Coleman UGAB100BUJ, UGAB075BUJ, UGAA075BUJ Installation Guide

......................................... I-I ', H', ,'1.-¢" 'l.I
HIGH EFFICIENCY CLAM TUBE HEAT EXCHANGER SERIES
MODELS: UGAA/UGAB
(Single Stage Multi-Position)
75- 100 MBH INPUT (21.98 - 29.31 KW) INPUT
!
LIST OF SECTIONS
SAFETY ................................................ 1 TWINNING AND STAGING ................................ 15
DUCTWORK ............................................ 4 VENT/COMBUSTION AIR SYSTEM ......................... 16
FILTERS .............................................. 10 SAFETY CONTROLS .................................... 22
GAS PIPING ........................................... 11 START-UP AND ADJUSTMENTS ........................... 22
ELECTRICAL POWER ................................... 13 WIRING DIAGRAM ...................................... 29
LIST OF FIGURES
Upflow/Horizontal Configuration .............................. 5
Downflow/Horizontal Configuration ........................... 5
Vent Blower ............................................. 6
Top Cap ................................................ 6
Dimensions ............................................. 7
Combustible Floor Base Accessory ........................... 8
Typical Attic Installation .................................... 9
Typical Suspended Furnace ! Crawl Space Installation ............ 9
Side Return Cutout Markings ............................... 10
Horizontal Mount and Filter ................................ 10
Downflow Filter .......................................... 10
Return Filter Grill and Return Duct Installation .................. 11
Gas Valve .............................................. 11
Upflow Configuration ..................................... 11
Downflow Configuration ................................... 12
Gas Piping ............................................. 12
Burner Assembly ........................................ 12
Electrical Wiring - Upflow Position ........................... 14
Single Stage Heat Thermostat Connections ................... 14
Accessory Connections ................................... 14
Typical Twinned Furnace Application ......................... 15
Single Stage Twinning Wiring Diagram ....................... 16
Two-Stage Twinning Wiring Diagram ......................... 16
Vent Termination ........................................ 16
Vent Termination ........................................ 17
Alternate Air Intake, Air Outlet and Chimney Connections ......... 17
Air Inlet, Outlet and Chimney Connections ..................... 17
Typical Sidewall Vent Application ............................ 18
Typical Sidewall Vent and Termination Configuration ............ 18
Typical Chimney Connections .............................. 18
Horizontal Air Inlet, Outlet and Chimney Connections ............ 18
Home Layout ........................................... 19
Combustion Airflow Path Through The Furnace
Casing to the Burner Box .................................. 20
Outside and Ambient Combustion Air ......................... 21
Pressure Switch Tubing Routing ............................ 22
Gas Valve .............................................. 25
Reading Gas Pressure .................................... 25
Furnace Control Board .................................... 26
Wiring Diagram .......................................... 29
Certified Quality
Management System
LIST
Unit Clearances to Combustibles ............................. 4
Minimum Duct Sizing For Proper Airflow ....................... 6
External Static Pressure Range .............................. 7
Cabinet and Duct Dimensions ............................... 7
Recommended Filter Sizes ................................ 10
High Altitude Conversion .................................. 13
Ratings & Physical ! Electrical Data - Upflow Models ............ 14
Roof Pitch .............................................. 17
Horizontal Sidewall Venting Clearances ...................... 18
SECTION h SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious iniurv. WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious iniurv. CAUTION indicates a potentially hazardous situation, which, if not
avoided mav result in minor or moderate iniurv. It is also used to
alert against unsafe practices and hazards involving only property dam- age.
OF TABLES
Estimated Free Area ...................................... 20
Free Area .............................................. 20
Unconfined Space Minimum Area in Square Inches ............. 20
Field Installed Accessories - Non Electrical .................... 23
Inlet Gas Pressure Range ................................. 25
Nominal Manifold Pressure ................................. 25
Filter Performance - Pressure Drop Inches W.C. and (kPa) ........ 27
Blower Performance - CFM ................................ 28
_WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte- nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con- tractor, installer or service agency.
CAUTION
This product must be installed in strict compliance with the installa- tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical
codes.
288130-UIM-A-0407
288130-UIM-A-0407
SPECIFIC SAFETY RULES AND PRECAUTIONS
1. Only Natural gas or Propane (LP) gas are approved for use with this furnace. Refer to the furnace rating plate or Section IV of
these instructions.
2. Install this furnace only in a location and position as specified in SECTION I of these instructions.
3. A gas-fired furnace for installation in a residential garage must be installed as specified in SECTION I of these instructions.
4. Provide adequate combustion and ventilation air to the furnace space as specified in SECTION VII of these instructions.
5. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SEC-
TION VII of these instructions.
_WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing prop- erty damage, personal injury or loss of life.
6. Test for gas leaks as specified in SECTION Xl of these instruc- tions.
7. Always install the furnace to operate within the furnace's intended temperature rise range. Only connect the furnace to a duct system
which has an external static pressure within the allowable range, as specified on the furnace rating plate.
8. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace,
the return air shall also be handled by duct(s) sealed to the fur- nace casing and terminating outside the space containing the fur-
nace.
9. It is permitted to use the furnace for heating of buildings or struc- tures under construction. Installation must comply with all manu-
facturer's installation instructions including:
Proper vent installation; Furnace operating under thermostatic control;
Return air duct sealed to the furnace;
Air filters in place;
Set furnace input rate and temperature rise per rating plate marking; Means for providing outdoor air required for combustion;
Return air temperature maintained between 55°F (13°C) and 80°F (27°C);
The air filter must be replaced upon substantial completion of
the construction process; Clean furnace, duct work and components upon substantial
completion of the construction process, and verify furnace- operating conditions including ignition, input rate, temperature
rise and venting, according to the manufacturer's instructions.
10. When installed in a Non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from
occupied spaces.
11. The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved
methods may be used.
12. Mobile Home Installations: This appliance must be installed with a vent terminating in the
same atmospheric zone, external to the building.
13. Modular and Manufactured (Mobile) Home Installations: This appliance must be installed so that the vent pipe from the
vent connection on the furnace can be easily connected to a B type vent that terminates outdoors. This appliance cannot be con-
nected to a vent that is serving another appliance. This appliance shall be installed in an area where there is an adequate supply of
combustion air available to assure proper combustion and ambient air temperatures are maintained within safe operating limits.
If an adequate supply of combustion air is not available to assure proper combustion and ventilation air, outside air shall be intro-
duced to the space in which the appliance is located. An outside combustion air duct may be used to provide the outside air to the
space. Refer to ANSI Z223.1 National Fuel Gas Code or in Can- ada B149-00 National Gas and Propane Installation Code for
proper duct sizing and installation.
NOTE: Air for combustion must never be taken from occupied spaces.
Appliance combustion air must be provided from outdoors.
14. Modular Home Definition: Factory-built home constructed to the state, local, or regional code
where the house will be located. The home is transported in one or more modules and joined at the home site.
15. Mobile Home Definition: Factory-built home constructed, transported, and installed under
the federal building code administered by the U.S. Department of Housing and Urban Development (HUD Code), rather than to
building codes at their destination. The house is built, transported, and installed on a non-removable chassis.
16. This furnace is not approved for installation in trailers or recre- ational vehicles.
SAFETY REQUIREMENTS
This furnace should be installed in accordance with all national and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes. In the absence of local codes, install in accordance with the National Fuel Gas
Code ANSI Z223.1/NFPA 54, National Fuel Gas Code, and!or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). Furnaces have been certified to the latest edition
of standard ANSI Z21-47 CSA 2.3.
A manufactured (mobile) home installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when such standard is not applicable, the
standard for Manufactured Home Installations (Manufactured
Home Sites, Communities, and Set-ups) ANSI/NCS A225.1, and/
or the Canadian Standard for CAN/CSA Z240 MH, Series M92
Mobile Homes. Furnaces have been certified to the latest edition
of standard ANSI Z21-47 CSA 2.3.
Refer to the unit rating plate for the furnace model number, and
then see the dimensions page of this instruction for return air ple-
num dimensions in Figure 5. The plenum must be installed
according to the instructions.
Provide clearances from combustible materials as listed under Clearances to Combustibles.
Provide clearances for servicing ensuring that service access is
allowed for both the burners and blower.
These models ARE NOT CSA listed or approved for installation
into a HUD APProved Modular Home or a Manufactured
(Mobile) Home.
This furnace is not approved for installation in trailers or recre- ational vehicles.
Failure to carefully read and follow all instructions in this
manual can result in furnace malfunction, death, personal injury and/or property damage.
2 Unitary Products Group
Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material
other than wood flooring.
Check the rating plate and power supply to be sure that the elec-
trical characteristics match. All models use nominal 115 VAC, 1
Phase, 60-Hertz power supply. DO NOT CONNECT THIS APPLI-
ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE
130 VOLTS. Furnace shall be installed so the electrical components are pro-
tected from water.
Installing and servicing heating equipment can be hazardous due
to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service
gas heating equipment. Untrained service personnel can perform
basic maintenance functions such as cleaning and replacing the
air filters. When working on heating equipment, observe precau- tions in the manuals and on the labels attached to the unit and
other safety precautions that may apply. These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.
COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)
The furnace will require OUTDOOR AIR for combustion when the fur- nace is located in any of the following environments.
Restricted Environments Commercial buildings
Buildings with indoor pools Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas
Chemical exposure
The furnace will require OUTDOOR AIR for combustion when the fur- nace is located in an area where the furnace is being exposed to the fol- lowing substances and / or chemicals.
Permanent wave solutions Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals Carbon tetrachloride
Halogen type refrigerants Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc. Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
If outdoor air is used for combustion, the combustion air intake duct sys- tem termination must be located external to the building and in an area where there will be no exposure to the substances listed above.
288130-UIM-A-0407
,&WARNING
The furnace area must not be used as a broom closet or for any
other storage purposes, as a fire hazard may be created. Never
store items such as the foflowing on, near or in contact with the fur- nace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning com- pounds; plastic items or containers; gasoline, kerosene, ciga-
rette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
FOR FURNACES INSTALLED IN THE COMMON- WEALTH OF MASSACHUSETTS ONLY
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for resi-
dential purposes, including those owned or operated by the Com- monwealth and where the side wall exhaust vent termination is less
than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following require- ments shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas
fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of
hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon mon-
oxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each car- bon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be perma- nently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC- TIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes car- bon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Unitary Products Group 3
288130-UIM-A-0407
INSPECTION
As soon as a unit is received, it should be inspected for possible dam- age during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts, which may have loosened in transit, and any shipping or spacer brackets which
need to be removed.
FURNACE LOCATION AND CLEARANCES The furnace shall be located usina the followina auidelines:
1. Where a minimum amount of air intake/vent piping and elbows will be required.
2. As centralized with the air distribution as possible.
3. Where adequate combustion air will be available (particularly when the appliance is not using outdoor combustion air).
4. Where it will not interfere with proper air circulation in the confined space.
5. Where the outdoor vent terminal will not be blocked or restricted. Refer to "VENT CLEARANCES" located in SECTION VII of these
instructions. These minimum clearances must be maintained in the installation.
6. Where the unit will be installed in a level position with no more than 1/4" (0.64 cm) slope side-to-side and front-to-back to provide
proper condensate drainage.
Installation in freezina temperatures:
1. Furnace shall be installed in an area where ventilation facilities provide for safe limits of ambient temperature under normal oper-
ating conditions. Ambient temperatures falling below 32° F (0° C) may result in the flue temperature falling below 260 ° F (127 ° C) at
any point in the flue pipe between the furnace and the chimney or a B-Vent. The flue products will condense in the vent pipe if the
flue temperature falls below 260 ° F (127 ° C) causing the vent pipe to deteriorate rapidly.
2. Do not allow return air temperature to be below 550 F (13 ° C) for extended periods. To do so may cause condensation to occur in
the main heat exchanger, leading to premature heat exchanger failure.
TABLE 1: Unit Clearances to Combustibles
,&WARNING
Improper installation in an ambient below 32°F (0.0 ° C) could create
a hazard, resulting in damage, injury or death.
3. If this furnace is installed in an unconditioned space and an extended power failure occurs, there will be potential damage to
the internal components. Following a power failure situation, do not operate the unit until inspection and repairs are performed.
Clearances for access: Ample clearances should be provided to permit easy access to the unit.
The following minimum clearances are recommended:
1. Twenty-four (24) inches (61 cm) between the front of the furnace and an adjacent wall or another appliance, when access is
required for servicing and cleaning.
2. Eighteen (18) inches (46 cm) at the side where access is required for passage to the front when servicing or for inspection or replace-
ment of flue/vent connections.
In all cases, accessibility clearances shall take precedence over clear-
ances for combustible materials where accessibility clearances are greater.
,&WARNING
Downflow furnaces for installation on combustible flooring only when installed on the accessory combustible floor base on wood flooring only and shall not be installed directly on carpeting, tile or
other combustible material. Check the rating plate and power supply to be sure that the electri-
cal characteristics match. All models use nominal 115 VAC, 1 Phase 60Hz power supply.
Furnace shall be installed so the electrical components are pro- tected from water.
Installation in a residential aaraee: A gas-fired furnace for installation in a residential garage must be
installed so the burner(s) and the ignition source are located not less than (18) inches (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles.
