Cole Parmer 05012-20, 05012-30, 05012-40 Installation And Operational Manual

Page 1
HORIZONTAL AIR FLOW
OVEN
MODEL: 05012-20, 05012-30
05012-40
INSTALLATION AND OPERATIONAL MANUAL
COLE-PARMER INSTRUMENT COMPANY_____________________________________________________________________ 625 East Bunker Court, Vernon Hills, IL 60061 (847) 549-7600 FAX (847) 549-7676
Page 2
TABLE OF CONTENTS
SECTION 1.0 RECEIVING AND INSPECTION
SECTION 2.0 GRAPHIC SYMBOLS
SECTION 3.0 INSTALLATION
SECTION 4.0 CONTROL OVERVIEW
SECTION 5.0 PRECAUTIONS
SECTION 6.0 CLEAN ROOM READY
INSTRUCTIONS, 05012-30,05012-40
SECTION 7.0 OPERATION
SECTION 8.0 MAINTENANCE
SECTION 9.0 TROUBLESHOOTING
SECTION 10.0 PARTS LIST
UNIT SPECIFICATIONS
SCHEMATICS
REV. 5/99 4861302
These units are for professional, industrial or educational use where the preparation or testing of materials is done at approximately atmospheric pressure and no flammable, volatile or combustible materials are being heated. These units are not intended for hazardous or household locations or use.
22
Page 3
Section
1
RECEIVING AND INSPECTION
Your satisfaction and safety require a complete understanding of this unit. Read the instructions thoroughly and be sure all operators are given adequate training before attempting to put the unit in service. NOTE: This equipment must be used only for its intended application; any alterations or modifications will void your warranty.
1.1 Inspection: The carrier, when accepting shipment, also accepts responsibility
for safe delivery and is liable for loss or damage. On delivery, inspect for visible exterior damage, note and describe on the freight bill any damage found, and enter your claim on the form supplied by the carrier.
1.2 Inspect for concealed loss or damage on the unit itself, both interior and exterior. If necessary, the carrier will arrange for official inspection to substantiate your claim.
1.3 Return Shipment: Save the shipping crate until you are sure all is well. If for any reason you must return the unit, first contact your customer representative for authorization. Supply nameplate data, including model number and serial number. Please see the manual cover for information on where to contact customer service.
1.4 Accessories: Verify that all of the equipment indicated on the packing slip is included with the unit. Carefully check all packaging before discarding. These units are equipped with 2 shelves, 8 shelf clips, and 4 leveling feet.
33
Page 4
Section
2
GRAPHIC SYMBOLS
Your oven has been provided with a display of graphic symbols which should help in identifying the use and function of the available user adjustable components.
2.1 This symbol indicates that you should consult your
manual for further description or discussion of a control or user item.
2.2 Indicates ÒAC PowerÓ
2.3 Indicates ÒManual ControlÓ
2.4 Indicates ÒTemperatureÓ
2.5 Indicates ÒOver Temperature SafetyÓ
2.6 Indicates ÒGroundÓ
2.7 Indicates ÒPotential Shock HazardÓ
44
Page 5
Section
3
INSTALLATION
Local city, county or other ordinances may govern the use of this equipment. If you have any questions about local requirements, please contact the appropriate local agency. Installation may be performed by the end user.
Under normal circumstances this unit is intended for use indoors, at room temperatures
between 5° and 40°C, at no greater than 80% Relative Humidity (at 25°C) and with a
supply voltage that does not vary by more than 10%. Customer service should be contacted for operating conditions outside of these limits.
3.1 Power Source: The electrical supply circuit to the incubator must conform to all national and local electrical codes. Consult the incubatorÕs serial data plate for the voltage and ampere requirements before making connection. VOLTAGE SHOULD NOT VARY MORE THAN 10% FROM THE DATA PLATE RATING. This unit is intended for 50/60 Hz application. A separate circuit is recommended to prevent possible loss of product due to overloading or failure of other equipment on the same circuit. For installation of the units, the cord must be plugged directly into a grounded outlet, without the use of an extension cord.
3. 2Lo ca tio n: In sele cting a locat ion , con sid er all cond it ion s which mig ht ef fect pe rf orm ance, su ch as he at fr om rad ia tor s, ovens, a ut oclave s, et c. Avoid d ir ect su n, fa st mo vin g air cu rr ent s, he ating/ co oling du cts an d hig h-t ra ffic are as. Allow a minimum of 5cm bet we en the unit an d walls or pa rtitions wh ich migh t obstru ct fr ee air flo w.
