95.5% SINGLE STAGE
GAS-FIRED RESIDENTIAL
MULTI-POSITION GAS FURNACES
MODELS: TG9S
NATURAL GAS
40 - 130 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional efficiency rating information can
be found at www.gamanet.org.
400992-CTG-B-0708
DESCRIPTION
These compact units employ induced combustion, reliable hot
surface ignition and high heat transferaluminized tubula r heat
exchangers. The units are factory shipped for installation in
upflow or horizontal applications and may be converted for
downflow applications.
These furnaces are designed for residential installation in a
basement, closet, alcove, attic, recreation room or g ara ge and
are also ideal for commercial applications. All units are factory
assembled, wired and tested to assure saf e dependable and
economical installation and operation.
These units are Category IV listed and may be vented either
through side wall or roof applications using approved plastic
combustion air and venr piping.
WARRANTY
Lifetime limited warranty on the heat exchanger.
10-year heat exchanger warranty on commercial applications.
5-year limited parts warranty.
FEATURES
•Easily applied in upflow, horizontal left or right, or
downflow installation with minimal conversion necessary.
•Compact, easy to install, ideal height 33" tall cabinet.
•Blower-off delay for cooling SEER improvement.
•Easy access to controls to connect power/control wiring.
•Built-in, high level self diagnostics with fault code displays
standard on integrated control module for reliable
operation.
•Low unit amp requirement for easy replacement
application.
•Single wire twinning or staging feature available.
•All models are convertable to use propane (LP) gas.
•Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
•100% shut off main gas valve for extra safety.
•
4 speed, direct drive PSC motor.
•24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
Air Temp.
Rise
Max
Over-Current
Protect
Min. wire Size
(awg) @ 75 ft
one way
Max. Outlet
Air Temp
2Johnson Controls Unitary Products
Page 3
400992-CTG-B-0708
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters.
All applications of these furnaces require the use of field
installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabinet. DO NOT attempt to install any filters inside the furnace.
NOTE: Single side return above 1800 CFM is app roved as
long as the filter velocity does not exceed filter manufacturer’s recommendation and a transition is used to allow use
on a 20x25 filter.
Recommended Filter Sizes (High velocity 600 FPM)
CFM
800A16 x 2514 x 25
1000A16 x 2514 x 25
1200A16 x 2514 x 25
1200B16 x 2516 x 25
1600B16 x 2516 x 25
1600C16 x 2520 x 25
2000C(2) 16 x 2520 x 25
2200C(2) 16 x 2520 x 25
2000D(2) 16 x 2522 x 25
NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute (91.4 m/min). All velocities over this require the
use of high velocity filters.
2. Do not exceed 1800 CFM using a single side return and a 16x25
filter. For CFM greate r than 1800, you may use t wo side returns or
one side and the bottom or one return with a transition to allow
use of a 20x25 filter.
Cabinet
Size
Side
(in)
Bottom
(in)
Unit Clearances to Combustibles
Application
Top1" 0" 0"
Vent0" 0" 0"
Rear0" 0" 0"
Side0" 0" 1"
Front*0" 0" 0"
FloorCombustible
ClosetYesYesYes
Line ContactNoNoYes
1. For combustible floors only when used with special sub-base.
* - 24" clearan ce in f ront and 18" on side recomme nded for service access.
All furnaces approved for alcove and attic installation.
UpflowDownflowHorizontal
1
Combustible
Combustible
ACCESSORIES
PROPANE (LP) CONVERSION KIT -
S1-1NP0347 - All Models except 130K Model
S1-1NP0501 - 130K Model
This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation.
CONCENTRIC VENT TERMINATION -
S1-1CT0302 (2")
S1-1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Eliminates unslightly elbows for a cleaner installation.
SIDEWALL VENT TERMINATION KIT -
S1-1HT0901 (3")
S1-1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
available from the Source 1 Parts (p/n 026-30228-000).
SIDE RETURN FILTER RACKS -
S1-1SR0200 - All Models
S1-1SR0402 - All Models
S1-1SF0101 - All Models (Upflow Only)
BOTTOM RETURN FILTER RACKS -
S1-1BR0514 or 1BR0614 - For 14-1/2” cabinets
S1-1BR0517 or 1BR0617 - For 17-1/2” cabinets
S1-1BR0521 or 1BR0621 - For 21” cabinets
S1-1BR0524 or 1BR0624 - For 24-1/2” cabinets
1BR05xx series are galvanized steel filter racks. 1BR06xx
are pre-painted steel filter racks to match the appearance of
the furnace cabinet.
COMBUSTIBLE FLOOR BASE KIT -
For installation of these furnaces in downflow applications
directly onto combustible flooring material, These kits are
required to prevent potential overheating situations.tible floor
base kit provides access for combustible airflow.
S1-1CB0514 - For 14-1/2” cabinets
S1-1CB0517 - For 17-1/2” cabinets
S1-1CB0521 - For 21” cabinets
S1-1CB0524 - For 24-1/2” cabinets
EAC TRANSITION KITS -
For installation of EAC accessories with these furnaces to
provide easy transition of return airflow through the EAC to
get the proper sealing and reduced airflow leakage.
S1-1 TK1001 - For all models using side return
S1-1 TK1014 - For 14-1/2” cabinets using bottom return
S1-1 TK1017 - For 17-1/2” cabinets using bottom return
S1-1TK1021 - For 21” cabinets using bottom return
S1-1 TK1024 - For 24-1/2” cabinets using bottom return
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 5,000 feet it is
not required that the pressure switch be changed. For altitudes above 5,000 feet, see kits below.