Airflow Data for 230 Volt - Heat Pump Models . . . . . . . . . . . . . . . . . .13
Airflow Data for 208 Volt - Heat Pump Models . . . . . . . . . . . . . . . . . .14
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified contractor, installer or service agency.
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
292043-UIM-B-0707
292043-UIM-B-0707
SPECIFIC SAFETY RULES AND PRECAUTIONS
FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
A fire or electrical hazard may result causing property damage, per-
sonal injury or loss of life.
1.Install this air handler only in a location and position as specified in
SECTION I of these instructions.
2.Always install the air handler to operate within the air handler’s
intended maximum outlet air temperature. Only connect the air
handler to a duct system which has an external static pressure
within the allowable range, as specified on the air handler rating
plate.
3.When an air handler is installed so that supply ducts carry air circulated by the air handler to areas outside the space containing
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating outside the space
containing the air handler.
4.The air handler is not to be used for temporary heating of buildings
or structures under construction.
5.The size of the unit should be based on an acceptable heat loss
calculation for the structure. ACCA, Manual J or other approved
methods may be used.
SAFETY REQUIREMENTS
• This air handler should be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes.
• Refer to the unit rating plate for the air handler model number,
and then see the dimensions page of this instruction for supply air
plenum dimensions in Figure 1. The plenum must be installed
according to the instructions.
• Provide clearances from combustible materials as listed under
Clearances to Combustibles.
• Provide clearances for servicing ensuring that service access is
allowed for both the burners and blower.
• Failure to carefully read and follow all instructions in this
manual can result in air handler malfunction, death, personal
injury and/or property damage.
• Check the rating plate and power supply to be sure that the electrical characteristics match.
• Air handler shall be installed so the electrical components are
protected from water.
• Installing and servicing heating equipment can be hazardous due
to the electrical components. Only trained and qualified personnel
should install, repair, or service heating equipment. Untrained
service personnel can perform basic maintenance functions such
as cleaning and replacing the air filters. When working on heating
equipment, observe precautions in the manuals and on the labels
attached to the unit and other safety precautions that may apply.
• These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.
GENERAL INFORMATION
This Single Piece Air Handler provides the flexibility for installation in
any upflow or horizontal application. These versatile models may be
used for cooling or heat pump operation with or without electric heat.
BRAND LABEL (available from Distribution) apply to center of the
blower access panel.
The unit can be positioned for bottom return air in the upflow position,
and right or left return in the horizontal position.
Top and side power wiring and control wiring, accessible screw terminals for control wiring, easy to install drain connections and electric
heaters all combine to make the installation easy, and minimize installation cost.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. Also, before
installation the unit should be checked for screws or bolts, which may
have loosened in transit. There are no shipping or spacer brackets
which need to be removed.
Also check to be sure all accessories such as heater kits, suspension
kits, and coils are available. Installation of these accessories or field
conversion of the unit should be accomplished before setting the unit in
place or connecting any wiring, electric heat, ducts or piping.
LIMITATIONS
These units must be wired and installed in accordance with all national
and local safety codes.
Voltage limits are as follows:
1
Air Handler VoltageVoltage code
208/230-1-6006187-253
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for
electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°FDry Bulb Temp. °F
Min.Max.Min.Max.
57726595
Normal Operating
Voltage Range
CLEARANCES
Clearance must be provided for:
1.Refrigerant piping and connections - minimum 12” recommended.
2.Maintenance and servicing access - minimum 36” from front of unit
recommended for blower motor / coil replacement.
3.Condensate drain line.
4.Filter removal - minimum 36” recommended.
LOCATION
Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the following in choosing a suitable location:
1.Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections.
2.Use hanging brackets to wall mount unit as shown under suspension kits section.
3.Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bedrooms, study,
etc.
4.Precautions should be taken to locate the unit and ductwork so
that supply air does not short circuit to the return air.
5.Select a location that will permit installation of condensate line to
an open drain.
NOTE: When the coil is installed in a draw-thru application, it is recommended to trap the primary and secondary drain line. If the secondary
drain line is not used, it must be capped.
The coil is provided with a secondary drain. It should be piped to a location that will give the occupant a visual warning that the primary drain is
clogged. If the secondary drain is not used it must be capped.
