Coleman PxXU-V series, PxXU-G9V-UP series, PxXD-G9V-DH series, PxXD-V series Installation Instructions Manual

Page 1
INSTALLATION
TWO-STAGE ULTRA
HIGH-EFFICIENCY GAS-FIRED
INSTRUCTIONS
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . 3
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . 12
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . 13
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . 14
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . 22
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . 24
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . 25
VARIABLE SPEED FURNACES
UPFLOW - P*XU - “V” / G9V-UP
60 To 120 MBH Input
DOWNFLOW/HORIZONTAL - P*XD-V / G9V-DH
80 To 120 MBH Input
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 29
AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . 32
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 35
EFFICIENCY RATING CERTIFIED
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
035-17468-001 Rev. A (801)
Page 2
IMPROPER INSTALLATION MAY CREATE A CON­DITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALI­FIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLA­TION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUD­ING BUT NOT LIMITED TO, BUILDING, ELECTRI­CAL AND MECHANICAL CODES.
035-17468-001 Rev. A (801)
GENERAL INFORMATION
DESCRIPTION
This Category IV, dual certified direct vent and 1-pipe vent furnace is designed for residential or commercial application. It may be installed without modification to the condensate system in a basement, garage, equipment room, alcove, attic or any other indoor location provided the space temperature is 32 °F or higher and where all required clearance to com­bustibles and other restrictions are met. If the furnace is being installed where the space temperature is below 32°F, refer to BELOW FREEZING LOCATIONS on Page 4.
This furnace is constructed at the factory for natural gas-fired operation from 0 - 4,500 ft. above sea level, but may be con­verted to operate on propane (LP) gas and at altitudes up to 10,000 ft. For applications at altitudes between 2,000 - 4,500 ft., see COMBUSTION AIR/VENT PIPE SIZING on Page 14, for required vent length reductions. For application at alti­tudes greater than 4,500 feet, see high altitude instructions 035-14460-000.
High altitude and propane (LP) changes or conversions required in order for the appliance to satisfactory meet the application must be made by an authorized distributor or dealer. In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The blower in this furnace is programmed to supply a con­stant volume of airflow to compensate for duct system static.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other clean-
ing compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill.
A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts which may have loos­ened in transit. There are no shipping or spacer brackets which need to be removed.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property damage may occur if installation procedures are not handled properly.
The cooling coil must be installed in the supply air duct. Cooled air may not be passed over the heat exchanger.
2 Unitary Products Group
Page 3
035-17468-001 Rev. A (801)
VENT SAFETY CHECK PROCEDURE
This furnace may not be common vented with any other appliance, since it requires separate, properly­sized vent lines. The furnace shall not be connected to any type of B, BW or L vent or vent connector, and not connected to any portion of a factory-built or masonry chimney.
If this furnace is replacing a common-vented fur­nace, it may be necessary to resize the existing vent line and chimney to prevent oversizing problems for the new combination of units. Refer to the National Gas Code (ANSI Z223.1) or CAN/CGA B149.1 or.2 Installation Code (latest editions).
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1, or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ance(s) is located and other spaces of the building. Turn on clothes dryers. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall oper­ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
8. Any corrections to the common venting system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest edi­tions). If the common vent system must be resized, it should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the above codes.
SPECIFIC UNIT INFORMATION
LIMITATIONS & LOCATION
This furnace should be installed in accordance with all national and local building/safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA B149.1 or .2 Installation Code (latest editions), local plumbing or waste water codes, and other applicable codes.
CLEARANCES FOR ACCESS
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recom­mended:
1. Twenty-four (24) inches between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue/vent connections.
NOTE: In all cases, accessibility clearances shall take prece­dence over clearances for combustible materials where accessibility clearances are greater.
Do not install the furnace in an unconditioned space or garage that could experience ambient tempera­tures of 32° F (0° C) or lower. For application in below freezing locations, See “BELOW FREEZING LOCATIONS” on page 4.
The furnace is not to be used for temporary heating of buildings or structures under construction.
This unit must be installed in a level (1/4”) position side-to-side and front-to-back to provide proper con­densate drainage.
Do not allow return air temperature to be below 55°F for extended periods. To do so may cause conden­sation to occur in the maim fired heat exchanger.
Only use natural gas in furnaces designed for natu­ral gas. Only use propane (LP) gas for furnaces that have been properly converted to use propane (LP) gas. Do not use this furnace with butane. Using wrong gas could create a hazard, resulting in dam­age, injury or death.
Unitary Products Group 3
Page 4
Furnaces shall not be installed directly on carpeting, tile or other combustible material other than wood flooring. An accessory combustible floor base is available to allow direct installation of downflow models on combustible flooring.
Furnace shall be installed so the electrical compo­nents are protected from water.
The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
Refer to furnace rating plate for the type of gas approved for this furnace - only use those approved gases.
Check the rating plate and power supply to be sure that the electrical characteristics match. All models use nominal 115 VAC, 1 Phase, 60 Hertz power supply.
For installations above 2,000 feet, reduce input 4% for each 1,000 feet above sea level.
For installation between 2000 and 4500 feet, it is not required that the pressure switch be changed, provided the maximum vent/intake pipe lengths are adjusted as shown in the Note from Tables 5 & 6 on Pages 15 & 19. For altitudes above 4,500 feet, refer to instructions 035-14460-000 for correct pressure switch/orifice or other required conversion informa­tion.
The furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
A furnace installed in a residential garage shall be located so that all burners and burner ignition devices are located not less that 18" above the garage floor, and located or protected to prevent damage by vehicles.
Allow clearances from combustible materials as listed under Clearances to Combustibles, ensuring that service access is allowed for both the burners and blower.
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with or in the supply air side of the furnace to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow shall be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool posi­tion.
035-17468-001 Rev. A (801)
The furnace shall be located using these guidelines:
1. Where a minimum amount of air intake/vent piping and elbows will be required.
2. As centralized with the air distribution system as possi­ble.
3. Where adequate combustion air will be available (particularly when installing as 1-pipe system).
4. In an area where ventilation facilities provide for safe lim­its of ambient temperature under normal operating condi­tions. Ambient temperatures must not fall below 32°F (0°C) unless the condensate system is protected from freezing (Refer to BELOW FREEZING LOCATIONS below).
5. Where it will not interfere with proper air circulation in the confined space.
6. Where the outdoor combustion air/vent terminal will not be blocked or restricted.
CLEARANCES TO COMBUSTIBLES
Minimum clearances from combustible construction are shown in Table 3, “UNIT CLEARANCES TO COMBUSTI­BLES,” on Page 6. These minimum clearances must be maintained in the installation.
BELOW FREEZING LOCATIONS
If this furnace is installed in any area where the ambient tem­perature may drop below 32° F, a UL listed self regulated heat tape must be installed on any condensate drain lines. It is recommended that self regulating heat tape rated at 3 watts per foot be used. This must be installed around the con­densate drain lines in the unconditioned space. Always install the heat tape per the manufacturer's instructions. Cover the self-regulating heat tape with fiberglass or other heat resis­tant, insulating material.
If this unit is installed in an unconditioned space and an extended power failure occurs, there could be potential damage to the condensate trap, drain lines and internal unit components. Following a power failure situation, Do Not Operate the Unit Until
Inspection and Repair Are Performed.
4 Unitary Products Group
Page 5
035-17468-001 Rev. A (801)
20
6-3/8
1-1/4
B
3-1/8
20
D INTAKE CONNECTION
OPTIONAL SIDE RETURN CUT-OUT (EITHER SIDE)
CONDENSATE DRAIN
28-1/2
B
FRONT
TOP IMAGE
E VENT CONNECTION (vent size)
28-1/2
2-3/4
6-1/8
T’ STAT WIRING 7/8” K.G.
9-7/8
6-7/8
23
BOTTOM IMAGE
A
C
WITH K.O. REMOVED
FRONT
4-1/8
45
20-5/8
A
MODELS
P*XU -V & G9V-UH
60 / 55 / 1200 /”B”
80 / 75 / 1600 /”C”
100 / 95 / 2000 /”C”
120 / 112 / 2000 /”D”
1. Vent pipe must be increased to 3” on this unit.
3/4” FLANGE
6
1-3/4
A
17-1/2
21
21
24-1/2
1-3/4
14-1/2
16-1/4
19-3/4
19-3/4
23-1/4
8-7/8
22-3/4
B
CDE
13-1/8
16-5/8
16-5/8
20-1/8
3/4
2
2
2
2
2
2
3
1
2
FIGURE 1 : Dimensions - Upflow models
Table 1 : RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS
P*XU-V/G9V—UH
INPU
OUTPUT
MBH
H/L
MBH
H/L
NOM.
CFM
AFUE
1
LOW FIRE
TEMP.
RISE °F
HIGH
FIRE
TEMP.
RISE °F
MAX.
OUTLET
AIR
TEMP. °F
60/39 55/36 1200 93.5 45 - 75 45 - 75 175 1/2 1.7 11x8 9.6 20 14
80/52 75/48 1600 93.5 30 - 60 30 - 60 165 3/4 3.6 11x8 12.0 20 14
100/65 95/60 2000 94.0 30 - 60 30 - 60 160 1 4.3 11x10 14.5 20 12
120/78 112/72 2000 94.0 45 - 75 45 - 75 175 1 4.4 11x10 14.5 20 12
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to instructions 035-14460-000.
· Wire size based on copper conductors, 60°C, 3% voltage drop.
· Continuous return air temperature must not be below 55°F.
·
BLOWER
HP AMPS SIZE
TOTAL
UNIT
AMPS
MAX.
OVER-CURRENT
PROTECT
2
MIN WIRE SIZE (AWG) @ 75 FT.
ONE WAY
2
Unitary Products Group 5
Page 6
035-17468-001 Rev. A (801)
20
1-7/8
B
20
3/4
T'STAT WIRING 7/8 K.O.
45
CONDENSATE DRAIN ACCESS 3-1/4 x 3
AIR INTAKE 3-5/8 x 3-5/8 ( CONN. SIZE/
G
PIPE SIZE)
GAS INLET 1-1/4 x 2-1/2
5-1/4
1-1/4
3-3/4
1-3/4
2-3/4
A
FRONT RIGHT SIDE
B
28-1/2
LEFT SIDE
A
D
VENT CONNECTION
35
18-1/2
16-3/4
7-1/2
6-1/4
4-1/8
3-3/4
1-1/4
ALT. GAS INLET 1-1/4 x 2-1/2
1-3/8
VENT CONNECTION
POWER WIRING 7/8 K.O.
E F
TOP IMAGE
RETURN END
(VENT SIZE
5-3/8
19-1/4
C
H
FRONTFRONT
BOTTOM IMAGE
RETURN END
P*XD-V / G9V-DH
80/75/1200/B
120/112/2000/D
8
MODELS
ABCDEFG
17-1/2
16-1/4
24-1/2
23-1/4
14-3/4
21-3/4
2
2 (3)
1. VENT PIPE MUST BE INCREASED TO 3" ON THIS MODEL.
ALL DIMENSION ARE IN INCHES, AND ARE APPROXIMATE.
CONDENSATE DRAIN ACCESS 3-1/4 x 3
AIR INTAKE 3-5/8 x 3-5/8 ( CONN. SIZE/
G
PIPE SIZE)
6-5/8
1
10-1/8
2-1/4
2-1/423
FIGURE 2 : Dimensions - Downflow/Horizontal Models
Table 2 : RATINGS & PHYSICAL / ELECTRICAL DATA - DOWNFLOW/HORIZONTAL MODELS
P*XD-V/G9V-DH
INPU
OUTPUT
MBH
H/L
MBH
H/L
NOM.
CFM
CABINET
WIDTH
(INCHES)
AFUE
1
TEMP.
RISE °F
LOW FIRE
HIGH
FIRE
TEMP.
RISE °F
MAX.
OUTLET
AIR
TEMP. °F
80/52 75/48 1200 17-1/2 92.0 35-65 35-65 165 1/2 1.7 11 x 8 12.0 20 14 128
120/78 112/72 2000 24-1/2 92.0 40-70 40-70 170 1 4.4 11 x 10 14.5 20 12 184
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 035-14460-000.
Wire size based on copper conductors, 60°C, 3% voltage drop.
Continuous return air temperature must not be below 55°F.
BLOWER
HP AMPS SIZE
TOTAL
UNIT
AMPS
MAX.
OVER-CURRENT
PROTECT
2
MIN WIRE SIZE (AWG) @ 75 FT.
ONE WAY
2
OPERATING
WT. (LBS)
Table 3 : UNIT CLEARANCES TO COMBUSTIBLES
APPLICATION TOP FRONT REAR
LEFT
SIDE
RIGHT
SIDE
FLUE FLOOR/BOTTOM CLOSET ALCOVE ATTIC
UPFLOW MODELS (P*XU-V / G9V-UP)
UPFLOW 1 3 0 0 0 0 COMBUSTIBLE YES YES YES NO
DOWNFLOW / HORIZONTAL MODELS (P*XD-V / G9V-DH)
DOWNFLOW 1 3 0 0 0 0
HORIZONTAL 1 3 0 0
1.
Special floor base or air conditioning coil required for use on combustible floor.
2.
Minimum of 8” clearance required to install condensate removal system.
3.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of
+
0
COMBUSTIBLE
0
COMBUSTIBLE
1
YES YES YES NO
2
NO YES YES
the furnace jacket and building joists, studs or framing.
LINE
CONTACT
YES
3
6 Unitary Products Group
Page 7
035-17468-001 Rev. A (801)
DUCTWORK
The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions) or appli­cable national, provincial, local fire and safety codes.
3. Create a closed duct system. The supply duct system must be connected to the furnace outlet and the return duct system must be connected to the furnace inlet. Both supply and return duct systems must terminate outside the space containing the furnace.
4. Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the conditioned space.
The cooling coil must be installed in the supply air duct. Cooled air must not be passed over the heat exchanger.
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow must be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operating of either unit unless the damper is in the full heat or cool position.
UPFLOW MODELS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the fur­nace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to pre­vent leaks.
RETURN DUCT CONNECTION
Return air may enter the furnace through the side(s) or bot­tom depending on the type of application. Return air may not be connected into the rear panel of the unit. Refer to the "Filter Installation" section of this instruction for the type of application desired for specific installation details.
