Coleman P-LBX16F14501, P-LBX20F19001 Installation Instructions Manual

INSTALLATION
INSTRUCTIONS
CONTENTS
INTRODUCTION.....................................................2
HEAT LOSS............................................................2
LOCATION OF UNIT..............................................2
AIR CONDITIONING...............................................3
COMBUSTION AIR.................................................3
CHIMNEY VENTING............................................... 3
OIL TANK ...............................................................6
PIPING INSTALLATION......................................... 6
ELECTRICAL CONNECTIONS.............................. 6
CIRCULATING AIR BLOWER...............................7
OIL BURNER.......................................................... 8
FURNACE INSTALLATION SET-UP..................... 9
MAINTENANCE AND SERVICE............................ 9
TABLE A-4: DIRECT DRIVE BLOWER
TABLE A-5: BELT DRIVE BLOWER
R7184 DETAILED SEQUENCE OF OPERATION
(FIGURE 7) .............................................................14
TABLE C-3: SYSTEM AND GENERAL
TROUBLESHOOTING............................................ 19
OIL-FIRED WARM AIR
FURNACE
P-LBX16F14501 P-LBX20F19001
(Lowboy Models)
1
Read this manual completely before beginning installation. Important: These instructions must be kept with the furnace for future reference.
IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE FUEL SUPPLIER.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THESE INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO: BUILDING, ELECTRICAL AND MECHANICAL CODES.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners or other painting materials and compounds.
4. Paper bags, boxes, or other paper or cardboard products.
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
DO NOT USE GASOLINE, CRANKCASE OIL, OR ANY OTHER OIL CONTAINING GASOLINE AS A FUEL FOR THIS FURNACE.
Please read these instructions completely and carefully before installing and operating the furnace.
The furnace must be installed and set up by a qualified contractor.
Model P*LBX16F14501 is a rear-breech lowboy model with an output range of 130,000 to 143,000 BTUH. Model P*LBX20F19001 is a rear-breech lowboy model with an output range of 168,000 to 188,000 BTUH.
All models are listed with the Canadian Standards Association, (CSA), and comply with the standards of both the United States and Canada for use with No. 1 (Stove) and No. 2 (Furnace) Oil.
In the United States, the installation of the furnace and related equipment shall be installed in accordance with the regulations of NFPA No. 31, Installation of Oil Burning Equipment, as well as in accordance with local codes.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in accordance with local codes.
When installation or application questions arise, regulations prescribed in the National Codes and Local Regulations take precedence over the general instructions provided with this installation manual. When in doubt, please consult your local authorities.
The P*LBX16F14501 model is shipped assembled, pre-wired, and ready for lowboy furnace applications. The P*LBX16F14501 model is air conditioning ready. The furnace should be carefully inspected for damage when being unpacked.
INTRODUCTION
The P*LBX20F19001 is shipped in two pieces, a furnace section and a blower section, and must be assembled at the installation site. Some field wiring is required. The P*LBX20F19001 is shipped as a heating only furnace; however, air conditioning may be added with the addition of field-installed controls.
HEAT LOSS
To determine the correct furnace and firing rate for an application, it is necessary to calculate the maximum hourly heat loss of the building based on local design conditions. In new construction, the heat loss should be calculated on a room-by-room basis to enable proper sizing of the trunk and branch ductwork. In retrofit applications, a building shell (overall) heat loss calculation may be used.
In the United States, Manual J. "Load Calculation Conditioning Contractors of America, (ACCA), describes a suitable procedure for calculating the maximum hourly heat loss.
In Canada, the maximum hourly heat loss may be calculated in accordance with the procedures described in the manuals of the Heating, Refrigeration and Air Conditioning Institute (HRAI), or by other method prescribed by authorities having jurisdiction that are suitable for local conditions.
" published by the Air
titled,
LOCATION OF UNIT
The furnace should be located such that the flue connection to the chimney is short, direct and consists of as few elbows as possible. When possible, the unit should be centralized with respect to the supply and return air ductwork. A central location minimizes the trunk duct sizing.
Minimum installation clearances are listed in Table 1.
NOTE: The recommended installation clearances do not necessarily take into consideration the clearances necessary to replace the air filter or perform other routine maintenance.
