The 18200-00 is a USB 1.1 low-speed device. It is designed for USB 1.1 ports, and was tested for full
compatibility with both USB 1.1 and USB 2.0 ports.
The 18200-00 features eight analog inputs, two 10-bit analog outputs, 16 digital I/O connections, and one
32-bit external event counter. The 18200-00 is powered by the +5 volt USB supply from your computer.
No external power is required.
The 18200-00 analog inputs are software configurable for either eight 11-bit single-ended inputs, or four
12-bit differential inputs. An on-board industry standard 82C55 programmable peripheral interface chip
provides the 16 digital I/O lines in two 8-bit ports. You can configure each digital port independently for
either input or output.
About this Operating Manual...............................................................................................................5
What you will learn from this manual ................................................................................................................5
Conventions in this manual ................................................................................................................................5
Where to find more information.........................................................................................................................5
Chapter 1
Introducing the 18200-00......................................................................................................................6
Unpacking the 18200-00 ....................................................................................................................................9
Installing the software ......................................................................................................................................10
Installing the hardware .....................................................................................................................................10
USB connector.................................................................................................................................................................12
LED .................................................................................................................................................................................12
Main connector and pin out .............................................................................................................................................13
Analog input terminals (CH0 IN - CH7 IN).....................................................................................................................14
Digital I/O terminals (Port A0 to A7, and Port B0 to B7)................................................................................................17
Power terminals ...............................................................................................................................................................17
Analog input section......................................................................................... Error! Bookmark not defined.
Analog output section....................................................................................... Error! Bookmark not defined.
Digital input/output........................................................................................... Error! Bookmark not defined.
External trigger................................................................................................. Error! Bookmark not defined.
Counter section................................................................................................. Error! Bookmark not defined.
Non-volatile memory........................................................................................ Error! Bookmark not defined.
Power................................................................................................................ Error! Bookmark not defined.
General ............................................................................................................. Error! Bookmark not defined.
3
Page 4
18200-00 Operating Manual
Environmental .................................................................................................. Error! Bookmark not defined.
Mechanical ....................................................................................................... Error! Bookmark not defined.
Main connector and pin out.............................................................................. Error! Bookmark not defined.
4-channel differential mode ............................................................................................. Error! Bookmark not defined.
8-channel single-ended mode........................................................................................... Error! Bookmark not defined.
4
Page 5
Preface
About this Operating Manual
What you will learn from this manual
This manual explains how to install, configure, and use the 18200-00 so that you get the most out of its
temperature measurement and data logging features.
This manual also refers you to related documents available on our web site, and to technical support resources.
Conventions in this manual
For more information on …
Text presented in a box signifies additional information and helpful hints related to the subject matter you are
reading.
Caution! Shaded caution statements present information to help you avoid injuring yourself and others,
damaging your hardware, or losing your data.
<#:#> Angle brackets that enclose numbers separated by a colon signify a range of numbers, such as those assigned
to registers, bit settings, etc.
bold text Bold text is used for the names of objects on the screen, such as buttons, text boxes, and check boxes. For
example:
1. Insert the disk or CD and click the OK button.
italic text Italic text is used for the names of manuals and help topic titles, and to emphasize a word or phrase. For
example:
The InstaCal® installation procedure is explained in the Quick Start Guide. Never touch the exposed pins or circuit connections on the board
Where to find more information
The following electronic documents provide helpful information relevant to the operation of the 18200-00.
Cole-Parmer's Specifications: 18200-00 (the PDF version of the Electrical Specification Chapter in this
guide) is available on our web site at www.coleparmer.com/catalog/MoreInfo/18200-00-spec.pdf
Cole-Parmer's Quick Start Guide is available on our web site at
18200-00 Operating Manual (this document) is also available on our web site at
www.coleparmer.com/cpusbdaq1/18200-00.pdf
.
5
Page 6
Chapter 1
Introducing the 18200-00
This manual contains all of the information you need to connect the 18200-00 to your computer and to the
signals you want to measure. The 18200-00 is part of the Cole-Parmer brand of USB-based data acquisition
products.
The 18200-00 is a USB 1.1 low-speed device supported under popular Microsoft
systems. It is designed for USB 1.1 ports, and was tested for full compatibility with both USB 1.1 and USB 2.0
ports.
Refer to the "Be sure you are using the latest system software
make sure you are using the latest USB drivers.
The 18200-00 features eight analog inputs, two 10-bit analog outputs, 16 digital I/O connections, and one 32-bit
external event counter. The 18200-00 is powered by the +5 volt USB supply from your computer. No external
power is required.
The 18200-00 analog inputs are software configurable for either eight 11-bit single-ended inputs, or four 12-bit
differential inputs. An on-board industry standard 82C55 programmable peripheral interface chip provides the
16 digital I/O lines in two 8-bit ports. You can configure each digital port independently for either input or
output.