NOTE: In order to achieve the airflow indicated in the table, it is recommended those applications over 1800 CFM use return air from two sides, one side and the bottom or bottom only. For single return application, see data and notes on blower performance data tables in this manual.
UPFLOW FILTER INSTALLATION
All applications require the use of a filter. A high velocity filter and retainer are provided for field installation.
Internal Installation
1. Select desired filter position (left/right side, and/or bot­tom). Remove the corresponding cabinet cut-outs per instructions provided.
2. Install snap-in retainer clips into the corresponding slots from the outside rear of the cabinet (Refer to Figure 3.) To prevent cabinet air leaks, install snap-in plugs (pro­vided) into the unused slots at the outside rear of the cabinet.
3. Install the wire retainer inside the cabinet. Insert the open ends of the wire retainer into the clip loops at the rear of the blower compartment. The retainer wire should pivot freely like a hinge, on the clips at the rear of the cabinet. See Figure 4.
FURNACE (REAR CABINET)
RIGHT SIDE SLOTS
BOTTOM SLOTS
CABINET SLOT
FILTER SUPPORT CLIPS (PROVIDED)
LEFT SIDE SLOTS
PLUG UNUSED CABINET SLOTS WITH PLUGS (PROVIDED)
FIGURE 3 : Furnace Filter Slot Locations
Unitary Products Group 7
Page 8
POSITION WIRE RETAINER PROVIDED UNDER FLANGE
035-17468-001 Rev. A (801)
NOTE: Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instructions supplied with the accessory for side opening requirements.
FILTER
CLIPS
RIGHT SIDE INSTALLATION SHOWN
PROVIDED
FURNACE FRONT
FIGURE 4 : Side Filter Retainer Placement
4. Install the filter(s) provided. Cut filter if necessary to match air opening in cabinet. Filter should extend beyond opening edge as much as possible to prevent air from bypassing the filter. DO NOT remove stiffening rods from inside the filter. Shorten the rods, if necessary, to match final filter size.
5. Position the filter between the wire retainer and the cabi­net wall (or floor) so it completely covers the cabinet air opening and secure the filter in place at the front of the cabinet by fastening the closed (looped) end of the retainer wire under the flanged edge of the cabinet. When properly installed the filter should fit flush with all four sides of the cabinet wall.
NOTE: Air velocity through throw-away type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indi­cate the size of the cutout to be made in the furnace side panel, See Figure 5.
FRONT OF
CORNER MARKINGS
FURNACE
FIGURE 5 : Side Return Cutout Markings
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another loca­tion in the return air system, the ductwork may be directly attached to the furnace side panel.
All installations must have a filter installed.
The return duct may be attached to the furnace by S-cleat, bend tabs or other approved methods. Be sure to seal the duct to the furnace to prevent air leakage.
Where the return duct system is not complete, the return con­nection must run full size to a location outside the utility room or basement. For further details, consult Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1, or CAN/CGA B149.1 or.2, Installation Code ­latest editions.
Bottom Return
Bottom return applications normally pull return air through a base platform or return air plenum. Be sure the return plat­form structure is suitable to support the weight of the furnace. Be sure to seal the furnace to plenum connection to prevent air leakage.
The bottom panel is equipped with a perforated opening for easy removal. Tabs must be cut with sheet metal snips to allow removing knock-out. Scribe marks are included for forming flanges for attachment of the return air ductwork.
NOTE: If an external mounted filter rack is being used, see the instructions provided with that accessory for proper hole cut size.
Upflow attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
DOWNFLOW/HORIZONTAL MODELS
COOLING COIL TRANSITION
These furnace models are equipped with perforations in the supply air wrapper flanges that allow for easy application of air conditioning coil to the furnace without the use of sheet metal transition pieces, These perforations can be bent in either direction depending on the type of application - either downflow or horizontal left and right. Refer to either the “Downflow Application” or “Horizontal Application” section below for specific instructions on how to install the coil.
Downflow Installations
For installation of air conditioning coil in a downflow applica­tion, the perforations in the wrapper flanges must be bent in towards the heat exchanger to allow for the coil duct flange to recess into the furnace. Refer to the installation instructions supplied with the air conditioning coil for additional informa­tion and completion of the coil installation.
NOTE: Duct pliers or other suitable tool can be used to bend perforations. To help bend flanges in a straight line, scribe a line between the perforations prior to bending.
8 Unitary Products Group
Page 9
035-17468-001 Rev. A (801)
Horizontal Installations
For installation of an air conditioning coil in a horizontal appli­cation, the perforations in the wrapper flanges must be bent away from the heat exchanger to create duct flanges so the air conditioning coil can be properly seated on the furnace. Refer to the installation instructions supplied with the air con­ditioning coil for additional information and completion of the coil installation.
NOTE: Duct pliers or other suitable tool can be used to bend perforations. To help bend flanges in a straight line, scribe a line between the perforations prior to bending.
DOWNFLOW APPLICATION
DOWNFLOW FILTERS
A top return filter rack is supplied with the furnace. Two 14" x 20" permanent washable filters are supplied with each unit.
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air duct. See Figure 6.
Any branch duct must attach to the ver­tical ductwork above the filter height (FH).
The filter rack (provided) should be secured to the center of the front and rear flanges at the furnace top. Drill a hole through the front and rear duct flange into the filter rack and secure it with a sheet metal screw.
Refer to the unit rating plate for furnace model then see the dimensions page of this instruction for return air plenum dimensions. Install the plenum following instructions under Ductwork in this instruction
SUPPLY AIR DUCTS
Installations on combustible material or floors must use a combustible floor base (shown in Figure 7 - 1CB0317 or 1CB0324) as specified on the rating plate or a matching cool­ing coil. Follow the instructions supplied with the combustible floor base accessory.
This base can be replaced with a matching cooling coil, prop­erly sealed to prevent leaks. Follow the cooling coil instruc­tions for installing the plenum.
All downflow application supply duct systems must be designed and installed in accordance with the standards of NFPA 90A and 90B, and/or all local codes.
FILTER RACK
(FACTORY SUPPLIED)
A
DUCTWORK
A
NOTE: FILTER ACCESS THRU DUCT­WORK MUST BE PROVIDED FOR REMOVALAND CLEANING
CROSS SECTION A-A
(WITH PLENUM AND FILTERS)
RACK AND FILTERS SECURED INSIDE BLOWER SECTION FOR SHIPMENT
CASING SIZE DIMENSION FH
16-1/4 12-3/4
22-1/4 11 26-1/4 8-1/4
FILTERS
FILTER RACK
FIGURE 6 : DOWNFLOW FILTERS
COMBUSTIBLE FLOOR BASE ACCE
BRANCH DUCTS
FH
DOWNFLOW FURNACE
ARM AIR PLENUM
W
ITH 1" FLANGES
W
FIBERGLASS INSULATION
FIBERGLASS TAPE UNDER FLANGE
SSORY
Unitary Products Group 9
FIGURE 7 : Combustible Floor Base Accessory
Page 10
DOWNFLOW / HORIZONTAL MODELS ­HORIZONTAL APPLICATION
Downflow furnaces may be installed horizontally with the sup­ply airflow toward the left or right by laying the unit on the left or right side panel.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY THE INTERSECTION OF FURNACE TOP AND TWO SIDES AND BUILDING JOISTS, STUDS OR FRAMING
GAS PIPING
035-17468-001 Rev. A (801)
SUPPLY AIR
VENT (Maintain required clearances to combustibles)
SHEET METAL IN FRONT OF FURNACE COMBUSTION AIR OPENINGS IS RECOMMENDED
12”
30” MIN. WORK AREA
Do not install the unit on the rear panel.
After determining the best orientation, lay the unit on top of the shipping carton to protect the finish. The appropriate elec­trical knock-outs for power wiring, control wiring and gas pip­ing should be removed at this time.
For horizontal application, return air may enter through the bottom, left side or right side panel or any combination of these openings. Return air may not be connected into the rear panel of the unit.
HORIZONTAL FILTERS
All filters and mounting provision must be field supplied. Fil­ter(s) may be located in the duct system external to the fur­nace or in a return filter grille(s). Refer to furnace accessories on Page 30 for External Filter Kit options.
ATTIC INSTALLATION
This appliance is design certified for line contact for furnaces installed horizontally. The intersection of the furnace top and sides form a line. This line may be in contact with combustible material. Refer to Figure 8.
Secure a platform constructed of plywood or other building material to the floor joists. Sheet metal, 12" in front of the fur­nace combustion air openings is recommended. (Refer to Figure 8).
NOTE: The unit must be elevated to allow clearance to the condensate trap and drain pipe. A minimum of 8” clearance is required for this purpose.
RETURN AIR
SEDIMENT
TRAP
FIGURE 8 : Typical Attic Installation
When a furnace is installed in an attic or other insu­lated space, keep all insulating materials at least 12" away from furnace and burner combustion air open­ings.
NOTE: See crawl space installation for suspending the fur­nace in attic installations.
CRAWL SPACE INSTALLATION
The furnace can be hung from floor hoists or installed on suit­able blocks or pad. Blocks or pad installations shall provide adequate height to ensure the unit will not be subject to water damage.
When suspending the furnace from rafters or floor joists using rod, pipe or straps, refer to Physical Data and,Table 3, “UNIT CLEARANCES TO COMBUSTIBLES,” on Page 6, for fur­nace weights to determine suitable means of suspension.
Angle supports should be placed at the supply air end and near the blower deck. (Refer to Figure 9.) Do not support at
return air end of unit.
Units may also be suspended by using straps or other mate­rial at the same location. All four suspension points must be level to ensure quiet furnace operation
If this furnace is installed over a finished space, a condensate safety pan must be installed.
10 Unitary Products Group
Page 11
035-17468-001 Rev. A (801)
ANGLE IRON BRACKET
1” MAX. BETWEEN ROD & FURNACE
6” MIN BETWEEN ROD & FURNACE
1” MAX. BETWEEN ROD & FURNACE
FIGURE 9 : Typical Furnace Installation Using
Suspension Materials
In any application where temperatures below freez­ing are possible, See “BELOW FREEZING LOCA­TIONS” on page 4.
GAS PIPING
SUPPORT ROD
An overpressure protection device, such as a pres­sure regulator, which conforms to the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CAN-B149.1 or .2 (Canada) and acts to limit the downstream pressure to a value that does not exceed 0.5 PSI (14” w.c.), must be installed in the gas piping system upstream of the furnace. Failure to do so may result in a fire or explosion or cause damage to the furnace or some of its components.
EXTERNAL MANUAL SHUTOFF VALVE
GROUND JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT
TO GAS SUPPLY
DROP LEG
TO GAS SUPPLY
The gas supply should be a separate line and must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1 (latest edition), or the CAN/CGA B149.1 or .2 Installation Codes (latest edition) and all applicable local and utility requirements.
Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. The installation of a drop leg and ground union is required (Refer to Figure 10).
Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace (Refer to Figure 1 for locations and dimensions).
NOTE: Plan your combustion air piping before determining the correct gas pipe entry. Use 90 degree service elbow(s), or short nipples and conventional 90 degree elbow(s) to enter through the cabinet access holes.
INLET GAS PRESSURE RANGE
NATURAL GAS PROPANE (LP)
Minimum 4.5 In. W.C. 11 In. W.C.
Maximum 13.8 In. W.C. 13.8 In. W.C.
NOTE: An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet of the furnace.
GAS VALVE
FIGURE 10 : Gas Piping
NOTE: A 1/8” NPT plug is included in the inlet side of the gas
valve for measuring incoming gas pressure.
The furnace must be isolated from the gas supply piping sys­tem by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (3.48 kpa).
The furnace and its individual shutoff valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 psig (3.48 kpa).
Never apply a pipe wrench to the body of the combi­nation automatic gas valve. A wrench must be placed on the projection or wrench boss of the valve when installing piping to it.
Unitary Products Group 11
Page 12
Compounds used on threaded joints of gas piping must be resistant to the action of liquefied petroleum LP gases. After connections are made, leak-test all pipe connections.
After all gas piping connections are completed, leak test all joints, fittings and furnace connections with rich soap and water solution, commercially available bubble type leak detection fluid, or other approved means.
Do not use an open flame or other source of ignition for leak testing.
ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in accordance with the provisions of the National Electrical Code ANSI/NFPA No. 70-latest edition, Canadian Electric Code C22.1 Part 1 - (latest edition) and/or local codes. Elec­tric wires which are field installed shall conform with the tem­perature limitation for 63°F / 35°C rise wire when installed in accordance with instructions. Specific electrical data is given for the furnace on its rating plate and in Table 1 on Page 5 or Table 2 on Page 6.
Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/ national electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect switch in the OFF position, check all wiring against the unit wiring label. Also, see the wiring diagrams in this instruction.
NOTE: The furnace’s control system depends on correct polarity of the power supply and a proper ground connection. Refer to FURNACE CONTROL DIAGNOSTICS on Page 37, for symptoms of reversed power supply polarity.
Use copper conductors only.
Connect the power supply as shown on the unit wiring label on the inside of the blower compartment door and Figure 11 or 12 on Page 12. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white furnace lead must be connected to neutral. Also, the green equip­ment ground wire must be connected to the power supply ground.
Remove the screws retaining the wiring box cover. Route the power wiring through the opening in the unit into the junction box with a conduit connector or other proper connection. Make wiring connections referring to Figure 11 or 12 and replace the junction box cover and screws.
035-17468-001 Rev. A (801)
GND.
N
L1 (HOT)
WHT
GRN
BLK
JUNCTION BOX
DOOR SWITCH
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
IGNITION MODULE
HUM (HOT)
EAC (HOT)
CFM/TIMER BOARD
BLK/BLK WHT/WHT GRN/GRN
HUM
EAC
WIRING INSIDE JUNCTION BOX
BURNER COMPARTMENT
BLOWER
COMPARTMENT
FIGURE 11 : Electrical Wiring - Upflow Models
JUNCTION BOX
BLOWER COMPARTMENT
IGNITION MODULE
TRANSFORMER
DOOR SWITCH
BURNER COMPARTMENT
L1 (HOT)
BLK
N
WHT
HUM (HOT)
GND
GRN
EAC (HOT)
WIRING INSIDE JUNCTION BOX
VENT PIPE
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
BLK/BLK WHT/WHT GRN/GRN
FLUE CHASE
FIGURE 12 : Electrical Wiring - Downflow / Horizontal
Models
An alternate wiring method is to use a field provided 2 x 4 box and cover on the outside of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel.