2
Table 1: Clearance to Combustibles
Furnace P*LBX Location Upflow Top 3 in. Bottom 0 in. S/A Plenum 0 in. Rear 1 in.1 Sides 6 in.2 Front 24 in. Flue Pipe 9 in.3 Enclosure Standard
1
24” Required for Service
2
18” Required on one Side for
access to rear
3
18” in USA
NON-SUSPENDED INSTALLATION
Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requires a clearance of 1 inch. This can be done by using a noncombustible material such as one inch thick channel iron or similar material. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. Use shims made of noncombustible material.
SUSPENDED INSTALLATION
Maintain clearances to combustibles as outlined in Table 1. The furnace may be suspended by field fabricating a cradle of angle iron and threaded rod. Secure the furnace with 2 inch minimum slotted angle or equivalent. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Position the supports so as to not interfere with accessing the burner and blower compartments. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot.
AIR CONDITIONING
If the furnace is used in conjunction with air conditioning, the furnace shall be installed in parallel with or upstream from the evaporator coil to avoid condensation in the heat exchanger. In a parallel installation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifically approved for such service.
Generally, a six-inch clearance between the air conditioning evaporator coil and the heat exchanger will provide adequate airflow through the evaporator coil.
The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evaporator coil. Refer to Appendix B for recommended wiring and electrical connections of the air conditioning controls.
COMBUSTION AIR
When a furnace is installed in the full basement of a typical frame or brick house, infiltration is normally adequate to provide air for combustion and draft operation. If the furnace is installed in a closet or utility room, two (2) ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bathroom). One opening shall be located 6" from the top and bottom of the enclosure at the front of the furnace. For furnaces located in buildings of unusually tight construction, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. Size all of the openings and associated ductwork by the standards provided in the latest Oil Installation Code editions; NFPA 31 in the United States, CAN/CSA B139 in Canada. Take all fuel burning appliances in the area into consideration when calculating combustion and ventilation air requirements.
CHIMNEY VENTING
The chimney must be sized correctly and be in good repair. If the chimney is oversized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.
If the chimney serves the P*LBX16F14501 furnace only, the vent should be sized at 4-inch minimum, 6­inch maximum. If the chimney serves the P*LBX20F19001 furnace only, the vent should be sized at 5-inch minimum, 7­inch maximum. The data provided in Table 3 is based on dedicated venting. If the furnace is to be co-vented with other appliances, refer to NFPA 211, Standard
for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, NFPA 31, Standard for the Installation of Oil Burning Equipment or CAN/CSA B139, Installation Code For Oil Burning Equipment for correct sizing information.
NOTE: This furnace is approved for use with L-Vent.
NOTE: Maximum temperature for L­Vent is 575°F (300°C).
IMPORTANT: The chimney must be
capable of providing sufficient draft at all times for the safe removal of the products of combustion.
The chimney should be tested under “winter” conditions; doors and windows closed, all other fossil fuel burning appliances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot overcome the competition for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re-evaluate the availability of combustion and ventilation air, and take corrective action.
3
The flue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch to the foot. The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace. The flue pipe may be reduced in size to fit a smaller diameter chimney with the use of a tapered reducer fitting at the chimney inlet. The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
See Figure 2 and Table 2 for common chimney problems and their remedies.
THE FURNACE MUST BE CONNECTED TO A FLUE HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE APPLIANCE.
The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deterioration during the annual inspection and servicing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment. In Canada, refer to the latest edition of CAN/CSA B139 for rules governing the installation of oil burning equipment.
DRAFT REGULATOR CONTROL
This device is used in conjunction with conventional chimney venting. This control (or draft regulator) automatically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, must be installed within the same room or enclosure as the furnace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters from the furnace breeching and installed in accordance to the instructions supplied with the regulator.
4
Fig. 2: Common Chimney Problems
Table 2: Common Chimney Problems
Refer to Figure 2
Key Trouble Diagnostic Remedy
Top of chimney lower than
A
surrounding objects
Chimney Cap
B
or ventilator.
Coping restricts
C
opening.
Observation
Observation Remove
Observation
Extend chimney above all surrounding objects within 30 feet.
Make opening as large as inside of chimney.