Application
Upflow 1 (2.5) 2 (5.1) 0 (0.0) 0 (0.0) 6(15.2)
Upflow B-Vent 1(2.5) 3 (7.6) 0 (0.0) 0 (0.0) 6 (15.2)
Horizontal 1 (2.5) 2 (5.1) 0 (0.0) 1 (5.08) 6 (15.2)
Horizontal B-Vent 1 (2.5) 3 (7.6) 0 (0.0) 0 (0.0) 6 (15.2)
Downflow 1 (2.5) 2 (5.1) 0 (0.0) 0 (0.0) 6(15.2)
Downflow B-Vent 1 (2.5) 3 (7.6) 0 (0.0) 0 (0.0) 6 (15.2)
1. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
SECTION Ih DUCTWORK
DUCTWORK GENERAL INFORMATION The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and
90B (latest editions) or applicable national, provincial, or state, and local fire and safety codes or in Canada, refer to the Natural Gas
and Propane Installation Code B149.1-00.
Top Front Rear Sides Single Wall Vent
In, (cm) In, (cm) In, (cm) In, (cm) In, (cm)
3. Create a closed duct system. For residential and Non-HUD Modu- lar Home installations, when a furnace is installed so that the sup-
ply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled
by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
4. Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the condi-
tioned space.
5. For manufactured (mobile) home and modular home return duct system installation: The return air duct and the return air
plenum are required by the furnace manufacturer.
Floor/ Line
Bottom Contact
Combustible Yes Yes Yes No Combustible Yes Yes Yes No
Combustible No Yes Yes Yes1
Combustible No Yes Yes Yes1 Non-Combustible Yes Yes Yes No Non-Combustible Yes Yes Yes No
Closet Alcove Attic
4 Unitary Products Group
[,& CAUTION
The cooling coil must be installed in the supply air duct, down- stream of the furnace. Cooled air may not be passed over the heat exchanger.
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be adequate to prevent chilled air from entering the furnace. If manually operated, the damper must be equipped with means to pre- vent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.
AWARNING
The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.
Refer to Table 7 and the furnace rating plate for the correct rise range and static pressures
If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.
288130-UIM-A-0407
14. Remove the rectangular knockout in the center of the top cap. See Figure 4.
15. Install the top cap at the same end of the furnace as the vent blower, using the sheet metal screws saved earlier. See Figure 1.
16. Install the bottom cap on the bottom of the furnace using the sheet metal screws saved earlier. See Figure 1.
17. The conversion is now complete. The furnace may now be installed in the upflow position or in the horizontal position on
either side.
TRANSITION
TOP j_ VENT
EXTRA PRESSURE
SCREWS
GASKET /
CAP
_i : ::::: PAN
' k J/ ,b; =- = e
J HOSE
/i
PRESSURE
SWITCH
VENT
BLOWER
i
INSTALLATION POSITION
This furnace may be installed in an upflow, downflow or horizontal posi- tion. Depending on the configuration shipped from the factory, it may be necessary to convert the furnace from downflow to upflow or from upflow to downflow configuration. Use conversion instructions in this
document.
CONVERSION INFORMATION
This furnace may be shipped in either the upflow or the downflow con- figuration. To convert from upflow to downflow or vice-versa it is neces- sary only to exchange the top and bottom casing caps and to rotate the vent blower 180 degrees. Use the step by step instructions to perform
the conversion.
TO CONVERT FROM DOWNFLOW TO UPFLOW CONFIGURATION
1. Lay the furnace on its back.
2. Remove the front door.
3. Remove the seven sheet metal screws that are used to fasten the top cap to the casing. Remove the top cap and save the screws.
4. Remove the four sheet metal screws that are used to fasten the bottom cap to the casing. Remove the bottom cap and save the
screws.
5. Unplug the vent blower wires.
6. Disconnect the pressure hose from the vent blower.
7. Remove the four machine screws that fasten the vent blower to the vent pan and save the screws. Leave the gasket in place on
the pan.
8. Remove the two extra machine screws in the vent pan front and save the screws.
9. Rotate the vent blower and transition 180° so that its outlet points to the outlet air end of the furnaces as shown in Figure 1.
10. Line up the vent blower mounting holes with the holes in the vent pan and screw it into place. Use the same machine screws that
held the vent blower in place previously.
11. Install the two extra machine screws in the two open holes in the front of the vent pan See Figure 1.
12. Plug in the vent motor wires.
13. Plug the pressure hose into the vent blower.
BOTTOM
j CAP
FIGURE 1: Upflow/Horizontal Configuration
TOP
CAP
TRANSITION
BOTTOM
CAP \_
/ /
PRESSURE VENT EXTRA VENT
HOSE PAN SCREWS BLOWER
/
_GASKET
FIGURE 2: Downflow/Horizontal Configuration
TO CONVERT FROM UPFLOW TO DOWNFLOW CONFIGURATION
1. Lay the furnace on its back.
2. Remove the front door.
3. Remove the seven sheet metal screws that are used to fasten the top cap to the casing.
4. Remove the four sheet metal screws that are used to fasten the bottom cap to the casing. Remove the bottom cap and save the
screws.
Unitary Products Group 5
288130-UIM-A-0407
5. Unplug the vent blower wires.
6. Disconnect the pressure hose from the vent blower.
7. Remove the four machine screws that fasten the vent blower to the vent pan and save the screws. Leave the gasket in place on
the vent pan.
8. Remove the two extra machine screws in the vent pan front and save the screws.
9. Install the cast aluminum transition on the vent blower, using the three screws supplied on the vent blower. See Figure 3.
TRANSITION-
FIGURE 3: Vent Blower
10. Rotate the vent blower 1800so that its outlet points toward the inlet air end of the furnace. See Figure 2.
11. Line up the vent blower mounting holes with the holes in the vent pan and screw it into place. Use the same machine screws that held the vent blower in place previously.
12. Install the two extra machine screws in the two open holes in the front of the vent pan. See Figure 2.
13. Plug in the vent motor wires.
14. Plug the pressure hose into the vent blower.
15. Remove the round knockout at the right side of the top cap. See Figure 4.
UPFLOW _ VENT
VENT _ _ .......... _C:.. OPENING
OPENING ...... ........._ .........
FIGURE 4: Top Cap
16. Install the top cap at the opposite end of furnace from the vent blower, using the seven sheet metal screws saved earlier. See
Figure 2.
17. Install the bottom cap on the bottom of the furnace using the sheet metal screws saved earlier. See Figure 2,
18. The conversion is now complete. The furnace may now be installed in the downflow position or in the horizontal position on
either side.
DOWNFLOW
FLOOR BASE AND DUCTWORK INSTALLATION Upflow Instructions
Attach the supply plenum to the furnace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use
of an approved flexible duct connector is recom- mended on all installations. This connection should be
sealed to prevent air leakage. The sheet metal should be cross-hatched to eliminate any popping of the sheet metal when the indoor fan is energized.
When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12" (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con- trols may not operate at all.
The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly. The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.
Table 2 is a guide for determining whether the rectangular duct system that the furnace is being connected to be of sufficient size for proper fur- nace operation.
Use the Example below to help you in calculating the duct area to deter- mine whether the ducts have sufficient area so that the furnace oper- ates at the specified external static pressure and within the air temperature rise specified on the nameplate.
Example: The furnace input is 80,000 BTUH, 1,200 CFM. The recom- mended duct area is 280 sq.in, there are two 8 x 14 rectangular ducts attached to the plenum and there are two 7 inch round ducts attached to
the furnace.
1. Take 8 x 14, which equals 112 sq.in. X 2, which equals 224 square inch then go to round duct size located in Table 2.
2. The square inch area for 7 inch round pipe is 38.4, multiply by 2 for two round ducts which equals 76.8 square inch.
3. Then take the 224 square inch from the rectangular duct and add it to the 76.8 sq.in, of round duct. The total square inch of duct
attached to the furnace plenum is 300.8 square inch. This exceeds the recommended 280 square inch of duct.
In this example, the duct system attached to the plenum has a sufficient area so that the furnace operates at the specified external static pres- sure and within the air temperature rise specified on the nameplate.
Consideration should be given to the heating capacity required and also to the air quantity (CFM) required. These factors can be determined by calculating the heat loss and heat gain of the home or structure. If these calculations are not performed and the furnace is over-sized, the follow- ing may result:
1. Short cycling of the furnace.
2. Wide temperature fluctuations from the thermostat setting.
3. Reduced overall operating efficiency of the furnace.
The supply and return duct system must be of adequate size and designed such that the furnace will operate within the designed air tem- perature rise range and not exceed the maximum designed static pres-
sure. These values are listed Tables 2 and 3. TABLE 2: Minimum Duct Sizing For Proper Airflow
Input Airflow Return I Rectangular 2 Round 2 Supply 3
BTU/H CFM In_ in. x in. in. In_
(kW) (m3) (cm 2) (cm x cm) (cm) dia. (cm2) 75,000 1,200 280 14 x 20 18 216 (21.98) (33.98) (1806) (35.6 x 50.8) (45.7) (1394)
75,000 1,600 360 18 x 20 22 280 (21.98) (45.31) (2322) (45.7 x 50.8) (55.8) (1806)
100,000 1,600 360 18 x 20 22 280
(29.31) (45.31) (2322) (45.7 x 50.8) (55.8) (1806)
NOTE: This chart does not replace properduct sizing calculationsor take into account static pressure dropfor run length andfittings. Watch outfor thetemper- ature rise and static pressures.
1. Maximum return air velocity in rigid duct @ 700 feet per minute (213 m/min).
2. Example return main trunk duct minimum dimensions.
3. Maximum supply air velocity in rigid duct @ 900 feet per minute (274 m/min)
6 Unitary Products Group
288130-UIM-A-0407
TABLE 3: External Static Pressure Range
Input
MBH kW
75 22.0 75 22.0
100 29.3
TABLES 2 and 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow (CFM) through the furnace. TABLES 2 and 3 ARE NOT to be used to design ductwork for the building where the furnace is being installed. There are several variables associated with proper duct sizing that are not included in the tables. To properly design the ductwork for the build- ing, Refer to the ASHRAE Fundamentals Handbook, Chapter on "DUCT DESIGN" or a company that specializes in Residential and Mod- ular Home duct designs.
IMPORTANT: The minimum plenum height is 12" (30.5 cm). The fur- nace will not operate properly on a shorter plenum height. The mini-
mum recommended rectangular duct height is 4 inches (10 cm) attached to the plenum.
Nominal AirFlow
CFM cmm 1200 34.0
1600 45.3 1600 45.3
DOWNFLOW
Ext. Static Pressure
Minimum Maximum
In,W,C kPa In,W,C kPa
0.12 0.0299 0.50 0.1245
0.12 0.0299 0.50 0.1245
0.15 0.0374 0.50 0.1245
IMPORTANT: The air temperature rise should be taken only after the furnace has been operating for at least 15 minutes. Temperatures and
external static pressures should be taken 6" (15 cm) past the first bend from the furnace in the supply duct and the return duct. If an external fil-
ter box or an electronic air cleaner is installed, take the return air read- ings before the filter box or air cleaner.
kWARNING
The supply air temperature MUST NEVER exceed the Maximum
Supply Air Temperature, specified on the nameplate. Operating the furnace above the maximum supply air temperature will cause the heat exchanger to overheat, causing premature heat exchanger failure. Improper duct sizing, dirty air filters, incorrect manifold pressure, incorrect gas orifice and/or a faulty limit switch can cause the furnace to operate above the maximum supply air temperature. Refer to sections II, III and IX for additional informa- tion on correcting the problem.
If a matching cooling coil is used, it may be place directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for
installing the supply plenum. On all installations without a coil, a remov- able access panel is recommended in the outlet duct such that smoke
or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be
attached in such a manner as to prevent leaks.
UPFLOW
i 3%1/2
BOTTOM VIEW
FIGURE 5: Dimensions
TABLE 4: Cabinet and Duct Dimensions
BTUH (kW)
Input
75 (22.0)
75 (22.0
100 (29.3)
BTUH (kW)
Input
75 (22.0) 75 (22.0)
100 (29.3)
1. All models are supplied with 3" (7.62 cm) vent connections. An installer supplied transition to 4" (10.16 cm) or 5" (12.7 cm) must be used where necessary. * Dimensions "B", "C", "D", and "E" are with duct flanges turned up. "F", "G", "H", & "J" are with flanges flat.
Nominal Cabinet Cabinet Dimension
CFM (m3/min) Size A(in.) A(cm) B(in.) B(cm) C(in.) C(cm) D(in.) D(cm) E(in.) E(cm)
1200 (34.0) B 17 1/2 44.5 16 1/2 41.9 20 3/8 51.8 20.0 50.8 16 40.6 1600 (45.3) C 21 53.3 20 50.8 20 3/8 51.8 20.0 50.8 19 1/2 49.5 1600 (45.3) C 21 53.3 20 50.8 20 3/8 51.8 20.0 50.8 19 1/2 49.5
Nominal Cabinet K Vent K Vent
CFM (m3/min) Size F(in.) F(cm) G(in.) G(cm) H(in.) H(cm) J(in.) J(cm) (in.) (cm)
1200 (34.0) B 14 3/4 37.46 18 3/4 47.62 15 1/8 38.4 19.0 48.2 41 10.161 1600 (45.3) C 18 1/4 46.35 18 3/4 47.62 18 5!8 47.3 19.0 48.2 41 10.161 1600 (45.3) C 18 1/4 46.35 18 3/4 47.62 18 5!8 47.3 19.0 48.2 41 10.161
BOTTOM VIEW
Unitary Products Group 7
288130-UIM-A-0407
RESIDENTIAL AND NON HUD MODULAR HOME UPFLOW RETURN PLENUM CONNECTION
Return air may enter the furnace through the side(s) or bottom depend- ing on the type of application. Return air may not be connected into the rear panel of the unit. For single return application, see data and notes on blower performance data tables in this manual.
