Coleman PxXU-V series, PxXU-G9V-UP series, PxXD-G9V-DH series, PxXD-V series Installation Instructions Manual

INSTALLATION
TWO-STAGE ULTRA
HIGH-EFFICIENCY GAS-FIRED
INSTRUCTIONS
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . 3
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . 12
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . 13
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . 14
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . 22
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . 24
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . 25
VARIABLE SPEED FURNACES
UPFLOW - P*XU - “V” / G9V-UP
60 To 120 MBH Input
DOWNFLOW/HORIZONTAL - P*XD-V / G9V-DH
80 To 120 MBH Input
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 29
AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . 32
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 35
EFFICIENCY RATING CERTIFIED
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
035-17468-001 Rev. A (801)
IMPROPER INSTALLATION MAY CREATE A CON­DITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALI­FIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLA­TION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUD­ING BUT NOT LIMITED TO, BUILDING, ELECTRI­CAL AND MECHANICAL CODES.
035-17468-001 Rev. A (801)
GENERAL INFORMATION
DESCRIPTION
This Category IV, dual certified direct vent and 1-pipe vent furnace is designed for residential or commercial application. It may be installed without modification to the condensate system in a basement, garage, equipment room, alcove, attic or any other indoor location provided the space temperature is 32 °F or higher and where all required clearance to com­bustibles and other restrictions are met. If the furnace is being installed where the space temperature is below 32°F, refer to BELOW FREEZING LOCATIONS on Page 4.
This furnace is constructed at the factory for natural gas-fired operation from 0 - 4,500 ft. above sea level, but may be con­verted to operate on propane (LP) gas and at altitudes up to 10,000 ft. For applications at altitudes between 2,000 - 4,500 ft., see COMBUSTION AIR/VENT PIPE SIZING on Page 14, for required vent length reductions. For application at alti­tudes greater than 4,500 feet, see high altitude instructions 035-14460-000.
High altitude and propane (LP) changes or conversions required in order for the appliance to satisfactory meet the application must be made by an authorized distributor or dealer. In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The blower in this furnace is programmed to supply a con­stant volume of airflow to compensate for duct system static.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops,
vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other clean-
ing compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill.
A separate request for inspection by the carrier's agent should be made in writing. Also, before installation the unit should be checked for screws or bolts which may have loos­ened in transit. There are no shipping or spacer brackets which need to be removed.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property damage may occur if installation procedures are not handled properly.
The cooling coil must be installed in the supply air duct. Cooled air may not be passed over the heat exchanger.
2 Unitary Products Group
035-17468-001 Rev. A (801)
VENT SAFETY CHECK PROCEDURE
This furnace may not be common vented with any other appliance, since it requires separate, properly­sized vent lines. The furnace shall not be connected to any type of B, BW or L vent or vent connector, and not connected to any portion of a factory-built or masonry chimney.
If this furnace is replacing a common-vented fur­nace, it may be necessary to resize the existing vent line and chimney to prevent oversizing problems for the new combination of units. Refer to the National Gas Code (ANSI Z223.1) or CAN/CGA B149.1 or.2 Installation Code (latest editions).
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1, or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ance(s) is located and other spaces of the building. Turn on clothes dryers. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall oper­ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
8. Any corrections to the common venting system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 or.2 Installation Code (latest edi­tions). If the common vent system must be resized, it should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the above codes.
SPECIFIC UNIT INFORMATION
LIMITATIONS & LOCATION
This furnace should be installed in accordance with all national and local building/safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA B149.1 or .2 Installation Code (latest editions), local plumbing or waste water codes, and other applicable codes.
CLEARANCES FOR ACCESS
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recom­mended:
1. Twenty-four (24) inches between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Eighteen (18) inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue/vent connections.
NOTE: In all cases, accessibility clearances shall take prece­dence over clearances for combustible materials where accessibility clearances are greater.
Do not install the furnace in an unconditioned space or garage that could experience ambient tempera­tures of 32° F (0° C) or lower. For application in below freezing locations, See “BELOW FREEZING LOCATIONS” on page 4.
The furnace is not to be used for temporary heating of buildings or structures under construction.
This unit must be installed in a level (1/4”) position side-to-side and front-to-back to provide proper con­densate drainage.