The 18200-00 is shown in Figure 1-1. I/O connections are made to the screw terminals located along each side
of the 18200-00.
" note in Chapter 2, "Installing the 18200-00," to
®
Windows® operating
Figure 1-1. 18200-00
6
Page 7
18200-00 Operating Manual Introducing the 18200-00
18200-00 block diagram
18200-00 functions are illustrated in the block diagram shown here.
USB1.1
Compliant
Interface
USB
Microcontroller
82C55 DIO
PortAPort
B
88
Screw terminal I/O connector
Analog Input
8 SE (
4 Diff. (
11-bit ) channels
12-bit ) channels
Analog Output
10-bit
2 channels
32-bit
Event Counter
1 channel
or
8
2
1
Figure 1-2. 18200-00 functional block diagram
Software features
For information on the features of InstaCal and the other software included with your 18200-00, refer to the
Quick Start Guide that shipped with your device. The Quick Start Guide is also available in PDF at
18200-00 Operating Manual Introducing the 18200-00
Connecting a 18200-00 to your computer is easy
Installing a data acquisition device has never been easier.
The 18200-00 relies upon the Microsoft Human Interface Device (HID) class drivers. The HID class
drivers ship with every copy of Windows that is designed to work with USB ports. We use the Microsoft
HID because it is a standard, and its performance delivers full control and maximizes data transfer rates for
your 18200-00. No third-party device driver is required.
The 18200-00 is plug-and-play. There are no jumpers to position, DIP switches to set, or interrupts to
configure.
You can connect the 18200-00 before or after you install the software, and without powering down your
computer first. When you connect an HID to your system, your computer automatically detects it and
configures the necessary software. You can connect and power multiple HID peripherals to your system
using a USB hub.
You can connect your system to various devices using a standard four-wire cable. The USB connector
replaces the serial and parallel port connectors with one standardized plug and port combination.
You do not need a separate power supply module. The USB automatically delivers the electrical power
required by each peripheral connected to your system.
Data can flow two ways between a computer and peripheral over USB connections.
8
Page 9
Installing the 18200-00
What comes with your 18200-00 shipment?
As you unpack your 18200-00, verify that the following components are included.
Hardware
18200-00
Chapter 2
USB cable (2 meter length)
Additional documentation
In addition to this hardware manual, you should also receive the Quick Start Guide (available in PDF at
software you received with your 18200-80 and information regarding installation of that software. Please read
this booklet completely before installing any software or hardware.
.). This booklet supplies a brief description of the
Unpacking the 18200-00
As with any electronic device, you should take care while handling to avoid damage from static
electricity. Before removing the 18200-00 from its packaging, ground yourself using a wrist strap or by simply
touching the computer chassis or other grounded object to eliminate any stored static charge.
If your 18200-00 is damaged, notify Cole-Parmer immediately by phone, fax, or email:
Refer to the Quick Start Guide for instructions on installingthe software on the C-P Data Acquisition Software
CD. This booklet is available in PDF at www.coleparmer.com/catalog/MoreInfo/CP-Quick-Start.pdf.
Installing the hardware
Be sure you are using the latest system software
Before you connect the 18200-00, make sure that you are using the latest versions of the USB drivers.
Before installing the 18200-00, download and install the latest Microsoft Windows updates. In particular, when
using Windows XP, make sure you have XP Hotfix KB822603 installed. This update is intended to address a
serious error in Usbport.sys when you operate a USB device. You can run Windows Update or download the
update from www.microsoft.com/downloads/details.aspx?familyid=733dd867-56a0-4956-b7fe-
e85b688b7f86&displaylang=en. For more information, refer to the Microsoft Knowledge Base article
"AvailabilityoftheWindowsXPSP1USB1.1and2.0update." This article is available at
support.microsoft.com/?kbid=822603.
To connect the 18200-00 to your system, turn your computer on, and connect the USB cable to a USB port on
your computer or to an external USB hub that is connected to your computer. The USB cable provides power
and communication to the 18200-00.
When you connect the 18200-00 for the first time, a Found New Hardware popup balloon (Windows XP) or
dialog (other Windows versions) opens as the 18200-00 is detected by your computer.
Another
USB Human Interface Device.
When this balloon or dialog closes, the installation is complete. The LED on the 18200-00 should flash and then
remain lit. This indicates that communication is established between the 18200-00 and your computer.
Caution! Do not disconnect any device from the USB bus while the computer is communicating with the
If the LED turns off
If the LED is illuminated but then turns off, the computer has lost communication with the 18200-00. To restore
communication, disconnect the USB cable from the computer, and then reconnect it. This should restore
communication, and the LED should turn back on.