BOTTOM RETURN AND ATTIC INSTALLATIONS
Bottom return applications normally pull return air through a base plat- form or return air plenum. Be sure the return platform structure or return air plenum is suitable to support the weight of the furnace.
The furnace base is equipped with a rectangular blockoff panel that can be removed by performing the following steps:
1. Lay the furnace on its back.
2. Remove the screws from the toe plate.
3. Remove the toe plate.
4. Pull the base plate out of the furnace base.
5. Reinstall the toe plate and secure with the screws that were removed.
Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
IMPORTANT: If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size.
FLOOR BASE AND DUCTWORK INSTALLATION Downflow Combustible Floor Base
Installations on combustible material or floors must
use a combustible floor base shown in Figure 6. The perforations in the wrapper flanges must be bent in towards the heat exchanger to allow for the coil duct flange to recess into the furnace Follow the instruc- tions supplied with the combustible floor base acces- sory. This combustible floor base can be replaced with
a matching cooling coil, properly sealed to prevent leaks. Follow the instructions supplied with the cooling coil cabinet for installing the cabinet to the duct connector. Refer to the installation
instructions for additional information.
Downflow Duct Connectors
DOWNFLOW
FURNACE
iI WARM AIR PLENUM
J WITH 1" FLANGES
__ FIBERGLASS
INSULATION
FIBERGLASS TAPE
_/ UNDER FLANGE
-- COMBUSTIBLEFLOOR BASEACCESSORY
FIGURE 6: Combustible Floor Base Accessory
All downflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace. The duct connec- tors are designed to be connected to the rectangular duct under the floor and sealed. Refer to the instructions supplied with the duct con- nector for proper installation. Refer to the separate accessory parts list at the end of these instructions for the approved accessory duct con-
nectors. When replacing an existing furnace, if the existing plenum is not the
same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new
furnace.
IMPORTANT: If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size.
Downflow Air Conditioning Coil Cabinet The furnace should be installed with coil cabinet part number specifi-
cally intended for downflow application. If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to pre- vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil
cabinet. The perforations in the wrapper flanges must be bent away from the
heat exchanger to create duct flanges so the air conditioning coil can be properly seated on the furnace. Attach the air conditioning coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the furnace, air conditioning coil cabinet, duct connector, and supply air duct must be sealed to prevent air leak- age.
IMPORTANT: On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected
light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in
such a manner as to prevent leaks.
RESIDENTIAL AND NON HUD MODULAR HOME DOWNFLOW RETURN PLENUM CONNECTION
The return duct system must be connected to the furnace inlet and the return duct system must terminate outside the space containing the fur- nace. When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new
furnace. Attach the return plenum to the furnace inlet duct flanges. This is typi-
cally through the use of "S" cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. The connection of the plenum to the furnace and all the ducts connecting to the plenum must be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.
The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly. The
ducts attached to the furnace must be of sufficient size so that the fur- nace operates at the specified external static pressure and within the air
temperature rise specified on the nameplate. IMPORTANT: If an external mounted filter rack is being used see the
instructions provided with that accessory for proper hole cut size.
HORIZONTAL MODELS
//
Ls_f
IMPORTANT: This furnace may be installed in a horizontal position on either side as shown above. It must not be installed on its back.
Horizontal Installations With a Cooling Coil Cabinet The furnace should be installed with coil cabinet part number specifi-
cally intended for Horizontal application. If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to pre-
vent leakage. Follow the coil instructions for installing the supply ple- num. For details of the coil cabinet dimensions and installation
requirements, refer to the installation instructions supplied with the coil cabinet
The perforations in the wrapper flanges must be bent away from the heat exchanger to create duct flanges so the air conditioning coil can be
properly seated on the furnace.
8 Unitary Products Group
288130-UIM-A-0407
Attach the supply plenum to the air conditioning coil cabinet outlet duct flanges through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. The connection to the furnace, air conditioning coil cabinet and the supply plenum should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.
The minimum plenum height is 12" (30.5 cm). If the plenum is shorter than 12" (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit controls may not operate at all. Also the plastic drain pan in the air conditioning coil can overheat and melt. Refer to the installation instructions supplied with the air conditioning
coil for additional information.
Horizontal Installations Without a Cooling Coil Cabinet
When installing this appliance, the furnace must be installed so as to create a closed duct system, the supply duct system must be con- nected to the furnace outlet and the supply duct system must terminate outside the space containing the furnace. When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace.
Attach the supply plenum to the furnace outlet duct flanges through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized. On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.
Residential and Non Hud Modular Home Horizontal Return Plenum Connections
The return duct system must be connected to the furnace inlet and the return duct system must terminate outside the space containing the fur- nace. When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new
furnace. Attach the return plenum to the furnace inlet duct flanges. This is typi-
cally through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. The connection of the plenum to the furnace and all the ducts connecting to the plenum must be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.
The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly. The
ducts attached to the furnace must be of sufficient size so that the fur- nace operates at the specified external static pressure and within the air
temperature rise specified on the nameplate. Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
IMPORTANT: if an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size.
ATTIC INSTALLATION
LINE CONNECT ONLY PERMISSIBLE BETWEEN LINES FORMED BY THE INTERSECTION OF FURNACE TOP AND TWO SIDES AND BUILDING
JOISTS, STUDS, OR FRAMING
FILTER RACK MUST f , /; --_
BEAMINIMUM DISTANCE J .... (_ /_ _']
OF 18" (45.7 CM) FROM / I I t_ /
T.EFURNAOE ,, IV/
TRAP / ___Z2/PLYWOOD
FIGURE 7: Typical Attic Installation
This appliance is design certified for line contact when the furnace is installed in the horizontal left or right position. The line contact is only permissible between lines that are formed by the intersection of the top and two sides of the furnace and the building joists, studs or framing. This line may be in contact with combustible material.
"_-_-_ FLOOR
SHEET METAL IN FRONT OFFURNACE COMBUSTION AIR OPENINGS IS RECOMMENDED
_WARNING
When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12 inches (30.5 Cm) away from furnace and burner combustion air openings.
SUSPENDED FURNACE / CRAWL SPACE INSTALLATION
The furnace can be hung from floor joists or installed on suitable blocks or pad. Blocks or pad installations shall provide adequate height to ensure the unit will not be subject to water damage. Units may also be suspended from rafters or floor joists using rods, pipe angle supports or straps. Angle supports should be placed at the supply air end and near the blower deck. Do not support at return air end of unit. All four sus- pension points must be level to ensure quiet furnace operation. When suspending the furnace use a secure platform constructed of plywood or other building material secured to the floor joists. Refer to Figure 8 for typical crawl space installation.
\
BRACKETX-- II I I
II RT
1" MAN. BETWEEN 6" MIN BETWEEN 1" MAX.BETWEEN ROD & FURNACE ROD & FURNACE ROD & FURNACE
FIGURE 8: Typical Suspended Furnace / Crawl Space Installation
Unitary Products Group 9
288130-UIM-A-0407
SECTION IIh FILTERS
FILTER INSTALLATION
All applications require the use of a filter. TABLE 5: Recommended Filter Sizes
UPFLOW
Input
MBH
75 75
100
DOWN FLOW
MBH kW
75 22.0 B 75 22.0 C
100 29.3 C
NOTES:
1.Air velocity through throwaway type filters may not exceed 300 feet per minute.
2.Air flows above 1800 CFM require either return from two sides or one side plus
kW
22.0
22.0
29.3
In _ut
Air Flow
CFM m3/min 1200 34.0
1600 45.3 1600 45.3
Air Flow
CFM m3/min 1200 34.0
1600 45.3 1600 45.3
Cabinet
Size
B C C
Cabinet Size
Side
Return
in,
25x 16 25x 16 25x 16
Top Return (Downflow)
Cleanable Air Filters
in. cm
14 x 20 (2) 36 x 51 16x20 (2)41 x51 16x20 (2)41 x51
All velocities over this require the use of high velocity filters. bottom.
cm
64 x41 64 x41 64 x41
in.
25x 16 25 x 20 25 x 20
Top Return (Downflow)
Disposable Air Filters
in. cm
(2) 14 x 20 (2) 36 x 51 (2) 16x20 (2)41 x51 (2) 16 x 20 (2) 41 x 51
Bottom/End
Return
cm
64 x41 64 x 51 64 x 51
SIDE RETURN/BOTTOM EXTERNAL INSTALLATION
Locate and knock out the square corner Iocators. These indicate the size of the cutout to be made in the furnace side panel. Refer to Figure 9.
FURNACE
ER INGS
FIGURE 9: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another location in the return air system, the ductwork may be directly attached to the furnace side panel. An accessory filter rack is available for mounting the filter exter-
nal to the cabinet. Some accessories such as electronic air cleaners and pleated media
may require a larger side opening. Follow the instructions supplied with that accessory for side opening requirements. Do not cut the opening larger than the dimensions shown in Figure 5.
EXTERNAL INSTALLATION FOR UPFLOW/HORIZONTAL CONFIGURATIONS
1. Select desired filter position for upflow/horizontal (left/right side, side and bottom). Remove the corresponding cabinet cutouts per
instructions provided.
2. Install the external filter box to the side of the cabinet and secure to the cabinet as specified in the instructions provided with the air
filter kit. If a side return is to be used, cut out the side of the casing 14" high by 16 1/4" wide using the lances in the casing side as a
guide. DO NOT CUT THE OPENING LARGER THAN 14" X 16 1! 4". It is not permissible to cut out the back of the furnace. For bot-
tom returns you place the external filter box between the return air plenum and the base of the furnace. The casing bottom is
embossed to indicate where to bend the flanges. Refer to Figure 5 for the maximum return air opening sizes. Seal this connection to
prevent leaks. Do not cut the opening larger than the dimensions shown in Figure
5.
3. Install the return air duct to the air filter box and secure with screws. Seal this connection to prevent leaks.
4. Install the field provided filter. Refer to Table 5 for the recom- mended filter size for your furnace.
NOTE: Air velocity must not exceed 300 feet per minute through low velocity disposable filters. Air velocity must not exceed 650 feet per minute through high velocity cleanable permanent filters. Use of a filter that is too small will cause static pressure in the duct system to be too high, which will have an adverse effect on heating and cooling opera-
tion.
RETURN DUCT
AIR _lJ
FILTER
FIGURE 10: Horizontal Mount and Filter
I% N-,t
[] [] []
[] []
[] [] []
/_ FILTER RACK
FURNACE
Di
[]
RACK AND FILTERS SECURED
...... SECT,ON
NOTE: FILTERACCESS THROUGH (
_ DUCTWORK MUST BE PROVIDED _ BRANCH
/ FOR REMOVALAND CLEANING _ DUCTS
( ',, FILTERS
DUCTWORK
CROSS SECTION A-A
(with Plenum and filters)
FIGURE 11: Downflow Filter
10 Unitary Products Group
Downflow Filters
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the )lenum must attach to the vertical plenum above the filter height. Refer to Figure 11 for proper
installation. Filter(s) may be located in the duct system external to the furnace using
an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and ! or supports is required to support the weight of the external filter box. Refer to Fig-
ure 10. If the accessory electronic air cleaner is installed, be sure the air
cleaner is designed to accommodate the furnace CFM (cm/m) and the air cleaner is installed so it does not obstruct the return airflow. Consid-
eration should be given when locating the air cleaner for maintenance and temperatures should the indoor fan motor fail to operate. The use of straps and ! or supports is required to support the weight of the elec-
tronic air cleaner. It is recommended that the air cleaner not be located within 12 inches (2.5 cm) from the top of the return air opening on the
furnace. Refer to the instructions supplied with the electronic air cleaner.
If pleated media air filters or any filter that has a large pressure drop is installed in the return air duct system be sure that the pressure drop caused by the air filter will not prevent the furnace from operating within the rise range specified on the rating plate. If the furnace does not oper- ate within the specified rise range then a larger air filter or an air filter that has a lower pressure drop must be installed. Refer to Table 13 and the furnace accessories for accessory external filter kit options.
IMPORTANT: For easier filter access in a downflow configuration, a removable access panel is recommended in the vertical run of the
return air plenum immediately above the furnace.
.-"" i "",. _ CLOSET
::. "-... RETURN
VENT_ T" " FILTERS PIPE : _! :
288130-UIM-A-0407
kWARNING
For applications requiring more than 1800 CFM, it is required to use both side returns or one side plus the bottom return.
Single side return is not approved on 5 Ton models. 18" minimum height for return air box for bottom return only or Heating only appfications with furnace in the upflow configuration 24" minimum height for return air box for bottom return only on A.
C appfications with furnace in the upflow configuration.
SECTION IV: GAS PIPING
GAS SAFETY
This furnace is designed to operate on NATURAL GAS or PRO- PANE GAS ONLY. Do not bum any other fuel in this furnace. Burn- ing any fuel except NATURAL GAS or PROPANE GAS can cause premature heat exchanger burnout, high levels of carbon monox- ide, excessive sooting, a fire hazard, personal injury, property dam- age and/or death.
kDANGER
An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 PSI (14" w.c. (3.48 kPa). Pressures exceeding
0.5 PSI (14" w.c. (3.48 kPa) at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.
OUTLET __
PRESSURE
PORT i
VENT PORT
I.
WRENCH J _
BOSS INLET// __
PRESSURE PORT
FIGURE 13: Gas Valve
ON/OFF SWITCH (Shownin ON position)
::i:':TO.
