
-200
(1)
Mbh = 1000 Btu per hour
(2)
Net Water Ratings shown based on piping and pickup allowance of 1.15.
Input
Btu/hr
50,000
100,000
125,000
150,000
199,999
Heating
Capacity
(1)
Mbh
42
82
103
122
160
Net
Rating
Water,
Mbh
37
71
90
1060
139
AFUE
(1)
(2)
83.0%
82.0%
82.0%
80.0%
80.0%
No.
of
Burners
1
2
3
3
4
Water
Content
(Gals.)
2.4
4.0
5.6
5.6
7.2
Contact manufacturer before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination Aquastat Relay, Theraltimeter Gauge,
Circulator, Main Gas Burners, Electric Ignition System, A.S.M.E relief Valve, Drain Valve, Induced Draft Fan, and Safety Pressure Switch
All boilers are design certied for installation on non-combustible oors. For installation on combustible oors, use combustible oor kit.
Boiler is Category III Designed Certied appliance which requires a special horizontal through the wall venting system. Only HEAT-FAB SAF-T-VENT™, FLEX-L STAR-34™, ProTech™ FasNSeal, and Z-FLEX Z-VENT™ vent material products shall be used.
Electric service to be 120 Volts, 15 Amps, 60 Hz.
5
VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
• Engineered Installations. Must be approved by authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if minimum volume not available.
о Standard Method. Cannot be used if known air
inltration rate is less than 0.40 air changes per hour. See Table 3 for space with boiler only. Use equation for multiple appliances.
Volume ≥ 50 ft3 x Total Input [Mbh]
о Known Air Inltration Rate. See Table 3 for
space with boiler only. Use equation for multiple appliances. Do not use an air inltration rate (ACH) greater than 0.60.
Volume ≥ 15 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
National Gas and Propane Installation Code Requires providing air supply in accordance with:
• All Outdoor Air. Provide permanent opening(s) communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2 Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides and back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
о Does not have draft control device.
• Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code for specic air supply requirements for enclosure or structure where boiler is installed, including air
supply openings and ducts.
Table 3
Input Mbh
50 2500 7500 3750 2500 1875 1500 1250
100 5000 15000 7500 5000 3750 3000 2500
125 6250 18750 9375 6250 4688 3750 3125
150 7500 22500 11250 7500 5625 4500 3750
200 10000 30000 15000 10000 7500 6000 5000
Standard
Method
0.1 0.2 0.3 0.4 0.5 0.6
Known Air Inltration Rate Method (Air Changes Per Hour)
6
CONNECTING SUPPLY & RETURN PIPING
IMPORTANT: Circulators in following illustrations
are mounted on system supply side, but mounting on system return side is also acceptable practice.
1.
Maintain minimum clearance of one inch (25mm) to hot water pipes.
2.
Boiler, when used in connection with refrigeration system, must be installed so chilled medium is piped in parallel with boiler with appropriate valves to prevent chilled medium from entering boiler.
3.
Boiler piping system of hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
4.
Hot water boiler installed above radiation level or as required by the Authority having jurisdiction, must be provided with low water cutoff device either as part of boiler or at time of boiler installation.
5.
When boiler is connected to heating system that utilizes multiple zoned circulators, each circulator must be supplied with ow control valve to prevent gravity circulation.
6.
Hot water boilers and system must be lled with water and maintained to minimum pressure of 12 psi.
7.
Bypass piping is option which gives ability to adjust supply boiler water temperature to t system or condition of installation. This method of piping, however, is not typically required for baseboard heating systems. Typical installations where bypass piping is used are as follows:
A. This method is used to protect boilers from
condensation forming due to low temperature return water. Generally noticed in large converted gravity systems or other large water volume systems. See
B. This method is used to protect systems using
radiant panels and the material they are encased in from high temperature supply water from boiler, and protect boiler from condensate. See and 4.
C. This method is used to protect boilers from
condensate forming as well as protecting heating system from high water temperatures, see
4
.
gure 2
.
gure 3
gure
7
Figure 2 - BYPASS PIPING
CONNECTING SUPPLY & RETURN PIPING
SUPPLY
SYSTEM TEMPERATURE GAUGE
FLOW VALVE
EXPANSION
TANK
Figure 3 - MIXING VALVE PIPING
FEED
WATER
ZONE
CIR.
"B"
VALV E
"A"
VALV E
RETURN
6"
SUPPLY
EXPANSION
TANK
SYSTEM
TEMPERATURE
GAUGE
ZONE
CIR.