Found New Hardware balloon or dialog opens after the first closes that identifies the 18200-00 as a
18200-00, or you may lose data and/or your ability to communicate with the 18200-00.
10
Page 11
Chapter 3
Functional Details
Theory of operation - analog input acquisition modes
The 18200-00 can acquire analog input data in three different modes – software paced, continuous scan, and
burst scan.
Software paced mode
In software paced mode, you can acquire one analog sample at a time. You initiate the A/D conversion by
calling a software command. The analog value is converted to digital and returned to the computer. You can
repeat this procedure until you have the total number of samples that you want from one channel.
Software pacing is limited by the 20 mS round-trip requirement of a USB interrupt-type endpoint operation.
The maximum throughput sample rate in software paced mode is 50 S/s.
Continuous scan mode
In continuous scan mode, you can acquire data from up to eight channels. The analog data is continuously
acquired, converted to digital values, and written to an on-board FIFO buffer until you stop the scan. The FIFO
buffer is serviced in blocks as the data is transferred from the 18200-00 to the memory buffer on your computer.
The maximum continuous scan rate of 1.2 kS/s is an aggregate rate. The total acquisition rate for all channels
cannot exceed 1.2 kS/s. You can acquire data from one channel at 1.2 kS/s, two channels at 600 S/s and four
channels at 300 S/s. You can start a continuous scan with either a software command or with an external
hardware trigger event.
Burst scan mode
In burst scan mode, you can acquire data using the full capacity of the 18200-00 4 k sample FIFO. You can
initiate a single acquisition sequence of up to 4096 samples channels by either a software command or an
external hardware trigger. The captured data is then read from the FIFO and transferred to a user buffer in the
host PC.
Burst scans are limited to the depth of the on-board memory, as the data is acquired at a rate faster than it can be
transferred to the computer. The maximum sampling rate is an aggregate rate. The maximum rates that you can
acquire data using burst scan mode is 8 kS/s divided by the number of channels in the scan.
11
Page 12
18200-00 Operating Manual Functional Details
External components
The 18200-00 has the following external components, as shown in Figure 3-1.
USB connector
LED
Screw terminal banks (2)
Screw terminals
Pins 1-20
LED
Screw terminals
Pins 21-40
USB connector/cable
Figure 3-1. 18200-00 external components
USB connector
The USB connector is on the right side of the 18200-00 housing. This connector provides +5V power and
communication. The voltage supplied through the USB connector is system-dependent, and may be less than
5V. No external power supply is required.
LED
The LED on the front of the housing indicates the communication status of the 18200-00. It uses up to 5 mA of
current and cannot be disabled. Table 3-1 defines the function of the 18200-00 LED.
Table 3-1. LED illumination
When the LED is… It indicates…
Steady green The 18200-00 is connected to a computer or external USB hub.
Blinks continuously Data is being transferred.
Blinks three times Initial communication is established between the 18200-00 and the computer.
Blinks at a slow rate
The analog input is configured for external trigger. The LED stops blinking and illuminates
steady green when the trigger is received.
Screw terminal wiring
The 18200-00 has two rows of screw terminals—one row on the top edge of the housing, and one row on the
bottom edge. Each row has 20 connections. Pin numbers are identified in Figure 3-2.
12
Page 13
18200-00 Operating Manual Functional Details
Figure 3-2. 18200-00 Screw terminal pin numbers
Screw terminal – pins 1-20
The screw terminals on the top edge of the 18200-00 (pins 1 to 20) provide the following connections:
Eight analog input connections (
CH0 IN to CH7 IN)
Two analog output connections (D/A OUT 0 to D/A OUT 1)
One external trigger source (TRIG_IN)
One external event counter connection (
CTR)
Seven GND connections (GND)
One calibration terminal (CAL)
Screw terminal – pins 21-40
The screw terminals on the bottom edge of the (pins 21 to 40) provide the following connections:
16 digital I/O connections (
PortA0 to Port A7, and Port B0 to Port B7)
One power connection (PC+5 V)
Three ground connections (GND)
Main connector and pin out
Connector type Screw terminal
Wire gauge range 16 AWG to 30 AWG
13
Page 14
18200-00 Operating Manual Functional Details
CH7 IN
CH6 IN
CH3 IN LO
CH3 IN HI
CH2 IN LO
20 CTR
19 GND
18 TRIG_IN
17 GND
16 CAL
15 GND
14 D/A OUT 1
13 D/A OUT 0
12 GND1110
9GND
8
7CH2 IN HI
6GND
5CH1 IN LO
4CH1 IN HI
3GND
2CH0 IN LO
1CH0 IN HI
20 CTR
19 GND
18 TRIG_IN
17 GND
16 CAL
15 GND
14 D/A OUT 1
13 D/A OUT 0
12 GND1110
9GND
CH5 IN
8
7CH4 IN
6GND
5CH3 IN
4CH2 IN
3GND
2CH1 IN
1CH0 IN
GND40
Port B7 39
Port B6 38
Port B5 37
Port B4 36
GND31
PC+5V 30
GND29
Port B3 35
Port B2 34
Port B1 33
Port A7 28
Port B0 32
Port A6 27
Port A5 26
Port A4 25
Port A3 24
Port A2 23
4-channel differential mode pin out
GND40
Port B7 39
Port B6 38
Port B5 37
Port A1 22
Port A0 21
Port B4 36
8-channel single-ended mode pin out
GND31
PC+5V 30
GND29
Port B3 35
Port B2 34
Port B1 33
Port A7 28
Port B0 32
Port A6 27
Port A5 26
Port A4 25
Port A3 24
Port A2 23
Port A1 22
Port A0 21
Analog input terminals (CH0 IN - CH7 IN)
You can connect up to eight analog input connections to the screw terminal containing pins 1 to 20 (CH0 IN
through CH7 IN). Refer to the pinout diagrams
You can configure the analog input channels as eight single-ended channels or four differential channels. When
configured for differential mode, each analog input has 12-bit resolution. When configured for single-ended
mode, each analog input has 11-bit resolution, due to restrictions imposed by the A/D converter.