12 Unitary Products Group
Page 13
035-17468-001 Rev. A (801)
NOTE: The power connection leads and wiring box on upflow units may be relocated to the left side of the furnace. Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fasten using holes pro­vided.
BLK
WHT
GRN
BLK (HOT)
WHT (NEUTRAL)
GRD
NOMINAL 120 VOLT
ELECTRICAL CONTROL CONNECTIONS
Install the field-supplied thermostat. The thermostat instruc­tions for wiring are packed with the thermostat. With the ther­mostat set in the OFF position and the main electrical source disconnected, complete the low-voltage wiring from the ther­mostat to the terminal strip on the cfm timer board. Connect Class 2 control wiring for single stage thermostat (refer to (Refer to Figure 13 on Page 13)) or for two stage thermostat (refer to (Refer to Figure 14 on Page 13).
Set the heat anticipator in the room thermostat as shown below.
Setting it lower will cause short cycles. Setting it higher will cause
NOTE: Some electronic thermostats do not have adjustable heat anticipators. They may have other type cycle rate adjust­ments. Follow the thermostat manufacturer's instructions.
FIGURE 13 : Field Wiring for Single Stage Thermostat
the room temperature to exceed the setpoint.
Two-Stage Thermostat
First Stage .4 Amps
Second Stage .1 Amps
Single Stage Thermostat .4 Amps
TYPICAL FIELD WIRING - SINGLE STAGE
HUMY2
SINGLE STAGE THERMOSTAT
Y1
R
W1
G C
HUM
Y1
Y
RW1W2G
C
OX/L
10 15 20
MINUTE SELECT
CFM/TIMER BOARD
HEATPUMP
COOL HEAT DELAY ADJ
HUMDISTAT
HUM
Y2
Y1
Y
R
W1W2
O
C
O
X/L
TIME OFF
10 15 20
MINUTE SELECT
LOW HEAT TIME ADJUSTMENT
P9
P6
W1
W2
TYPICAL FIELD WIRING - TWO STAGE
TWO STAGE
THERMOSTAT
Y2 Y1
R W1 W2
G
C
X/L
CFM/TIMER BOARD
HUM
Y2
Y1
Y
RW1W2
G
COX/L
OUTDOOR
UNIT
Y2 Y1
Y2 OUT
R C X/L
JUMPER MUST BE IN
TIMER OFF POSITION
FIGURE 14 : Field Wiring for Two Stage Thermostat
The 24-volt, 40 VA transformer is sized for the furnace compo­nents only, and should not be connected to power auxiliary devices such as humidifiers, air cleaners, etc. The transformer may provide power for an air conditioning unit contactor.
NOTE: Apply strain relief to thermostat lines passing through cabinet.
ACCESSORY CONNECTIONS
Do not exceed 1.0 amp loading.
The furnace control will allow power switching control of vari­ous accessories. Refer to Figure 15 for connection details.
ELECTRONIC AIR CLEANER CONNECTION
The junction box contains a clearly marked wire for connec­tion to an electronic air cleaner. This wire provides 120 VAC (1.0 amp maximum) during circulating blower operation.
HUMIDIFIER CONNECTION
The junction box contains a clearly marked wire for connec­tion to a humidifier. This wire provides 120 VAC (1.0 amp maximum) during heat speed operation of the circulating blower
HUM. HOT
EAC HOT
BLK
WHT
BLK
WHT
EAC
HUM
EAC
HUM
SWITCHED CIRCUITS
NEUTRALS
115 VOLT HUMIDIFIER
115 VOLT ELECTRONIC AIR CLEANER
Unitary Products Group 13
FIGURE 15 : Accessory Connections
Page 14
COMBUSTION AIR AND VENT SYSTEM
T
035-17468-001 Rev. A (801)
This furnace is certified to be installed with one of three possible intake/vent configurations.
1. Two-pipe with a sealed combustion intake/vent system using outdoor combustion air.
2. Single pipe vent system using combustion air from the area surrounding the furnace.
3. Two-pipe intake/vent system using combustion air from a ventilated attic space and a vent pipe to the outside.
Be sure to follow the appropriate venting section details, related information and limitations for your type of installation.
Furnace Intake / Vent Connection Size (All Models)
60 - 100 MBH 120 MBH
Intake 2” 3"
Vent 2”
1.
Vent must be increased to 3" on this model.
Note 1:Any vent pipe size change must be made outside
furnace casing in a vertical pipe section to allow proper drainage of condensate.
Note 2: An offset using two 45 degree elbows will be required
for plenum clearance when the vent is increased to 3”.
1
2"
METHOD ONE: TWO PIPE SEALED COMBUSTION AIR & VENT SYSTEM
COMBUSTION AIR INTAKE/VENT CONNECTIONS
This type installation requires outdoor combustion air. Two separate, properly-sized pipes must be used. One bringing air from the outdoors to the furnace combustion air intake col­lar on the burner box, and a second pipe from the furnace vent connection (top right of unit) back to the outdoors. Refer to Figure 16 or 17.
The intake/vent should be located either through the wall (horizontal or side vent) or through the roof (vertical vent). Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from enter­ing or combustion products from leaving the terminal.
Also, the terminal assembly should be located as far as pos­sible from a swimming pool or a location where swimming pool chemicals might be stored. Be sure the terminal assem­bly follows the outdoor clearances listed in Table 3 for U.S. installations: In Canada, refer to CAN/CGA-B149.1 or .2 Installation Code (latest edition-Venting Systems and Air Supply).
COMBUSTION AIR PIPE PASSES THROUGH TOP PANEL
CONNECTS TO COLLAR ON TOP OF BURNER BOX
VENT PIPE CEMENTS INTO SOCKE JUST UNDER TOP PANEL
FIGURE 16 : Air Intake and Vent Locations - Upflow
VENT PIPE PASSES THROUGH TOP PANEL
OPTIONAL LEFT SIDE COMBUSTION AIR PIPE ROUTING
COMBUSTION AIR PIPE CONNECTS TO COLLAR ON BOTTOM OF BURNER BOX
FIGURE 17 : Air Intake and Vent Locations -
Downflow/Horizontal
COMBUSTION AIR/VENT PIPE SIZING
To select the proper size piping for combustion air intake and venting refer to Table 6 on Page 19. The size will be deter­mined by a combination of furnace model, total length of run, and the number of elbows required. The following rules must also be observed.
14 Unitary Products Group
Page 15
035-17468-001 Rev. A (801)
Table 4 : INTAKE/VENT PIPING - 2 PIPE SYSTEM
Upflow Models
60 / 55 / 1200 / B
100 / 95 / 2000 / C
60 / 55 / 1200 / B
100 / 95 / 2000 / C
120 / 112 / 2000 / D 3” Only 6 5 4 N/A
1.
Elbow count does not include the elbows required for the termination. See Step 4 under Combustion Air/Vent Pipe Sizing
Pipe Size
Max. Elbows vs. One Way Vent
Length (Ft.)
5 - 40 45 50 75
2”654N/A80 / 75 / 1600 / C
3”876580 / 75 / 1600 / C
1
Tabl e 5 : INTAKE/VENT PIPING - 2 PIPE SYSTEM
Downflow/Horizontal
Models
80 / 75 / 1200 / B 2” 6 5 4 N/A 80 / 75 / 1200 / B 3” 8765
120 / 112 / 2000 / D 3” Only 6 5 4 N/A
1.
Elbow count does not include the elbows required for the termination. See Step 4 under Combustion Air/Vent Pipe Sizing
Pipe Size
Max. Elbows vs. One Way Vent
Length (Ft.)
5 - 30 35 40 60
1
NOTE: If installing furnace at altitudes between 2000 - 4500 ft., the maximum allowable intake and vent pipe length must be reduced by 10 ft. If the installation requires the maximum allowable intake and vent pipe length, the furnace must be converted for high altitude operation. Refer to the proper high altitude application instruction for details.
1. Long radius elbows are required for all units.
2. Elbows are assumed to be 90 degrees. Two 45 degree elbows count as one 90 degree elbow.
3. Elbow count refers to combustion air piping and vent pip­ing separately. For example, if the table allows for 5 elbows, this will allow a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping.
Three vent terminal elbows (two for vent pipe and one for
4. air intake pipe) are already accounted for and should not be counted in the allowable total indicated in the table. See section on vent terminal. These parts are shown shaded.
5. Combustion air and vent piping must be of the same diameter.
6. All combustion air/vent pipe and fittings must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC­DWV), F891 (PVC-DWV Cellular Core). D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Sched­ule 40 ABS. Pipe cement and primer must conform to ASTM Standards D2564 (PVC) or D2235 (ABS).
7. The use of flexible connectors or no hub connectors in the vent system is not allowed. This type connection is allowed in the combustion air pipe near the furnace for air conditioning coil accessibility.
VENT TERMINATION (2-PIPE)
Side wall horizontal vent terminals and roof mounted vertical terminals may be field fabricated. Standard PVC/SRD fittings may be used. Terminal configuration must comply as detailed in this section.
NOTE: Combustion air and vent pipes must terminate together in the same atmospheric zone, either through a roof or sidewall.
NOTE: Accessory concentric intake/vent terminations, models 1CT0302 and 1CT0303 are available and approved for use with these furnaces. Refer to instructions 035-14287-000 for installation details.
When selecting the location for combustion air/vent termina­tion the following should be considered:
1. Comply with all clearance requirements as listed below.
2. Termination should be positioned where vent vapors will not damage plants or shrubs or air conditioning equip­ment.
3. Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.
4. Termination should be located where it will not be dam­aged or exposed to flying stones, balls, etc.
5. Termination should be positioned where vent vapors are not objectionable.
VENT CLEARANCES (2-PIPE) U.S. ONLY
Dryer Vent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
Plumbing Vent Stack. . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
Gas Appliance Vent Terminal . . . . . . . . . . . . . . . . . . . .3 ft.*
From any mechanical fresh air intake. . . . . . . . . . . . . . 1 ft.
From any door, window or non-mechanical fresh air or
combustion air intake . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ft.
Above grade and anticipated snow depth . . . . . . . . . . 1 ft.
Above grade when adjacent to public walkway . . . . . . 7 ft.
From electric, gas meters, regulators and relief equipment -
min. horizontal distance . . . . . . . . . . . . . . . . . . . . . . . . 4 ft.
* Does not apply to multiple installations of this furnace model. Refer to multi-unit vent terminations.
In Canada, refer to CAN/CGA-B149.1 or .2 Installation Code (latest edition - Venting Systems and Air Supply)
NOTE: Consideration must be given for degradation of build­ing materials by flue gases.
Unitary Products Group 15
Page 16
035-17468-001 Rev. A (801)
NOTE: Shaded components of the combustion air/vent sys­tem shown in the following figures are considered to be part of the vent terminal. These components should not be counted when determining piping limitations. Refer to Figure 18 thru Figure 20. Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistance material to protect against combustion product corrosion.
OVERHANG
12” MINIMUM
VENT
90°
COMBUSTION AIR
12 SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12” CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER
FIGURE 18 : Horizontal Termination Configuration with 12”
Minimum Clearance
OVERHANG
OVERHANG
12” MINIMUM
VENT
90°
18” MAX.
COMBUSTION AIR
12 SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12” CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER
FIGURE 20 : Horizontal Termination Configuration with
Horizontal Extension
VENTING MULTIPLE UNITS
Each unit must have its own intake/vent piping and termina­tion. Do not use common pipes for combustion air or venting. The vent terminals must be located as shown in refer to Fig­ure 22 thru Figure 23.
VENT
12” MINIMUM
VENT
90°
COMBUSTION AIR
12 SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM OF VENT
MAINTAIN 12” CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER
FIGURE 19 : Horizontal Termination Raised
Configuration for Additional Clearance
12” VERTICAL SEPARATION BETWEEN COMBUSTION AIR AND VENT
VENT
COMBUSTION AIR
MAINTAIN 12” MINIMUM CLEARANCEABOVE HIGHEST ANTICIPATED SNOWLEVEL. MAXIMUM OF 24” ABOVE ROOF.
COMBUSTION AIR
2”
FIGURE 22 : Double Sidewall Termination
6”
FIGURE 23 : Double Rooftop Termination
FIGURE 21 : Vertical Termination
16 Unitary Products Group
Page 17
035-17468-001 Rev. A (801)
PIPING ASSEMBLY
The final assembly procedure for the vent/combustion air pip­ing is as follows:
1. Cut piping to the proper length, beginning at the furnace.
2. Deburr the piping inside and outside.
3. Chamfer the outer edges of the piping.
4. Dry-fit the entire vent/combustion air piping assembly.
5. Disassemble the piping and apply cement primer and cement per the cement manufacturer's instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.
Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames (including pilots). Do not breathe vapors and avoid contact with skin and eyes.
6. All joints must be made to provide a permanent, air-tight, water-tight seal.
7. Support the combustion air and vent piping such that it is angled 1/4” per linear foot so that condensate will flow back toward the furnace. Piping should be supported with pipe hangers to prevent sagging. Maximum spacing between hangers is five (5) feet, except SDR-PVC pip­ing, where maximum spacing is three (3) feet.
8. Seal around the openings where the combustion air and vent piping pass through the roof of side wall.
For upflow models combustion air is brought into the furnace through the unit top panel opening. Do not install a pipe into the intake collar on top of the burner box. Refer to Figure 24.
COMBUSTION AIR
VENT PIPE CEMENTS INTO SOCKET JUST UNDER TOP PANEL
FIGURE 24 : Vent Pipe Connection - Upflow
For downflow/horizontal models combustion air is brought into the furnace through the unit side panel openings.
VENT PIPE PASSES THROUGH TOP PANEL
Vent piping must be insulated with 1/2” Armaflex insulation if it will be subjected to freezing
GAS PIPING KNOCKOUTS
temperatures such as routing through unheated areas or through an unused chimney.
When combustion air pipe is installed above a suspended ceiling, the pipe must be insulated with 1/2” Armaflex type insulation. The combustion air pipe should also be insulated when it passes through a warm, humid space.