2Unitary Products Group
6.When an evaporator coil is installed in an attic or above a finished
ceiling, an auxiliary drain pan should be provided under the coil as
is specified by most local building codes.
7.Proper electrical supply must be available.
8.Clearances must also be taken into consideration, and provided
for as follows:
A.Refrigerant piping and connections are located in the front.
B.Maintenance and servicing through the front or access side
of unit with both sides and rear of unit having zero inch clearance.
C.Condensate drain lines are connected in the front (clear of fil-
ter).
D.Filter removal.
E. When no electric heat is used, the unit as well as all duct
work and plenum are designed for zero clearance to combus-
tible materials.
292043-UIM-B-0707
If electric heat is used, a minimum clearance of 1” must be maintained on all sides of the supply air duct and/or plenum continuously
for up to 3’ (See Figure 1).
MINIMUM CLEARANCE
OF 1” ALL SIDES
POWER WIRING
TO MAIN
POWER SOURCE
REFRIGERANT
LINES
TO
CONDENSATE
DRAIN
SUPPLY
AIR
ELECTRIC HOT WATER HEATER
(Must comply with water heater installation instructions)
FIGURE 2: Typical Installation
HORIZONTAL DRAIN PAN CONVERSION
These air handler units are supplied ready to be installed in a right hand
horizontal position. If unit requires left hand positioning, the unit must
have the pan installed in the correct position.
1.Remove blower access, coil access, and center access panels.
NOTE: Conversion must be made before brazing the refrigerant con-
nections to the coil.
2.See Figure 3, remove two screws from horizontal drain pan, to
remove pan from position “3A” if factory installed.
3.Position horizontal pan, as required in either “A” or “B” position,
locking it into the vertical drain pan as shown.
4.Horizontal drain pans have 4 plugged drains. Remove plugs from
connections being used.
NOTE: If this step is overlooked, it can lead to a water problem later.
5.Use removed plug to plug primary of upflow drain pan.
6.Attach horizontal pan with 2 screws removed in step no. 2 or supplied with the unit. Ensure that the drain pan is lying flat against the
insulation of the cabinet.
7.Horizontal drain cutout in the center access panel should be
removed by using a utility knife (if not previously cut out).
8.Re-position and replace access panels.
FLEXIBLE
DUCT COLLAR
3’
FIGURE 1: Plenum Clearances
POWER WIRING
CONTROL
WIRING
THERMOSTAT
FILTER
ACCESS
LOUVERED
DO NOT TRY TO KNOCK OUT PANEL OPENING FOR SECONDARY DRAIN PAN. SEE ITEM 7.
Models F*FP045,048,060 have a coil baffle and support bracket
factory installed for right hand horizontal application (refer to Figure
3C). For left hand applications the coil support bracket must be
moved to the right side of the coil, and the coil baffle must be
rotated to avoid water blow-off.
To rotate baffle, remove the coil assembly from the unit (remove
front two screws holding the coil support bracket and the two
screws holding the drain pan). Remove four screws in coil baffle
and remove the coil baffle and rotate ends.
Resecure the baffle and reinstall the coil assembly ensuring that
the rear of the drain pan is secured under the back flange of the
unit. Reinstall the coil support bracket on the right side of the coil.
Unitary Products Group3
292043-UIM-B-0707
BLOWER
COMPARTMENT
(ACCESS PANEL
REMOVED)
PRIMARY
DRAIN
SECONDARY
DRAIN
HORIZONTAL
DRAIN PAN
POSITION "B”
VERTICAL
DRAIN PAN
SECONDARY
DRAIN UPFLOW
3/4" THREADED
DUCT WORK MAY BE FASTENED
CAUTIOUSLY WITH SCREWS TO
THE SIDES AND REAR OF UNIT
Use 1/2" screws to connect ductwork to bottom of unit. Longer
screws will pierce the drain pan and cause leakage. If pilot holes
are drilled, drill only though field duct and unit bottom flange.
NOTE: The electric heat accessory should be installed before the supply air duct is attached to the supply air openings. Refer to the electric
heater kit instructions for proper installation.
Air supply and return may be handled in one of several ways best
suited to the installation. See Figure 4 for dimensions for duct inlet and
outlet connections.