Single-ended configuration
When all of the analog input channels are configured for single-ended input mode, eight analog channels are
available. The input signal is referenced to signal ground (GND), and delivered through two wires:
The wire carrying the signal to be measured connects to CH# IN.
The second wire connects to GND.
The input range for single-ended mode is ±10V. No other ranges are supported in single-ended mode. Figure
3-3 illustrates a typical single-ended measurement connection.
above for the location of these pins.
Figure 3-3. Single-ended measurement connection
14
Page 15
18200-00 Operating Manual Functional Details
Single-ended measurements using differential channels
To perform a single-ended measurement using differential channels, connect the signal to "CHn IN HI" input,
and ground the associated "CHn IN LO" input.
Differential configuration
When all of the analog input channels are configured for differential input mode, four analog channels are
available. In differential mode, the input signal is measured with respect to the low input.
The input signal is delivered through three wires:
The wire carrying the signal to be measured connects to CH0 IN HI, CH1 IN HI, CH2 IN HI, or
CH3 IN HI.
The wire carrying the reference signal connects to CH0 IN LO, CH1 IN LO, CH2 IN LO, or CH3 IN LO.
The third wire connects to GND.
A low-noise precision programmable gain amplifier (PGA) is available on differential channels to provide gains
of up to 20 and a dynamic range of up to 12-bits. Differential mode input voltage ranges are ±20 V, ±10 V,
±5 V, ±4 V, ±2.5 V, ±2.0 V, 1.25 V, and ±1.0 V.
In differential mode, the following two requirements must be met for linear operation:
Any analog input must remain in the −10V to +20V range with respect to ground at all times.
The maximum differential voltage on any given analog input pair must remain within the selected voltage
range.
The input [common-mode voltage + signal] of the differential channel must be in the
−10 V to +20 V range in order to yield a useful result. For example, you input a 4 V pp sine wave to CHHI, and
apply the same sine wave 180° out of phase to CHLO. The common mode voltage is 0 V. The differential input
voltage swings from 4 V-(-4 V) = 8 V to -4 V-4 V = -8V. Both inputs satisfy the -10 V to +20 V input range
requirement, and the differential voltage is suited for the ±10 V input range (see Figure 3-4).
+4V
CHHI
CHLO
0V
-4V
8V Differential
+4V
-4V
Figure 3-4. Differential Voltage Example: Common Mode Voltage of 0 V
+/-8V
Measured Signal
If you increase the common mode voltage to 11 V, the differential remains at ±8 V. Although the [commonmode voltage + signal] on each input now has a range of +7 V to +15 V, both inputs still satisfy the -10 V to
+20 V input requirement (see Figure 3-5).
15
Page 16
18200-00 Operating Manual Functional Details
+15V
CHHI
+11V
Measured Signal
+/-8V
CHLO
8V Differential
+11V
+7V
Figure 3-5. Differential Voltage Example: Common Mode Voltage of 11V
If you decrease the common-mode voltage to -7 V, the differential stays at ±8 V. However, the solution now
violates the input range condition of -10 V to +20 V. The voltage on each analog input now swings from -3V to
-11V. Voltages between -10 V and -3 V are resolved, but those below -10 V are clipped (see Figure 3-6).