NOTE: Vent pipe must be sloped 1/4” per foot to allow con­densate to flow back to the furnace.
FIGURE 25 : Vent Pipe Connection -
COMBUSTION AIR
Downflow/Horizontal
METHOD TWO: ONE PIPE SYSTEM
This type installation will use combustion air from within the space surrounding the furnace. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors. It is not directly ducted into the furnace. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided.
Unitary Products Group 17
For downflow/horizontal models, remove a minimum of two gas piping knockouts for combustion air access. Do not install a pipe into the intake collar on bottom of the burner box. For details, refer to Figure 25.
Page 18
035-17468-001 Rev. A (801)
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Com­bustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest editions.
An unconfined space is not less than 50 cubic feet per 1000 Btu/hr input rating for all appliances installed in that area.
Rooms communicating directly with the space containing the appliances are considered part of the unconfined space, if openings are not furnished with doors.
A confined space is an area with less than 50 cubic feet per 1000 Btu/hr input rating for all appliances installed in that area.
The following must be considered to obtain proper air for combustion and ventilation in confined spaces.
Air Source from Inside the Building
Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall each have a free area of not less than one square inch per 1,000 Btuh of total input rating of all appliances located in the space. The openings shall communicate freely with inte­rior areas having adequate infiltration from the outside.
NOTE: At least 100 square inches free area shall be used for each opening.
Air Source from Outdoors
1. Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall communicate directly, or by means of ducts, with the outdoors or to such crawl or attic spaces that freely communicate with the outdoors.
a. Vertical Ducts - Each opening must have a free
area of not less than one square inch per 4,000 Btuh of total input of all appliances located in the space.
EXAMPLE:
Total Input of All Appliances
4000
= Square Inches Free Area
b. Horizontal Ducts - Each opening must have a free
area of not less than one square inch per 2,000 Btuh of total input of all appliances located in the space.
NOTE: Ducts must have the same cross-sectional area as the free area in the opening to which they are connected. The minimum dimension of rectangular ducts shall be three inches.
2. One permanent opening, commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appli­ance. The opening shall communicate through a vertical or horizontal duct to the outdoors, or spaces (crawl or attic) that freely communicate with the outdoors and shall have a minimum free area of:
a. 1 sq. in. per 3000 Btu per hr of the total input rating
of all equipment located in the enclosure.
b. Not less than the sum of the areas of all vent con-
nectors in the confined space.
3. Louvers, Grilles and Screens
a. In calculating free area, consideration must be given
to the blocking effects of louvers, grilles and screens.
b. If the free area of a specific louver or grille is not
known, refer to the Table below, to estimate free area.
Wood or Metal
Louvers or Grilles
2
Screens
1.
Do not use less than 1/4 in. mesh
2.
Free area or louvers an grilles varies widely; installer should follow louver or grille manufacturer’s instruc­tions.
Wood 20-25%
Metal 60-70%
1/4 in. mesh or larger 100%
1
1
NOTE: If mechanically operated louvers are used, a means to prevent main burner ignition and operation must be pro­vided should louvers close during startup or operation.
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre­ate conditions requiring special attention to avoid unsatisfac­tory operation of gas appliances.
Specially Engineered Installations
The above requirements shall be permitted to be waived where special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combus­tion, ventilation and dilution of flue gases.
Combustion Air Quality
The recommended source of combustion air is to use the out­door air supply. Excessive exposure to contaminated com­bustion air will result in safety and performance related problems. However, the use of indoor air in most applications is acceptable, except as described below.
1. If the furnace is installed in a confined space it is recom­mended that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct or direct opening.
2. If indoor combustion air is used, there must be no expo­sure to the installations or substances listed below.
18 Unitary Products Group
Page 19
035-17468-001 Rev. A (801)
3. The following types of installations may require OUT­DOOR AIR for combustion, due to chemical exposure.
a. Commercial buildings
b. Buildings with indoor pools
c. Furnaces installed in laundry rooms
d. Furnaces installed in hobby or craft rooms
e. Furnaces installed near chemical storage areas
f. Permanent wave solutions
g. Chlorinated waxes and cleaners
h. Chlorine based swimming pool chemicals
i. Water softening chemicals
j. De-icing salts or chemicals
k. Carbon tetrachloride
l. Halogen type refrigerants
m. Cleaning solvents (such as perchloroethylene)
n. Printing inks, paint removers, varnishes, etc.
o. Hydrochloric acids
p. Cements and glues
q. Antistatic fabric softeners for clothes dryers
r. Masonry acid washing chemicals
VENT PIPE SIZING (1-PIPE SYSTEM)
Refer to Table 6 to select the proper size piping for venting. The size will be determined by a combination of furnace model, total length of run, and the number of elbows required. The following rules must also be observed.
NOTE: Furnace vent pipe connections are sized for 2-in. pipe. Any pipe size change must be made outside the fur­nace casing in a vertical pipe section to allow proper drainage of vent connections.
NOTE: An offset using two 45 degree elbows may be required for plenum clearance when the vent is increased to 3".
1. Long radius elbows are required for all units.
2. Elbows are assumed to be 90 degrees. Two 45 degree elbows count as one 90 degree elbow.
3. One Vent terminal elbow is already accounted for and should not be counted in the allowable total indicated in the table. Refer to the section of this manual on vent ter­minal. This part is shown shaded.
4. All vent pipe and fittings must conform to American National Standards Institute (ANSI) standards and Amer­ican Society for Testing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core), D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS. Pipe cement and primer must conform to ASTM Stan­dards D2564 (PVC) or D2235 (ABS).
5. The use of flexible connectors or no hub connectors in the vent system is not allowed.
Table 6 : VENT PIPING / 1-PIPE SYSTEM - ALL MODELS
Max. Elbows vs. One Way Vent
Model Pipe Size
5-40 45 50 75
All Models Except:
120 / 112 / 2000 / D
All Models Except:
120 / 112 / 2000 / D 120 / 112 / 2000 / D 3” Only 6 5 4 N/A
2” 6 5 4 N/A
3” 8 7 6 5
Length (Ft.)
NOTE: If installing furnace at altitudes between 2000 - 4500 ft., intake and vent pipe length must be reduced by 10 ft. If the installation requires the maximum allowable intake and vent pipe length, the furnace must be converted for high altitude operation. Refer to the proper high altitude application instruction for details.
VENT TERMINATION (1-PIPE SYSTEM)
Side wall horizontal vent terminals and roof mounted vertical terminals may be field fabricated. Standard PVC/SRD fittings may be used. Terminal configuration must comply as detailed in this section.
When selecting the locations for vent termination, the follow­ing should be considered:
1. Comply with all clearance requirements. Refer to Figure
26.
2. Termination should be positioned where vent vapors will not damage plants or shrubs or air conditioning equip­ment.
3. Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.
4. Termination should be located where it will not be dam­aged or exposed to flying stones, balls, etc.
5. Termination should be positioned where vent vapors are not objectionable.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation Code (latest edition - Venting Systems and Air Supply)
VENT TERMINAL LOCATION CLEARANCES
The vent must be installed with the following minimum clear­ances, (Figure 26), and complying with local codes or utility requirements or other authority having jurisdiction.
1. 1 foot above grade and above normal snow levels.
2. Not above any walkway.
3. 4 feet below, 4 feet horizontally from, or 1 foot above any door/window or gravity air inlet to the building, or from gas or electric meters.
4. 6 feet from any inside corner formed by two exterior walls. 10 feet is recommended where possible.
5. At least 4 feet horizontally from any soffit or undereave vent.
Unitary Products Group 19
Page 20
6. 10 feet from any forced air inlet to the building. Any fresh air or make up inlet as for a dryer or furnace area is con­sidered to be a forced air inlet.
7. Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
NOTE: Consideration must be given for degradation of build­ing materials by flue gases.
SOFFIT VENTS
4”
4”
035-17468-001 Rev. A (801)
6”
(10” RECOMMENDED)
INSIDE CORNER
ELECTRIC METER
FURNACE VENT
4”
4”
4”
4”
3”
1’ PLUS SNOW CLEARANCE
10”
FORCED AIR INTAKE
FIGURE 26 : Minimum Vent Terminal Clearances
(1-Pipe System) - U.S. Only
NOTE: Shaded components of the vent system shown in Fig­ures 27 & 28 are considered to be terminations. These com­ponents should not be counted when determining piping limitations. Sidewall termination may require sealing or shielding of building surfaces with a corrosive resistant mate­rial due to vent system corrosive combustion products.
FIGURE 28 : Horizontal Termination Raised Configuration
for Additional Clearance
FIGURE 29 : \Rooftop Termination
PIPING ASSEMBLY
The final assembly procedure for the vent piping is as follows:
1. Cut piping to the proper length, beginning at the furnace.
2. Deburr the piping inside and outside.
3. Chamfer the outer edges of the piping.
4. Dry-fit the entire vent piping system.
5. Disassemble the piping and apply cement primer and cement per the cement manufacturer's instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.
FIGURE 27 : Horizontal Termination Configuration with 12”
Minimum Clearance
20 Unitary Products Group
Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames (including pilots). Do not breathe vapors and avoid contact with skin and eyes.
Page 21
035-17468-001 Rev. A (801)
6. All joints must be made to provide a permanent, air tight. water tight seal.
7. Support the vent piping such that it is angled 1/4” per lin­ear foot so that condensate will flow back towards the furnace. Piping should be supported with pipe hangers to prevent sagging. Maximum spacing between hangers is 5 feet, except SDR-PVC piping, where maximum spac­ing is 3 feet.
8. Seal around the openings where the vent piping passes through the roof or side wall.
Vent piping must be insulated with 1/2” Armaflex insulation if it will be subjected to freezing tempera­tures such as routing through unheated areas or through an unused chimney.
When combustion air pipe is installed above a sus­pended ceiling, the pipe must be insulated with 1/2” Armaflex type insulation. The combustion air pipe should also be insulated when it passes through a warm, humid space.
NOTE: Vent pipe must be sloped 1/4” per foot to allow con­densate to flow back to the furnace.
METHOD THREE: TWO PIPE SYSTEM USING COM­BUSTION AIR FROM A VENTILATED ATTIC SPACE
This type installation requires two properly sized pipes. One brings combustion air from a properly ventilated attic space and a second pipe from the furnace vent connection (top right of unit) exits to the outdoors.
In Canada, refer to CAN/CGA-B149.1 or.2 Installation Code (latest edition - Venting Systems and Air Supply)
COMBUSTION AIR INTAKE
Refer to Tables 4 or 5 on Page 14 or 15, for intake pipe siz­ing, allowable length and elbow usage. Follow all notes, pro­cedures and required materials in the Two-Pipe Sealed Combustion section (Method 1) when installing the combus­tion air pipe within the unit and into the ventilated attic space.
COMBUSTION AIR TERMINATION
Refer to Figure 30, for required termination method and con­figuration for the intake pipe. For attic termination, use two 90 elbows with the open end in a downward position. Be sure to maintain 12" clearance above any insulation, flooring or other
Be sure to instruct the owner not to block this intake pipe.
FIGURE 30 : Attic Combustion Air Termination
COMBUSTION AIR REQUIREMENTS
The ventilated attic space from which the combustion air is taken must comply with the requirements shown on page 13 in this instruction or in Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (cur­rent edition).
VENT PIPE
For vent pipe sizing, allowable length and elbow usage, see Tables 4 or 5 on Page 14 or 15. Follow all notes, installation procedures and required materials in the METHOD TWO: ONE PIPE SYSTEM on Page 17 to install the vent pipe from the unit to the outdoors.
VENT TERMINATION
The vent pipe termination must be installed within the allow­able locations, (Refer to Figure 26 on Page 20) and Section
7.8 in the National Fuel Gas Code, ANSI Z223.1 (current edi­tion). Follow all local agency and utility requirements if more restrictive than those shown. For vent termination, refer to Figure 27 thru Figure 29.
Unitary Products Group 21
Page 22
035-17468-001 Rev. A (801)
HORIZONTAL VENT APPLICATIONS
If installing a horizontal venting system, it is recommended that a vent drain be added to the vent pipe to prevent the accumulation of excess condensate in the inducer motor dur­ing operational cycles. Refer to Figure 31.
3.00” MINIMUM LOOP DIA.
ATTACH THIS END TO CONDENSATE DRAIN SYSTEM
FIGURE 31 : Horizontal Vent Drain - Upflow Models
To install the vent drain, complete the following steps:
1. Place a tee of the proper diameter for the vent system being installed (2" or 3") in the horizontal run closest to the furnace.
2. Place a reducer bushing of proper diameter in the stem portion of the tee. The recommended size for the reducer is 5/8”.
3. Place a piece of 5/8” diameter or other selected size pipe a minimum of 3" long into the reducer to serve as a nipple.
NOTE: Tee, reducer and nipple must be properly cemented together using the appropriate method and materials speci­fied in the Combustion Air Intake/Vent Connections section of these instructions.
4. Connect a piece of flexible drain tubing such as EPDM rubber, Vinyl or PVC to the nipple.
5. Loop the drain tubing to provide a trap.
6. Connect the discharge end of the drain tube to the con­densate disposal system externally to the furnace.
CONDENSATE PIPING
The condensate drain connection is packed in the furnace for field installation. It consists of a formed hose with a 1/2” NPT male connection. A 1/2” FM x 3/4” PVC slip coupling is provided.
This drain hose may be installed to allow left or right side con­densate drain connection. Refer to Figure 33. Cut the hose to allow for proper fit for left or right exit.
LH DRAIN
3.00 MINIMUM LOOP DIA.
RH DRAIN
ATTACH THIS END TO CONDENSATE DRAIN SYSTEM
FIGURE 33 : Condensate Piping - Upflow Models
.
To install the drain hose assembly, remove the 7/8” knockout in the side panel. Remove the conduit nut from the 1/2” male fitting. Push the male fitting through the hole and reinstall the nut. The use of the 3/4” PVC coupling is optional.
FIGURE 32 : Horizontal Vent Drain -
Downflow/Horizontal Models
22 Unitary Products Group
Page 23
035-17468-001 Rev. A (801)
CONDENSATE TRAP TUBING
FIGURE 34 : Downflow/Horizontal Models
CONVERSION FOR HORIZONTAL APPLICATIONS
Remove the condensate trap and its mounting bracket from the unit side panel. Remove all drain hoses.