Do not allow return air temperature to be below 55°F for extended periods. To do so may cause conden­sation to occur in the maim fired heat exchanger.
Only use natural gas in furnaces designed for natu­ral gas. Only use propane (LP) gas for furnaces that have been properly converted to use propane (LP) gas. Do not use this furnace with butane. Using wrong gas could create a hazard, resulting in dam­age, injury or death.
Unitary Products Group 3
Furnaces shall not be installed directly on carpeting, tile or other combustible material other than wood flooring. An accessory combustible floor base is available to allow direct installation of downflow models on combustible flooring.
Furnace shall be installed so the electrical compo­nents are protected from water.
The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
Refer to furnace rating plate for the type of gas approved for this furnace - only use those approved gases.
Check the rating plate and power supply to be sure that the electrical characteristics match. All models use nominal 115 VAC, 1 Phase, 60 Hertz power supply.
For installations above 2,000 feet, reduce input 4% for each 1,000 feet above sea level.
For installation between 2000 and 4500 feet, it is not required that the pressure switch be changed, provided the maximum vent/intake pipe lengths are adjusted as shown in the Note from Tables 5 & 6 on Pages 15 & 19. For altitudes above 4,500 feet, refer to instructions 035-14460-000 for correct pressure switch/orifice or other required conversion informa­tion.
The furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
A furnace installed in a residential garage shall be located so that all burners and burner ignition devices are located not less that 18" above the garage floor, and located or protected to prevent damage by vehicles.
Allow clearances from combustible materials as listed under Clearances to Combustibles, ensuring that service access is allowed for both the burners and blower.
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with or in the supply air side of the furnace to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow shall be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool posi­tion.
035-17468-001 Rev. A (801)
The furnace shall be located using these guidelines:
1. Where a minimum amount of air intake/vent piping and elbows will be required.
2. As centralized with the air distribution system as possi­ble.
3. Where adequate combustion air will be available (particularly when installing as 1-pipe system).
4. In an area where ventilation facilities provide for safe lim­its of ambient temperature under normal operating condi­tions. Ambient temperatures must not fall below 32°F (0°C) unless the condensate system is protected from freezing (Refer to BELOW FREEZING LOCATIONS below).
5. Where it will not interfere with proper air circulation in the confined space.
6. Where the outdoor combustion air/vent terminal will not be blocked or restricted.
CLEARANCES TO COMBUSTIBLES
Minimum clearances from combustible construction are shown in Table 3, “UNIT CLEARANCES TO COMBUSTI­BLES,” on Page 6. These minimum clearances must be maintained in the installation.
BELOW FREEZING LOCATIONS
If this furnace is installed in any area where the ambient tem­perature may drop below 32° F, a UL listed self regulated heat tape must be installed on any condensate drain lines. It is recommended that self regulating heat tape rated at 3 watts per foot be used. This must be installed around the con­densate drain lines in the unconditioned space. Always install the heat tape per the manufacturer's instructions. Cover the self-regulating heat tape with fiberglass or other heat resis­tant, insulating material.
If this unit is installed in an unconditioned space and an extended power failure occurs, there could be potential damage to the condensate trap, drain lines and internal unit components. Following a power failure situation, Do Not Operate the Unit Until
Inspection and Repair Are Performed.
4 Unitary Products Group
035-17468-001 Rev. A (801)
20
6-3/8
1-1/4
B
3-1/8
20
D INTAKE CONNECTION
OPTIONAL SIDE RETURN CUT-OUT (EITHER SIDE)
CONDENSATE DRAIN
28-1/2
B
FRONT
TOP IMAGE
E VENT CONNECTION (vent size)
28-1/2
2-3/4
6-1/8
T’ STAT WIRING 7/8” K.G.
9-7/8
6-7/8
23
BOTTOM IMAGE
A
C
WITH K.O. REMOVED
FRONT
4-1/8
45
20-5/8
A
MODELS
P*XU -V & G9V-UH
60 / 55 / 1200 /”B”
80 / 75 / 1600 /”C”
100 / 95 / 2000 /”C”
120 / 112 / 2000 /”D”
1. Vent pipe must be increased to 3” on this unit.
3/4” FLANGE
6
1-3/4
A
17-1/2
21
21
24-1/2
1-3/4
14-1/2
16-1/4
19-3/4
19-3/4
23-1/4
8-7/8
22-3/4
B
CDE
13-1/8
16-5/8
16-5/8
20-1/8
3/4
2
2
2
2
2
2
3
1
2
FIGURE 1 : Dimensions - Upflow models
Table 1 : RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS
P*XU-V/G9V—UH
INPU
OUTPUT
MBH
H/L
MBH
H/L
NOM.
