LEDEP08
INSTALLATION INSTRUCTIONS
SWITCHED LIVE EARTHNEUTRAL
UNSWITCHED LIVE CIRCUIT
(TO EMERGENCY LED UNITS ONLY)
EMERGENCY LED POSITION
See overleaf for single mains circuit option (1 x 4-core cable)
PERMANENT LIVE
LOOP OUT TO NEXT
SWITCHED LIVE CIRCUIT
(TO ALL LED UNITS)
LOOP OUT TO
NEXT LED UNIT
4
3
Ø7mm MAX
Plug and Play connectors
8
NOT USED
NOT USED
UNSW. L
N
NOT USED
SW. L OUT
SW. L IN
LED UNIT
LEDEP08
LED DRIVER
NOT
USED
BATT
+-
+-
POWER
LED
IND
+-
NOT USED
EN
Installation
1. Refer to the LED unit installation instructions, cut
the downlight holes and install all non-emergency
LED units.
2. For each emergency light position, drill an 8mm
hole close to the downlight hole. This is for the
LEDEP08 indicator LED.
3
3. SWITCHED LIVE CIRCUIT
Connect the LED driver mains cable to the
switched live supply.
4
4. UNSWITCHED LIVE CIRCUIT
Connect the LEDEP08 unswitched live and neutral
terminals to the unswitched live supply.
5. Fit cable clamps to secure the wires at both ends
of the LEDEP08.
6. Fit end covers to both ends of the LEDEP08.
EN
t +44 (0) 1604 495 151 f +44 (0) 1604 495 095 e sales@collingwoodgroup.com w collingwoodlighting.com
FR
t +33 (0) 4 816 816 10 f +33 (0) 4 816 816 11 e ventes@collingwoodgroup.com w collingwoodlighting.com
DE
t +49 (0)89 411123 777 f +49 (0)89 411123 778 e verkauf@collingwoodgroup.com w collingwoodlighting.com
Collingwood Lighting, Brooklands House, Sywell Aerodrome, Sywell, Northampton NN6 0BT, United Kingdom
7. Connect the battery pack to the LEDEP08 (plug &
play).
8
8. Connect the LEDEP08 output wires with plug and
play connectors to the relevant connectors of the
LED unit and LED driver.
9. Feed the junction boxes/connectors and LEDEP08
though the ceiling hole.
10. Feed the indicator LED down through the 8mm
hole.
11. Fit the indicator housing to the indicator LED, then
press the housing into the ceiling.
Note: If the drilled hole is slightly larger than 8mm,
it may be necessary to apply a little adhesive to the
housing to secure it.
12. Fit the LED unit into the ceiling.
13. See overleaf for commissioning.
HLI 1176 V1

LEDEP08
INSTALLATION INSTRUCTIONS / CONSIGNES D’INSTALLATION / MONTAGEANLEITUNG
UNSWITCHED LIVEEARTHSWITCHED LIVE NEUTRAL
SWITCHED AND UNSWITCHED
MAINS SUPPLY
LOOP OUT TO ALL
LED POSITIONS
EN
Ø7mm MAX
Plug and Play connectors
8
NOT USED
NOT USED
UNSW. L
N
NOT USED
SW. L OUT
SW. L IN
LED UNIT
LEDEP08
LED DRIVER
NOT
USED
BATT
+-
+-
POWER
LED
IND
+-
NOT USED
Emergency Pack Commissioning
1. Install unit in ceiling according to the instructions.
2. Provide an uninterrupted mains power supply for
24 hours.
3. Check that the indicator LED light is lit. This
confirms that the batteries are charging.
4. Remove the mains supply – the lamp will operate
under battery power for 3 hours minimum.
5. Restore mains power to the unit, check light
functions correctly.
Note
• In normal operation, the green LED will be
constantly lit to indicate that the battery is
charging. If the green LED is ever not lit,
investigate immediately and rectify the fault.
• Periodic testing of the unit must be performed in
line with the appropriate regulations.
EN
t +44 (0) 1604 495 151 f +44 (0) 1604 495 095 e sales@collingwoodgroup.com w collingwoodlighting.com
FR
t +33 (0) 4 816 816 10 f +33 (0) 4 816 816 11 e ventes@collingwoodgroup.com w collingwoodlighting.com
DE
t +49 (0)89 411123 777 f +49 (0)89 411123 778 e verkauf@collingwoodgroup.com w collingwoodlighting.com
Collingwood Lighting, Brooklands House, Sywell Aerodrome, Sywell, Northampton NN6 0BT, United Kingdom
HLI 1176 V1