CHHI
CHLO
-3V
-7V
-11V
-3V
-7V
-11V
3V
8V Differential
+/-7V
Figure 3-6. Differential Voltage Example: Common Mode Voltage of -7 V
Measured Signal
Since the analog inputs are restricted to a −10 V to +20 V signal swing with respect to ground, all ranges except
±20V can realize a linear output for any differential signal with zero common mode voltage and full scale signal
inputs. The ±20 V range is the exception. You cannot put −20 V on CHHI and 0 V on CHLO since this violates
the input range criteria.
Table 3-2 shows some possible inputs and the expected results.
Table 3-2. Sample Inputs and Differential Results
CHHI CHLO Result
-20 V 0 V Invalid
-15 V +5 V Invalid
-10 V 0 V -10 V
-10 V +10 V -20 V
0 V +10 V -10 V
0 V +20 V -20 V
+10 V -10 V +20 V
+10 V 0 V +10 V
+15 V -5 V +20 V
+20 V 0 +20 V
For more information on analog signal connections
For more information on single-ended and differential inputs, refer to the Guide to Signal Connections (this
document is available on our web site at www.coleparmer.com/catalog/MoreInfo/CPsignals.pdf.)
16
Page 17
18200-00 Operating Manual Functional Details
Digital I/O terminals (Port A0 to A7, and Port B0 to B7)
You can connect up to 16 digital I/O lines to the screw terminal containing pins 21 to 40 (Port A0 to Port A7,
and Port B0 to Port B7.) Refer to the pinout diagrams on page 14 for the location of these pins. You can
configure each digital port for either input or output.
When you configure the digital bits for input, you can use the digital I/O terminals to detect the state of any
TTL level input. Refer to the switch shown in Figure 3-7 and the schematic shown in Figure 3-8. If the switch is
set to the +5 V input, Port A0 reads TRUE (1). If you move the switch to GND, Port A0 reads FALSE.
Figure 3-7. Digital connection Port A0 detecting the state of a switch
Port A0
+5V+GND
Figure 3-8. Schematic showing switch detection by digital channel Port A0
For more information on digital signal connections
For more information on digital signal connections and digital I/O techniques, refer to the Guide to Signal
Connections (available on our web site at www.coleparmer.com/catalog/MoreInfo/CPsignals.pdf.)
Power terminals
The PC +5 V connection (pin 30) is on the bottom screw terminal of the 18200-00. Refer to the pinout diagrams
on page 14 for the location of this pin. This terminal draws power from the USB connector. The +5 V screw
terminal is a 5 volt output that is supplied by the host computer.
Caution! The +5V terminal is an output. Do not connect to an external power supply or you may damage
the 18200-00 and possibly the computer.
The maximum total output current that can be drawn from all 18200-00 connections (power, analog and digital
outputs) is 500 mA. This maximum applies to most personal computers and self-powered USB hubs.
Bus-powered hubs and notebook computers may limit the maximum available output current to 100 mA.
Just connecting the 18200-00 to your computer draws 20 mA of current from the USB +5 V supply. Once you
start running applications with the 18200-00, each DIO bit can draw up to 2.5 mA, and each analog output can
17
Page 18
18200-00 Operating Manual Functional Details
draw 30 mA. The maximum amount of +5 V current available for experimental use, over and above that
required by the 18200-00, is the difference between the total current requirement of the USB device (based on
the application), and the allowed current draw of the PC platform (500 mA for desktop PCs and self-powered
hubs, or 100 mA for bus-powered hubs and notebook computers).
With all outputs at their maximum output current, you can calculate the total current requirement of the 1820000 USB +5 V as follows:
(18200-00 @ 20 mA) + (16 DIO @ 2.5 mA ea) + (2 AO @ 30 mA ea ) = 120 mA
For an application running on a PC or powered hub, the maximum available excess current is 500 mA−120 mA
= 380 mA. This number is the total maximum available current at the PC+5V screw terminals. Measurement
Computing highly recommends that you figure in a safety factor of 20% below this maximum current loading
for your applications. A conservative, safe user maximum in this case would be in the 300-320 mA range.
Since laptop computers typically allow up to 100 mA, the 18200-00 in a fully-loaded configuration may be
above that allowed by the computer. In this case, you must determine the per-pin loading in the application to
ensure that the maximum loading criteria is met. The per-pin loading is calculated by simply dividing the +5 V
by the load impedance of the pin in question.
Ground terminals
The 10 ground connections (GND) are identical, and provide a common ground for all 18200-00 functions.
Refer to the pinout diagrams on page 14 for the location of the GND terminal pins.
Calibration terminal
The CAL connection (pin 16) is an output you should use only to calibrate the 18200-00. Refer to the pinout
diagrams on page 14 for the location of this pin. Calibration of the 18200-00 is software-controlled via InstaCal.
Trigger terminal
The TRIG_IN connection (pin 18) is an external digital trigger input. You can configure this terminal with
software for either trigger high or trigger low.