CFM
AFUE
1
LOW FIRE
TEMP.
RISE °F
HIGH
FIRE
TEMP.
RISE °F
MAX.
OUTLET
AIR
TEMP. °F
60/39 55/36 1200 93.5 45 - 75 45 - 75 175 1/2 1.7 11x8 9.6 20 14
80/52 75/48 1600 93.5 30 - 60 30 - 60 165 3/4 3.6 11x8 12.0 20 14
100/65 95/60 2000 94.0 30 - 60 30 - 60 160 1 4.3 11x10 14.5 20 12
120/78 112/72 2000 94.0 45 - 75 45 - 75 175 1 4.4 11x10 14.5 20 12
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition). For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to instructions 035-14460-000.
· Wire size based on copper conductors, 60°C, 3% voltage drop.
· Continuous return air temperature must not be below 55°F.
·
BLOWER
HP AMPS SIZE
TOTAL
UNIT
AMPS
MAX.
OVER-CURRENT
PROTECT
2
MIN WIRE SIZE (AWG) @ 75 FT.
ONE WAY
2
Unitary Products Group 5
035-17468-001 Rev. A (801)
20
1-7/8
B
20
3/4
T'STAT WIRING 7/8 K.O.
45
CONDENSATE DRAIN ACCESS 3-1/4 x 3
AIR INTAKE 3-5/8 x 3-5/8 ( CONN. SIZE/
G
PIPE SIZE)
GAS INLET 1-1/4 x 2-1/2
5-1/4
1-1/4
3-3/4
1-3/4
2-3/4
A
FRONT RIGHT SIDE
B
28-1/2
LEFT SIDE
A
D
VENT CONNECTION
35
18-1/2
16-3/4
7-1/2
6-1/4
4-1/8
3-3/4
1-1/4
ALT. GAS INLET 1-1/4 x 2-1/2
1-3/8
VENT CONNECTION
POWER WIRING 7/8 K.O.
E F
TOP IMAGE
RETURN END
(VENT SIZE
5-3/8
19-1/4
C
H
FRONTFRONT
BOTTOM IMAGE
RETURN END
P*XD-V / G9V-DH
80/75/1200/B
120/112/2000/D
8
MODELS
ABCDEFG
17-1/2
16-1/4
24-1/2
23-1/4
14-3/4
21-3/4
2
2 (3)
1. VENT PIPE MUST BE INCREASED TO 3" ON THIS MODEL.
ALL DIMENSION ARE IN INCHES, AND ARE APPROXIMATE.
CONDENSATE DRAIN ACCESS 3-1/4 x 3
AIR INTAKE 3-5/8 x 3-5/8 ( CONN. SIZE/
G
PIPE SIZE)
6-5/8
1
10-1/8
2-1/4
2-1/423
FIGURE 2 : Dimensions - Downflow/Horizontal Models
Table 2 : RATINGS & PHYSICAL / ELECTRICAL DATA - DOWNFLOW/HORIZONTAL MODELS
P*XD-V/G9V-DH
INPU
OUTPUT
MBH
H/L
MBH
H/L
NOM.
CFM
CABINET
WIDTH
(INCHES)
AFUE
1
TEMP.
RISE °F
LOW FIRE
HIGH
FIRE
TEMP.
RISE °F
MAX.
OUTLET
AIR
TEMP. °F
80/52 75/48 1200 17-1/2 92.0 35-65 35-65 165 1/2 1.7 11 x 8 12.0 20 14 128
120/78 112/72 2000 24-1/2 92.0 40-70 40-70 170 1 4.4 11 x 10 14.5 20 12 184
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 035-14460-000.
Wire size based on copper conductors, 60°C, 3% voltage drop.
Continuous return air temperature must not be below 55°F.
BLOWER
HP AMPS SIZE
TOTAL
UNIT
AMPS
MAX.
OVER-CURRENT
PROTECT
2
MIN WIRE SIZE (AWG) @ 75 FT.