D
E
F
G
H Offset
I
J
K
L
M
Obstruction in chimney
Joist protruding into chimney.
Break in chimney lining.
Collection of soot at narrow space in flue opening.
Two or more openings to the same chimney.
Loose-seated pipe in flue opening.
Smoke pipe extends into chimney.
Failure to extend the length of flue partition to the floor.
Loose-fitted clean-out door.
Can be found by light and mirror reflecting conditions in chimney.
Lowering a light on an extension cord.
Smoke test ­build smudge fire blocking off other opening, watching for smoke to escape.
Lower light on extension cord.
Lower light on extension cord.
Found by inspection from basement.
Smoke test.
Measurement of pipe from within or observation of pipe by means of a lowered light.
By inspection or smoke test.
Smoke test.
Use weight to break and dislodge.
Must be handled by competent masonry contractor.
Must be handled by competent masonry contractor.
Clean out with weighted brush or bag of loose gravel on end of line.
Change to straight or to long offset.
The least important opening must be closed, using some other chimney flue.
Cementing all pipe openings should eliminate leaks.
Length of pipe must be reduced to allow end of pipe to be flush with inside of tile.
Extend partition to floor level.
Close all leaks with cement.
5
Table 3: Minimum Chimney Base
Temperatures (°F)
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance < R6
0.50 300 400 535 725
0.65 275 340 430 535
0.75 260 320 380 475
0.85 250 300 355 430
1.00 245 300 355 430
1.10 245 290 345 400
1.20 240 275 320 365
1.50 240 275 320 365
1.65 235 270 300 345
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance > R6
0.50 185 200 220 250
0.65 175 185 205 220
0.75 175 185 195 210
0.85 165 185 195 205
1.00 165 185 195 205
1.10 165 185 195 205
1.20 165 180 190 200
1.50 165 175 185 195
1.65 165 175 180 190
< - less than, > - greater than
OIL TANK
Oil storage tanks must be selected and installed in compliance with applicable codes; in the United States, NFPA 31,
Standard for the Installation of Oil Burning Equipment, Chapter 2. and in Canada, CAN/CSA-B139, Installation Code for Oil Burning Equipment, Section
6. Observe all local codes and by-laws. In general, the oil tank must be properly
supported and remain stable in both empty and full condition. The oil tank must be fitted with vent and supply pipes to the outdoors. Refer to the above­mentioned codes for sizing. The vent pipe must be no less than 1¼ inches I.P.S., and terminate with an appropriate vent cap in a location where it will not be blocked. The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery.
If located indoors, the tank should normally be in the lowest level, (cellar, basement, etc.). It must be equipped with a shut-off valve at the tank outlet used for the oil supply. The oil tank must be located as to not block the furnace / room exit pathway. Observe all clearances specified in the above­mentioned codes.
PIPING INSTALLATION
In the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment, Chapter 2.
In Canada, the entire fuel system should be installed in accordance with the requirements of CAN/CSA B139, and local regulations. Use only approved fuel oil tanks piping, fittings and oil filters.
Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do not use compression fittings.
Do not use Teflon tape on any fittings. Pressurized or gravity feed installations
must not exceed 3 PSIG. Pressures greater than 10 PSIG may cause damage to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds 11½ feet, it may be necessary to use a pressure-regulating device approved for this purpose.
The furnace may be installed with a one­pipe system with gravity feed or lift. The maximum allowable lift on a single line system is 8 feet. Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting, bend and component in the line. In general, keep single line systems short as possible. 2­stage oil pumps are not available for P*LBX furnaces. The following chart shows the allowable line lengths (horizontal + vertical) for single and two­line oil piping systems. All distances are in feet.
Table 4: Oil Lines
Copper Tubing Oil Line Length (Feet)
Lift
(Feet)
0 53 100 68 100 1 49 100 65 100 2 45 100 63 100 3 41 100 60 100 4 37 100 58 100 5 33 100 55 100 6 29 100 53 100 7 25 99 50 100 8 21 83 48 100
9 17 68 45 100 10 13 52 42 100 12 - - - - - - 37 100 14 - - - - - - 32 100 16 - - - - - - 27 100 18 - - - - - - 22 88
Single-Pipe Two-Pipe
3/8”
OD
1/2”
OD
3/8”
OD
1/2”
OD
In retrofit applications, where an existing oil line system is in place, a vacuum check will help determine the efficacy of the existing oil line system The vacuum in a system should not exceed 6” Hg. for a single pipe system, nor 12” Hg. for a two-pipe system.