3.3 L if ti ng / Ha n dl in g: T he se un it s are hea vy an d car e sho uld be ta ken to use a pp ro pr iat e lif ting de vices tha t are su ff icien tly rat ed fo r t he se lo ad s. Units sh ou ld o nly be lift e d fr om th eir bot to m sur f aces. Do or s, ha nd les an d kn ob s are no t a de qu at e for lift in g or sta bilizat io n . Th e unit sho uld be co m plet ely rest ra in ed fr om t ip ping du rin g lift ing or tra nsp or t. All mo ving pa rt s, su ch as she lve s and tra ys sho uld be re m oved an d do o rs nee d to be po sit ively locke d in the clo sed po sition d ur in g tra nsf er t o pre ve n t sh if t in g and d am a ge .
3 .4 L ev el in g : T he unit must sit le ve l and solidly. Leveling fe et are su pp lie d an d must
b e in st a lled in the fo ur ho le s in th e bot to m cor n er s of th e unit. Wit h the fee t insta lle d an d the un it st an ding up rig ht , ea ch fo o t ca n be ra ise d by tu rn ing it in a cou nt er clo ckwise dir ectio n. Ad just the foo t at each co r ne r unt il th e un it st an d s level an d so lid wit h ou t rocking . If th e un it mu st be mo ve d, tu rn th e le velin g fee t all t he way clockwise t o p re ven t da m ag e while m o ving .
55
Page 6
3 .5 Adj us tme n ts : Whe n re m ovin g int er ior it em s fo r cle a ning or any ot he r rea so n ,
n ot e th a t yo u must, first rem ove the line r bot to m inser t bef o re rem o ving line r sid e inser ts. Th is re qu ire s a 8 /3 2 nut d r iver t o r em o ve t he ca p nut s.
3.6 Cle an in g : The un it ch am be r sho uld be cle an ed an d disin fe cte d pr ior to use . Rem ove all of the in te rio r pa rt s, if asse mb led , and cle a n th o ro ug hly, in clu ding all cor ne rs usin g a suit ab le disinf e ct an t tha t is ap p ro pr ia t e to yo ur ap plica tion . Reg ular pe rio dic cle an in g is re q uire d . Spe cia l car e sh o uld be ta ke n whe n cle an ing a ro un d sen sin g he ad s to pre ve nt da ma g e. DO NOT USE chlorine-based bleaches or abrasive cleaners as this will damage the stainless steel interior. DO NOT USE spray cleaners that might leak through openings and cracks and get on electrical parts or that may contain solvents that will harm the coatings. F or M od els 050 12 - 30 a nd 05 01 2 -4 0 se e Sectio n 6 fo r f ur t he r in str uct io n.
Warning: Never clean the unit with alcohol or flammable cleaners with the unit connected to the electrical supply. Always disconnect the unit from the electrical service when cleaning and assure all volatile or flammable cleaners are evaporated and dry before reattaching the unit to the power supply.
3 .7 Pla ce sh elve s in th e cha m be r as de sir ed .
66
Page 7
Section
4
CONTROL PANEL OVERVIEW
4.1 Power Switch: The main power I/O (on/off) switch controls all power to the unit
and must be in the I/ON position before any systems are operational.
4.2 High Limit Thermostat: This control is marked HIGH LIMIT and is equipped with an adjustable knob and a graduated dial from 0-10. It is independent of the Main Controller and guards against any failure which would allow the temperature to rise past the Main Controllers set point. This allows continued operation of the oven until the problem can be corrected or service can be arranged. It is not recommended that the unit be operated for extended periods of time using only the Overtemperature Safety as the controller as temperature uniformity will suffer.
4.3 High Limit Activated: This pilot lamp will come on when the High Limit Thermostat is activated and taken control of the heating element. Under normal operating conditions this pilot lamp should never be on.
4.4 Main Temperature Controller: This is a microprocessor based temperature / Time Control with ramp and soak capabilities ( Watlow model 981 ).
4.5 Fuse: Located at the back of the unit next to the power cord, the fuse provides protection for the units electrical circuitry against power fluctuations. When blown, the fuses must be replaced before the unit can continue operation.
4.6 Power Exhaust Outlet: Located at the back of the unit next to the power cord, for easy installation of a power exhaust accessory. The 05012-30 does not come equipped with this feature.