ADJUSTMENT
-,$j
FIGURE 12: Return Filter Grill and Return Duct Installation
Accessory External Filter Installation
1. Install the return filter rack on the top of the furnace return air opening. Secure the filter rack to the front and back flanges with
screws. The return air plenum can be placed over the filter rack and the branch ducts (rectangular ducts and ! or round ducts) can
be attached to the plenum. Route the combustion air and the vent PVC pipes around the access panels for the filters.
2. Install the filter(s) provided or you may install Permanent washable filters. Filter should extend through the entire length of the filter
rack to prevent air from bypassing the filter.
IMPORTANT: Air velocity through throwaway type filters must not exceed 300 feet per minute (1.52 m/m). All velocities over this require the use of high velocity filters. Refer to Table 16.
CAUTION
All installations must have a filter instafled.
Unitary Products Group 11
FIGURE 14: Upflow Configuration
288130-UIM-A-0407
4 ¸ •i•
FURNACE CONTROL\
BLOWER DOOR \ SWITCH\'\
ROLL-OUT
BURNERS
HOT SURFACE
IGNITOR
GAS ..........
VALVE
PRESSURE -j SWITCH
FIGURE 15: Downflow Configuration
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con- nector. Do not use a connector that has previously serviced another gas appliance.
Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal- lation of a drip leg and ground union is required. Refer to Figure 17.
EXTERNAL MANUAL SHUTOFF VALVE
TOGAS _' "]_, TOGAL_
T .... VENT
VENTP,PE
i i TRANSITION
ii GAS
i4 ....... PIPE
3" DIAMETER VENT PIPE
GAS
?_'- SHUT-OFF
VALVE
ROLUOUT
.... SWITCH
zz DIRT LEG
VENT
BLOWER
GAS ORIFICE CONVERSION FOR PROPANE (LP)
Refer toTable 7 for the proper gas orifice size.
A.WARNING
The conversion shaft be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified ser- vice agency is responsible for the proper installation. The installa- tion is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer's instruc-
tions.
A.WARNING
Improper installation may damage equipment, can create a shock hazard, and will void the warranty.
IMPORTANT: These instructions are for the use of qualified individuals specially trained, experienced and certified in the installation of this type
of equipment and related system components. Installation and service personnel are required by some states to be licensed. Persons not
qualified shall not install this equipment nor interpret these instructions. NOTE: The words "Shall" or "Must" indicate a requirement, which is
essential to satisfactory and safe product performance.
NOTE: The words "Should" or "May" indicate a recommendation or
advice which is not essential and not required but which may be useful or helpful.
CONTENTS
1. Burner orifices for LP (propane) gas are located in bag attached to the gas valve.
2. Conversion plate.
BURNER GASVALVE
DRIP/" MAY BE INSTALLED LEG INSIDE OR OUTSIDE UNIT.
FIGURE 16: Gas Piping
IMPORTANT: An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet (1.8 m) of the fur-
nace. Refer to Figures 14, 15, and 16. The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (3.5 kPa).
CAUTION]
Never apply a pipe wrench to the body of the gas valve when installing piping. A wrench must be placed on the octagon hub located on the gas inlet side of the valve. Placing a wrench to the body of the gas valve will damage the valve causing improper oper-
ation and/or the valve to leak.
Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace. Refer to Figure 5 dimensions.
GAS ORIFICE GAS
MANIFOLD
FIGURE 17: Burner Assembly
CONVERSION PROCEDURE
CAUTION
The gas supply must be shut off prior to disconnecting the electrical
power, before proceeding with the conversion.
AWARNING
SHOCK HAZARD - Turn off electrical supply to furnace
12 Unitary Products Group
288130-UIM-A-0407
1. Shut off gas supply at valve upstream from furnace or at meter as required. Refer to Figures 9 and 10.
2. Disconnect as supply piping from gas valve on furnace.
3. Disconnect electrical wires from gas valve, nothing which wires are connected to which terminals.
4. Remove the four screws that attach the gas manifold to the burner support box. See Figure 11.
5. Remove and discard natural gas orifices.
6. Remove LP (Propane) orifices from the bag attached to the gas valve.
7. Install the LP (Propane) gas orifices supplied with the furnace. Tighten to 15 - 25 inch - pounds of torque.
8. Reinstall the manifold in the assembly by reversing the removal process.
9. Reconnect the wires to the proper terminals on the gas valve.
10. Remove the regulator with the blue cap and turn it upside down so the letters "LP" are upright. Place the blue cap on the opposite end
of the regulator.
11. Convert the gas valve for LP (propane) gas operation by following the instructions. Remove the natural tag and replace with the pro- pane tag supplied in the orifice bag to the gas burner mounting
plate to show that is has been converted.
12. Remove the blue conversion label on the furnace door after the furnace has been converted.
13. Reconnect the gas supply piping to the gas valve and insure that all gas connections are tight.
14. Remove pressure tap plugs from gas valve and connect water gauge to the pressure tap ports. See Figure 8 for location of the
gas valve pressure taps and pressure regulator adjustment.
15. Turn on gas supply to furnace and check all gas connections with suitable leak detector.
kWARNING
Never use an open flame to check for leaks. Fire or explosion could occur. Since some leak solutions including soap and water may cause corrosion or stress cracking, the piping must be rinsed with water after testing unless it has been determined that the leak test
solution is non-corrosive.
HIGH ALTITUDE GAS ORIFICE CONVERSION
This furnace is constructed at the factory for natural gas-fired operation at 0 - 2,000 ft. (0 m - 610 m) above sea level.
The gas orifices on this furnace must be changed in order to maintain proper and safe operation, when the furnace is installed in a location where the altitude is greater than 2,000 ft. (610 m) above sea level on natural gas or the altitude is greater than 4,000 ft. (1219 m) above sea level on propane (LP) gas. Refer to Table 7 for the proper gas orifice
size. The unit may also be converted for altitudes up to 10,000 ft. (3048 m)
on natural and propane (LP) gas with additional derate as shown in Table 7 or refer to ANSI Z223.1 NFPA 54 National Fuel Gas Code or in
Canada CAN/CGA-B149.1-00 Natural Gas and Propane Installation Code.
kDANGER
PROPANE AND HIGH ALTITUDE CONVERSION KITS
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed. Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-
pane (LP) gas. Do not use this furnace with butane gas. Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death. High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application. An authorized distributor or dealer must make all gas conversions. In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed. Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames, causing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage
and/or death.
TABLE 6: High Altitude Conversion
Type Orifice at 2,000 ft. 3,000 ft. 4,000 ft. 5,000 ft. 6,000 ft. 7,000 ft. 8,000 ft. 9,000 ft. 10,000 ft.
Of Gas Sea Level (610 m) (914 m) (1219 m) (1524 m) (1829 m) (2134 m) (2438 m) (2743 m) (3048 m)
Natural #42 #42 #43 #43 #43 #44 #44 #45 #46 #47
Propane #54 #54 #55 #55 #55 #55 #55 #56 #56 #56
SECTION V: ELECTRICAL POWER
ELECTRICAL POWER CONNECTIONS
Field wiring to the unit must be grounded. Electric wires that are field installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 7 in these instructions for specific furnace electrical data.
Use copper conductors only.
CAUTION]
Unitary Products Group 13
288130-UIM-A-0407
TABLE 7: Ratings & Physical / Electrical Data - Upflow Models
Input
MBH kW
75 22.0 75 22.0
100 29.3
Input
MBH kW
75 22.0 75 22.0
100 29.3
Nominal external static pressure is 0.50" w.c. at furnace outlet ahead of cooling coils. Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures. Wire size and over current protection must comply with the National Electrical Code (NFPA-70qatest edition) and all local codes.
SUPPLY VOLTAGE CONNECTIONS
1. Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/national
electrical codes. The switch should be close to the unit for conve- nience in servicing. With the disconnect or fused switch in the OFF
position, check all wiring against the unit wiring label. Refer to the wiring diagram in this instruction.
2. Remove the screws retaining the wiring box cover. Route the power wiring through the opening in the unit into the junction box
with a conduit connector or other proper connection. In the junc- tion box there will be three wires, a Black Wire, a White Wire and a
Green Wire. Connect the power supply as shown on the unit-wir- ing label on the inside of the blower compartment door or the wir-
ing schematic in this section. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white
furnace lead must be connected to neutral. Connect the green fur- nace lead (equipment ground) to the power supply ground. An
alternate wiring method is to use a field provided 2" (51 mm) x 4" (102 mm) box and cover on the outside of the furnace. Route the
furnace leads into the box using a protective bushing where the wires pass through the furnace panel. After making the wiring con-
nections replace the wiring box cover and screws. Refer to Figure
18.
3. The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figure 19.
BLK A BLK (HOT) o--E::::_<_----4_'_
WHT _WHT (NEUTRAL) f NOMINAL120VOLT
GRN #& GRN _L
Output
MBH kW
60 17.6 60 17.6
80 23.4
Max. Outlet
Air Temp
oF oc
165 73.9 160 71.1 170 76.7
Nominal Airflow
CFM m3min 1200 34.0
1600 45.3 1600 45.3
Blower
Hp Amps 1/2 7.0
1/2 10.4 1/2 10.4
Cabinet Width
In. cm
17-1/2 44.45
21 53.34 21 53.34
Blower
Size
In. cm
10 x 8 25.4 x 20.3 10x10 25.4 x 25.4 10x10 25.4 x 25.4
FIGURE 19: Single Stage Heat Thermostat Connections
IMPORTANT: Some electronic thermostats do not have adjustable heat anticipators. They may have other type cycle rate adjustments. Follow
the thermostat manufacturer's instructions. IMPORTANT: Set the heat anticipator in the room thermostat to 0.40
amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the set points.
The 24-volt, 40 VA transformer is sized for the furnace components only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.
ACCESSORY CONNECTIONS
The furnace control will allow power-switching control of various acces- sories. Refer to Figure 20 for connection details.
Total
Unit
Amps
8.0
11.4
11.4
Max
Over-current
protect
15 15 15
ROOM FURNACE CONDENSING THERMOSTAT CONTROL UNIT
Min.Wire Size (awg) @ 75 ft.
_[_ TO AIR CONDITIONER
.y _ ......................
.................. .........
115 VOLT HUMIDIFIER
HUM. HOT
AFUE
80.0
80.0
80.0
one way
14 14 14
Air Temp. Rise
oF oc
35-65 19.4-36.1 30-60 16.7-33.3
40-70 22.2-38.9
Operation
Weight
LBS Kg
118 53.5 129 58.5 135 61.2
CONTROLS
FIGURE 18: Electrical Wiring - Upflow Position
IMPORTANT: The power connection leads and wiring box may be relo- cated to the left side of the furnace. Remove the screws and cut wire tie
holding excess wiring. Reposition on the left side of the furnace and fas- ten using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied thermostat by following the instructions that come with the thermostat. With the thermostat set in the OFF position and the main electrical source disconnected, connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module, as shown in Figure 19. Electronic thermo- stats may require the common wire to be connected as shown with the dashed line in Figure 19. Apply strain relief to thermostat wires passing through cabinet. If air conditioning equipment is installed, use thermo- stat wiring to connect the Y and C terminals on the furnace control board to the yellow and brown wires on the condensing unit (unit out- side). Refer to Figure 19.
AtR CLEANER J""""""q_
FIGURE 20: Accessory Connections
ELECTRONIC AIR CLEANER CONNECTION
Two 1/4" (0.6 cm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals
provide 115 VAC (1.0 amp maximum) during circulating blower opera- tion.
EAC HOT _ --
115VOLT -- B_ ELECTRONIC I WHT
|
/
14 Unitary Products Group
HUMIDIFIER CONNECTION
Two 1/4" (0.6 cm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.
SECTION Vh TWINNING AND STAGING
NOTE: You can twin two furnaces that have the same integrated control module. Check the part number on the integrated control module. You cannot twin two furnaces that have different integrated control module part numbers. If the part numbers of the two integrated control modules are different they may not communicate with each other so they will not work in a twinning application.
In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver, twinning can be used to make two furnaces operate in tandem. When two furnaces are installed using the same duct system, it is very important that the two furnace cir- culating air blowers operate in unison. If one blower starts before the second blower, the duct system will become pressurized and the blower on the second furnace will turn backwards causing the second furnace to overheat, resulting in damage to the furnace. Twinning is used to make two furnaces operate in tandem, using one duct system, one room thermostat and causing both furnaces to turn on and off simulta- neously.
_WARNING
Before installing the relay and wiring, disconnect electrical power to both furnaces. Failure to cut power could result in electrical shock
or equipment damage.
TWINNING DUCT SYSTEM
Twinned furnaces must only be applied on a common duct system. A single air supply plenum must be used for both furnaces and coil(s).
Separate plenums and supply ducts systems cannot be utilized. A sin- gle return air plenum, common to both furnaces must be used. It is sug- gested that a return platform be utilized, with bottom air entrance into each furnace. If a side entrance returns system is used, the common return duct must be divided equally so as to supply each furnace with an equal amount of return air.
Both furnaces must be identical models in both heating capacity and CFM capacity. Both furnaces must be operated on the same motor speed tap. See typical application, Figure 21.
If furnace staging is desired with two single stage furnaces on a com- mon duct, where the gas burner on the first furnace operates on W1 and the gas burner on the second furnace operates on W2, then the use of an air-mixing device in the plenum to mix the air from both fur- naces is strongly recommended. The mixing device must be installed before any ducts that supply air to occupied spaces. Twinning causes both indoor fans to operate simultaneously. If a mixing device is not used, any ducts that are connected down stream from the furnace that operates on W2, will be supplying cold air in the Heating mode to the occupied spaces unless W2 is energized.