Reinstall the trap/bracket on the side panel which will be on the bottom when the unit is located horizontally. Use the orig­inal mounting screws.
Refer to Figure 35 for hose locations and Table 7 on Page 23 for hose cut lengths. All hoses are identified as shown in Fig­ure 35.
For horizontal left airflow (inducer and vent low) or horizontal right airflow (inducer and vent high), install condensate drain hoses as follows:
RIGHT AIRFLOW (Inducer High) - Three hoses are required. Hoses are supplied with furnace. Refer to Figure 35 and Table 7 on Page 23 for application.
LEFT AIRFLOW (Inducer Low) - Two hoses are required. Inducer outlet to trap is supplied. Condensate pan to trap must be field supplied using 5/8” I.D. hose material. Refer to Figure 35 and Table 7 on Page 23, for hose placement and sizing.
Table 7 : HORIZONTAL CONDENSATE DRAIN HOSE
SIZES - MODELS P*DH / FG9-DH / G9T-DH
CABINET SIZE (IN.)
DIM.
A 4-1/2 4-3/4 3-1/2 5-1/4
B 7-1/2 10-1/2 14 17-1/2
C 13-1/2 16-1/2 20 23-1/2
D 3-3/8 3-1/4 3-1/4 3-1/4
RIGHT AIRFLOW (INDUCER HIGH)
14-1/2 17-1/2 21 24-1/2
LEFT AIRFLOW (INDUCER LOW)
Plug all unused condensate trap, condensate pan and inducer drain connection points using plugs provided.
Drain Connection: The following steps apply to all models.
1. It is recommended that either 1/2” or 3/4” PVC or equiva­lent pipe be field installed as drain pipe. The condensate piping may be tied together with the air conditioning con­densate drain if the air conditioning condensate drain line is trapped upstream of the tie-in and the combined drains are constructed of the same material.
2. All pipe joints must be cleaned, de-burred and cemented using PVC primer and cement.
3. The furnace contains an internal trap. Therefore, no external trap should be used.
4. If a condensate pump is used, it must be suitable for use with acidic water.
5. Where required, a field-supplied neutralizer can be installed in the drain line, external to the furnace.
NOTE: The condensate drain from the furnace may be con­nected in common with the drain from an air conditioning coil if allowed by local code. Follow the instructions with the coil for trapping the drain.
Unitary Products Group 23
Page 24
RIGHT AIRFLOW (INDUCER HIGH)
035-17468-001 Rev. A (801)
HOSE IDENTIFIER NUMBERS:
C
B
A
1
3
2
1. CONDENSATE PAN TO TRAP “A” DIMENSIONS.
2. INDUCER BOTTOM TO TRAP “B” DIMENSIONS.
3. INDUCER OUTLET TO TRAP “C” DIMENSIONS.
LEFT AIRFLOW (INDUCER HIGH)
D
4
5
FIGURE 35 : Horizontal Application Condensate Drain Connection
SAFETY CONTROLS
Rollout Switch Controls:
burner box assembly. If the temperature in the burner com-
Control Circuit Fuse: A 3 amp. fuse is provided to protect the 24 volt transformer from overload caused by control cir­cuit wiring errors. This is an ATO 3, automotive type fuse and is located in the unit wiring harness between the control transformer and the furnace control.
Blower Door Safety Switch:
This unit is equipped with an Electrical Interlock Switch mounted in the blower compart­ment. This switch interrupts all power at the unit when the panel covering the blower compartment is removed.
partment exceeds its set point, the igniter control and the gas valve are de-energized. The operation of this control indi­cates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. This is a manual reset control and must be reset before operation can continue.
Pressure Switches:
switches which monitor the flow through the combustion air/ vent piping system. These switches de-energize the ignition control module and the gas valve if any of the following condi­tions are present.
1. Blockage of combustion air piping or terminal:
Blower and burner must never be operated without the blower panel in place.
Electrical supply to this unit is dependent upon the panel that
2. Blockage of vent piping or terminal: covers the blower compartment being in place and properly positioned.
3. Failure of combustion air blower motor:
Main power to the unit must still be interrupted at the main power disconnect switch before any service or
4. Blockage of condensate drain piping:
repair work is to be done to the unit. Do not rely upon the interlock switch as a main power disconnect.
5. Blockage of condensate drain piping (horizontal right
HOSE IDENTIFIER NUMBERS:
1. INDUCER OUTLET TO TRAP USE AS PROVIDED.
5. CONDENSATE PAN TO TRAP “D” DIMENSIONS.
This control is mounted on the
This furnace is supplied with pressure
• Low fire (1LP)
• High fire (2 LP)
• Low fire (1LP)
• High fire (2 LP)
• Low fire (1LP)
• High fire (2 LP)
• Low fire (1LP)
• High fire (2 LP)
installations only).
• Low fire (3 LP)
• High fire (3 LP)
24 Unitary Products Group
Page 25
035-17468-001 Rev. A (801)
R
E
P
L
A
C
E
S
C
R
E
W
LIMIT CONTROL
There are high temperature limit control(s) located on the fur­nace vestibule panel near the gas valve. These are automatic reset controls and provide over temperature protection due to reduced airflow, such as a dirty filter.
START-UP AND ADJUSTMENTS
The initial start-up of the furnace requires the following addi­tional procedures:
1. When the gas supply is initially connected to the furnace, the gas piping may be full of air. In order to purge this air, it is recommended that the ground union be loosened until the odor of gas is detected. When gas is detected, immediately retighten the union and check for leaks. Allow five minutes for any gas to dissipate before con­tinuing with the start-up procedure.
Be sure proper ventilation is available to dilute and carry away any vented gas.
b. The ignition module will energize (open) the main
gas valve on low fire for seven seconds.
c. After flame is established, the supply air blower will
start in about 30 seconds.
NOTE: Burner ignition may not be satisfactory on first start­up due to residual air in the gas line or until gas manifold pressure is adjusted. The ignition control will make 3 attempts to light before locking out.
4. With furnace in operation, paint the pipe joints and valve gasket lines with a rich soap and water solution. Bubbles indicate a gas leak. Take appropriate steps to stop the leak. If the leak persists, replace the component.
DO NOT omit this test! Never use a flame to check for gas leaks.
GAS VALVE OPERATION
The electronic switch is a two-position (ON-OFF) type. To turn the valve ON, flip the switch to line up the word ON on the switch housing, Refer to Figure 36.
Perform the following procedures only after the con­densate trap has been properly piped to a drain con­nection using the procedure in this instruction.
2. The condensate trap must be filled with water before put­ting the furnace into operation. The recommended pro­cedure is as follows:
a. Disconnect the condensate drain hose from the
induced draft blower discharge.
b. Elevate this hose and fill with water using a funnel.
c. Replace the condensate drain hose and clamps.
NOTE: If this procedure is not followed, the unit may not properly drain on initial start up.
3. All electrical connections made in the field and in the factory should be checked for proper tightness.
IGNITION SYSTEM SEQUENCE
1. Turn the gas supply ON at external valve and main gas valve.
2. Set the thermostat above room temperature to call for heat.
3. System start-up will occur as follows:
a. The induced draft blower motor will start at high
speed and wait for low pressure switch contacts to close, then switch to low speed and the hot surface ignitor will glow for approximately 17 seconds.
PM
C
O
HI
INLET
F F
ON
S
C
R
E
E
C
W
A
L
P
E
R
OUTLET
WRENCH BOSS
ON / OFF SWITCH
LOW FIRE REGULATOR ADJUSTMENT SEAL SCREW
HIGH FIRE REGULATOR
LO ADJUST
HI ADJUST
ADJUSTMENT SEAL SCREW
FIGURE 36 : Gas Valve (Top) Manual Control Knob
(Bottom) Regulator Adjustments
Unitary Products Group 25
Page 26
035-17468-001 Rev. A (801)
CHECKING GAS INPUT (NATURAL GAS)
NOTE: Front door of burner box must be secured when
checking gas input.
1. Turn off all other gas appliances connected to gas meter.
2. With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical domestic gas meter usually has a 1/2 or 1 cubic foot test dial.
3. Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from Table 4 on page 15.
NOTE: To find the Btuh input, multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in your particular locality. Contract your gas company for this information, as it varies widely from city to city.
EXAMPLE:
It is found by measurement that it takes 26 sec­onds for the hand to turn on the 1 cubic foot dial to make a revolution with only a 120,000 Btuh furnace running. Using this information, locate 26 seconds in the first column of.
Read across to the column headed 1 Cubic Foot where you will see that 138 cubic feet of gas per hour are consumed by the furnace at that rate. Multiply 138 by 850 (the BTU rating of the gas obtained from the local gas company). The result is 117,300 Btuh, which is close to the 120,000 Btuh rating of the furnace.
If the actual input is not within +
2% of the furnace rating, with allowance being made for the permissible range of the regu­lator setting (0.3 inches W.C.), replace the orifice spuds with spuds of the proper size.
Be sure to relight any gas appliances that were turned off at the start of this input check.
SECONDS FOR
ONE REVOLUTION
10 180 360
12 150 300
14 129 257
16 113 225
18 100 200
20 90 180
22 82 164
24 75 150
26 69 138
28 64 129
30 60 120
32 56 113
34 53 106
36 50 100
38 47 95
40 45 90
42 43 86
44 41 82
46 39 78
48 37 75
50 36 72
52 35 69
54 34 67
56 32 64
58 31 62
60 30 60
SIZE OF TEST DIAL
1/2 CUBIC
FOOT
1 CUBIC FOOT
26 Unitary Products Group
Page 27
035-17468-001 Rev. A (801)
ADJUSTMENT OF MANIFOLD GAS PRESSURE
Manifold gas pressure may be measured by two different pro­cedures. It may be measured with the burner box cover in place or it may be measured with the burner box cover removed. Follow the appropriate section, 1a or 1b in the instructions below.
1. Read the inlet gas pressure using either of the two methods below.
a. Reading the gas pressure with the burner box
cover in place - Disconnect the pressure reference hose from the right side of the burner box. Using a tee fitting and a short piece of hose, connect the negative side of the manometer to the burner box pressure reference port. Connect the positive side of the manometer to the adapter previously installed in the gas valve, See Figure 37 or 38.
b. Reading the gas pressure with the burner box
cover removed - Remove the screws securing the burner box front cover plate. Remove the cover. It is gasketed and may stick in place. Connect the posi­tive side of the manometer to the adapter previously installed in the gas valve as shown in Figure 37 or
38. There will be no second connection to the manometer as it will reference atmospheric pres­sure.
The regulated outlet pressures, both low and high, have been calibrated at the factory. Additional pressure adjustment should not be necessary. If adjustment is necessary, set to the following specifications. After adjustment, check for gas leakage.
Natural Gas
Low Fire 1.6 IWG
High Fire 3.5 IWG
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
High Outlet Pressure Adjustment
1. Turn off all electrical power to the system at main fuse or circuit breaker.
2. Attach a manometer to the outlet pressure tap of the valve.
3. Turn on power and energize main and redundant (P.M.) solenoids as well as the HI terminal.
4. Remove high adjustment seal screw to expose the 3/32” set screw (Refer to Figure 36).
5. To increase outlet pressure, turn the 3/32” set screw clockwise. To decrease outlet pressure, turn the set screw counterclockwise. Adjust regulator until pressure shown on manometer matches the pressure specified on the appliance rating plate.
6. Replace low adjustment seal screw and tighten securely. Cycle the valve several times to verify regulator setting.
7. Remove manometer and replace the outlet pressure tap plug.
Low Outlet Pressure Adjustment
1. Turn off all electrical power to the system at main fuse or circuit breaker.
2. Attach a manometer to the outlet pressure tap of the valve.
3. Turn on power and energize main and redundant (P.M.) solenoids. Do not energize HI terminal.
4. Remove low adjustment seal screw, See Figure 36.
5. To increase outlet pressure, turn the 3/32” set screw below the low adjustment seal screw clockwise. To decrease outlet pressure, turn the set screw counter­clockwise. Adjust regulator until pressure shown on manometer matches the pressure specified on the appli­ance rating plate.
6. Replace high adjustment seal screw and tighten securely. Cycle the valve two or three times to verify reg­ulator setting.
7. Remove manometer and replace the outlet pressure tap plug.
.
OUTLET PRESSURE TAP
BURNER BOX PRESSURE REFERENCE HOSE
BURNER BOX WITH COVER
6
U-TUBE MANOMETER
5 4 3 2 1 0 1 2 3 4 5 6
FIGURE 37 : Reading Gas Pressure - Upflow Models
Unitary Products Group 27
GAS VALVE
TEE FITTING
3.5 IN WATER COLUMN GAS PRESSURE SHOWN
OUTLET PRESSURE TAP
BURNER BOX WITH COVER REMOVED
U-TUBE MANOMETER
GAS VALVE
BURNER BOX PRESSURE REFERENCE HOSE (NOT USED)
6 5 4 3
3.5 IN
2 1
WATER COLUMN
0 1
GAS PRESSURE
2 3
SHOWN
4 5 6
Page 28
035-17468-001 Rev. A (801)
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
BURNER BOX
BURNER BOX PRESSURE REFERENCE HOSE
TEE FITTING
WITH COVER
GAS VALVE
U-TUBE MANOMETER
OUTLET PRESSURE TAP
6 5 4 3 2 1 0 1 2 3 4 5 6
3.5 IN WATER COLUMN GAS PRESSURE SHOWN
BURNER BOX PRESSURE REFERENCE HOSE
FIGURE 38 : Reading Gas Pressure - Downflow/Horizontal Models
After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet from the furnace where
The manifold pressure must be checked with the screw-off cap for the gas valve pressure regulator in place. If not, the nominal manifold pressure setting will result in an over-fire condition.
If manifold pressure is too high, an over-fire condi­tion exists which could cause heat exchanger fail­ure. If the manifold pressure is too low, sooting and eventual clogging of the heat exchanger could occur.
Be sure that gas valve regulator cap is replaced and burner box to gas valve pressure reference hose is reconnected.
Once the correct gas pressure to the burners has been
they will not be affected by radiant heat.
Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
All direct-drive blowers have multi-speed motors. The blower motor speed taps are located in the control box in the blower compartment.
You may select a heating speed and a cooling speed. They may be the same speed or a different speed.
To use the same speed tap for heating and cooling, the heat terminal and cool terminal must be connected using a jumper wire and connected to the desired motor lead. Place all unused motor leads on Park terminals. Two Park terminals
are provided. established, turn the gas valve switch to OFF and turn the electrical supply switch to OFF; then remove the pressure tap at the gas valve and re-install the plug, using a compound (on the threads) resistant to the action of LP gases. Replace the burner box front cover or the pressure reference hose.
Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the plug with a soap and water solution.
ADJUSTMENT OF TEMPERATURE RISE
DIRECT DRIVE MOTORS (ONLY APPLIES TO PSC REPLACEMENT)
VARIABLE SPEED MOTORS
The temperature rise, or temperature difference between the
return air and the heated air from the furnace, must be within
the range shown on the furnace rating plate and within the
application limitations shown in Table 1 on Page 5 or Table 2
on Page 6. The temperature rise, or temperature difference between the return air and the heated air from the furnace, must be within the range shown on the furnace rating plate. Application limi­tations are shown in Table 1 or 2. After the temperature rise has been determined, the cfm can be calculated.
BURNER BOX WITH COVER REMOVED
OUTLET PRESSURE TAP
6 5 4
GAS VALVE
U-TUBE MANOMETER
3 2 1 0 1 2 3 4 5 6
3.5 IN WATER COLUMN GAS PRESSURE SHOWN
Do not energize more than one motor speed at a time or damage to the motor will result.
28 Unitary Products Group
Page 29
035-17468-001 Rev. A (801)
FURNACE ACCESSORIES
E
LECTRICAL
*ET03700324 Thermostat, One-stage Heat/One-stage Cool, non-programmable
*ET03700124 Thermostat, One-stage Heat/One-stage Cool, Deluxe programmable
*ET03770010124 Thermostat, Two-stage Heat/Two-stage Cool, non-programmable
*ET03700024 Programmable Thermostat, Two-stage Heat/Two-stage Cool, Deluxe programmable
NON-
ELECTRICAL
1NP0480 Propane Conversion Kit
1SR0302BK External Side Filter Rack (6-Pack)
1BR0317 External Bottom or Horizontal Filter Rack - Cabinet “B”
1BR0321 External Bottom Filter Rack - Cabinet “C”
1BR0324 External Bottom or Horizontal Filter Rack - Cabinet “D”
1NK0301 Condensate Neutralizer Kit
1PS0315 High Altitude Pressure Switch Kit - 60 / 55 / 1200 “B”
1PS0316 High Altitude Pressure Switch Kit - 80 / 75 / 1600 “C”
1PS0317 High Altitude Pressure Switch Kit - 100 / 95 / 2000 “C”
1PS0318 High Altitude Pressure Switch Kit - 120 / 112 / 2000 “D”
1CT0302 Concentric Vent Kit - 2”
1CT0303 Concentric Vent Kit - 3”
1CT0317 Combustible Floor Base - Cabinet “B”
1CT0324 Combustible Floor Base - Cabinet “D”
* Substitute 2 for York brands and 6 for non York brands.
AIRFLOW
D C B A
COOL HEAT ADJ DELAY
HEAT PUMP HUMIDISTAT
FIGURE 39 : CFM Timer Board
CFM SELECTION BOARD
TAP SELECTION
D C B A
REMOVE FOR
Unitary Products Group 29
Page 30
035-17468-001 Rev. A (801)
HEATING AIRFLOW
The heating airflow has been preset at the factory to provide maximum CFM. If a lesser CFM is required for a specific HVAC system the “JUMPER” on the HEAT selection pins on the CFM-Timer Board may be moved to tap “B”, “C”, or “D”. Pin “A” will provide the highest CFM and “D” the lowest CFM (Refer to Tables 9 or 10).
NOTE: When changing jumper positions, make sure that the jumper is pushed all the way on the pins. If the jumper is not making good contact or is left off completely, the blower will operate as if the jumper were in the “A” position.
NOTE: Power to the blower must be removed for at least 4 seconds after a heat or cool tap selection change, in order for the motor to recognize an adjustment.
The fixed blower on delay and adjustable blower-off delay will function as described in the “OPERATION AND MAINTENANCE" Section on Page 32 of this instruction.
COOLING AIRFLOW
The cooling airflow is preset at the factory to provide approxi­mately 90 percent of the maximum CFM and must be field adjusted to match the HVAC system at installation. Refer to the outdoor unit installation instruction for the recommended airflow for the cooling system.
The "DELAY" Tap should be set in the "B" position for a two­stage condenser. This results in a 45 second off delay at 82% of the programmed cooling airflow with a 15-second coast to stop. It should be set in the "C" position for a system with a TXV or solenoid valve. This results in a 45 second off delay at 75% of the programmed cooling airflow with a 15-second coast to stop. It should be set in the "D" position for a system without a TXV or solenoid valve. This results in a 60 second off delay at 82% of the programmed cooling airflow with a 15­second coast to stop. The "A" position is the factory setting and is used for test purposes. With the delay set in the “A” position, the blower will operate at 100% of the programed cooling air flow for 60 seconds, with a 15 second coast to stop.
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The fan-on is fixed at 30 seconds. The fan-off delay is factory set to 60 seconds (refer to Table 8 and Figure 40), however, it is field-adjustable to 90, 120 or 180 seconds. The fan-off setting must be long enough to adequately cool the furnace, but not so long that cold air is blown into the heated space.
The continuous fan speed dip switch (switch 3) on the ignition control has no affect on setting and should be left in the off position, as continuous fan speed is determined by the vari-
Tab le 8: FAN CONTROL SETTINGS
IGNITION CONTROL
To Delay Fan-Off By:
60 Sec. On-On
90 Sec. Off-On
120 Sec. On-Off
180 Sec. Off-Off
OFF
SWITCH 3 SHOULD BE LEFT IN “OFF” POSITION
ON
COOL HEAT LO HEAT HI LINE
WI
W2
Set Switch
1-2
FAN OFF ADJUSTMENT SWITCHES
Y
R
G
B
FIGURE 40 : Typical Heat/Cool Speed Tap
Connections (PSC Motor)
CONTINUOUS BLOWER
There are two modes of continuous blower operation. In one mode the blower is controlled directly through the blower motor. In the second mode the blower is controlled through the ignition control. In the first mode, when the thermostat fan-switch is set to the ON position a circuit is completed between terminals “R” and “G” of the thermostat. The contin­uous fan speed will be 63% of the high cool speed. If more air is desirable the green wire labeled (G Cool Speed) may be connected to the “G” terminal of the ignition control to achieve HIGH COOL speed (DIP switch number 3 on the ignition con­trol must be in the OFF position). The air cleaner and the blower motor are energized through the ignition control or directly through the motor.
INTERMITTENT BLOWER COOLING
On cooling/heating thermostats with fan switch, when the fan switch is set in the auto position and the thermostat calls for cooling, a circuit is completed between the R, Y and G termi­nals. The motor is energized through the Y1 cool terminal and runs on the speed selected on the CFM Timer board. The fan off setting is fixed at 60 seconds for SEER enhance­ment.
30 Unitary Products Group
Page 31
035-17468-001 Rev. A (801)
Table 9 : AIRFLOW DATA - UPFLOW MODELS
HIGH/LOW SPEED COOLING AND HEAT PUMP CFM
P1XUB12V05501 G9V06012UPB11
High Low High Low High Low High Low COOL TAP ADJ TAP 1315 720 1655 930 2030 1090 2180 1210 A B 1095 610 1555 855 1780 945 1760 970 B B 1200 655 1510 830 1890 1000 2000 1100 A A 1010 545 1440 790 1630 850 1600 910 B A 1065 595 1375 755 1685 895 1780 990 A C
870 500 1350 745 1555 830 1540 860 C B 885 505 1280 700 1430 785 1410 820 B C 655 450 1150 620 1310 740 1300 770 D B 870 460 1230 670 1400 770 1400 800 C A 610 445 1030 555 1220 665 1220 710 D A 715 450 1120 600 1245 700 1230 740 C C 545 450 915 495 1075 605 1060 660 D C
P1XUC16V07501 G9V08016UPC11
P1XUC20V09501 G9V10020UPC11
P1XUD20V11201
G9V12020UPD11
JUMPER SETTINGS
HIGH/LOW HEAT CFM
P1XUB12V05501 G9V06012UPB11
High Low High Low High Low High Low HEAT TAP ADJ TAP 1020 665 1635 1065 1940 1225 1870 1205 A Any
925 610 1540 990 1745 1105 1715 1105 B Any 850 555 1400 890 1595 1010 1590 1020 C Any 785 515 1265 805 1475 930 1480 950 D Any
P1XUC16V07501 G9V08016UPC11
P1XUC20V09501 G9V10020UPC11
P1XUD20V11201
G9V12020UPD11
JUMPER SETTINGS
Table 1 0: AIRFLOW DATA - DOWNFLOW/HORIZONTAL MODELS
HIGH/LOW SPEED COOLING AND HEAT PUMP CFM
P1XDB12V07501 G9V08012DHB11
High Low High Low COOL TAP ADJ TAP 1345 740 2230 1290 A B 1120 620 1810 1025 B B 1225 675 2100 1150 A A 1020 560 1680 950 B A 1100 605 1850 1045 A C
880 490 1600 900 C B 920 505 1500 840 B C 660 450 1410 770 D B 800 450 1510 825 C A 600 420 1265 700 D A 720 440 1320 740 C C 545 420 1120 625 D C
P1XDD20V11201 G9V12020DHD11
JUMPER SETTINGS
HEATING AIRFLOW
P1XDB12V07501
G9V08012DHB11
High Low High Low COOL TAP ADJ TAP 1380 900 1925 1260 A Any 1260 820 1750 1165 B Any 1150 750 1600 1055 C Any 1075 700 1475 985 D Any
P1XDD20V11201
G9V12020DHD11
JUMPER SETTINGS
All CFM’s are shown at 0.5” w.c. external static pressure. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not rec­ommended.
Unitary Products Group 31
NOTE: At some settings, LOW COOL and/or LOW HEAT air flow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.
Page 32
035-17468-001 Rev. A (801)
OPERATION AND MAINTENANCE
SEQUENCE OF OPERATION
The following describes the sequence of operation of the fur­nace as it relates to a furnace equipped with a variable speed blower. Refer to the schematic wiring diagram for component location on Page 39 or 40.
HEATING OPERATIONAL SEQUENCE
TWO STAGE THERMOSTAT
The ignition control in this furnace is unique to this product. The control allows for a 24 volt or a 115 volt circulator input/ output. This allows for the replacement of the variable speed motor with a multi-speed PSC motor in the event a variable speed motor is not available at the time of servicing.
In a typical system, a call for first stage heat is initiated by closing the W1 thermostat contacts. The inducer blower is energized at high speed and the control waits for the low pressure switch contacts to close. The inducer blower is energized at low speed and the 120 VAC silicon carbide ignitor is powered.
At the end of the ignitor warm-up time, the first stage of the two stage gas valve is energized (low fire). Flame must be detected within 7 seconds. If flame is detected, the delay-to­fan-on period begins. After the delay-to-fan-on period ends, the circulator fan is energized at low heat speed and the air cleaner and humidifier are energized.
A call for second stage heat (W1 and W2) after a call for first stage heat will energize the inducer at high speed and ener­gize the circulator at high heat speed. The circulator will ener­gize at high heat speed after 30 seconds with a call for second stage heat. If the furnace has been operating in first stage heat for more than 30 seconds and the control receives a call for second stage heat, the blower will immediately switch to high speed. The second stage pressure switch con­tacts will close and energize the second stage gas valve (high fire).
If a call for second stage heat occurs at the same time as a call for first stage heat, the second stage heat is energized immediately after flame rectification is sensed on first stage.
When the second stage of the thermostat is satisfied, the inducer motor is reduced to low speed and the 2nd stage gas valve is de-energized to 1st stage. The circulator remains on high heat speed for 30 seconds then de-energizes to low heat speed.
When the first stage of the thermostat is satisfied, the gas valve is de-energized and the heat delay to fan off begins tim­ing. The inducer will postpurge for an additional 15 seconds, then the inducer and humidifier will de-energize. Upon com­pletion of the heat delay-to-fan-off, the circulator and air cleaner are de-energized. Control timing, refer to (Refer to Figure 41 on Page 33).
If flame is not detected during the trial for ignition period, the gas valve is de-energized, the ignitor is turned off and the ignition control goes into the “re-try” sequence.
The ”re-try” sequence provides a 60 second wait with inducer interpurge following an unsuccessful ignition attempt (flame not detected). After this wait, the ignition sequence is restarted with an additional 10 seconds of ignitor warm-up time. Two retries will be attempted before the control goes into system lockout. If flame is established for more than 10 seconds after ignition, the ignition controller will clear the igni­tion attempt (or retry) counter.
If flame is detected, then lost, the ignition control will repeat the initial ignition sequence. After 5 attempts to sustain flame, the control will go into system lockout.
During burner operation, a momentary loss of power of 50 milliseconds or longer will de-energize the main gas valve. When power is restored, the gas valve will remain de-energized and a restart of the ignition sequence will begin immediately.
A momentary loss of gas supply, flame blowout, or a shorted or open condition in the flame probe circuit will be sensed within 0.8 seconds. The gas valve will de-energize and the control will restart the ignition sequence.
Recycles will begin and the burner will operate normally if the gas supply returns, or the fault condition is corrected, before the last ignition attempt. Otherwise, the control will go into system lockout.
If the control has gone into system lockout, it may be possible to reset the control by a momentary power interruption of one second or longer. Refer to the FURNACE CONTROL DIAG­NOSTICS on Page 37 of this instruction for reset information.
32 Unitary Products Group
Page 33
035-17468-001 Rev. A (801)
W2 SIGNAL
HIGH INDUCER
HIGH STAGE PRESSURE
SWITCH AND 2ND STAGE
MAIN VALVE
CIRCULATOR HIGH HEAT SPEED
2ND STAGE
HIGH LIMIT
W1 SIGNAL
LOW INDUCER
ON
OFF
ON
OFF
ON
OFF
ON
OFF
CLOSED
OPEN
ON
OFF
ON
OFF
CALL HIGH HEAT AFTER LOW HEAT IS ESTABLISHED
HIGH HEAT OFF DELAY 30 SEC.