RETURN
4 WAY MIXING
VALV E
FEED
WATER
6"
8
CIRCULATOR
VALV E
EXPANSION
TANK
VALV E
RETURN
SUPPLY
12"
MAX.
CIRCULATOR
FLOW
VALV E
SYSTEM
TEMPERATURE
GAUGE
"B"
"A"
SYSTEM
PRIMARY
6"
FEED
WATER
CONNECTING SUPPLY & RETURN PIPING
Figure 4 - PRIMARY SECONDARY PIPING WITH BYPASS
NOTE #1: When using bypass piping, adjust
valves A and B until desired system temperature is obtained.
NOTE #2: Bypass loop must be same size piping as
the supply and return piping.
8.
Installation using circulators is shown in
9.
Installation using zone valves is shown in
10.
For further piping information refer to the I=B=R Installation and Piping Guide.
gure 5
gure 6
.
.
9
CONNECTING SUPPLY & RETURN PIPING
WARNING
To avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation, a discharge line shall be installed to relief valve outlet connection.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from oor or allowable safe point of discharge.
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or place any obstruction in discharge line.
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375° F; or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
WARNING
Burn and scald hazard. Safety relief valve
!
could discharge steam or hot water during operation. Install discharge piping per these instructions.
11.
Install discharge piping from safety relief valve.
• Use ¾" or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C) or greater.
• Individual boiler discharge piping shall be independent of other discharge piping.
• Size and arrange discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate.
• Run pipe as short and straight as possible to location protecting user from scalding and properly drain piping.
• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve outlet and downstream of union (if used).
• Terminate pipe with plain end (not threaded).
10
CIRCULATOR
DRAIN COCK
RELIEF VALVE
HOT WATER
OUTLET
THERMAL
TRAP
PUMP CONTROL
WIRING FOR
THERMOSTAT/
SYSTEM RETURN
PIPING
INLET
COLD WATER
VALV E
TANK ZONE
6"
6"
PRESSURE REDUCING
VALV E
BACKFLOW PREVENTER
REDUCED PRESSURE
GATE VALVE
Figure 5 - Piping with Circulator
REDUCED PRESSURE BACKFLOW PREVENTER
CONNECTING SUPPLY & RETURN PIPING
GATE VALV E
SYSTEM
CIRCULATOR
FLOW CONTROL
OR CHECK VALVE
6"
Figure 6 - Piping with Zone Valves
PRESSURE REDUCING
VALV E
TANK
CIRCULATOR
FEED
WATER
RELIEF VALVE
DRAIN COCK
COLD WATER
INLET
6"
HOT WATER
OUTLET
THERMAL
TRAP
WIRING FOR
THERMOSTAT/
PUMP CONTROL
All installations of boilers and venting should be done only by a qualied expert and in accordance
!
with the appropriate installation manual. Installing or venting a boiler or any other gas appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
WARNING
11
APPLICABLE FEDERAL CODES
NFPA 54/ANSI Z223.1, National Fuel Gas Code and NFPA/
ANSI 211, Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances. These codes contain information on special gas vents for Category II, III and IV appliances, vent sizing, location, air space clearances to combustibles and safe installation practices. The gas vent installer should be familiar with these Federal Codes as well as Local Codes and Regulations.
General Information Gas Vents And Appliances:
By Federal Codes, gas appliances are categorized by
the pressure and temperature of the ue gas vented from the appliance. Category I and II appliances are natural draft (draft hood) vented, with high ue gas temperatures (Category I), and low ue gas temperatures (Category II). Category III and IV appliances are fan forced vents with high temperature (Category III) and low temperature (Category IV) ue gasses. Appliance efciency is directly related to ue gas temperature. Higher efciency appliances remove more heat from the gas, so they will have lower temperature ue products.
VENT SYSTEM MODIFICATION
When ue gas temperatures are lowered, corrosive condensates may form in the gas vent or in the appliance. Condensates may form in Category II, III, IV appliance vents, so special, corrosive resistant venting systems are required for higher efciency appliances.
WARNING
Vents for Category I appliances may not be
!
suitable for use with Category II, III, or IV appliances because condensate may corrode the vent.
WARNING
Vents for Category III appliances may not be
!
suitable for use with Category I appliances because ue gas temperatures may be too
high.
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for the proper venting of the appliances remained connected to it. If this situation occurs, the following test procedure must be followed:
REMOVAL OF BOILER FROM VENTING SYSTEM At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1.
Seal an unused opening in the common venting system.
2.
Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deciencies which could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.
4.
5.
6.
