LEDEP09
INSTALLATION INSTRUCTIONS
SWITCHED LIVE EARTHNEUTRAL
When wiring a back lit panel
When wiring Thea downlights
fig 1 fig 2
Indicator LED
driver
7
+
+
-
8
Plug and Play connectors
UNSWITCHED
LIVE CIRCUIT
PERMANENT LIVE
(TO EMERGENCY LED
UNITS ONLY)
LOOP OUT TO NEXT
EMERGENCY LED
POSITION
SWITCHED LIVE
CIRCUIT
(TO ALL LED UNITS)
LOOP OUT TO NEXT
LED UNIT
4
3
Emergency driver Battery
Unswitched
supply input
L-Brown
N-Blue
Input external
Output LED unit
LED DRIVER
LED UNIT
See overleaf for single mains circuit options (1x4 core cable)
EN
Installation
1. Refer to the LED unit installation instructions, install all non-emergency LED units.
2. For each emergency light position, drill an 18mm hole close to the LED unit. This
is for the LEDEP09 indicator LED.
3. SWITCHED LIVE CIRCUIT
3
Connect the LED driver mains cable to the switched live supply.
4. UNSWITCHED LIVE CIRCUIT
4
Connect the LEDEP09 live and neutral terminals to the unswitched live supply.
5. Attach plug & play connector to relevant terminals dependant on LED product
being used (see fig1 / fig 2)
6. Fit end covers to both ends of the LEDEP09.
7
7. Connect the battery pack to the LEDEP09 (plug & play).
8. Connect the LEDEP09 output wires with plug and play connectors to the relevant
8
connectors of the LED unit and LED driver.
9. Feed the junction boxes/connectors and LEDEP09 though the ceiling hole.
UNSWITCHED
LIVE CIRCUIT
PERMANENT LIVE
(TO EMERGENCY LED
UNITS ONLY)
LOOP OUT TO NEXT
EMERGENCY LED
POSITION
SWITCHED LIVE
CIRCUIT
(TO ALL LED UNITS)
LOOP OUT TO NEXT
LED UNIT
driver
7
+
+
-
8
Plug and Play connectors
4
3
Emergency driver Battery
Unswitched
supply input
L-Brown
N-Blue
Input external
Output LED unit
LED DRIVER
LED UNIT
10. Feed the indicator LED down through the hole.
11. Fit the indicator housing to the indicator LED, then press the housing into the
ceiling.
Note: If the drilled hole is slightly larger than 18mm, it may be necessary to apply a
little adhesive to the housing to secure it.
12. Fit the LED unit into the ceiling.
13. See overleaf for commissioning.
Indicator LED
EN
t +44 (0) 1604 495 151 f +44 (0) 1604 495 095 e sales@collingwoodgroup.com w collingwoodlighting.com
FR
t +33 (0) 4 816 816 10 f +33 (0) 4 816 816 11 e ventes@collingwoodgroup.com w collingwoodlighting.com
Collingwood Lighting, Brooklands House, Sywell Aerodrome, Sywell, Northampton NN6 0BT, United Kingdom
HLI 1196 V2

LEDEP09
INSTALLATION INSTRUCTIONS
When wiring a back lit panel When wiring Thea downlights
fig 1 fig 2
UNSWITCHED LIVEEARTHSWITCHED LIVE NEUTRAL
Emergency driver Battery
SWITCHED AND
UNSWITCHED MAINS
SUPPLY
LOOP OUT TO ALL
LED POSITIONS
Unswitched
supply input
L-Brown
N-Blue
LED DRIVER
Input external
Output LED unit
LED UNIT
driver
EN
Emergency Pack Commissioning
1. Install unit in ceiling according to the instructions.
2. Provide an uninterrupted mains power supply for 24 hours.
3. Check that the indicator LED light is lit. This confirms that the batteries are
charging.
4. Remove the mains supply – the lamp will operate under battery power for 3 hours
minimum.
5. Restore mains power to the unit, check light functions correctly.
Indicator LED
+
+
-
Plug and Play connectors
SWITCHED AND
UNSWITCHED MAINS
SUPPLY
LOOP OUT TO ALL
LED POSITIONS
Note
• In normal operation, the green LED will be constantly lit to indicate that the
battery is charging. If the green LED is ever not lit, investigate immediately and
rectify the fault.
• Periodic testing of the unit must be performed in line with the appropriate
regulations.
Indicator LED
Emergency driver Battery
Unswitched
supply input
L-Brown
N-Blue
LED DRIVER
Input external
Output LED unit
LED UNIT
driver
+
+
-
Plug and Play connectors
Battery must be replaced when the unit no longer meet it’s rated emergency duration,
or if a battery fault occurs. Contact Collingwood Lighting for a suitable replacement.
EN
t +44 (0) 1604 495 151 f +44 (0) 1604 495 095 e sales@collingwoodgroup.com w collingwoodlighting.com
FR
t +33 (0) 4 816 816 10 f +33 (0) 4 816 816 11 e ventes@collingwoodgroup.com w collingwoodlighting.com
Collingwood Lighting, Brooklands House, Sywell Aerodrome, Sywell, Northampton NN6 0BT, United Kingdom
HLI 1196 V2