CLOSED
OPEN
ON
OFF
ON
OFF
PRESENT
ABSENT
ON
OFF
LOW PRESSURE SWITCH CLOSE RECOGNITION
HSI WARM UP 17 SEC.
IGNITION ACTIVATION PERIOD 4 SEC.
TRIAL FOR IGNITION 7 SEC.
LOW CIRCULATOR HEAT SPEED
NOTE:
LOW STAGE PRESSURE SWITCH
HSI
1ST STAGE MAIN VALVE
FLAME SENSE
1ST STAGE
1. THIS DIAGRAM SHOWS TWO IGNITION ATTEMPTS
2. TIMING LENGTHS ARE NOT TO SCALE
FIGURE 41 : Sequence Timing for Ignition Control
INTER­PURGE 60 SEC.
IGNITION DEACTIVATION PERIOD 3 SEC.
HSI WARM UP 27 SEC.
HEAT FAN DELAY ON 30 SEC.
BURN TIME
POST PURGE 15 SEC.
HEAT FAN DELAY OFF SELECTABLE 60,90,120,180 SEC.
Unitary Products Group 33
Page 34
035-17468-001 Rev. A (801)
SINGLE STAGE THERMOSTAT
If a single stage thermostat is used the unit will be controlled through the CFM Timer board timer adjustment pins (Refer to Figure 13 on Page 13.). For the furnace to operate on High Fire the timer jumper must be placed on the 10, 15 or 20 minute adjustment terminals. On a call for heat the unit will operate on low fire as detailed above. If the heating require­ments cause the cycle to exceed the jumper settings, the high fire timer will energize the second stage heat. The sec­ond stage operation will function as detailed above. The heat­ing cycle will be completed in high fire operation. If the timer jumper is in the “TIME OFF” position with a single-stage ther­mostat, the unit will stay in low fire operation.
HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a match or any other means). There may be a poten­tial shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
MAINTENANCE
AIR FILTERS
The filters should be checked periodically for dirt accumula­tion. Dirty filters greatly restrict the flow of air and overburden the system.
Clean the filters at least every three months. On new con­struction, check the filters every week for the first four weeks. Inspect the filters every three weeks after that, especially if the system is running constantly.
All filters used with the furnace are the high velocity, clean­able type. Clean these filters by washing in warm water. Make sure to shake all the water out of the filter and have it reasonably dry before installing it in the furnace. When replacing filters, be sure to use the same size and type as originally supplied.
UPFLOW FILTER REMOVAL AND REPLACEMENT
1. Turn off electrical power supply to the furnace at discon­nect switch. Remove access doors.
2. In the blower compartment disengage the looped end of the filter retainer wire from the front edge of the cabinet. The wire will now pivot on the hinged ends at the rear of the cabinet. (Refer to Figure 4 on Page 8)
3. Remove the filter and follow the cleaning instructions above. DO NOT remove the filter stiffener rods, if pro­vided.
4. When reinstalling the filter, be sure the filter completely covers the cabinet opening and is secured in place by the wire retainer.
LUBRICATION
Blower and ventor motors in these furnaces are permanently lubricated and do not require periodic oiling.
BLOWER CARE
Label all wires prior to disconnecting when servicing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after ser­vicing.
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner.
The procedure for removing the direct drive blower assembly for cleaning is as follows:
1. Disconnect the electrical supply to the furnace and remove the access doors.
2. Remove blower assembly mounting screws and slide the blower assembly out of the slots in the deck. If the two shipping screws were not previously removed, also remove and discard these two screws located on each front corner of the blower assembly.
3. To reassemble, reverse the procedure, restore power to the furnace and verify operation.
BURNER AND FLAME SENSOR REMOVAL/CLEANING
The main burners and flame sensor should be checked peri­odically for dirt accumulation or oxidation.
If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shutoff valve and loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
5. Remove burners from the burner assembly.
6. Burners may be cleaned by rinsing in hot water.
7. Reassemble the burners in the reverse order.
8. Remove the retaining screw to the flame sensor and remove the sensor from the burner box. Clean the flame sense rod with steel wool and replace.
34 Unitary Products Group
Page 35
035-17468-001 Rev. A (801)
CLEANING THE HEAT EXCHANGER
1. Turn off the main manual gas valve external to the furnace.
2. Turn off electrical power to the furnace.
3. Remove the upper access panel and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after ser­vicing.
5. Remove the screws that hold the burner box assembly to the vestibule panel and remove the assembly. The lower portion of the heat exchanger will now be exposed.
6. Remove the upper cover plate at the top of the furnace. Remove the internal baffle.
7. The upper portion of the heat exchanger is now exposed.
8. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Vacuum loose scale and dirt from each tube.
9. Clean - vacuum all burners.
10. Replace all components in reverse order. Reconnect all wiring.
11. Restore electrical power and gas supply to the furnace.
12. Check furnace operation.
CLEANING THE SECONDARY HEAT EXCHANGER
1. Follow steps 1 thru 10 under Cleaning the Primary Heat Exchanger.
2. Remove the vent piping from the venter housing. Discon­nect the drain lines from the venter and from the conden­sate drain pan. Remove the venter blower and the condensate pan. The turbulators can then be gently removed from the secondary heat exchanger.
3. With a stiff wire brush, brush out loose scale or soot.
4. Vacuum the secondary heat exchanger.
5. Finish the cleaning procedure by following steps 10 thru 12 under Cleaning the Primary Heat Exchanger.
VENT/AIR INTAKE
Should it be necessary to service the vent/air intake system, the manufacturer recommends this service be conducted by a qualified service agency.
The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
TROUBLESHOOTING
The following visual checks should be made before trouble­shooting:
1. Check to see that the power to the furnace and the igni­tion control module is ON.
2. The manual shutoff valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation.
Start the system by setting the thermostat above the room temperature. Observe the system's response. Then use the troubleshooting section in this manual to check the system's operation.
TROUBLESHOOTING THE BLOWER ASSEMBLY
Check to see that there is power to the furnace and the igni­tion circuit module by turning the furnace power OFF for 5 seconds then ON. The red ignition control LED should light for an instant then go out.
NO AIRFLOW OR MOTOR DOESN’T RUN
Verify that the blower wheel is properly tightened on the motor shaft.
Verify 115 Volts AC at the power connector at the motor.
Be sure the connectors at the motor, ignition control and CFM Selection Board are properly connected and fully seated.
Switch the thermostat to CONTINUOUS FAN mode. If the motor does not run, verify 24 VAC on the R to C lines. If there is no voltage correct the cable/wiring, trans­former fault. If there is voltage at the connector, the motor has failed.
Check High Heat, Low Heat or Cool output terminals for 24 volts.
Check motor for tight shaft.
Perform Moisture Check. Be sure motor connectors are facing down. Arrange the wire harness to create a drip loop under the motor. Check for plugged condensate drain. Check for low airflow. Check and plug leaks in return ducts.
MOTOR ROCKS BUT WON’T START
Check for loose or compliant motor mount.
Perform motor/control replacement check.
MOTOR OPERATION IS INTERMITTENT
Verify that all connectors are firmly seated. Gently pull the motor connector wires at both ends of the cables individually to be sure they are properly crimped into the housings.
MOTOR RUNS WHEN IS SUPPOSED TO BE OFF
Allow a few minutes for the motor to shut off. Motor-off delays are controlled by the ignition control.
Unitary Products Group 35
Page 36
035-17468-001 Rev. A (801)
MOTOR STARTS BUT: RUNS ERRATICALLY
Check the line voltage for variation.
Check low voltage connections at motor, unseated pins in motor harness connectors.
Check “Bk” for erratic CFM command.
MOTOR HUNTS OR “PUFFS”
Excessive restriction in duct system or filter. Reduce maximum air flow.
STAYS AT LOW CFM DESPITE SYSTEM CALL FOR COOL OR HEAT CFM
Check low voltage wires and connections.
Verify fan is not in delay mode - wait until delay is com­plete.
“R” missing /not connected at motor or terminal strip.
Perform motor/control replacement check.
STAYS AT HIGH CFM
“R” missing/not connected at motor or terminal strip.
Is fan in delay mode? Wait until delay is complete.
Perform motor/control replacement check.
BLOWER WON’T SHUT OFF
Current leakage from controls into G, Y, or W? Check for Triac switched thermostat or solid state relay.
EXCESSIVE NOISE
Determine if it’s air noise, cabinet, duct, or motor noise.
AIR NOISE
Check for loose blower housing, panels, etc.
High static creating high blower speed.
REPLACEMENT OF FAILED MOTOR CONTROL MODULE
NOTE: The motor control module may be removed and
replaced without voiding the GE warranty.
You must have the correct replacement control mod­ule for the furnace being serviced. The controls are factory programmed for specific operating modes. Consult the parts list supplied with this furnace to obtain the correct part number before ordering the part.
Using the wrong control module voids all product warranties and may produce unexpected results.
BLOWER REMOVAL FOR CONTROLLER REPLACEMENT
Refer to BLOWER CARE on Page 34 of this manual for blower removal instructions.
Rest the blower on its side so the end of the motor is accessible and facing up.
Wait at least 5 minutes after disconnecting AC power from the furnace before opening the motor.]
Remove the 2-1/4” Hex head bolts from the motor while holding the control module.
When the hex bolts are removed from the control module, the module is free from the motor but still connected by a plug and cable. Carefully rotate the control so as to gain access the plug on the end of cable. Squeeze the release latch and gently pull the plug out of the control module. Do not pull on the wires.
Verify with an ohmmeter that the resistance of each motor lead is greater than 100K ohms by connecting one meter lead to the motor lead and the other to an unpainted portion of the motor housing. If any one of the leads fails this test THE MOTOR IS DEFECTIVE AND MUST BE REPLACED.
Verify that the replacement control module is the correct one and carefully orient the control module close to the motor so the cable can be plugged into the module. BE
SURE THE PLUG LATCHES WITH A CLICK.
Carefully align the locating pin of the control module with the matching motor hole. Replace the 2-1/4” hex head bolts and tighten snugly. DO NOT OVERTIGHTEN.
REPLACEMENT OF THE VARIABLE SPEED MOTOR WITH A PSC DIRECT DRIVE MOTOR
NOTE: A failed variable speed motor should always be
replaced with a variable speed motor suitable for the furnace model being serviced. However, if one is not available, a 3 speed direct drive motor may be used in the interim.
REMOVAL OF THE VARIABLE SPEED BLOWER ASSEM­BLY AND MOTOR
Follow the Blower Removal Instructions in the Maintenance section of this instruction under, BLOWER CARE on Page
34.
1. Loosen the blower wheel set screw and the motor mount bolt, and slide the variable speed motor out of the blower housing.
36 Unitary Products Group
Page 37
035-17468-001 Rev. A (801)
INSTALLATION OF PSC MOTOR
1. Install the PSC direct drive motor into motor mount.
2. Slide motor in motor mount insuring there is no interfer­ence between moving and stationary parts. Position wire leads downward. Tighten motor mount band screw to 30
8. Connect white main harness lead to Line neutral.
9. Connect motor leads to cool, heat lo and heat high per electrical wire diagram table in the Installation manual.
10. Connect brown capacitor leads from motor to capacitor and cover terminals with boot supplied.
in. lbs.
3. Center the blower wheel in the blower housing and align the shaft flat with the blower wheel set screw. Tighten set screw to 30 in. lbs.
4. Replace blower assembly and fasten with 5 screws
5. Strap motor capacitor to electric panel. Refer to Table 11 on page 37, for proper capacitor selection.
6. Fasten electric panel to blower housing.
7. Remove red wire from Circ. input terminal. Plug jumper wire (attach to motor power harness) on 120 volt line ter-
POWER SUPPLY POLARITY - Ignition Control
If the power supply polarity is reversed, the following unit operation will occur. On a call for heat, the inducer will run, the HSI will glow and the gas valve will energize and the burners will ignite. The burners will immediately extinguish and the unit will recycle. This will occur 3 times and then the unit will lockout. A “7” flash code will be displayed. This code means the flame could not be established. This occurs because the control cannot sense flame with the power supply polarity reversed.
minal on ignition control and jumper to Circ. Input. Con­nect brown door switch wire to jumper.
Table 11: PSC MOTOR SELECTION
UPFLOW MODELS
Model Number Motor Part Number Motor Horsepower Capacitor Part Number Capacitor Rating MF 60 / 55 / 1200 / B 024-23271-000 1/2 024-20045-000 7.5 80 / 75 / 1600 / C 024-26002-000 3/4 024-20046-000 10.0
100 / 95 / 2000 / C 024-23288-001 1 024-20446-000 15.0
120 / 112 / 2000 / D 024-23238-001 1 024-20446-000 15.0
DOWNFLOW/HORIZONTAL MODELS
Model Number Motor Part Number Motor Horsepower Capacitor Part Number Capacitor Rating MF 80 / 75 / 1200 / B 024-23271-000 1/2 024-20045-000 7.5
120 / 112 / 2000 / D 024-23238-001 1 024-20446-000 15.0
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self diagnostic capability. If a system problem occurs, a fault code is shown by a blinking LED. It is located behind a clear view port in the blower compartment door. DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control's memory of the fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indi­cate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced as the control is not field repairable.
If the sensed failure is in the system (external to the control), the LED will flash in the following flash-pause sequences to indicate failure status.
Flash sequence codes 1 thru 4 are as follows. LED will turn on for 1/4 second and off for 1/4 second. This pattern will be repeated the number of times equal to the code. For exam­ple, two on flashes equals a number 2" fault code.
All flash code sequences are broken by a 2 second off period.
IGNITION CONTROL (P/N 031-01909-000)
Normal flame sense current is approximately
µ
2.4 microamps DC (
a)
Low flame signal control lockout point is
µ
0.15 microamps (DC (
CONTINUOUS FLASH (1 sec on - 1 sec off):
a)
This indi­cates that flame was sensed when there was not a call for heat. With this fault code the control will also turn on both the inducer motor and supply air blower. This fault would typically be caused by a gas valve that leaks through or is slow clos­ing.