The vast majority of problems encountered with combination heating
and cooling systems can be linked to improperly designed or installed
duct systems. It is therefore highly important to the success of an installation that the duct system be properly designed and installed.
Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space. If electric heat is used, non-flammable
material must be used.
Where return air duct is short, or where sound may be a problem,
sound absorbing glass fiber should be used inside the duct. Insulation
of duct work is a must where it runs through an unheated space during
the heating season or through an uncooled space during the cooling
season. The use of a vapor barrier is recommended to prevent absorption of moisture from the surrounding air into the insulation.
The supply air duct should be properly sized by use of a transition to
match unit opening. All ducts should be suspended using flexible hangers and never fastened directly to the structure. This unit is not
designed for non-ducted (freeblow) applications. Size outlet plenum or
transition to discharge opening sizes shown in Figure 4.
Duct work should be fabricated and installed in accordance with local
and/or national codes. This includes the standards of the National Fire
Protection Association for Installation of Air-Conditioning and Ventilating Systems, NFPA No. 90B.
A suspension kit is available. Models 1BH0601 (unit sizes 018-060) is
designed specifically for the units contained in this instruction (upflow
application only). For installation of these accessory kits, see the
instructions packed with the kit.
For suspension of these units in horizontal applications, it is recommended to use angle steel support brackets with threaded rods, supporting the units from the bottom, at the locations shown in Figure 5.
COIL METERING DEVICES
The coil in this Air Handler unit will have a TXV metering device
installed at the factory.
The model number will have the following format:
F*FPxxxH06T2y - The coil will have a Thermal Expansion Valve (TXV)
installed. The y character specifies which TXV is installed at the factory.
Please refer to the TXV Metering Device section for installation notes.
Air filters must be field supplied. A 1" filter access rack has been built
into the unit. See Figure 4. Remove filter access cover shown. Install
proper size filter. Standard 1" size permanent or throw away filter may
be used, or, permanent washable filters are available using model numbers: 1PF0601, 602, 603BK. See Table 3 for filter size.
Equipment should never be operated without filters.
SUSPENSION KITS
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS*
2
WW
NOTE: USE SUPPORTS UNDER UNIT.
XX
Units
(Nominal Tons)
WWXX
018, 024, 030, 036, 040, 04214”40-3/4”
045, 048, 06019-1/2”50-3/4”
FIGURE 5: Typical Horizontal Installation
1-1/2
Dimension
EXPANSION
BULB
EXPANSION
BULB CLAMP
FIGURE 6: TXV Bulb Installation
Please refer to Table 2 to verify which TXV is installed in this Air Handler unit and that this AHU is a valid system match for the AC or HP unit
installed.
The TXV is bolted into the coil assembly of this Air Handler unit at the
factory. The temperature sensing bulb will need to be attached to the
coil suction header line after the line set is brazed to the coil.
• Make sure the TXV bulb is outside of the Air Handler cabinet.
Excess tubing should remain inside the cabinet.
• Take caution not to apply high temperatures to the TXV assembly
or equalizer line while brazing.
• Attach field line sets and braze to coil connections. Replace
access panels & secure.
• Secure the TXV bulb to the suction line with the clamp provided.
Choose a horizontal location as close to the cabinet as possible,
but not directly on the brazed connection joint. Refer to Figure 7.
• The bulb should be in direct contact with the coil suction line
along the length of the bulb.
Unitary Products Group5
292043-UIM-B-0707
• If the suction line is 3/4" diameter - position the bulb near the top
of the copper tube as shown. If the tube is 7/8" diameter - position
the bulb near the bottom of the tube. Refer to Figure 7.
• Wrap the clamp, bulb & line securely with insulation provided.
TAIL
END
UP
*
ROTATE BULB TO KEEP
TAILAT BOTTOM
VERTICAL
RISER
FIGURE 7: Bulb Location
COIL UNDER PRESSURE.
Relieve pressure by removing plug from piping connection. Coil will
have factory installed TXV. See outdoor unit documentation for correct TXV to be used. Refer to unit nameplate for TXV identification
for this unit.