Figure One
77
Page 8
Section
5
PRECAUTIONS
5.1 This unit has been designed with vents from the chamber. In order to work
effectively and safely, some precautions will need to be taken by the operator.
a. In most applications, the exhaust damper will need to be open during
drying or degassing for best results.
b. THIS OVEN IS NOT DESIGNED TO HANDLE COMBUSTIBLE GASSES,
AND IS NOT AN EXPLOSION PROOF OVEN. DO NOT PLACE EXPLOSIVE, COMBUSTIBLE OR FLAMMABLE MATERIALS INTO THE CHAMBER.
c. Some of the out gassed byproducts may be hazardous or unpleasant to
operating personnel. If this is the case, the exhaust should be positively ventilated to the outside and dealt with according to local regulations. Contact your dealer about power exhausts.
5.2 Do not operate near noxious fumes.
5.3 Do not place sealed or filled containers in the oven chamber.
5.4 Do not cut or remove the ground prong from the power cord.
5.5 Do not use a 2-prong adapter plug.
5.6 Be sure that the power supply is as the same voltage as specified.
5.7 Disconnect the unit from its electrical source before proceeding to make any
electrical repairs or replacement.
5.8 If a mercury thermometer is used and breakage should occur, all spilled mercury MUST be completely removed from the chamber before continuing operation.
5.9 This oven is NOT designed for the use in Class I, II, or III locations as defined by the National electric Code.
5.10 This oven is not intended, nor can it be used, as a patient connected device.
88
Page 9
Section
6
CLEAN ROOM READY INSTRUCTIONS
The 05012-30 and 05012-40 have been designed to operate at class 100 standards. It is not shipped clean room ready and the instructions below must be followed for proper installation. See Figures Two and Three.
6.1 BURN-IN OF THE HEPA FILTER
Before using this oven, it is important that the filter be Òburnt-inÓ properly. During burn-in, the Hepa filter will off gas. Because of this, the intake and exhaust port must be open with the exhaust port being ducted outside. A material safety data sheet is included with your operation literature for reference.
A. To burn in filter:
1. Set oven at: 175°C for 1 hour;
220°C for 4 hours; 225°C for 1 hour; 250°c for 1 hour.
2. If operating temperature is higher than 250°C, continue the cycle of one (1) hour at 25° increments until the operating temperature is
achieved.
B. After burn-in, the interior must be disassembled and cleaned. Make sure
unit is unplugged before disassembly. This requires an 8/32 nut driver to remove the cap nuts. Remove the bottom liner insert before removing the liner side inserts.
6.2 CONTROL AREA EXHAUST
As part of this design the control compartment is sealed and requires a minimum of 30 C.F.M. (Cubic Feet Per Minute) to be drawn from the control compartment exhaust port. This is required to limit control compartment temperature and maintain Class 100 integrity. If you are unable to exhaust the minimum 30 C.F.M. from the control compartment, then you must limit the maximum operating
temperature to 280°C. Operation of the unit above 280°C, without required 30
C.F.M. control compartment exhaust will result in control degradation and
99
Page 10
process failure. Not supplying the required 30 C.F.M. may also keep the unit from operating at class 100 specifications by allowing particulars from the control compartment to escape into the room.
Figure Two
05012-40 Intake/Exhaust
111100
00
Page 11
Figure 3
05012-30 Intake/Exhaust
111111
11
Page 12
Section
7
OPERATION
7.1 Power Supply: As mentioned is Section 3.1, be certain the power source
matches the requirements listed on the data plate.
7.2 Turn the power switch to the I/ON position and turn the High Limit Thermostat to its maximum position, clockwise. This allows the setting of the Main Temperature without interference of the High Limit..
7.3 Set Main Temperature Controller: This is explained in full detail in the enclosed Watlow 982 users manual. A simplified 981 instruction sheet is included with the manual for your convenience. Please refer to the users manual and instruction sheet for operation and maintenance details.
7.4 Set High Limit Thermostat: Prior to setting the High Limit Control be certain the Main Temperature Control has reached the input set point and has remained stable for several hours. This will insure that the High Limit is set at the proper temperature. As mentioned in step 7.2, the High Limit should be at maximum position. Now turn the Thermostat counterclockwise until the High Limit Activated indicator light comes on. Next, turn the Thermostat clockwise just until the light turns off. Then turn the Thermostat two (2) of the smallest divisions on its scale past the point where the indicator light went out. The High Limit should
now be set approximately 10° higher than the Main Temperature Controller.
Please note that the High Limit is a safety feature only. If the unit is allowed to operate using only the High Limit Thermostat, the temperature stability will suffer.
7.5 Power Exhaust Outlet: The power exhaust outlet is controlled by the Main temperature Controller. This is described in paragraphs 2 and 3 on the back page of the 981 simplified instructions and in the Watlow 982 users Manual. The 05012-30 does not come equipped with this feature.