2 FLASH:
This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or mis-wiring.
Unitary Products Group 37
Page 38
035-17468-001 Rev. A (801)
3 FLASH: This indicates the normally open pressure switch contact did not close at the beginning of the heat cycle. This could be caused by a number of problems; faulty inducer, blocked vent pipe, high winds at vent terminal, broken pres­sure switch hose or faulty pressure switch.
4 FLASH:
This indicates that a primary limit, or auxiliary limit, or rollout limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and the ventor. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.
6 FLASH:
This indicates that after the unit was operating, the pressure switch opened 5 times during the call for heat. This could be caused by a number of problems; blocked vent or chimney, faulty inducer, cracked pressure switch hose. The ignition control will lock-out after the pressure switch opens 5 times.
7 FLASH:
This fault code indicates that flame could not be established. This no-light condition occurred 3 times during the call for heat before locking out. This may be caused by low gas pressure, faulty gas valve, faulty hot surface igniter, reversed line polarity, or burner problem.
8 FLASH:
This fault is indicated if the flame is lost 5 times during the heating cycle.This could be caused by low gas pressure or faulty gas valve. The ignition control will lock-out if the flame is lost 5 times.
LED ON CONSTANTLY: This indicates an internal fault in the furnace control discovered during its self-check procedure. Replace the control.
60 MINUTE AUTOMATIC RESET FROM LOCKOUT:
This control includes a watchdog type circuit that will reset from a lockout condition after 60 minutes. This provides protection to an unoccupied structure if a temporary conditions exists causing a unit malfunction. An example would be a low incoming gas supply pressure condition preventing unit oper­ation. When the gas pressure was restored, at some point the watchdog would restart the unit and provide heat for the house.
NOTE: The control will blink one time when initially powered. This is normal and not an indication of any malfunction.
RESET FROM LOCKOUT:
To reset the control from any lockout condition break the line voltage supply or 24 volt sig­nal from the thermostat for 30 seconds.
Do not try to repair controls. Replace defective con­trols with Source 1 Parts.
Never adjust pressure switch to allow furnace oper­ation.
Never jump pressure switch or rewire in an attempt to allow furnace operation. To do so will allow fur­nace to operate under potentially hazardous condi­tions.
38 Unitary Products Group
Page 39
035-17468-001 Rev. A (801)
ELEMENTARY DIAGRAM
--CAUTION
CONNECTION DIAGRAM
WIRING DIAGRAM - UPFLOW MODELS
NOTE: The furnace’s control system requires correct polarity of the power supply.
CONNECTION DIAGRAM
GND
GRN
BLK
P8/S8
ICM
H
COOL
YEL/BLK
WHT
BRN
MOTOR
BLOWER
S7
RED
M
P1/S1
120
2STAGE
GAS VALVE
MAIN
C
HI
P
5
/
S
5
BLK
WHT
YEL
GRN
AA
RV
T
LC
HUM
EAC
VAC
B
G
R
Y
BLU/WHT
W2
W1
BLU
ELEMENTARY DIAGRAM
GND
GRN
SEE NOTE 1
POWER SUPPLY120-1-60
DS
LS1
FLAME
C
1LP
NO
WHT
BLU
1
2
0
O
T
V
A
C 3A
XFMR
EAC
HEAT LO
CIRC IN
LINE
HEAT HI
HUM
WHT
BRN
BRN
BLK
BLK
BRN
RED
BRN
BLK
RED
BRN
RED
120V
NO
DOOR
N.O. SW
PRI
C
24V SEC
COM
BLK
BLU
120
VAC
GRN
BLK
BLK
GND
P4/S4
120VAC
LINE
SENSOR
ROS1
C
PUR
ORG
2LP
NO
BLK
3
1
2
WHT
5
4
6
BLK
7
9
8
BLU
11
10
12
BLU
RED
N1
E2
P2/S2
3
2
1
WHT
BLK
BRN
RED
WHT
BRN
RED
1
1
3
2
2
WHT
BLK
REDRED
VENTOR
MOTOR
GRN
GND
UO
LINE
XFMR
5
4
BLK
WHT
WHT
2
1
P3/S3
WHT
WHT
IGNITER
HOT SURFACE
9
1
MOTOR
BLOWER
ORG
BLK
BLK
WHT
GRN
--CAUTION
BRN
BLK
EAC
EAC
GRN
RED
RED
RED
EAC
OPEN ALL DISCONNECTS BEFORE
1
4
3
6
P6
BRN
YEL
YEL
WHT
SERVICE THIS UNIT
BLU
BLU/WHT
YEL/BLK
YEL/BLK
GRN
BLK
PUR
HUM
HUMIDIFIER
HUM
LEGEND
FUSE
16
P7
8
HIGH
1LP PRESSURE SW, FIRST STAGE
YEL/BLK
GRN
YEL
RED BRN BLK
ORG
9
VENTOR
2LP PRESSURE SW, SECOND STAGE
16
P9
MOTOR
LOW
24V CONNECTION ROOM THERMOSTAT
1T TRANSFORMER 40VA
W1 W2
S6
S9
8
BLK PUR YEL WHT RED BLK BLK
1
IGN
FACTORY WIRING AND DEVICES
FIELD WIRING AND DEVICES
FIELD CONNECTION
MINUTE SELECT
TIMEROFF
ADJ
DELAYHEATCOOL
CFM TIMERBOARD
1T (40VA)
COM
PRI
120V
3A
CONTROL BOARD
RELAY CONTACTS ON IGNITION
X/L
O
CG
W2
W1
R
Y
Y1
Y2
HUM
HUMIDISTAT
HEATPUMP
24V SEC
R
R
SEE NOTES
NOTES:
B/C
G
G
GV GAS vALVE
DS DISCONNECT SWITCH
(B) CANADIAN ELECTRICAL CODE (CEC) AND/OR
ALL FIELD WIRING PER: (A) NATIONAL ELECTRICAL CODE (NEC) AND/OR
1.
GRN
Y
Y
IGN HOT SURFACE IGNITOR
P1/S1 - 12 PIN PLUG & SOCKET ON IGN. CONTROL BOARD
(C) LOCAL OR CITY CODES.
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE
2.
P2/S2 - 5 PIN PLUG & SOCKET ON IGN. CONTROL BOARD
P3/S3 - 2 PIN PLUG & SOCKET AT HOT SURFACE IGNITOR
HAVING ATEMPERATURE RATING OF AT LEAST 22.1°F (105 HAVING A
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRINGMATERIAL
P4/S4 - 3 PIN PLUG & SOCKET AT INDUCER MOTOR
TEMPERATURE RATING OF ATLEAST 221°C).
LS1
ROS1
1LP
P5/S5 3 PIN PLUG & SOCKET ON VALVE
GV
C
NO
W1
W
P7/S7 - 16 PIN PLUG & SOCKET FOR MOTOR
P6/S6 - 6 PIN PLUG & SOCKET ON CFM TIMER BOARD
ALL REPLACEMENT COMPONENTS MUST BE PROPERLY GROUNDED.
CONNECTIONS SUITABLE FOR COPPER CONDUCTORS ONLY.
4.
3.
1ST STAGE
W2
Ls1 - PRIMARY LIMIT SWITCH
P8/S8 5 PIN PLUG & SOCKET ON ICM BLOWER MOTOR
P9/S9 - 16 PIN PLUG & SOCKET ON CFM TIMER BOARD
MOTORS ARE INHERENTLY PEOTECTED.
PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
5.
6.
2LP
ROS1 - ROLL OUT SWITCH, LEFT SIDE
TIMER JUMPER MUST BE IN OFF POSITION WHEN USING A TWO STAGE THERMOSTAT.
7.
90% UPFLOW TWO-STAGE FURNACE - VARIABLE SPEED
C
NO
2ND STAGE
FIGURE 42 : Upflow Models
Unitary Products Group 39
N.O. SW
C
NO
DOOR SWITCH
RELAY
IGNITER
ON
AUTO
COOL
HEAT
OFF
HEAT/COOLTHERMOSTAT
Page 40
WIRING DIAGRAM - DOWNFLOW/HORIZONTAL MODELS
ELEMENTARY DIAGRAM
NOTES:
LEGEND
--CAUTION
CONNECTION DIAGRAM
NOTE: The furnace’s control system requires correct polarity of the power supply.
CONNECTION DIAGRAM
GND
GRN
BLK
P8/S8
ICM
BLOWER
S7
H
COOL
YEL/BLK
WHT
BRN
MOTOR
RED
LS1
ROS1
WHT
NO
1LP
BLU
1
2
0
O
T
V
A
XFMR
EAC
HEAT LO
CIRC IN
LINE
HEAT HI
HUM
WHT
BRN
BRN
BLK
BRN
RED
BRN
BLK
RED
120V
PRI
COM
BLU
GRN
BLK
GND
120VAC
LINE
RED
C
RED
C 3A
BLK
RED
BRN
NO
DOOR
C
24V SEC
BLK
120
VAC
BLK
P4/S4
WHT
FLAME
SENSOR
ROS 2
RED
LS2
RED
P2/S2
3
4
2
1
WHT
BLK
BRN
RED
N.O. SW
WHT
BRN
RED
1
1
3
2
2
WHT
BLK
RED
VENTOR
MOTOR
GRN
GND
C
PUR
ORG
2LP
NO
BLK
3
1
2
WHT
5
4
6
BLK
7
9
8
BLU
11
10
12
BLU
RED
N1
E2
UO
XFMR
LINE
5
BLK
WHT
WHT
2
1
120
P3/S3
WHT
WHT
IGNITER
HOT SURFACE
M
P1/S1
T
VAC
MAIN
2STAGE
--CAUTION
GAS VALVE
C
HI
P
5
/
S
5
BLK
WHT
YEL
GRN
GND
GRN
B
G
R
Y
BLU/WHT
AA
RV
LC
W2
W1
HUM
EAC
BLU
SEE NOTE 1
POWER SUPPLY120-1-60
ELEMENTARY DIAGRAM
DS
ORG 9 1
BLK
MOTOR
BLOWER
GND.
SERVICE THIS UNIT
OPEN ALL DISCONNECTS BEFORE
GRN
RED
BLK
BRN
BLK
WHT
RED
EAC
EAC
LEGEND
24V CONNECTION ROOM THERMOSTAT
1LP PRESSURE SW, FIRST STAGE
2LP PRESSURE SW, SECOND STAGE
YEL/BLK GRN
YEL
RED
BRN BLK
ORG
3LP PRESSURE SW, CONDENSATE
16
9
1T TRANSFORMER 40VA
S6
S9
8
1
P9
FIELD CONNECTION
W1
W2
BLK PUR
YEL WHT RED BLK
BLK
FUSE
BLU
BLU/WHT
1
4
6
3
P6
YEL/BLK
RED
BRN
YEL
GRN
YEL/BLK
16
P7
8
BLK
YEL
WHT
PUR
FACTORY WIRING AND DEVICES
ADJ
DELAYHEATCOOL
RELAY CONTACTS ON IGNITION
FIELD WIRING AND DEVICES
MINUTE SELECT
TIMEROFF
CFM TIMERBOARD
CONTROL BOARD
X/L
O
CG
W2
W1
R
Y
Y1
Y2
HUM
HUMIDISTAT
HEATPUMP
SEE NOTES
NOTES:
(B) CANADIAN ELECTRICAL CODE (CEC) AND/OR
ALL FIELD WIRING PER: (A) NATIONAL ELECTRICAL CODE (NEC) AND/OR
1.
GND.
DS DISCONNECT SWITCH
(C) LOCAL OR CITY CODES.
HUM
IGN
1T (40VA)
COM
PRI
120V
EAC
HUM
HUMIDIFIER
HIGH
MOTOR
VENTOR
LOW
3A
LS2
ROS2
24V SEC
R
R
C
3LP
NO
Y
G
B/C
G
Y
GV GAS vALVE
IGN HOT SURFACE IGNITOR
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE
2.
P2/S2 - 5 PIN PLUG& SOCKETON IGN. CONTROL BOARD
P1/S1 - 12 PIN PLUG& SOCKETON IGN. CONTROL BOARD
TEMPERATURE RATING OF ATLEAST 221°C).
HAVING ATEMPERATURE RATING OF AT LEAST 22.1°F (105 HAVINGA
GV
ROS1
LS1
C
1LP
NO
W1
W
AT INDUCER MOTOR
AT HOT SURFACE IGNITOR
PLUG & SOCKET
PLUG & SOCKET
P4/S4-3PIN
P3/S3-2PIN
CONNECTIONS SUITABLE FOR COPPER CONDUCTORS ONLY.
3.
1ST STAGE
W2
P8/S8 5 PIN PLUG &SOCKET ON ICM BLOWER MOTOR
P7/S7 - 16 PIN PLUG& SOCKETFOR MOTOR
P6/S6 - 6 PIN PLUG& SOCKETON CFM TIMER BOARD
P5/S5 3 PIN PLUG &SOCKET ON VALVE
ALL REPLACEMENT COMPONENTS MUST BE PROPERLY GROUNDED.
MOTORS ARE INHERENTLY PEOTECTED.
PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
4.
5.
6.
C
2LP
NO
LS1 - PRIMARY LIMIT SWITCH
P9/S9 - 16 PIN PLUG& SOCKETON CFM TIMER BOARD
TIMER JUMPER MUST BE IN OFF POSITION WHEN USING ATWOSTAGE THERMOSTAT.
7.
2ND STAGE
LS2 - AUXILIARY LIMIT SWITCH ON BLOWER
ROS2 - ROLL OUT SWITCH, RIGHTSIDE
ROS1 - ROLL OUT SWITCH, LEFTSIDE
90% DOWNFLOW/HORIZONTAL TWO-STAGE FURNACE - VARIABLE SPEED
FIGURE 43 : Downflow/Horizontal Models
Subject to change without notice. Printed in U.S.A. 035-17468-001 Rev. A (801)
©
Copyright
by York International Corp. 2001. All rights reserved. Supersedes: 035-17468-000 Rev. A (1000)
Unitary 5005 Norman Products York OK Group Drive 73069
N.O. SW
C
NO
DOOR SWITCH
RELAY
IGNITER
ON
AUTO
COOL
HEAT
HEAT/COOLTHERMOSTAT
OFF
Loading...