Counter terminal
The CTR connection (Pin 20) is input to the 32-bit external event. Refer to the pinout diagrams on page 14 for
the location of this pin. The internal counter increments when the TTL levels transition from low to high. The
counter can count frequencies of up to 1 MHz.
Accuracy
The overall accuracy of any instrument is limited by the error components within the system. Quite often,
resolution is incorrectly used to quantify the performance of a measurement product. While "12-bits" or "1 part
in 4096" does indicate what can be resolved, it provides little insight into the quality of an absolute
measurement. Accuracy specifications describe the actual results that can be realized with a measurement
device.
There are three types of errors which affect the accuracy of a measurement system:
offset
gain
nonlinearity.
18
Page 19
18200-00 Operating Manual Functional Details
The primary error sources in the 18200-00 are offset and gain. Nonlinearity is small in the 18200-00, and is not
significant as an error source with respect to offset and gain.
Figure 3-9 shows an ideal, error-free, 18200-00 transfer function. The typical calibrated accuracy of the 1820000 is range-dependent, as explained in the "Specifications
" chapter of this document. We use a ±10 V range
here as an example of what you can expect when performing a measurement in this range.
Inp ut Vo lta ge
+FS
Output Code
0
2048
4095
-FS
Figure 3-9. Ideal ADC transfer function
The 18200-00 offset error is measured at mid-scale. Ideally, a zero volt input should produce an output code of
2048. Any deviation from this is an offset error. Figure 3-10 shows the 18200-00 transfer function with an
offset error. The typical offset error specification on the ±10 V range is ±9.77 mV. Offset error affects all codes
equally by shifting the entire transfer function up or down along the input voltage axis.
The accuracy plots in Figure 3-10 are drawn for clarity and are not drawn to scale.
Inp ut Vo lta ge
+FS
Ideal
2
2048
9.77mV
Output Code
4095
0
Ac t ua l
Offset= 9.77m V
-FS
Figure 3-10. ADC transfer function with offset error
19
Page 20
18200-00 Operating Manual Functional Details
V
V
V
Gain error is a change in the slope of the transfer function from the ideal, and is typically expressed as a
percentage of full-scale. Figure 3-11 shows the 18200-00 transfer function with gain error. Gain error is easily
converted to voltage by multiplying the full-scale (FS) input by the error.
The accuracy plots in Figure 3-11 are drawn for clarity and are not drawn to scale.
Inp ut Volta g e
+FS
Id ea l
Gain error=+0.2%, or +20 m
Gain e rror= -0.2%, or -20 m V
Ac t ua l
Output Code
0
2048
4095
-FS
Figure 3-11. ADC Transfer function with gain error
For example, the 18200-00 exhibits a typical calibrated gain error of ±0.2% on all ranges. For the ±10 V range,
this would yield 10 V × ±0.002 = ±20 mV. This means that at full scale, neglecting the effect of offset for the
moment, the measurement would be within 20 mV of the actual value. Note that gain error is expressed as a
ratio. Values near ±FS are more affected from an absolute voltage standpoint than are values near mid-scale,
which see little or no voltage error.
Combining these two error sources in Figure 3-12, we have a plot of the error band of the 18200-00 for the
±10 V range. This is a graphical version of the typical accuracy specification of the product.
The accuracy plots in Figure 3-12 are drawn for clarity and are not drawn to scale
Ideal + 9.77mV + 20 m V
Ide al
Idea l -(9.77m V + 20 mV)
Inp u t Volta ge
+FS
9.77mV
0
-FS
Figure 3-12. Error band plot
2048
Ideal + 9.77m V + 20 m
Ideal + 9.77m V + 20 m
Ide al
Ide a l -(9.7 7m V + 20 m V)
Output Code
4095
20
Page 21
18200-00 Operating Manual Functional Details
18200-00 channel gain queue feature
The 18200-00's channel gain queue feature allows you to set up a scan sequence with a unique per-channel gain
setting and channel sequence.
The channel gain queue feature removes the restriction of using an ascending channel sequence at a fixed gain.
This feature creates a channel list which is written to local memory on the 18200-00. The channel list is made
up of a channel number and range setting. An example of a four-element list is shown in Table 3-3.
Table 3-3. Sample channel gain queue list
Element Channel Range
0 CH0 BIP10V
1 CH0 BIP5V
2 CH7 BIP10V
3 CH2 BIP1V
When a scan begins with the gain queue enabled, the 18200-00 reads the first element, sets the appropriate
channel number and range, and then acquires a sample. The properties of the next element are then retrieved,
and another sample is acquired. This sequence continues until all elements in the gain queue have been selected.
When the end of the channel list is detected, the sequence returns to the first element in the list.