111122
22
Page 13
Section
8
MAINTENANCE
Note: Disconnect the power cord from the power source before performing any service or maintenance on this unit.
8.1 Cleaning: Clean the oven interior and remove and clean shelves on a regular
basis. Use a disinfectant that is suitable for your application. DO NOT USE chlorine based bleaches or abrasive cleaners as this will damage the stainless steel interior. DO NOT USE spray cleaners that might leak through openings and cracks and get on electrical parts or that may contain solvents that will harm the coatings.
Warning: Never clean the unit with alcohol or flammable cleaners with the unit connected to the electrical supply. Always disconnect the unit from the electrical service when cleaning and assure all volatile or flammable cleaners are evaporated and dry before reattaching the unit to the power supply.
8.2 Use care when cleaning the door gasket to prevent damage which could impair the positive door seal.
8.3 Storage: To prepare the unit for storage, remove all shelves and shelf clips. Be certain that the door is positively locked in the closed position. See Section 3.3, Lifting/Handling, for proper transport procedures.
8.4 No maintenance is required on the electrical components. If the unit fails to operate as specified, please see the Troubleshooting guide, Section 9.0 before calling for service.
111133
33
Page 14
Section
9
TROUBLESHOOTING & SERVICE
FOR PERSONAL SAFETY, ALWAYS DISCONNECT THE POWER BEFORE SERVICING. If the unit fails to operate as specified, review the following
troubleshooting suggestions prior to calling customer service.
TEMPERATURE
Temp-1Temperature too high
1/ controller set too high-see your Watlow users manual 2/ controller failed on Ð call Customer Service 3/ wiring error Ð call Customer Service
Temp-2Chamber temp spikes
over set point and then settles to set point
Recalibrate Ð see Watlow users manual
Temp-3Temperature too low
1/ high limit set too low Ð see section 7.4 2/ controller set too low Ð see Watlow users manual 3/ unit not recovered from door opening Ð wait for display to stop changing 4/ unit not recovered from power failure or being turned off Ð ovens will need several hours to warm up and stabilize 5/ element failure Ð call Customer Service 6/ controller failure Ð confirm with front panel lights that controller is calling for heat 7/ high limit failure Ð confirm with front panel lights that High Limit is operating correctly 8/ wiring problem Ð check all functions and compare wiring to owners manual - especially around any areas recently worked on 9/ loose connection Ð check shadow box for loose connections
44
111144
Page 15
Temp-4Unit will not heat over
a temperature that is below set point
Temp-5Unit will not heat up at
all
Temp-6Indicated chamber
temperature unstable
1/ confirm that blower motor is moving and that amperage and voltage match data plate Ð check blower motor motion in shadow box and feel for air movement in chamber 2/ confirm that set point is set high enough Ðturn High Limitcounter clockwise and see if High Limit light comes on 3/ check connections to sensor 4/ check calibration Ð using independent reference thermometer, follow instructions in Watlow users manual
1/check amperage Ð amperage should be virtually at maximum rated (data plate) amperage 2/ do all controller functions work? 3/ is the High Limit set high enough? Ð for diagnostics, should be fully clockwise with the pilot light never on 4/ has the fuse/circuit breaker blown?
1/ ±0.1 may be normal 2/ is blower motor working? Ð remove top panel and verify movement of blower motor in shadow box 3/ is ambient room temperature radically changing Ð either door opening or room airflow from heaters or air conditioning ? Ð stabilize ambient conditions 4/ it may happen if exhaust stack is 100% open or if power exhaust is cycling Ð adjust stack to at least _ closed 5/ sensor miss-located, damaged or wires may be damaged - check mounts for control and High Limit sensors, then trace wires between sensors and controls 6/ calibration sensitivity Ð call Customer Service 7/ high limit set too low Ð be sure that high limit is more than 5 degrees over desired set point; check if high limit pilot is on continuously; turn controller knob completely clockwise to see if problem solved then follow instructions in section 7.4 for correct setting 8/ electrical noise Ð remove nearby sources of RFI including motors, arcing relays or radio transmitters 9/ bad connection on temperature sensor or faulty sensor Ð check connectors for continuity and mechanical soundness while watching display for erratic behavior; check sensor and wiring for mechanical damage
111155
55
Page 16
Temp-7Will not maintain set
point
Temp-8Display and actual
reference thermometer donÕt match
Temp-9Can't adjust set points
or calibration
Temp-10Calibrated at one
temperature, but not at another
10/ bad connections or faulty solid state relay Ð check connectors for mechanical soundness and look for corrosion around terminals or signs of arcing or other visible deterioration
1/ ASSURE THAT SET POINT IS AT LEAST 5 DEGREES OVER AMBIENT ROOM TEMPERATURE 2/ see if ambient is fluctuating
1/ calibration error Ð see Watlow users manual 2/ temperature sensor failure Ð call Customer Service 3/ controller failure Ð call Customer Service 4/ allow at least two hours to stabilize 5/ verify that reference thermometer is certified
1/ turn entire unit off and on to reset 2/ if repeatedly happens, call Customer Service
This can be a normal condition when operating temperature varies widely. For maximum accuracy, calibration should be done at or as close to the set point temperature.