NOTE: The coil should be open to the air for no more than 2 minutes to
keep moisture and contaminates from entering the system. If the coil
cannot be brazed into the refrigeration system in that time, the ends
should be temporarily closed or plugged. For a short term delay, use
masking tape over the ends of the copper tubing to close the tube to the
air. For a longer term delay, use plugs or caps. There is no need to
purge the coil if this procedure is followed.
REFRIGERANT LINE CONNECTION
See the outdoor unit installation instructions for the procedure to install
field supplied tubing for systems with sweat fittings.
Stub adapters are available to adapt sweat connections to quick connections.
Connect lines as follows:
NOTE: Route the refrigerant lines to the coil in a manner that will not
obstruct service access to the coil, air handling system or filter.
1.Suction line connections are made outside the center access
panel. Center access panel is recessed to assure sufficient room
for brazing or it can be removed and slid over the suction line during brazing.
2.Plan for TXV bulb placement.
3.Remove rubber plugs from refrigerant lines.
4.Braze the suction line. Re-attach the center access panel, if it had
been removed.
5.Braze the liquid line.
6.Install supplied grommets on both the suction and liquid lines to
complete the air seal.
7.See previous section for TXV bulb.
Lines should be sound isolated by using the appropriate hangers or
strapping.
When field supplied lines are used be sure to insulate the suction line
only.
ELECTRIC HEATERS & OPERATING CONTROLS
The low voltage transformer and fan / heater control, are standard on all
models. See Figure 8. The air handlers are shipped pre-wired to operate as cooling only applications. To complete the installation for cooling
only, install the 6-pin jumper plug to the control board to bypass the
heater limit controls. This jumper plug is secured to the duct cover near
the 4-pin power plug harness. Failure to install the plug will cause the
blower to run continuously. (See Figure 8).
FIGURE 8: Control Board
Mark the unit nameplate with the appropriate heater selection on the
space provided or NONE to indicate cooling only . To operate these unit s
with electric heat, it is necessary to field install an electric heater kit
(2HK). See Electric Heater Kit Accessory Installation instructions for
proper installation procedure. Prior to installing electric heat, it is necessary to perform the following procedure:
1.Remove the 4-pin power plug from the control board (See Figure
8).
NOTE: This pin must not be used when electric heaters are installed.
2.Remove the four (4) screws from the duct cover and remove the
duct cover from the air handler.
Right-hand Airflow Application Only - Models with Circuit
Breakers - See Figure 9
If unit is to be installed for right hand air flow, the circuit breakers in the
heat kit will need to be removed and rotated 180°, so the OFF position
will be down when the cabinet is positioned on the right side. This is an
NEC requirement. Do One Breaker At A Time - to make sure wiresare reconnected properly. Loosen terminal screws on the wires and
gently pull the wires back from the breaker. Remove screws securing
the breaker plate and rotate 180°, then secure the breaker plate and
reconnect the wires to the breaker. Proper torque for terminal screws is
35 in/lbs.
REMOVE 3 SCREWS TO
REMOVE THE CIRCUIT
BREAKER BRACKET
FROM HEAT KITASSEMBLY
JUMPER BAR
JUMPER BAR COVER
FIELD SUPPLY WIRING
WILL BE ATTACHED TO
THIS SIDE OF THE
CIRCUIT BREAKER(S)
CIRCUIT BREAKER(S) - THERE
MAY BE ONE, TWO OR THREE
HEAT KIT WIRING WILL BE
ATTACHED TO THIS SIDE OF
THE CIRCUIT BREAKER(S)
FIGURE 9: Electric Heaters in Horizontal Configuration - Right Hand
Air Flow
HEAT KITASSEMBLY
CIRCUIT
BREAKER
BRACKET
AIR FLOW
6Unitary Products Group
292043-UIM-B-0707
Unitary Products Group7
292043-UIM-B-0707
LOW V OLTAGE CONTROL CONNECTION
The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models. However, if the unit is connected to a 208 volt power supply the low voltage transformer must be
rewired to the 208 volt tap. See the unit wiring label.
Field supplied low voltage wiring can exit the unit on the top right hand
corner or the right hand side panel (see Fig. 5, item K).
Install a 7/8" plastic bushing in the selected hole and keep low voltage
wiring as short as possible inside the control box.