IMPORTANT: When two furnaces are twinned, typical system total air- flow will be approximately 85% of additive individual furnaces, i.e., two
2000 CFM units will yield a total 3400 CFM.
[ CAUTIONJ
If a return duct is connected to only one furnace (with a connection between the two furnaces) an imbalance in the airflow will occur and the furnace furthest from the return plenum will overheat.
288130-UIM-A-0407
VENT PIPE
ELECTRICAL SUPPLY
FIGURE 21: Typical Twinned Furnace Application
GAS PIPING
Furnace gas supplies must be provided as specified with these instruc- tions. Since the furnaces are side by side, with no space between, gas supplies must enter on the right and left respectively. All gas piping must be in accordance with the national fuel gas code, ANSI Z223.1, latest edition, and/or all local code or utility requirements.
GAS SUPPLY (both sides)
1COILFOR
_ EACHFURNACE
TWINNING
Single-Wire Twinning The control in the furnace has the single-wire twinning feature. With this
feature, a single wire is connected between the TWIN terminal on one furnace board to the TWIN terminal on the second furnace board. The
board then communicates the blower status from one furnace to the other along this wire. This communication makes the second furnace
blower come on at the same time, and on the same speed, as the first furnace blower.
Single-Wire Twinning Instructions
Connect the control wiring as shown in Figure 22.
1. Connect the low voltage wiring from the wall thermostat to the ter- minal strip on the control board of Furnace #1.
2. Connect a wire from the TWIN terminal of Furnace #1 to the TWIN terminal of Furnace #2.
3. Install a separate 24V relay as shown in the diagram below. Use of this relay is required, as it ensures that the transformers of the two
furnaces are isolated, thus preventing the possibility of any safety devices being bypassed.
NOTE: The twinned furnaces must be connected to the same leg of the line voltage to prevent phasing error problems. If this is not done prop- erly, the furnaces will not operate and the control board LEDs will flash a rapid red flash to indicate the twinning error.
CAUTION]
The relaymust not be installedin any locationwhere itcould be exposed to water.Ifthe relayhas been exposed to waterin any way,itmust notbe used.
Unitary Products Group 15
288130-UIM-A-0407
Single-Wire Twinning Operation
Heating - On a call for heat (W signal) from the wall thermostat, both furnaces will start the ignition sequence and the burners on both fur- naces will light. About thirty seconds after the burners light, the blowers on both furnaces will come on in heating speed. When the thermostat is satisfied, the burners will all shut off and, after the selected blower off delay time, both blowers will shut off at the same time. The twinned
controls ensure that both blowers come on and shut off at the same time.
Cooling - On a call for cooling (Y signal) from the wall thermostat, both furnace blowers will come on at the same time in cooling speed. When the thermostat is satisfied, both blowers will stay on for 60 seconds,
then will shut off at the same time. Continuous Fan - On a thermostat call for continuous fan (G signal),
both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.
FURNACE 1 CONTROL BOARD FURNACE 2 CONTROL BOARD
i=\#C
TWIN
ISOLATION
/_C! :i 1 ,\_/R
RELAY
i '
TOA!C w G R Y
VVALL THERMOSTAT
Single-Wire Staging Operation Heating - On a call for first-stage heat (W1 signal) from the wall thermo-
stat, Furnace #1 will start the ignition sequence and the burners will light. About thirty seconds after the burners light, the blowers on both furnaces will come on in heating speed. When the thermostat is satis- fied, the burners will shut off and, after the selected blower off delay time, both blowers will shut off at the same time. On a call for second stage of heat, the burners of Furnace #2 will also light and both blowers will run. The twinning control ensures that both blowers come on and
shut off at the same time. Cooling - On a call for cooling (Y signal) from the wall thermostat, both
furnace blowers will come on at the same time. When the thermostat is satisfied, both blowers will stay on for 60 seconds, then will shut off at
the same time. Continuous Fan - On a thermostat call for continuous fan (G signal),
both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.
FURNACE 1 CONTROL BOARD FURNACE 2 CONTROL BOARD
TO A/C Wl G R Y W2
WALL THERMOSTAT
FIGURE 23: Two-Stage Twinning Wiring Diagram
FIGURE 22: Single Stage Twinning Wiring Diagram
STAGING
SECTION Vlh VENT/COMBUSTION AIR SYSTEM
In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver, twinning can be used to make two furnaces operate in tandem, using one duct system and one room thermostat. This control can also be used along with a two-stage wall thermostat to stage two twinned furnaces, making them operate like a single two-stage furnace. This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand. When one duct system is used for two furnaces, it is necessary that the two blowers operate in unison. The twinning func-
tion of this board ensures that both blowers turn on and off simulta-
VENT SAFETY
This Category I, furnace is designed for residential application. It may be installed without modification in a basement, garage, equipment room, alcove, attic or any other indoor location where all required clear-
ance to combustibles and other restrictions are met.
_1-_ MORE THAN ---4_
10 FT (3.0 M) " _T_---- 3_FT (0,9 m )
neously, and operate on the same blower speed. Even when only one furnace is supplying heat, both furnace blowers must run.
Single-Wire Staging
The single-wire twinning feature of this board can also be used for stag- ing of two furnaces. With this feature, a single wire is connected
between the TWIN terminal on one furnace board to the TWIN terminal on the second furnace board. The board then communicates the blower
status from one furnace to the other along this wire. This communica- tion makes the second furnace blower come on at the same time, and
on the same speed, as the first furnace blower.
Single-Wire Staging Instructions
Connect the control wiring as shown in the Figure 23.
1. Connect the low voltage wiring from the wall thermostat to the ter-
WALL OR
PARAPET
.°: :
I : I IPARAPETREQUIRED',
° _ WHEN DISTANCE ',
_." FROM WALLS OR ,
_ PARAPET IS MORE _
THAN 10 FT (3.0 m). CHIMNEY
_4.__ MORE THAN
10FT 3.0M
2 FT(0.6 m),&
HEIGHT ABOVE ANY ROOF SURFACE WITHIN
10 FT (3.0 m) HORIZONTALLY
3 FT (0.9 m) MIN
minal strip on the control board of Furnace #1. For staging applica- tions, the wire from thermostat W1 is connected to the W
connection on the board on Furnace #1. The wire from thermostat W2 is connected to Furnace #2 through a separate relay, as
described below.
2. Connect a wire from the TWIN terminal of Furnace #1 to the TWIN terminal of Furnace #2.
3. Install a separate 24V relay as shown in the diagram below. Use of this relay is required, as it ensures that the transformers of the two
FIGURE 24: Vent Termination
CHIMNEY
furnaces are isolated, thus preventing the possibility of any safety devices being bypassed.
16 Unitary Products Group
288130-UIM-A-0407
LOWEST DISCHARGE OPENING
LISTED CAP
LISTED GAS -- VENT
J
FIGURE 25: Vent Termination
TABLE 8: Roof Pitch
ROOF PITCH H(min) ft m
Flat to 6/12 1.0 0.30
6/12 to 7/12 1.25 0.38 Over 7/12 to 8/12 1.5 0.46 Over 8/12 to 9/12 2.0 0.61
Over 9/12 to 10/12 2.5 0.76 Over 10/12 to 11/12 3.25 0.99 Over 11/12 to 12/12 4.0 1.22 Over 12/12 to 14/12 5.0 1.52 Over 14/12 to 16/12 6.0 1.83 Over 16/12 to 18/12 7.0 2.13 Over 18/12 to 20/12 7.5 2.27 Over 20/12 to 21/12 8.0 2.44
ROOF PITCH IS X/12
H (min) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
VENTING
Category I venting consists of vertically venting one or more appliances in B-vent or masonry chimney (as allowed), using single wall metal pipe
or B-vent connectors. Type B-vent system extends in a general vertical direction and does not contain offsets exceeding 45 degrees. A vent
system having not more than one 60 degree offset is permitted.
CHIMNEY OR GAS VENT
ALTERNATE
VENTIALTION LOUVERS FOR UNHEATED CRAWL SPACE
VENTILATION LOUVERS (Each end of attic)
OUTLET AIR
INLET
FIGURE 26: Alternate Air Intake, Air Outlet and Chimney Connections
CHIMNEY OR
VENTILATION LOUVERS
Each end of attic)
OUTLET
AIR
CATEGORY 1 - 450 IF. MAX. VENT TEMP. The venting system must be installed in accordance with Section 5.3,
Air for Combustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54 (latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1, National Gas and Propane Codes (latest edition) or applicable provisions of the local building code and these instructions.
The furnace shall be connected to any type of B, BW or L vent connec- tor, and shall be connected to a factory-built or masonry chimney. The furnace shall not be connected to a chimney flue serving a sepa- rate appliance designed to burn solid fuel,
The furnace rating plate lists the maximum vent gas temperature. This temperature must be used to select the appropriate venting materials
and clearances. It is recommended that the appliance is installed in a location where the
space temperature is 32 °F (0°C) or higher. If the appliance is installed in a location where the ambient temperature is below 32 °F (0°C), the flue by-products could condense causing damage to the appliance heat exchanger.
IMPORTANT: The "VENT SYSTEM" must be installed as specified in these instructions for Residential and Non HUD Modular Homes.
This appliance may be common vented with another gas appliance for residential installations as allowed by the codes and standards listed in
these instructions. Non-HUD approved Modular Homes must be vented with a listed dou-
ble wall or B-vent system and may not be common vented with other appliances.
INLETAIR DUCT
1 ft (30 cm)
above floor}
FIGURE 27: Air Inlet, Outlet and Chimney Connections
VENTING INTO AN EXISTING CHIMNEY
For Category I installations, the furnace shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a material acceptable to the authority having jurisdiction. Venting into an unlined masonry chimney or concrete chimney is prohibited.
Whenever possible, B-1 metal pipe should be used for venting. Where use of an existing chimney is unavoidable, the following rules must be
followed:
1. The masonry chimney must be built and installed in accordance with nationally recognized building codes or standards and must
be lined with approved fire clay tile flue liners or other approved liner material that will resist corrosion, softening, or cracking from
flue gases. THIS FURNACE IS NOT TO BE VENTED INTO AN UNLINED MASONRY CHIMNEY.
2. This furnace must be vented into a fire clay tile lined masonry chimney only if a source of dilution air is provided, such as by com-
mon venting with a draft hood equipped water heater. If no source of dilution air is available, Type B vent must be used, or masonry
chimney vent kit 1CK0603 or 1CK0604 must be used. Refer to the instructions with the kit to properly apply these masonry chimney kits.
Unitary Products Group 17
288130-UIM-A-0407
3. The chimney must extend at least three feet above the highest point where it passes through a roof of a building and at least two
feet higher than any portion of the building with a horizontal dis- tance of ten feet.
4. The chimney must extend at least five feet above the highest equipment draft hood or flue collar.
HORIZONTAL SIDEWALL VENTING
For applications where vertical venting is not possible, the only approved method of horizontal venting is the use of an auxiliary power vent. Approved power venters are Fields Controls Model SWG-4Y or Tjernlund Model GPAK-JT. Follow all application and installation details provided by the manufacturer of the power vent. Refer to Figures 28 and 29 for typical installation views.
FAN ASSISTED FURNACE & WATER HEATER
OPTIONAL
.... I _1 VENT SYSTEM
FURNACE WATER
HOT
FAN ASSISTED FURNACES
-- EXTERIOR
U
FIGURE 28: Typical Sidewall Vent Application
VENT PiPE
VENT
TABLE 9: Horizontal Sidewall Venting Clearances
Horizontal Vent Length Ft. (m) with 4 Elbows
Models Pipe Size Min. Vent Length Max. Vent Length
Inches cm Feet meters Feet meters
All Models 4 10.2 4.5 1.37 34.5 10.82
VENT PIPING ASSEMBLY
The final assembly procedure for the vent piping is as follows:
1. Cut piping to the proper length beginning at the furnace.
2. Deburr the piping inside and outside.
3. Dry-fit the vent piping assembly from the furnace to the termination checking for proper fit support and slope. Piping should be sup-
ported with pipe hangers to prevent sagging. The maximum spac- ing between hangers is 4 feet (1.22 m).
4. Assemble the vent piping from the furnace to the termination securing the pipe connections with screws.
GAS VENT
FLUE
TOP
OPTIONAL SIDEWALL
VENT SYSTEM
(field supplied)
.CELLAR ACCESS
WALL PANEL
FIGURE 29: Typical Sidewall Vent and Termination Configuration
FIGURE 30: Typical Chimney Connections
2_
FIGURE 31: Horizontal Air Inlet, Outlet and Chimney Connections
VENT CLEARANCES
IMPORTANT: The vent must be installed with the following minimum clearances as shown in Figure 32, and must comply with local codes
and requirements.