111166
66
Page 17
Mech-1 Door not sealing
Mech-2 Motor doesn't move
Mech-3 Motor makes noise
MECHANICAL
1/ check physical condition of gasket 2/ assure that gasket is in original location
1/ if shaft spins freely: check connections to motor and check voltage to motor; 2/ if shaft rubs or is frozen, relieve binding and retest
1/ If noise is from the motor, tap the top of motor shaft with ball peen hammer. 2/ If the sound gets worse, tap the other end of the shaft Ð avoiding touching the blower wheel. 3/ If there is no change, call Customer Service.
Other-1 Controller on at all
times - "locked-up"
Other-2 Controller timer resets
on its own
Other-3 Front panel displays
are off
Other-4 Unit or wall
fuse/circuit breaker is blown
OTHER
1/ turn unit off and on to reset 2/ if cannot change any condition on the front panel, call Customer Service
1/ confirm that power from wall is consistent and within specs 2/ call Customer Service with serial number
1/ Check for wire damage.
1/ check wall power source 2/ compare current draw and compare to specs on data plate 3/ see what other loads are on the wall circuit
111177
77
Page 18
Other-5 Unit will not turn on
Other-6 Unit is smoking Ðout
of box
OtherÐ7Contamination in
chamber
Other-8 Contamination in
sample
.
1/ check wall power source 2/ check fuse/circuit breaker on unit or in wall 3/ see if unit is on, e.g., fan or heater, and just controller is off 4/ check all wiring connections, esp. around the on/off switch
1/Put unit under vent and run at full power for one hour. 2/Models 1601 and 1605 follow special burn in procedures in section 6.0
1/ see cleaning procedure in operatorÕs manual 2/ develop and follow SOP for specific application; include definition of cleaning technique and maintenance schedule
1/ see ÒContamination in chamberÓ 2/ reduce air flow in chamber by dampening down inlet restrictor; be sure to verify adequate temperature uniformity at the reduced air flow 3/ protect open samples from areas of maximum air current, e.g., inlet air ducts
If this product should require service, contact your service representative. For information on where to reach customer service please see the front cover of this manual. Should return of the product be necessary, a return authorization number must be obtained and the product shipped, per instructions, to the indicated service center. If a return authorization number is not obtained the product will be returned back to the sender the same day it is received. To insure prompt handling, the return authorization number should be placed on the outside of the package and a detailed explanation of the return enclosed with the item.
111188
88
Page 19
Section
0
1
PARTS LIST
Description Part #
Adjustable Feet 200129 Blower Motor 4880512 Control Relay 102162 Convenience Outlet 101483 Cooling Fan 210001 EMI Filter - CE Complied Models 2800503 Fuse, 20 Amp ABC 101341 Heating Element Ð 05012-20, 05012-40 120073 Heating Element Ð 05012-30 200114 Hepa Filter Assembly Ð 05012-30 X1000577 Hepa Filter Assembly Ð 05012-40 9990503 High Limit Controller 1750571 High Limit Indicator Pilot Lamp 200020 On/Off Switch 103351 Power Cord 1800509 Power Relay 100064 Shelf Clips 200137 Temperature Probe 101827 Watlow 981 Main Temp. Controller 1750540
111199
99
Page 20
UNIT SPECIFICATIONS
Weight Shipping Net
05012-20 315 179
05012-30
05012-40 315 179
Call Customer
Service
135
Dimensions
05012-20 32X30.5X36.5 20X19X19
05012-30 28.5X25.5X29.25 16.5X13.75X15
05012-40 32X30.5X36.5 17X19X19
WxDxH (in.)
Exterior
Interior
WxDxH (in.)
Capacity Cubic Feet
05012-20 4.17
05012-30 1.96
05012-40 3.55
Temperature Range Sensitivity
05012-20
05012-30
05012-40
Amb. +5-200°C
Max 350°C
Amb. +5-200°C
Max 350°C
Amb. +5-200°C
Max 350°C
0.1
0.1
0.1
222200
00
Page 21
WIRE DIAGRAM
222211
11
Loading...