This sequence repeats until the specified number of samples is gathered. You must carefully match the gain to
the expected voltage range on the associated channel—otherwise, an over range condition can occur. Although
this condition does not damage the 18200-00, it does produce a useless full-scale reading. It can also introduce a
long recovery time from saturation, which can affect the next measurement in the queue.
21
Page 22
Chapter 4
Specifications
Typical for 25°C unless otherwise specified.
Specifications in italic text are guaranteed by design.
Analog input
Parameter Conditions Specification
A/D converter type Successive approximation type
Input voltage range for linear operation,
single-ended mode
Input common-mode voltage range for linear
operation, differential mode
Absolute maximum input voltage CHx to GND ±40V max
Differential 12 bits, no missing codes Resolution (Note 2)
Single ended 11 bits
Source 5 mA max CAL current
Sink 20 µA min, 200 nA typ
8 kS/s
Software configurable channel, range, and
gain.
Note 2: The AD7870 converter only returns 11-bits (0-2047 codes) in single-ended mode.
22
Page 23
18200-00 Operating Manual Specifications
Table 1. Accuracy, differential mode
Range Accuracy (LSB)
±20 V 5.1
±10 V 6.1
±5 V 8.1
±4 V 9.1
±2.5 V 12.1
±2 V 14.1
±1.25 V 20.1
±1 V 24.1
Table 2. Accuracy, single-ended mode
Range Accuracy (LSB)
±10 V 4.0
Table 3. Accuracy components, differential mode - all values are (±)
Range % of Reading Gain Error at FS
(mV)
±20 V 0.2 40 9.766 49.766
±10 V 0.2 20 9.766 29.766
±5 V 0.2 10 9.766 19.766
±4 V 0.2 8 9.766 17.766
±2.5 V 0.2 5 9.766 14.766
±2 V 0.2 4 9.766 13.766
±1.25 V 0.2 2.5 9.766 12.266
±1 V 0.2 2 9.766 11.766
Table 4. Accuracy components, single-ended mode - all values are (±)
Range % of Reading Gain Error at FS
(mV)
±10 V 0.2 20 19.531 39.531
Offset (mV) Accuracy at FS (mV)
Offset (mV) Accuracy at FS (mV)
Analog output
Parameter Conditions Specification
D/A converter type PWM
Resolution 10-bits, 1 in 1024
Maximum output range 0 -5 Volts
Number of channels 2 voltage output
Throughput Software paced 100 S/s single channel mode
50 S/s dual channel mode
Power on and reset voltage Initializes to 000h code
Maximum voltage (Note 3)
Output drive Each D/A OUT 30 mA
Slew rate 0.14 V/mS typ
Note 3: Vs is the USB bus +5V power. The maximum analog output voltage is equal to Vs at no-load.
V is system dependent and may be less than 5 volts.
No load Vs
1 mA load 0.99 * Vs
5 mA load 0.98 * Vs
23
Page 24
18200-00 Operating Manual Specifications
Digital input/output
Digital type 82C55
Number of I/O 16 (Port A0 through A7, Port B0 through B7
Configuration 2 banks of 8
Pull up/pull-down configuration
Input high voltage 2.0 V min, 5.5 V absolute max
Input low voltage 0.8 V max, –0.5 V absolute min
Output high voltage (IOH = -2.5 mA) 3.0 V min
Output low voltage (IOL = 2.5 mA) 0.4 V max
All pins pulled up to Vs via 47K resistors (default). Positions
available for pull down to ground. Hardware selectable via zero ohm
resistors as a factory option.
External trigger
Parameter Conditions Specification
Trigger source (Note 4) External digital TRIG_IN
Trigger mode Software selectable
Trigger latency Burst 25 µs min, 50 µs max
Trigger pulse width Burst 40 µs min
Input high voltage 3.0 V min, 15.0 V absolute max
Input low voltage 0.8 V max
Input leakage current ±1.0 µA
Note 4: TRIG_IN is protected with a 1.5KOhm series resistor.
Level sensitive: user configurable for
TTL level high or low input.
Counter
Counter type Event counter
Number of channels 1
Input source CTR screw terminal
Input type TTL, rising edge triggered
Resolution 32 bits
Schmidt trigger hysteresis 20 mV to 100 mV
Input leakage current ±1 µA
Maximum input frequency 1 MHz
High pulse width 500 ns min
Low pulse width 500 ns min
Input low voltage 0 V min, 1.0 V max
Input high voltage 4.0 V min, 15.0 V max
Non-volatile memory
Memory size 8192 bytes
Memory configuration
Address Range Access Description
0x0000 – 0x17FF Read/Write A/D data (4K samples)
0x1800 – 0x1EFF Read/Write User data area
0x1F00 – 0x1FEF Read/Write Calibration data
0x1FF0 – 0x1FFF Read/Write System data
24
Page 25
18200-00 Operating Manual Specifications
Power
Parameter Conditions Specification
Supply current (Note 5) 20 mA
Connected to Self-Powered Hub 4.5 V min, 5.25 V max +5V USB power available (Note 6)
Connected to Bus-Powered Hub 4.1 V min, 5.25 V max
Connected to Self-Powered Hub 450 mA min, 500 mA max Output current (Note 7)
Connected to Bus-Powered Hub 50 mA min, 100 mA max
Note 5: This is the total current requirement for the 18200-00 which includes up to 5mA for the status
LED.