18 Unitary Products Group
288130-UIM-A-0407
\
\
\
FIGURE 32: Home Layout
Canadian Installations I US Installation 2
A. Clearance above grade, veranda, porch, deck, or balcony 12 inches (30 cm) 12 inches (30 cm)
B. Clearance to window or door that may be opened 12 inches (30 cm) 4 Feet (1.22 m) C. Clearance to permanently closed window 12 inches (30 cm) 12 inches (30 cm)
D. Vertical clearance to ventilated soffit located above the terminal within a horizontal distance 4 Feet (1.22 m) 4 Feet (1.22 m)
of 2 feet (61 cm) from the center line of the terminal E. Clearance to unventilated soffit 12 Inches (30 cm) 12 Inches (30 cm) F. Clearance to outside corner 12 Inches (30 cm) 12 Inches (30 cm) G. Clearance to inside corner 6 Feet (1.83 m) 6 Feet (1.83 m)
H. Clearance to each side of center line extended
3 feet (0.91 m) within a height 3 feet (0.91 m) within a height
15 feet (4.57 m) above the 15 feet (4.57 m) above the
above meter/regulator assembly meter/regulator assembly meter/regulator assembly I. Clearance to service regulator vent outlet 3 feet (0.91 m) 3 feet (0.91 m)
J. Clearance to nonmechanical air supply inlet to 12 inches (30 cm) 4 Feet (1.22 m) building or the combustion air inlet to any other appliance
K. Clearance to a mechanical supply inlet 6 feet (1.83 m) 10 feet (3.04 m) horizontally
_. Clearance above paved sidewalk or paved
driveway located on public property
7 feet (2.13 m) t 7 feet (2.13 m) t
M. Clearance under veranda, porch, deck, or balcony 12 inches (30 cm) 12 inches (30 cm) Vent Termination from any Building Surface 12 inches (30 cm) 12 inches (30 cm) Above anticipated snow depth 12 inches (30 cm) 12 inches (30 cm)
1. In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code. 1" A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
_: Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. For clearance not specified in ANSI Z223.1 / NFPA
54 or CSA B149.1-00.
Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Manual. Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet. Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
A terminus of a vent shall be either: Fitted with a cap in accordance with the vent manufacturer's installation instructions, or In accordance with the installation instructions for a special venting system.
* Does not apply to multiple installations of this furnace model. Refer to "VENTING MULTIPLE UNITS" in this section of these instructions. IMPORTANT: Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building surfaces with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in order to prevent flue products and/ or condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension of 20 inches. It is recommended that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe. Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer. Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.
HORIZONTAL VENT APPLICATIONS AND
4. Termination should be located where it will not be damaged or
TERMINATION
When selecting the location for a horizontal combustion air / vent termi-
5. Termination should be positioned where vent vapors are not objec-
nation, the following should be considered:
1. Observe all clearances listed in vent clearances in these instruc-
6. Horizontal portions of the vent system must slope upwards and be
tions.
2. Termination should be positioned where flue products will not dam- age plants or shrubs or air conditioning equipment.
3. Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue
gases.
[] VENT TERMINAL
AIR SUPPLY
AREA WHERE TERMINAL IS NOT PERMITTED
3 feet (0.91 m) above if within
exposed to flying stones, balls, etc.
tionable.
supported to prevent sagging. The vent system may be supported by the use of clamps or hangers secured to a permanent part of
the structure every 4 ft. (1.22 m).
Unitary Products Group 19
288130-UIM-A-0407
FAN-ASSISTED COMBUSTION SYSTEM
An appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and!or heat exchanger.
Ambient Combustion Air Supply
This type installation will draw the air required for combustion from within the space surrounding the appliance and from areas or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts. A single, properly sized pipe from the furnace vent connector to the out- doors must be provided. For upflow models combustion air is brought into the furnace through the unit top panel opening.
VENT PIPE FITS INTOSOCKET JUST --'_
COMBUSTION !- AiR _ i:iii:ili:
ABOVE TOPPANEL
COMBUSTION
A,R
\
A confined space is an area with less than 50 cu.ft (1.42 m 3) per 1,000 Btu/hr (0.2928 kW) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces.
Combustion Air Source From Outdoors The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or grille is not known, refer to Table 10, to estimate free area.
TABLE 10: Estimated Free Area
Wood or Metal Wood 20-25%*
Louvers or Grilles Metal 60-70% *
Screens+
Do not use less than 1/4"(0.635 cm) mesh + Free area or louvers andgrille varies widely; theinstaller should follow lou-
ver or grillemanufacturer's instructions.
Dampers, Louvers and Grilles (Canada Only)
1. The free area of a supply air opening shall be calculated by sub- tracting the blockage area of all fixed louvers grilles or screens
from the gross area of the opening.
2. Apertures in a fixed louver, a grille, or screen shall have no dimen- sion smaller than 0.25" (0.635 cm).
3. A manually operated damper or manually adjustable louvers are not permitted for use.
4. A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position.
TABLE 11: Free Area
1!4" (0.635 cm)
mesh or larger 100%
UPFLOW DOWNFLOW
FIGURE 33: Combustion Airflow Path Through The Furnace Casing to
the Burner Box
_WARNING
This type of installation requires that the supply air to the appfi- ance(s) be of a sufficient amount to support all of the appliance(s) in the area. Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre- ate conditions requiring special attention to avoid unsatisfactory operation of gas appliances. A venting problem or a lack of supply air will result in a hazardous condition, which can cause the appli- ance to soot and generate dangerous levels of CARBON MONOX- IDE, which can lead to serious injury, property damage and / or
death.
An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/ hr (0.2928 kW) input rating for all of the appliances installed in that
area. Rooms communicating directly with the space containing the appli-
ances are considered part of the unconfined space, if openings are fur- nished with doors.
Minimum Free Area Required for Each Opening
BTUH Input Vertical Duct or
Rating Opening to Outside
75,000 38 in2 (245 cm 2) 19 in2 (123 cm2) 5" (13 cm)
100,000 50 in2 (322 cm 2) 25 in2 (161 cm2) 6" (15 cm)
EXAMPLE: Determining Free Area.
Appliance 1Appliance 2Total Input
100,000 + 30,000=(130,000+4,000)=32.5Sq. ln. Vertical
Appliance 1Appliance 2Total Input
100,000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal
TABLE 12: Unconfined Space Minimum Area in Square Inches
BTUH Input Rating Minimum Free Area Required for Each Opening
75,000 75 (484 cm 2)
100,000 100 (645 cm 2)
Horizontal Duct Round Duct
(2,000 BTUH) (4,000 BTUH) (4,000 BTUH)
20 Unitary Products Group
288130-UIM-A-0407
GAS
GABLE VENT
OPTIONAL
VENTILATED E_
CRAWL SPACE
5. A square or rectangular shaped duct shall only be used when the required free area of the supply opening is
9 in 2(58.06 cm 2)or larger. When a square or rectangular duct is used, its small dimensionshall not be less than 3 in (7.6 cm).
6. An air inlet supply from outdoors shall be equipped with a means to prevent the direct entry of rain and wind•
Such means shall net reduce the required free area of the air supply opening•
7. An air supply inlet opening from the outdoors shall be located not less than 12" (30.5 cm) above the
outside grade level.
VENT
AIR SUPPLY OPENINGS AND DUCTS
1• An opening may be used in lieu of a duct to provide to provide the outside air
supply to an appliance unless otherwise permitted by the authority having
jurisdiction. The opening shall be located within 12" (30.5 cm) horizontally from,
the burner level of the appliance. Refer to "AIR SOURCE FROM OUTDOORS AND VENTAND SUPPLY AIR SAFETY CHECK" in these instructions for
additional information and safety check procedure. OUTLE_
2• The duct shall be either metal, or a material meeting the class 1 AIR (b)
requirements of CAN4-S 110 Standard for Air Ducts.
3• The duct shall be least the same cross-sectional area as the free
area of the air supply inlet opening to which it connects.
4 The duct shall terminate within 12 in (30.5 cm) above, and
within 24 in (61 cm) horizontally from, the burner level of the appliance having the largest input.
GABLE VENT VENT
WATER
HFATER INLET 4.
FIGURE 34: Outside and Ambient Combustion Air
kWARNING
When a Category I furnace is removed or replaced, the original venting system may no longer be correctly sized to properly vent the attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE to spill into the living space causing personal injury, and or death.
Ventilated Combustion Air The ventilated attic space or a crawl space from which the combustion
air is taken must comply with the requirements specified in "AIR SOURCE FROM OUTDOORS" in this instruction or in Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (latest edition). This type installation requires a pipe that extends from the furnace vent connection (top right of unit) to the exte- rior of the building. Follow all notes, procedures and required materials
in the COMBUSTION AIR SUPPLY section in these instructions when installing the unit and into a ventilated attic space or crawl space. DO
NOT terminate vent pipe in an Attic or Crawl Space.
GAS
IIII
.W_TA_gR
INLET AIR (b) _ --
COMBUSTION AIR SOURCE FROM OUTDOORS
GAS
l I l I-I lAIR(a)
1. Two permanent openings, one within 12 in (30•5 mm) of the top and one within 12 in (30.5 mm) of bottom of the confined space, Two
permanent openings, shall communicate directly or by means of ducts
with the outdoors, crawl spaces or attic spaces•
2. One permanent openings, commencing within 12 in (30•5 mm)efthe top of the enclosure shall be permitted where the equipment has clearances of at least 1 in (2•54 cm) from the sides and back and
6 in (15•24 cm) from the front of the appliance• The opening shall communicate directly with the outdoors and shall have a minimum
free area of:
a. 1 square in per 3000 Btu per hour (6•45 cm20.879 kW) of the total
input rating of all equipment located in the enclosure.
b. Not less than the sum of all vent connectors in the confined space.
The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.
The blocking effects of louvers, grilles and screens must be given consideration in calculating free area. If the free area of a specific louver aor grille is not known.
Vent and Supply (Outside) Air Safety Check Procedure For Category I furnaces, vent installations shall be in accordance with
Parts 7 and 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and or Section 7 and Appendix B of the CSA B149.1, Natural Gas and
Propane Installation Codes, the local building codes, furnace and vent manufacture's instructions.
Multistory or common venting systems are permitted and must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1!
NFPA 54 and ! or the CSA B149.1, Natural Gas and Propane Installa- tion Codes, local codes, and the manufacture's instructions.
Vent connectors serving Category I furnaces shall not be connected into any portion of mechanical draft systems operating under positive pressure.
Horizontal portions of the venting system shall be supported to prevent sagging using hangers or perforated straps and must slope upwards not less than 1!4" per foot (0.635 cm/m) from the furnace to the vent ter-
minal. It is recommended that you follow the venting safety procedure below.
This procedure is designed to detect an inadequate ventilation system that can cause the appliances in the area to operate improperly causing
unsafe levels of Carbon Monoxide or an unsafe condition to occur.
t!I 1,,
t I I ] IJ AIR (a)
NLET
Unitary Products Group 21
288130-UIM-A-0407
_WARNING
CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances
connected to the venting system are not in operation:
1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other deficiencies, which could cause an unsafe condition
2. Close all building doors and windows and all doors.
3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Open the fireplace dampers. Do not operate a summer exhaust fan.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate contin- uously.
5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the
appliance as possible. Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a downdraft or inadequate draft condition.
6. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fire- place dampers and any other gas burning appliance to their normal condition.
7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can
function safely.
NOTE: An unsafe condition exists when the CO reading at the furnace vent exceeds 40 ppm and the draft reading is not in excess of - 0.1 in.
W.C. (-25 kPa) with all of the appliance(s) operating at the same time.
8. Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1-00 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the
appropriate tables in Appendix G of the above codes or for this appliance.
SECTION Vllh SAFETY CONTROLS
CONTROL CIRCUIT FUSE
A 3-amp fuse is provided on the control circuit board to protect the 24- volt transformer from overload caused by control circuit wiring errors. This is an ATO 3, automotive type fuse and is located on the control
board.
BLOWER DOOR SAFETY SWITCH
This unit is equipped with an electrical interlock switch mounted in the blower compartment. This switch interrupts all power at the unit when the panel covering the blower compartment is removed.
Electrical supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned.
l CAUTIONI
Main power to the unit must still be interrupted at the main power disconnect switch before any service or repair work is to be done to the unit. Do not rely uoon the interlock switch as a main cower dis-
connect. Blower and burner must never be operated without the blower
panel in place.
ROLLOUT SWITCH CONTROLS
These controls are mounted on the burner box assembly. If the temper- ature in the burner box exceeds its set point, the ignition control and the
gas valve are de-energized. The operation of this control indicates a malfunction in the combustion air blower, heat exchanger or a blocked
vent pipe connection. Corrective action is required. These are manual reset controls that must be reset before operation can continue.
PRESSURE SWITCHES
This furnace is supplied with a pressure switch, which monitors the flow through the combustion air/vent piping system. This switch de-ener-
gizes the ignition control module and the gas valve if any of the follow- ing conditions are present. Refer to Figure 35 for tubing connections.
1. Blockage of combustion air piping or terminal.
2. Blockage of vent piping or terminal.
3. Failure of combustion air blower motor.
FIGURE 35: Pressure Switch Tubing Routing
LIMIT CONTROLS
There is high temperature limit control located on the furnace vestibule panel near the gas valve. This is an automatic reset control that pro- vides over temperature protection due to reduced airflow, that may be caused by a dirty filter, or if the indoor fan motor should fail. The control module will lockout if the limit trips 3 consecutive times. Control will reset and try ignition again after 1 hour.
SECTION IX: START-UP AND ADJUSTMENTS
The initial start-up of the furnace requires the following additional procedures:
IMPORTANT: All electrical connections made in the field and in the fac- tory should be checked for proper tightness.
When the gas supply is initially connected to the furnace, the gas piping may be full of air. In order to purge this air, it is recommended that the ground union be loosened until the odor of gas is detected. When gas is detected, immediately retighten the union and check for leaks. Allow five minutes for any gas to dissipate before continuing with the start-up procedure. Be sure proper ventilation is available to dilute and carry away any vented gas.
22 Unitary Products Group
288130-UIM-A-0407
TOOLS AND INFORMATION THAT WILL BE REQUIRED IN ORDER TO PROPERLY PERFORM THE FURNACE STARTUP PROCEDURE.
1. Call the local gas supplier to obtain heating value of the natural gas. If you cannot obtain the heating valve of the gas from the gas supplier, you may use a default value of 1030 BTU/SCF (38.4 MJ /
m3).