The field wiring is to be connected at the screw terminals of the control
board. Refer to Figure’s 12 and 13.
NOTE: All wiring must comply with local and national electrical code
requirements. Read and heed all unit caution labels.
TYPICAL WIRING WITHOUT ELECTRIC HEAT
GND. LUG
POWER
SUPPLY
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
& BREAKER BAR REMOVED
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER
SUPPLY 1
POWER
SUPPLY 2
POWER
SUPPLY 3
GND.
LUG
GND.
LUG
WITHOUT CIRCUIT BREAKER
GND. LUG
POWER
SUPPLY
WITHOUT CIRCUIT BREAKER
SINGLE SOURCE (2.5 - 10 KW)
GND. LUG
POWER
SUPPLY
NOTE: It is possible to vary the amount of electric heat turned on during
the defrost cycle of a heat pump. Standard wiring will only bring on 5
KW of electric heat during defrost see T able 6 and Figures 12 and 13 for
alternate staging.
LINE POWER CONNECTIONS
Power may be brought into the unit through the supply air end of the
unit (top when unit is vertical) or the left side panel. Use the hole appropriate to the unit's orientation in each installation to bring conduit from
the disconnect. The power lead conduit should be terminated at the
electrical control box. Refer to Tables 4, 8 & 10 for wire requirements.
Also see Figure 10.
ELECTRIC HEAT
3 PHASE (10 - 15 KW)
ELECTRIC HEAT
GND.
LUG
GND.
LUG
POWER
SUPPLY
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
AS SHIPPED FROM FACTORY
SINGLE SOURCE
(2.5 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER WIRING (208/230-1-60)
NOTE: USE ONLY COPPER CONDUCTORS
GND.
LUG
FIGURE 10: Line Power Connections
BLOWER SPEED CONNECTIONS
Except for F4FP045, which has a 4-speed motor, and F5FP* which has
a 5-speed high efficiency X-13 motor, all air handlers contain three
speed blower motors which are pre-wired to the control board.
Adjust blower motor speed to provide airflow within the minimum and
maximum limits approved for evaporator coil, electric heat and outdoor
unit. Speed tap adjustments are made at the motor terminal block, See
Figure 11. Airflow data is shown in Tables 6 and 11.
TO
RELAY
BLU
YEL
208 / 230V
FAN MOTOR
4-5 TON HIGH EFFICIENCY MOTOR (X-13)
BLK
GRN
C
G
L
N
PUR
BLOWER
1
2
3
4
5
TO CONTROL
BOARD C
(Common)
GRN
YEL
TRANSFORMER
Higher efficiencies will be obtained if the indoor air volume is as high as
possible provided the CFM does not exceed limitations and the sound
level is not objectionable.
Connect motor wires to motor speed tap receptacle for speed desired.
See wiring label for motor wiring details. See Figure 11.
The unit control is designed for the addition of a two speed fan kit. See
accessory kit for details.
1-1/2 TON TO 4 TON STANDARD MOTOR
FACTORY WIRED TO
TRANSFORMER
TO
230V
YEL
FACTORY WIRED TO
FAN MOTOR RELAY
TERMINAL ON
CONTROL BOARD
230 VOLT
BLOWER MOTOR
CAP
BRN
HIGH
MED
LOW
GND.
PUR
PUR
FIGURE 11: Blower Speed Connections
8Unitary Products Group
292043-UIM-B-0707
TABLE 3:
Physical and Electrical Data
Models F*FP024030036040
Blower - Diameter x Width10 x 610 x 810 x 810 x 8
Motor
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowab l e external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
FIGURE 12: Cooling Models with Electric Heat Wiring
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
W1
W2
C
W2
Y
C
HUMIDISTAT
Air Handler Control Wiring
Typical A/C - Cooling only Applications
Y
Y
G
G
W1
O
C
HUM
X
Y1
Y2
CFM selection
board only on
F4FV model
1
Air Handler Control Wiring
Typical A/C with Electric Heat Applications
THERMOSTAT
AIR HANDLER
BOARD
1-STAGE
AIR CONDITIONING
RR
W1
W2
C
W2
Y
C
HUMIDISTAT
Y
Y
G
G
W1
O
C
HUM
X
Y1
Y2
CFM selection
board only on
F4FV model
1
Field
Installed
Jumper If Required
NOTE:
Dehumidification
control connection
(”Humidistat” jumper on
CFM selection board
must be removed)
1
NOTE:
Dehumidification
control connection
(”Humidistat” jumper on
CFM selection board
must be removed)
1
F* SERIESF* SERIES
292043-UIM-B-0707
AIR HANDLER
THERMOSTAT
R
Y
G
E
W2
O
C
L
W1
CFM selection board
only on F4FV model
FIGURE 13: Single Stage Heat Pump Control Wiring
NOTES:
1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second Blower Off Delay for
SEER enhancement.