ONE WAY
2
OPERATING
WT. (LBS)
Table 3 : UNIT CLEARANCES TO COMBUSTIBLES
APPLICATION TOP FRONT REAR
LEFT
SIDE
RIGHT
SIDE
FLUE FLOOR/BOTTOM CLOSET ALCOVE ATTIC
UPFLOW MODELS (P*XU-V / G9V-UP)
UPFLOW 1 3 0 0 0 0 COMBUSTIBLE YES YES YES NO
DOWNFLOW / HORIZONTAL MODELS (P*XD-V / G9V-DH)
DOWNFLOW 1 3 0 0 0 0
HORIZONTAL 1 3 0 0
1.
Special floor base or air conditioning coil required for use on combustible floor.
2.
Minimum of 8” clearance required to install condensate removal system.
3.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of
+
0
COMBUSTIBLE
0
COMBUSTIBLE
1
YES YES YES NO
2
NO YES YES
the furnace jacket and building joists, studs or framing.
LINE
CONTACT
YES
3
6 Unitary Products Group
035-17468-001 Rev. A (801)
DUCTWORK
The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions) or appli­cable national, provincial, local fire and safety codes.
3. Create a closed duct system. The supply duct system must be connected to the furnace outlet and the return duct system must be connected to the furnace inlet. Both supply and return duct systems must terminate outside the space containing the furnace.
4. Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the conditioned space.
The cooling coil must be installed in the supply air duct. Cooled air must not be passed over the heat exchanger.
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow must be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operating of either unit unless the damper is in the full heat or cool position.
UPFLOW MODELS
SUPPLY PLENUM CONNECTION
Attach the supply plenum to the fur­nace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to pre­vent leaks.
RETURN DUCT CONNECTION
Return air may enter the furnace through the side(s) or bot­tom depending on the type of application. Return air may not be connected into the rear panel of the unit. Refer to the "Filter Installation" section of this instruction for the type of application desired for specific installation details.
NOTE: In order to achieve the airflow indicated in the table, it is recommended those applications over 1800 CFM use return air from two sides, one side and the bottom or bottom only. For single return application, see data and notes on blower performance data tables in this manual.
UPFLOW FILTER INSTALLATION
All applications require the use of a filter. A high velocity filter and retainer are provided for field installation.
Internal Installation
1. Select desired filter position (left/right side, and/or bot­tom). Remove the corresponding cabinet cut-outs per instructions provided.
2. Install snap-in retainer clips into the corresponding slots from the outside rear of the cabinet (Refer to Figure 3.) To prevent cabinet air leaks, install snap-in plugs (pro­vided) into the unused slots at the outside rear of the cabinet.
3. Install the wire retainer inside the cabinet. Insert the open ends of the wire retainer into the clip loops at the rear of the blower compartment. The retainer wire should pivot freely like a hinge, on the clips at the rear of the cabinet. See Figure 4.
FURNACE (REAR CABINET)
RIGHT SIDE SLOTS
BOTTOM SLOTS
CABINET SLOT
FILTER SUPPORT CLIPS (PROVIDED)
LEFT SIDE SLOTS
PLUG UNUSED CABINET SLOTS WITH PLUGS (PROVIDED)
FIGURE 3 : Furnace Filter Slot Locations
Unitary Products Group 7
POSITION WIRE RETAINER PROVIDED UNDER FLANGE
035-17468-001 Rev. A (801)
NOTE: Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instructions supplied with the accessory for side opening requirements.
FILTER
CLIPS
RIGHT SIDE INSTALLATION SHOWN
PROVIDED
FURNACE FRONT
FIGURE 4 : Side Filter Retainer Placement
4. Install the filter(s) provided. Cut filter if necessary to match air opening in cabinet. Filter should extend beyond opening edge as much as possible to prevent air from bypassing the filter. DO NOT remove stiffening rods from inside the filter. Shorten the rods, if necessary, to match final filter size.
5. Position the filter between the wire retainer and the cabi­net wall (or floor) so it completely covers the cabinet air opening and secure the filter in place at the front of the cabinet by fastening the closed (looped) end of the retainer wire under the flanged edge of the cabinet. When properly installed the filter should fit flush with all four sides of the cabinet wall.
NOTE: Air velocity through throw-away type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indi­cate the size of the cutout to be made in the furnace side panel, See Figure 5.