2. You will need a thermometer or portable digital thermometer to read the supply and return air temperatures.
3. You will need a U-tube manometer or digital equipment that has the ability to read pressures between 0 - 15" in.w.c (0 - 3.73 kPa)
in order to measure the gas line and the manifold pressures.
4. You will need a 3/32" Allen wrench for the pressure port plugs in the gas valve.
5. You will need 2 pieces of 1/8" (0.3 cm) ID flexible tubing that is 12" (30 cm) in length, 2 - pieces of 1/8" (0.3 cm) tubing that are 4"
(10.0 cm) in length, a 1/8" (0.3 cm) tee and a 1/8" (0.3 cm) adapter to connect the U-tube manometer or the digital pressure measur-
ing equipment to the gas valve pressure ports.
There is an accessory kit (1PK0601) available from Source 1, which has the following items:
1 - 12" (30 cm) length x 1/8" (0.3 cm) diameter tubing
2 - pieces of 4" (10 cm) length x 1/8" (0.3 cm) diameter tubing
1 - 5/16" (0.8 cm) tee 1 - 5/16" (0.8 cm) x 1/8" (0.3 cm) reducing coupling 1 - 1/8" (0.3 cm) adapter
There is a accessory kit (1PK0602) available from Source 1, which has the following items:
12" (30 cm) length x 1/8" (0.3 cm) diameter tubing
2 - pieces of 4" (10 cm) length x 1/8" (0.3 cm) diameter tubing
1 - 5/16" (0.8 cm) tee 1 - 5/16" (0.8 cm) x 1/8" (0.3 cm) reducing coupling
1 - 1/8" (0.3 cm) adapter 1 - Dwyer- Manometer
These items are required in order to properly perform the required start- up procedure.
IGNITION SYSTEM SEQUENCE
1. Turn the gas supply ON at external valve and main gas valve.
2. Set the thermostat above room temperature to call for heat.
3. System start-up will occur as follows: a. The induced draft blower motor will start and come up to
speed. Shortly after inducer start-up, the hot surface ignitor will glow for about 17 seconds.
b. After this warm up, the ignition module will energize (open)
the main gas valve.
c. After flame is established, the supply air blower will start in
about 30 seconds.
_WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
IMPORTANT: Burner ignition may not be satisfactory on first startup due to residual air in the gas line or until gas manifold pressure is
adjusted. The ignition control will make 3 attempts to light before lock- ing out.
With furnace in operation, check all of the pipe joints, gas valve connec- tions and manual valve connections for leakage using an approved gas detector, a non-corrosive leak detection fluid, or other leak detection methods. Take appropriate steps to stop any leak. If a leak persists, replace the component.
The furnace and its equipment shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSI (3.45 kPa).
The furnace must be isolated from the gas supply piping system by closing the equipment shutoff valve during any pressure testing of the gas supply piping system.
CALCULATING THE FURNACE INPUT (NATURAL GAS)
NOTE: Burner orifices are sized to provide proper input rate using natu- ral gas with a heating value of 1030 BTU/Ft 3 (38.4 Mj/m3). If the heat-
ing value of your gas is significantly different, it may be necessary to replace the orifices.
NOTE: Front door of burner box must be secured when checking gas
input.
1. Turn off all other gas appliances connected to the gas meter.
2. At the gas meter, measure the time (with a stop watch) it takes to use 2 cubic ft. (0.0566 m3.) of gas.
3. Calculate the furnace input by using one of the following equa- tions.
TABLE 13: Field Installed Accessories - Non Electrical
PART NO,
1FB0318 1FB0319
1FB0320 1BR0312 1BR0316 1BR0320
1PS0466
1PS0467
2802-321P
High Altitude Conversion Kit for Natural Gas
High Altitude Conversion Kit for Propane (LP) Gas
DESCRIPTION
Combustible Floor Sub-Base
Bottom Filter Rack
Vent Pipe Extension
USED WITH
50,7512
7516,10016
10020,125
50,7512
7516,10016
10020,125,150
All Models All Models All Models
Unitary Products Group 23
288130-UIM-A-0407
In the USA use the following formula to calculate the furnace input. For natural gas multiply the heat content of the gas BTU/SCF (or Default 1030 BTU!SCF, times 2 cubic ft. of gas measured at the gas meter, times a
barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time (In seconds) it took to measure 2 cubic ft. of gas from the gas meter.
For propane (LP) gas multiply the heat content of the gas BTU/SCF (or Default 2500 BTU/SCF, times 1 cubic ft. of gas measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time (In seconds) it took to measure 1 cubic
ft. of gas from the gas meter. The formula for US input calculation using a cubic foot gas meter:
BTU/f 3x 2 cu.ft, x 0.960 x 3600
Seconds ittook to measure the 2 cu.ft,of gas NATURAL GAS INPUTCALCULATION EXAMPLE:
1030 x 2 x 0.960 x 3600
Natural Gas
In Canada you will use the following formula to calculate the furnace input if you are using a cubic foot gas meter. For Natural Gas multiply the Heat content of the gas MJ/m 3 (or Default 39.2), times 2 cu. ft. of gas x 0.02831 to convert from cubic feet to cubic
meters measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 2 cu.ft, of gas from the gas meter.
For Propane (LP) Gas multiply the Heat content of the gas MJim 3 (or Default 93.14), times 1 cu. ft. of gas x 0.02831 to convert from cubic feet to cubic meters measured at the gas meter, times a barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the
time it took to measure 1 cu.ft, of gas from the gas meter. The formula for metric input calculation using a cubic foot gas meter:
MJ/m 3 x (2 cu.ft, x Conv) x 0.960 x
Seconds ittook to measure the 2cu.ft, of gas NATURAL GAS INPUTCALCULATION
EXAMPLE:
Natural Gas
PROPANE(LP) GAS INPUTCALCULATION
EXAMPLE:
Propane Gas
In Canada use the following formula to calculate the furnace input if you are using a gas meter that measures cubic meters. For Natural Gas multiply the Heat content of the gas MJ/m 3 (or Default 39.2), times 0.0566 m 3 of gas measured at the gas meter, times a barometric
pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 0.0566 m3 of gas from the gas meter. For Propane (LP) Gas multiply the Heat content of the gas M Jim 3 (or Default 93.14), times 0.00283 m3 of gas measured at the gas meter, times a
barometric pressure and temperature correction factor of 0.960; times 3600, then divided by the time it took to measure 0.0283 cm of gas from the gas meter.
The formula for metric input calculation using a cubic foot gas meter:
MJ/m 3 x (2 cu.ft, x Conv) x 0.960 x
Seconds ittook to measure the 2cu.ft, of gas NATURAL GAS INPUTCALCULATION
EXAMPLE:
Natural Gas
PROPANE (LP) GAS INPUTCALCULATION EXAMPLE:
Propane Gas
90.5
BTU/SCF 1030
3600 = MJ/H x
39.2 X 2 X0.960 X 3600
90.5
BTU/SCF 1030 = 39.2 MJim 3
93.15 X 1 X0.960 X 3600 108
BTU/SCF 2500+93.15 MJim 3
3600 = MJ/H x
39.2 x 2 x 0.960 x 3600
90.5
BTU/SCF 1030 = 39.2 MJ/m 3
93.15 x 1 x 0.960 x 3600 108
BTU/SCF 2500+93.15 MJ/m 3
= BTUH/H
= 79,997.38
= 84.76 X
= 84.41 X
= 84.76 x
= 84.41 x
BTU/f 3 x 1 cu.ft, x 0.960 x 3600 =
Seconds ittook to measure the 2 cu.ft, of gas PROPANE (LP)GAS INPUT CALCULATION
EXAMPLE:
2500 x 1 x 0.960 x 3600
108
Propane Gas
0.2777 = kW x 3412.14 = BTUH/H
0.2777 = 23.54 x 3412.14 =
0.2777 = 23.45 x 3412.14 =
0.2777 = kW x 3412.14 = BTUH/H
0.2777 = 23.54 x 3412.14 =
0.2777 = 23.45 x 3412.14 =
BTU/SCF 2500
BTUH/H
80,000.00
80,312.6
2
80,000.0
0
80,312.6
2
80,000.0
0
DO NOT ADJUST the manifold pressure regulator if the actual input is equal to or within 8% less than the furnace input specified on the rating plate or if the furnace rise is above the specified rise range on the rating plate.
If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifice spuds with the gas ori- fice spuds of the proper size for the type of gas you are using.
24 Unitary Products Group
,&CAUTION
Be sure to relight any gas appliances that were turned off at the start of this input check.
TABLE 14: Inlet Gas Pressure Range
INLET GAS PRESSURE RANGE
Natural Gas Propane (LP)
Minimum 4.5" W.C. (1.12 kPa) 8.0" W.C. (1.99 kPa)
Maximum 10.5" W.C. (2.61 kPa) 13.0" (3.24 kPa) W.C.
IMPORTANT: The inlet gas pressure operating range table specifies what the minimum and maximum gas line pressures must be for the fur-
nace to operate safely. The gas line pressure MUST BE a minimum of
7" W.C. (1.74 kPA) for Natural Gas 11" W.C. (2.74 kPA) for Propane (LP) Gas
in order to obtain the BTU input specified on the rating plate and in these instructions.
ADJUSTMENT OF MANIFOLD GAS PRESSURE
Manifold gas pressure may be measured at the gas valve. Turn gas off at the ball valve or gas ¢o¢k on gas supply line
before the gas valve. Find the pressure ports on the gas valve marked OUT P and IN P.
1. The manifold pressure must be taken at the port marked OUT R
2. The gas line pressure must be taken at the port marked IN R
3. Using a 3/32" Allen wrench, loosen the setscrew by turning it 1 turn counter clockwise. DO NOT REMOVE THE SET SCREW
FROM THE PRESSURE PORT.
4. Use the 4" (10.2 cm) piece of 1/8" (0.3 cm) tubing to connect the positive side of the manometer to the gas valve pressure refer-
ence port. Refer to Figure 37 for connection details.
IMPORTANT: The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw. Loosening or tightening
the cap does not adjust the flow of gas.
5. Refer to Figure 36 for location of pressure regulator adjustment cap and adjustment screw on main gas valve.
6. Turn gas and electrical supplies on and follow the operating instructions to place the unit back in operation.
7. Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following:
TABLE 15: Nominal Manifold Pressure
Nominal Manifold Pressure
Natural Gas 3.5" w.c. (0.87 kPa)
Propane (LP) Gas 10.0" w.c. (2.488 kPa)
OUTLET ..... _'_
PRESSURErq ......f T"
PORT 1
WRENCH f _
oss
PRESSURE PORT
FIGURE 36: Gas Valve
ON/OFF SWITCH (Shown in ON position)
'_::7 VENT PORT
<--- OUTLET
MAIN REGULATOR ADJUSTMENT
288130-UIM-A-0407
IMPORTANT: If gas valve regulator is turned in (clockwise), manifold pressure is increased. If screw is turned out (counterclockwise), mani-
fold pressure will decrease.
8. After the manifold pressure has been adjusted, re-calculate the furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to "CALCULATING THE FURNACE INPUT (NATURAL GAS)".
9. Once the correct BTU (kW) input has been established, turn the gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing and fittings from the gas valve pressure tap and tighten the pressure tap plug using the 3/32" Allen wrench.
10. Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved gas detector, a non-corrosive leak detection fluid, or other leak detection methods.
AWARNING
The manifold pressure must be checked with the screw-off cap for the gas valve pressure regulator in place. If not, the manifold pres- sure setting could result in an over-fire condition. A high manifold pressure will cause an over-fire condition, which could cause pre- mature heat exchanger failure. If the manifold pressure is too low, sooting and eventual clogging of the heat exchanger could occur. Be sure that gas valve regulator cap is in place and burner box to
gas valve pressure reference hose is connected.
MAINFOLD PRESSURE "U" TUBE CONNECTION
_ OUTLET
_,_q_,_r__ _ PRESSURE TAP
GAS VALVE J "_ MANIFOLD PiPE
_ 1/4" TUBING
\ hLJ Ill-i-Ill± 3. ,N
\ {_ WATER
FLAME U-TUBE lU--,L--III COLUMN
SENSOR MANOMETER {m- __-_ GAS
MAINFOLD PRESSURE "U" TUBE CONNECTION
1/4"TUBING _e_ .... _rl SENSOR
OUTLET __N
PRESSURE
TAP MANIFOLD q_-_- _[
U-TUBE COLUMN
MANOMETER TGAS
FIGURE 37: Reading Gas Pressure
[_ ._ FLAME
PIPE _L_ _
WATER
PRESSURE SHOWN
I_--_--ml I PRESSURE
' SHOWN
GASVALVE
Unitary Products Group 25
288130-UIM-A-0407
ADJUSTMENT OF TEMPERATURE RISE
,,DANGER
The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application
limitations shown in Table 7 "ELECTRICAL AND PERFORMANCE DATA ".
The supply air temperature cannot exceed the "Maximum Supply Air Temperature" specified in these instructions and on the fur- nace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause premature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or
death.
The temperature rise, or temperature difference between the return air and the heated supply air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations
as shown in Table 7. After about 15 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.83 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
FAN OFF ADJUSTMENT_ JUMPER
TWAIN
oow
m_r
All direct-drive blowers have multi-speed motors. The blower motor speed taps are located in the control box in the blower compartment. Refer to Figure 38, and the unit wiring label to change the blower speed. To use the same speed tap for heating and cooling, the heat ter- minal and cool terminal must be connected using a jumper wire and
connected to the desired motor lead. Place all unused motor leads on Park terminals. Two are provided.