Note 6: Self-powered refers to USB hubs and hosts with a power supply. Bus-powered refers to USB
hubs and hosts without their own power supply.
Note 7: This refers to the total amount of current that can be sourced from the USB +5V, analog outputs
and digital outputs.
General
Parameter Conditions Specification
25 °C ±30 ppm max USB controller clock error
0 to 70 °C ±50 ppm max
Device type USB 1.1 low-speed
Device compatibility USB 1.1, USB 2.0
Environmental
Operating temperature range-0 to 70 °C
Storage temperature range-40 to 70 °C
Humidity0 to 90% non-condensing
Mechanical
Dimensions 79 mm (L) x 82 mm (W) x 25 mm (H)
USB cable length 3 Meters max
User connection length 3 Meters max
Main connector and pin out
Connector type Screw terminal
Wire gauge range 16 AWG to 30 AWG
25
Page 26
18200-00 Operating Manual Specifications
4-channel differential mode
Pin Signal Name Pin Signal Name
1 CH0 IN HI 21 Port A0
2 CH0 IN LO 22 Port A1
3 GND 23 Port A2
4 CH1 IN HI 24 Port A3
5 CH1 IN LO 25 Port A4
6 GND 26 Port A5
7 CH2 IN HI 27 Port A6
8 CH2 IN LO 28 Port A7
9 GND 29 GND
10 CH3 IN HI 30 PC+5V
11 CH3 IN LO 31 GND
12 GND 32 Port B0
13 D/A OUT 0 33 Port B1
14 D/A OUT 1 34 Port B2
15 GND 35 Port B3
16 CAL 36 Port B4
17 GND 37 Port B5
18 TRIG_IN 38 Port B6
19 GND 39 Port B7
20 CTR 40 GND
8-channel single-ended mode
Pin Signal Name Pin Signal Name
1 CH0 IN 21 Port A0
2 CH1 IN 22 Port A1
3 GND 23 Port A2
4 CH2 IN 24 Port A3
5 CH3 IN 25 Port A4
6 GND 26 Port A5
7 CH4 IN 27 Port A6
8 CH5 IN 28 Port A7
9 GND 29 GND
10 CH6 IN 30 PC+5V
11 CH7 IN 31 GND
12 GND 32 Port B0
13 D/A OUT 0 33 Port B1
14 D/A OUT 1 34 Port B2
15 GND 35 Port B3
16 CAL 36 Port B4
17 GND 37 Port B5
18 TRIG_IN 38 Port B6
19 GND 39 Port B7
20 CTR 40 GND
26
Page 27
Declaration of Conformity
Manufacturer: Measurement Computing Corporation
Address: 16 Commerce Boulevard
Middleboro, MA 02346
USA
Category: Electrical equipment for measurement, control and laboratory use.
Measurement Computing Corporation declares under sole responsibility that the product
18200-00
to which this declaration relates is in conformity with the relevant provisions of the following standards or other
documents:
EU EMC Directive 89/336/EEC: Electromagnetic Compatibility, EN 61326 (1997) Amendment 1 (1998)
Emissions: Group 1, Class B
EN 55011 (1990)/CISPR 11: Radiated and Conducted emissions.
Immunity: EN61326, Annex A
IEC 1000-4-2 (1995): Electrostatic Discharge immunity, Criteria A.
IEC 1000-4-3 (1995): Radiated Electromagnetic Field immunity Criteria A.
IEC 1000-4-8 (1994): Power Frequency Magnetic Field immunity Criteria A.
Declaration of Conformity based on tests conducted by Chomerics Test Services, Woburn, MA 01801, USA in
May, 2004. Test records are outlined in Chomerics Test Report #EMI3733.04.
We hereby declare that the equipment specified conforms to the above Directives and Standards.
Carl Haapaoja, Director of Quality Assurance
Page 28
HM 18200-00.doc
Cole-Parmer Instrument Company
625 East Bunker Court
Vernon Hills, Illinois 60061-1844
(847) 549-7600
Fax: (847) 247-2929 (Fax)
800-323-4340
www.coleparmer.com
E-mail: techinfo@coleparmer.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.