7.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the ame of a match or candle, or smoke from a cigarette, cigar or pipe.
After it has been determined that each appliance remaining connected to a common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, replace dampers and any other gas burning appliances to their previous condition of use.
Any improper operation if the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or the Natural Gas and Propane Installation Code, CAN/CSA B149.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or the Natural Gas and Propane Installation Code, CAN/CSA B149.1.
12
HORIZONTAL VENT PIPE INSTALLATION INSTRUCTIONS
Horizontal Vent Pipe Installation Instructions
(Through the wall)
This boiler is design certied for use with the following venting systems
Company HEAT-FAB
Product SAF-T-VENT™ STAR-34™ Z-VENT™ FasNSeal™
®
FLEX-L
CAUTION
The above vent pipe and ttings are used for venting gas burning category III and
!
IV appliances. Do not use this vent pipe or ttings for venting appliances burning fuels such as wood, oil, kerosene or coal.
CAUTION
!
Do not use this vent pipe and ttings for venting incinerators of any kind.
®
Z-FLEX
®
ProTech
®
WARNING
All installations of boilers and venting should be done only by a qualied expert and in accordance with the appropriate manufacturers manual. Installing or venting
!
a boiler or any other gas appliance with improper methods or materials may result in serious injury or death due to re or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible.
!
WARNING
1.
For correct installation of vent system, read all of these instructions and refer to the vent pipe manufacturer's instructions.
2.
Failure to use this venting system will void the manufacturer’s warranty and may result in rapid deterioration of the venting system, a potential health hazard.
3.
Faulty vent installation can allow toxic fumes to be released into living areas. This may cause serious bodily injury or property damage. Vent performance may also be affected by improper assembly.
4.
Install separate vents for forced exhaust appliances and natural draft appliances. A common vent between natural draft and forced exhaust appliances may cause toxic gases to exhaust through the natural draft appliance rather than to outside air. Breathing exhaust gases will cause serious personal injury or death.
13
HORIZONTAL VENT INSTALLATION INSTRUCTIONS
A. Boilers covered in this section are design-certied as
CATEGORY III for venting, only when installed with manufacturer specied vent system components and installation practices.
B. Install vent pipe beginning at the vent connector and
work toward the vent cap.
C. Vent pipe and ttings MUST NOT be routed into,
through, or within any other vent, such as an existing masonry chimney or factory built chimney. (Recommended installation is shown in gure 7a & 7b page 14, unacceptable installation is shown in gure 8 page 14).
D. Vent pipe lengths. The maximum length is the
combined length of straight horizontal and vertical runs, and the equivalent straight length of ttings. The required lengths for each boiler are as follows:
Vent Pipe Lenghts
Model
DV50/DV100 3" (7.6cm)
DV125 3" (7.6cm) 25 ft (7.6m) w/1 elbow 2 ft (0.6m) w/1 elbow 5 ft (1.5m)
DV150/200 4" (10.2cm) 30 ft (9.1m) w/1 elbow 2 ft (0.6m) w/1 elbow 5 ft (1.5m)
Example: 20 feet (6m) of vent pipe w/1 elbow is equivalent to 15 feet (4.6m) of vent pipe w/2 elbows. Note: condensate trap is not required on models DV150 thru 200.
Vent Pipe
Diameter
Maximum Minimum
30 ft (9.1m) w/condensate Tee & 2
elbows
Vent Lengths
Equivalent Feet
Per Fitting
2 ft (0.6m) w/1 elbow 5 ft (1.5m)
E. Slope horizontal runs upwards not less than 1/4 inch/
foot (21mm/m) from boiler to vent terminal.
F. No portion of the vent pipe should have dips or sags
where condensate could collect, see gure 9 on page 14 for a typical vent system.
G. Rigidly support vent pipe every 5 feet and at the
elbows. Plumbers straps may be used.
H. Clearances and enclosures. ALL vent pipe and ttings
must be installed with appropriate air space clearances to combustibles. These air space clearances apply to indoor or outdoor vents, whether they are open, enclosed, horizontal or vertical or pass through oors, walls, roofs, or framed spaces. The appropriate air space clearances should be observed to joists, studs, suboors, plywood, drywall, or plaster enclosures, insulated sheathing, rafters, roong, and any other combustible material. The minimum air space clearance also applies to electrical wires and any kind of building
insulation. I. Do not insulate or otherwise wrap vent pipe or ttings. J. For Horizontal runs maintain minimum clearance of
6 inches from vent pipe to any combustible material,
electric wires, and building materials.
14
Loading...
+ 30 hidden pages