FRONT OF
CORNER MARKINGS
FURNACE
FIGURE 5 : Side Return Cutout Markings
Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another loca­tion in the return air system, the ductwork may be directly attached to the furnace side panel.
All installations must have a filter installed.
The return duct may be attached to the furnace by S-cleat, bend tabs or other approved methods. Be sure to seal the duct to the furnace to prevent air leakage.
Where the return duct system is not complete, the return con­nection must run full size to a location outside the utility room or basement. For further details, consult Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1, or CAN/CGA B149.1 or.2, Installation Code ­latest editions.
Bottom Return
Bottom return applications normally pull return air through a base platform or return air plenum. Be sure the return plat­form structure is suitable to support the weight of the furnace. Be sure to seal the furnace to plenum connection to prevent air leakage.
The bottom panel is equipped with a perforated opening for easy removal. Tabs must be cut with sheet metal snips to allow removing knock-out. Scribe marks are included for forming flanges for attachment of the return air ductwork.
NOTE: If an external mounted filter rack is being used, see the instructions provided with that accessory for proper hole cut size.
Upflow attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.
DOWNFLOW/HORIZONTAL MODELS
COOLING COIL TRANSITION
These furnace models are equipped with perforations in the supply air wrapper flanges that allow for easy application of air conditioning coil to the furnace without the use of sheet metal transition pieces, These perforations can be bent in either direction depending on the type of application - either downflow or horizontal left and right. Refer to either the “Downflow Application” or “Horizontal Application” section below for specific instructions on how to install the coil.
Downflow Installations
For installation of air conditioning coil in a downflow applica­tion, the perforations in the wrapper flanges must be bent in towards the heat exchanger to allow for the coil duct flange to recess into the furnace. Refer to the installation instructions supplied with the air conditioning coil for additional informa­tion and completion of the coil installation.
NOTE: Duct pliers or other suitable tool can be used to bend perforations. To help bend flanges in a straight line, scribe a line between the perforations prior to bending.
8 Unitary Products Group
035-17468-001 Rev. A (801)
Horizontal Installations
For installation of an air conditioning coil in a horizontal appli­cation, the perforations in the wrapper flanges must be bent away from the heat exchanger to create duct flanges so the air conditioning coil can be properly seated on the furnace. Refer to the installation instructions supplied with the air con­ditioning coil for additional information and completion of the coil installation.
NOTE: Duct pliers or other suitable tool can be used to bend perforations. To help bend flanges in a straight line, scribe a line between the perforations prior to bending.
DOWNFLOW APPLICATION
DOWNFLOW FILTERS
A top return filter rack is supplied with the furnace. Two 14" x 20" permanent washable filters are supplied with each unit.
Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air duct. See Figure 6.
Any branch duct must attach to the ver­tical ductwork above the filter height (FH).
The filter rack (provided) should be secured to the center of the front and rear flanges at the furnace top. Drill a hole through the front and rear duct flange into the filter rack and secure it with a sheet metal screw.
Refer to the unit rating plate for furnace model then see the dimensions page of this instruction for return air plenum dimensions. Install the plenum following instructions under Ductwork in this instruction
SUPPLY AIR DUCTS
Installations on combustible material or floors must use a combustible floor base (shown in Figure 7 - 1CB0317 or 1CB0324) as specified on the rating plate or a matching cool­ing coil. Follow the instructions supplied with the combustible floor base accessory.
This base can be replaced with a matching cooling coil, prop­erly sealed to prevent leaks. Follow the cooling coil instruc­tions for installing the plenum.
All downflow application supply duct systems must be designed and installed in accordance with the standards of NFPA 90A and 90B, and/or all local codes.
FILTER RACK
(FACTORY SUPPLIED)
A
DUCTWORK
A
NOTE: FILTER ACCESS THRU DUCT­WORK MUST BE PROVIDED FOR REMOVALAND CLEANING
CROSS SECTION A-A
(WITH PLENUM AND FILTERS)
RACK AND FILTERS SECURED INSIDE BLOWER SECTION FOR SHIPMENT
CASING SIZE DIMENSION FH
16-1/4 12-3/4
22-1/4 11 26-1/4 8-1/4
FILTERS
FILTER RACK
FIGURE 6 : DOWNFLOW FILTERS
COMBUSTIBLE FLOOR BASE ACCE
BRANCH DUCTS
FH
DOWNFLOW FURNACE
ARM AIR PLENUM
W
ITH 1" FLANGES
W
FIBERGLASS INSULATION
FIBERGLASS TAPE UNDER FLANGE
SSORY
Unitary Products Group 9
FIGURE 7 : Combustible Floor Base Accessory
DOWNFLOW / HORIZONTAL MODELS ­HORIZONTAL APPLICATION
Downflow furnaces may be installed horizontally with the sup­ply airflow toward the left or right by laying the unit on the left or right side panel.
LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY THE INTERSECTION OF FURNACE TOP AND TWO SIDES AND BUILDING JOISTS, STUDS OR FRAMING
GAS PIPING
035-17468-001 Rev. A (801)
SUPPLY AIR
VENT (Maintain required clearances to combustibles)
SHEET METAL IN FRONT OF FURNACE COMBUSTION AIR OPENINGS IS RECOMMENDED
12”
30” MIN. WORK AREA
Do not install the unit on the rear panel.
After determining the best orientation, lay the unit on top of the shipping carton to protect the finish. The appropriate elec­trical knock-outs for power wiring, control wiring and gas pip­ing should be removed at this time.
For horizontal application, return air may enter through the bottom, left side or right side panel or any combination of these openings. Return air may not be connected into the rear panel of the unit.
HORIZONTAL FILTERS
All filters and mounting provision must be field supplied. Fil­ter(s) may be located in the duct system external to the fur­nace or in a return filter grille(s). Refer to furnace accessories on Page 30 for External Filter Kit options.
ATTIC INSTALLATION
This appliance is design certified for line contact for furnaces installed horizontally. The intersection of the furnace top and sides form a line. This line may be in contact with combustible material. Refer to Figure 8.
Secure a platform constructed of plywood or other building material to the floor joists. Sheet metal, 12" in front of the fur­nace combustion air openings is recommended. (Refer to Figure 8).
NOTE: The unit must be elevated to allow clearance to the condensate trap and drain pipe. A minimum of 8” clearance is required for this purpose.
RETURN AIR
SEDIMENT
TRAP
FIGURE 8 : Typical Attic Installation
When a furnace is installed in an attic or other insu­lated space, keep all insulating materials at least 12" away from furnace and burner combustion air open­ings.
NOTE: See crawl space installation for suspending the fur­nace in attic installations.
CRAWL SPACE INSTALLATION
The furnace can be hung from floor hoists or installed on suit­able blocks or pad. Blocks or pad installations shall provide adequate height to ensure the unit will not be subject to water damage.
When suspending the furnace from rafters or floor joists using rod, pipe or straps, refer to Physical Data and,Table 3, “UNIT CLEARANCES TO COMBUSTIBLES,” on Page 6, for fur­nace weights to determine suitable means of suspension.
Angle supports should be placed at the supply air end and near the blower deck. (Refer to Figure 9.) Do not support at
return air end of unit.
Units may also be suspended by using straps or other mate­rial at the same location. All four suspension points must be level to ensure quiet furnace operation
If this furnace is installed over a finished space, a condensate safety pan must be installed.
10 Unitary Products Group
035-17468-001 Rev. A (801)
ANGLE IRON BRACKET
1” MAX. BETWEEN ROD & FURNACE
6” MIN BETWEEN ROD & FURNACE
1” MAX. BETWEEN ROD & FURNACE
FIGURE 9 : Typical Furnace Installation Using
Suspension Materials
In any application where temperatures below freez­ing are possible, See “BELOW FREEZING LOCA­TIONS” on page 4.
GAS PIPING
SUPPORT ROD
An overpressure protection device, such as a pres­sure regulator, which conforms to the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CAN-B149.1 or .2 (Canada) and acts to limit the downstream pressure to a value that does not exceed 0.5 PSI (14” w.c.), must be installed in the gas piping system upstream of the furnace. Failure to do so may result in a fire or explosion or cause damage to the furnace or some of its components.
EXTERNAL MANUAL SHUTOFF VALVE
GROUND JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT
TO GAS SUPPLY
DROP LEG
TO GAS SUPPLY
The gas supply should be a separate line and must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1 (latest edition), or the CAN/CGA B149.1 or .2 Installation Codes (latest edition) and all applicable local and utility requirements.
Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. The installation of a drop leg and ground union is required (Refer to Figure 10).
Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace (Refer to Figure 1 for locations and dimensions).
NOTE: Plan your combustion air piping before determining the correct gas pipe entry. Use 90 degree service elbow(s), or short nipples and conventional 90 degree elbow(s) to enter through the cabinet access holes.
INLET GAS PRESSURE RANGE
NATURAL GAS PROPANE (LP)
Minimum 4.5 In. W.C. 11 In. W.C.
Maximum 13.8 In. W.C. 13.8 In. W.C.
NOTE: An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet of the furnace.
GAS VALVE
FIGURE 10 : Gas Piping
NOTE: A 1/8” NPT plug is included in the inlet side of the gas
valve for measuring incoming gas pressure.
The furnace must be isolated from the gas supply piping sys­tem by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (3.48 kpa).
The furnace and its individual shutoff valve must be discon­nected from the gas supply piping system during any pres­sure testing of that system at test pressures in excess of 1/2 psig (3.48 kpa).
Never apply a pipe wrench to the body of the combi­nation automatic gas valve. A wrench must be placed on the projection or wrench boss of the valve when installing piping to it.
Unitary Products Group 11
Compounds used on threaded joints of gas piping must be resistant to the action of liquefied petroleum LP gases. After connections are made, leak-test all pipe connections.
After all gas piping connections are completed, leak test all joints, fittings and furnace connections with rich soap and water solution, commercially available bubble type leak detection fluid, or other approved means.
Do not use an open flame or other source of ignition for leak testing.
ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in accordance with the provisions of the National Electrical Code ANSI/NFPA No. 70-latest edition, Canadian Electric Code C22.1 Part 1 - (latest edition) and/or local codes. Elec­tric wires which are field installed shall conform with the tem­perature limitation for 63°F / 35°C rise wire when installed in accordance with instructions. Specific electrical data is given for the furnace on its rating plate and in Table 1 on Page 5 or Table 2 on Page 6.
Provide a power supply separate from all other circuits. Install overcurrent protection and disconnect switch per local/ national electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect switch in the OFF position, check all wiring against the unit wiring label. Also, see the wiring diagrams in this instruction.
NOTE: The furnace’s control system depends on correct polarity of the power supply and a proper ground connection. Refer to FURNACE CONTROL DIAGNOSTICS on Page 37, for symptoms of reversed power supply polarity.
Use copper conductors only.
Connect the power supply as shown on the unit wiring label on the inside of the blower compartment door and Figure 11 or 12 on Page 12. The black furnace lead must be connected to the L1 (hot) wire from the power supply. The white furnace lead must be connected to neutral. Also, the green equip­ment ground wire must be connected to the power supply ground.
Remove the screws retaining the wiring box cover. Route the power wiring through the opening in the unit into the junction box with a conduit connector or other proper connection. Make wiring connections referring to Figure 11 or 12 and replace the junction box cover and screws.
035-17468-001 Rev. A (801)
GND.
N
L1 (HOT)
WHT
GRN
BLK
JUNCTION BOX
DOOR SWITCH
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
IGNITION MODULE
HUM (HOT)
EAC (HOT)
CFM/TIMER BOARD
BLK/BLK WHT/WHT GRN/GRN
HUM
EAC
WIRING INSIDE JUNCTION BOX
BURNER COMPARTMENT
BLOWER
COMPARTMENT
FIGURE 11 : Electrical Wiring - Upflow Models
JUNCTION BOX
BLOWER COMPARTMENT
IGNITION MODULE
TRANSFORMER
DOOR SWITCH
BURNER COMPARTMENT
L1 (HOT)
BLK
N
WHT
HUM (HOT)
GND
GRN
EAC (HOT)
WIRING INSIDE JUNCTION BOX
VENT PIPE
CLASS 2 SYSTEM CONTROL WIRING TO THERMOSTAT
BLK/BLK WHT/WHT GRN/GRN
FLUE CHASE
FIGURE 12 : Electrical Wiring - Downflow / Horizontal
Models
An alternate wiring method is to use a field provided 2 x 4 box and cover on the outside of the furnace. Route the furnace leads into the box using a protective bushing where the wires pass through the furnace panel.
12 Unitary Products Group
Loading...
+ 28 hidden pages