1
Optional Dehumidification Humidistat contacts open on rise.
2.
3. For F4FV model - Remove Humidistat Jumper on CFM Selection Board - if used.
4. For F4FV model - For Heat Pump Applications - Remove Heat Pump Jumper on CFM Selection Board.
5. To change quantity of heat during HP defrost cycle - Reverse connections at W1 and W2 on Air Handler Control Board.
BOARD
R
Y
G
W1
W2
O
C
HUM
X
Y1
Y2
HUMIDISTAT
1
NOTE:
Dehumidification control connection
(”Humidistat” jumper on CFM selection
board must be removed)
1
HEAT PUMP
R
Y
W1 Out
O
C
X/L
W
Unitary Products Group15
DRAIN CONNECTIONS
All drain lines should be trapped a minimum of three inches, should be
pitched away from unit drain pan and should be no smaller than the coil
drain connection.
Threaded drain connection should be hand-tightened, plus no
more than one turn.
Horizontal drain cutout in the center access panel should be
removed by using a utility knife. DO NOT TRY TO KNOCK OUT.
Route the drain line so that it does not interfere with accessibility to the
coil, air handling system or filter and will not be exposed to freezing
temperatures. See Figures 2, 3 and 4.
NOTE: When the coil is installed in an attic or above a finished ceiling,
an auxiliary drain pan should be provided under the coil as is specified
by most local building codes.
Coils should be installed level or pitched slightly toward the drain end.
Suggested pitch should not exceed 1/4 inch per foot of coil.
The coil is provided with a secondary drain that should be trapped and
piped to a location that will give the occupant a visual warning that the
primary drain is clogged. If the secondary drain is not used it must be
capped.
The drain pan connections are designed to ASTM Standard D 2466
Schedule 40. 3/4" PVC is preferred. Since the drains are not subject to
any pressure it is not necessary to use Schedule 40 pipe for drain lines.
It is recommended that all drain connections be sealed with teflon tape
or equivalent.
MAINTENANCE
Filters must be cleaned or replaced when they become dirty. Inspect at
least once per month. The frequency of cleaning depends upon the
hours of operation and the local atmospheric conditions. Clean filters
keep unit efficiency high.
COIL CLEANING
If the coil needs to be cleaned or replaced, it should be wash ed with
Calgon CalClean (mix one part CalClean to ten parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water.
Solution should not be permitted to come in contact with painted surfaces.
LUBRICATION
The bearings of the blower motor are permanently lubricated.
CONDENSATE DRAINS
During the cooling season check the condensate drain lines to be sure
that condensate is flowing from the primary drain but not from the secondary drain. If condensate ever flows from the secondary drain the unit
should be promptly shut off and the condensate pan and drains cleaned
to insure a free flowing primary drain.
TROUBLESHOOTING GUIDE
PROBLEMPOSSIBLE CAUSE
1. No heat units do not have 6-pin connector installed.
2. Limit open or not connected.
Blower Runs all of the time
Blown Fuse1. Low voltage short to C or ground from R, Y, G, W, or O.
No 24V
No 2nd stage heat
No Heat or Limited Heating
3. Variable speed break-out tab broken out.
4. Blower OFF delay (approx. 1 min).
5. Thermostat fan switch in “ON” position.
1. 4-pin connector loose.
2. Loose wire from control to transformer (24V and 230V).
3. Blown fuse on control board.
1. Check 6-pin connector and connections to panel mount relays.
2. Verify that both W
1. Check filter.
2. Closed registers.
3. Restricted airflow (supply registers or return registers)
4. Check blower motor operation.
5. If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.