[,& CAUTION
Do not energize more than one motor speed at a time or damage to the motor will result.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec- onds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space. The fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 38.
PARK PARK____ _
_------ YELLOW-MED. LOW
H_AT_L_.
EAC==_H
RED-LOW
BLACK-HI
BLUE-MED. HI
z
I OO ]
÷
FIGURE 38: Furnace Control Board
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn "on" for 1/4 second and "off" for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six "on" flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec- ond "off" period.
SLOW GREEN FLASH: Normal operation. SLOW AMBER FLASH: Normal operation with call for heat.
26 Unitary Products Group
RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check twinning wiring.
RAPID AMBER FLASH: Flame sense current is below 1.5 microamps. Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.
4 AMBER FLASHES: The control board is recieving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wir- ing.
1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.
2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring.
HUM +
288130-UIM-A-0407
3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, bro- ken pressure switch hose or faulty pressure switch.
4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the fail-
ure condition. 6 RED FLASHES: This indicates that after the unit was operating, the
pressure switch opened 4 times during the call for heat. If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.
7 RED FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.
8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will lock out for one hour and then restart. 9 RED FLASHES: Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.
10 RED FLASHES: Gas flow with no call for heat. Check gas valve and gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel. Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.
12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro- ken igniter.
STEADY ON RED: Control failure. Replace control board. 60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a "watchdog" type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the "watchdog" would restart the unit and pro-
vide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (pa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.1 microamps DC (pa)
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace
is lost. This feature should onlv be used bv a aualified service tech- nician.
The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error
codes. To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.
FILTER PERFORMANCE
The airflow capacity data published in Table 17 represents blower per- formance WITHOUT filters. To determine the approximate blower per- formance of the system, apply the filter drop value for the filter being used or select an appropriate value from the Table 16.
The filter pressure drop values in Table 16 are typical values for the type of filter listed and should only be used as a guideline. Actual pres- sure drop ratings for each filter type vary between filter manufacturers.
TABLE 16: Filter Performance - Pressure Drop Inches W.C. and (kPa)
Airflow Range
CFM m3/min In W.C. kPA In W.C. kPA In W.C.
0- 750 0- 21.4 0.01 0.00249 0.01 0.00249 0.15
751 -1000 21.25- 28.32 0.05 0.01245 0.05 0.01245 0.20 1001 -1250 28.33- 35.40 0.10 0.02491 0.10 0.02491 0.20 1251 -1500 35.41 -42.48 0.10 0.02491 0.10 0.02491 0.25 1501-1750 42.49-49.55 0.15 0.03736 0.14 0.03487 0.30 1751-2000 49.56-56.63 0.19 0.04733 0.18 0.04484 0.30
2001 & Above 56.64- Above 0.19 0.04733 0.18 0.04484 0.30
Unitary Products Group 27
Minimum
Opening Size
in2 cm 2 230 1484 330 2129 330 2129 330 2129 380 2452 380 2542 463 2987
Disposable
Filter Type
Washable Fiber
Pleated
kPA
0.03736
0.04982
0.04982
0.06227
0.07473
0.07473
0.07473
288130-UIM-A-0407
APPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in place, fol- low the steps below:
1. Select the filter type.
2. Select the number of return air openings or calculate the return opening size in square inches to determine the proper filter pres-
sure drop.
3. Determine the External System Static Pressure (ESP) without the filter.
4. Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the
ESP from Step 3 to determine the total system static.
5. If total system static matches a ESP value in the airflow table (i.e.
0.20 w.c. (50 Pa), 0.60 w.c. (150 Pa), etc.,) the system airflow cor- responds to the intersection of the ESP column and Model/Blower
Speed row.
6. If the total system static falls between ESP values in the table (i.e.
0.58 w.c. (144 Pa), 0.75 w.c. (187 Pa), etc.), the static pressure may be rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the following
Example: For a 75,000 BTUH (21.98 kW) furnace with 2 return open- ings and operating on high-speed blower, it is found that total system static is 0.38" w.c. To determine the system airflow, complete the follow- ing steps:
Obtain the airflow values at 0.30 w.c. (75 Pa) & 0.40 w.c. (99.6 Pa) ESR Airflow @ 0.30": 1408 CFM (39.8 m3/min) Airflow @ 0.40": 1343 CFM (38.0 m3/min)
Subtract the airflow @ 0.30 w.c. (75 Pa) from the airflow @ 0.40 w.c. (199.6 Pa) to obtain airflow difference.
1343 - 1408 = -65 CFM (1.89 m3/min) Subtract the total system static from 0.30 w.c. (75 Pa) and divide this
difference by the difference in ESP values in the table, 0.40 w.c. (99.6 Pa) - 0.30 w.c. (75 Pa), to obtain a percentage.
(0.38-0.30)/ (0.40-0.30)= 0.8
Multiply percentage by airflow difference to obtain airflow reduction.
(0.8)X(-65)= -52
Subtract airflow reduction value to airflow @ 0.30 w.c. (75 Pa) to obtain actual airflow @ 0.38 inwc (94.6 Pa) ESR 1408 - 52 = 1356
example.
TABLE 17: Blower Performance- CFM
BTU/H (kW) Cabinet Speed
Input Size Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
High 1535 1470 1408 1343 1275 1202 1115 1014 43.5 41.6 39.9 38.0 36.1 34.0 31.6 28.7
75 (22.01 B Med 1215 1199 1182 1151 1106 1039 976 887 34.4 34.0 33.5 32.6 31.3 29.4 27.6 25.1
Low 875 874 864 847 827 799 736 658 24.8 24.7 24.5 24.0 23.4 22.6 20.8 18.6
High 1792 1724 1630 1552 1462 1367 1264 1152 50.7 48.8 46.2 43.9 41.4 38.7 35.8 32.6
75(22.0) 1 C Med 1597 1555 1496 1444 1372 1287 1190 1086 45.2 44.0 42.4 40.9 38.9 36.4 33.7 30.8
Low 1115 1140 1167 1183 1149 1093 1023 939 31.6 32.3 33.0 33.5 32.5 31.0 29.0 26.6
High 1868 1781 1690 1600 1498 1396 1277 1156 52.9 50.4 47.9 45.3 42.4 39.5 36.2 32.7
100(29.3) 1 C Med 1602 1553 1503 1447 1376 1287 1181 1060 45.4 44.0 42.6 41.0 39.0 36.4 33.4 30.0
Low 1147 1147 1147 1147 1132 1078 1009 918 32.5 32.5 32.5 32.5 32.1 30.5 28.6 26.0
High 1634 1562 1484 1417 1340 1238 1154 1030 46.3 44.2 42.0 40.1 37.9 35.1 32.7 29.2
75(22.0) 1 B Med 1243 1228 1214 1184 1133 1079 999 912 35.2 34.8 34.4 33.5 32.1 30.6 28.3 25.8
Low 886 886 886 886 865 823 777 700 25.1 25.1 25.1 25.1 24.5 23.3 22.0 19.8
High 1978 1896 1803 1693 1589 1478 1366 1235 56.0 53.7 51.1 47.9 45.0 41.9 38.7 35.0
75(22.0) 1 C Med 1682 1657 1606 1530 1455 1366 1265 1137 47.6 46.9 45.5 43.3 41.2 38.7 35.8 32.2
Low 1235 1235 1235 1235 1198 1154 1083 987 35.0 35.0 35.0 35.0 33.9 32.7 30.7 27.9
High 2122 2027 1916 1821 1717 1590 1462 1312 60.1 57.4 54.3 51.6 48.6 45.0 41.4 37.2
100(29.3) 1 C Med 1667 1696 1656 1597 1523 1438 1330 1191 47.2 48.0 46.9 45.2 43.1 40.7 37.7 33.7
Low 1130 1145 1177 1194 1181 1146 1077 982 32.0 32.4 33.3 33.8 33.4 32.5 30.5 27.8
High 1552 1491 1420 1348 1271 1185 1080 970 43.9 42.2 40.2 38.2 36.0 33.6 30.6 27.5
75 (22.0) 1 B Med 1229 1237 1198 1164 1105 1039 956 861 34.8 35.0 33.9 33.0 31.3 29.4 27.1 24.4
Low 889 892 879 866 846 807 760 689 25.2 25.3 24.9 24.5 24.0 22.9 21.5 19.5
High 1946 1862 1775 1620 1518 1409 1291 1160 55.1 52.7 50.3 45.9 43.0 39.9 36.6 32.8
75(22.0) 1 C Med 1683 1611 1551 1484 1388 1300 1190 1080 47.7 45.6 43.9 42.0 39.3 36.8 33.7 30.6
Low 1110 1138 1175 1190 1175 1126 1041 937 31.4 32.2 33.3 33.7 33.3 31.9 29.5 26.5
High 1997 1920 1822 1723 1620 1500 1355 1211 56.5 54.4 51.6 48.8 45.9 42.5 38.4 34.3
100(29.3) 1 C Med 1728 1679 1635 1556 1465 1359 1249 1117 48.9 47.5 46.3 44.1 41.5 38.5 35.4 31.6
Low 1131 1156 1181 1190 1171 1126 1049 926 32.0 32.7 33.4 33.7 33.2 31.9 29.7 26.2
1. Return air is through side opposite motor (left side) for one side return (worst case). Airflows expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m3/min). Motor voltage is 115VAC.
External Static Pressure, Inches WC
CFM CFM CFM CFM CFM CFM CFM CFM
UPFLOW, SINGLE SIDE RETURN (WITHOUT FILTER)
DUAL RETURN (TWO SIDES OR ONE-SIDE & BOTTOM)
BOTTOM/END RETURN
(0.025) (0.050) (0.075) (0.099) (0.124) (0.149) (0.174) (0.199) m3/min m3/min m3/min m3/min m3/min m3/mn m3/m n m3/min
External Static Pressure (kPa)
28 Unitary Products Group
-11
r-
m c0
5"
co
_D
co
B
BLOWER SPEED CHART
LADDER DIAGRAM
80+ CLAM TUBE FURNACE CONNECTION DIAGRAM
(_c =ou_',,_sr _._ _ -- -- -- ALLo_er _O_eLSUS_ _W_Re MOTORS
,_ _ k_,Mr_E _ _,_CCOR_ _ _Y_L" _eRE ORLY PRESENT OR _ TON FURRAC£S
_es_re_B_O_ErSPEE_ BLU-_eO _ _LOWeRMOTOR V_TCSSE_ _O_LEr_E YEL-_
_L _AU_ERRZ_Z_tSEULE_E_tS_RLES
_OUR_A_S_S_ tO_ZS _OUt AutreMODZLe
_Rn i
i
NOTES:
ALL Ft_L_ weel_G PER _a_ _AT_O_ALeUe¢ COOZ(_EC_ANVJOR/
2 W AHy O_ THZ OR_GINAL W_RZ AS SUPPL_E_ W_T_ T_Z FURNACE MUST 5Z
REPLAC_O _T _T BE REPLAC[D WiTH W_R_N6 _ATER_AL HAVinG A
_PeRA_UR_ RA_NG Or at L_AS__ _ _os c_
3 CONRZCTOR$ SU_TABLZ FOR COPPER CONDUCTORS OMLY
ALL REPLACZ_ZNT COMPONENTS _UST BE PROPERLY GROUROED
PROWDZ D_CONRZCTS FOR ALL PO_ER SUPPUZS
B _OTOR5 AR£ _NH_RE_?LY PROTZCTZO
NO rE 3 :
1 TOUT FILAGE[_CHANTIERS_LO_; (A) CODE [LZC NATIONAL(C[N}ETIOU/
2 S_ LE F_LAGZDOIT ETREREMPLACEER PATR_ O_ Z_ TOUT _L OO_T
L'_TRZAVEC _ _AT ff]AUXPOUVAN_RESISTERA DESTEmPERAtURE5 SEULEMZNTDeS MARZTTZSpOUR F_LDE CU]VRe
4 TOUTECOMPOSA_E OEREMPLACEM_ DOIT {ETRZB_N _SE ZN TERRE 5 FOURN_SS{ZLZ$ DISJONCTZURSPOURL'AL_E,TA]TON 6 LE$ _OTEUR$SONT PROTEGES OZ PAR LEURCONCZPT_OM
I_I CANADIANELEC COD_(CEC)ANp/ORI
LOCALOR City CO_S
()B CODE ELZCCANAO_£N(CEC}ETIOUI {C} CO_ES L_AUX ZT MUN_C_PAUX
- CAUTION - ,G_
¢AUT IOF,
PrJs, _ P_ PLUG_ S_KE_ON_NeT,oN COntrOleO_R_
_LAM[S[NSOR FURNAC_CONTROL i ' tlGNIT_ON _e
(C_PT_UR_ _k FOURN_ISE_ ,'_i ' _ BL_
I_1_ LEG _D
_co_tr6LeDe La _i ' P s S_R_AC_CHAU_e_
OOOOO
__ wYZ _ R G c ] eL_
_G, _N,T_O__esu_Fac_¢.AuDe
r,,.)
oo oo
(..,o
,o
CE
,5
4_ 0 ...q
288130-UIM-A-0407
NOTES
30 Unitary Products Group
NOTES
288130-UIM-A-0407
Unitary Products Group 31
NOTES
Subject to change without notice. Printed in U.S.A. Copyright _> by York International Corp. 2007. All rights reserved.
Unitary Products
Group
EO.
Box 19014
288130-UIM-A-0407
Supersedes: 269326-UIM-A-1106
Wichita
KS
67204-9014
Loading...