NOTE: The oil burner requires the use of a bypass plug when converting from single-pipe to two-pipe oil piping systems. See burner manufacturer’s instructions.
All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. For best results, install the oil filter as close to the burner as possible. When using an indoor oil tank, the oil filter may be installed at the tank downstream from the shut-off valve. If firing the furnace under the 0.65 gph rate, a 7 to 10 micron line filter should be installed as close to the oil burner as possible.
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association (CSA). All models except for the P*LBX20F19001 are factory wired and require minimal field wiring. The P*LBX20F19001 model is pre-wired except for the wiring connections to the blower motor. The wires from the furnace section are routed through the grommet in the blower section blower division panel, and then connected to the blower motor. In the United States, the wiring must be in
6
accordance with the National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations. In Canada, all field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail.
The furnace should be wired to a separate and dedicated circuit in the main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device.
The power requirements for all models: 120 VAC, 1 , 60 Hz.
Maximum fuse size for the P*LBX16F14501 model: 15 amps. Maximum fuse size for the P*LBX20F19001 model: 20 amps.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the furnace circuit. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto­generating windings of the direct drive motor.
Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring diagrams. Some micro-electronic thermostats require additional controls and wiring. Refer to the thermostat manufacturer's instructions.
The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
Normal heat anticipator setting for the P*LBX models is 0.1 A. For more precise adjustment, the heat anticipator may be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure circuit without first removing one of the two wires first. To determine the heating circuit amperage draw:
1. Disconnect one of the “R” or “W” wires from the thermostat terminal.
2. Connect an ammeter between the wire and the thermostat terminal to which it was attached.
3. Note the amperage reading when the heating contacts are closed. (System switch must be on “
HEAT” if
so equipped.
4. Re-connect the thermostat wire. If the thermostat is serving a combination heating and air conditioning system, pay particular attention to polarity.
5. When the thermostat is reconnected and re-plumbed, adjust the heat anticipator setting to match the observed amperage reading.
CIRCULATING AIR BLOWER
The P*LBX16F14501 furnace models are equipped with a direct drive blower system. Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. The motor RPM and air CFM delivery will vary automatically to accommodate conditions within the usual range of external static pressures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over- amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem.
Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagram in Appendix B or the wiring diagram label affixed to the furnace. THE NEUTRAL WIRE
(normally the white wire) IS NEVER
MOVED TO ADJUST THE BLOWER SPEED.
DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DESIGNATED NEUTRAL TERMINAL.
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape.
If the joining of the blower speed wiring is done in the furnace junction box, tape off both ends of the unused wire.
The P*LBX20F19001 furnace model is equipped with a belt drive blower system. The blower speed (RPM) and resultant airflow can be varied by adjusting the variable speed motor pulley.
DISCONNECT THE POWER SUPPLY TO THE FURNACE BEFORE OPENING THE BLOWER ACCESS DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURE TO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECTEDLY, CREATING A RISK OF DEATH OR PERSONAL INJURY.
Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformers. The unused motor taps auto-generate sufficiently high voltages to damage accessory equipment.
Do not start the burner or blower fan unless the blower access door is securely in place.
7
OIL BURNER
P*LBX furnaces are equipped with Beckett AF Series oil burners with the Beckett CleanCut pump and R7184B oil primary control. The oil burner must align properly with combustion chamber (firepot). The combustion chamber is initially quite soft, but hardens and becomes quite brittle after the first firing. The firepot is held in place by a retaining bracket; however, it is possible for the firepot to shift if subjected to rough handling during transit.
BEFORE OPERATING THE FURNACE CHECK BURNER ALIGNMENT WITH COMBUSTION CHAMBER. THE END CONE OF THE AIR TUBE MUST BE CENTRED TO THE ACCOMODATING RING PROVIDED IN THE DESIGN OF THE COMBUSTION CHAMBER. ADJUST ALIGNMENT AS NECESSARY BEFORE THE FIRST FIRING.
OIL BURNER NOZZLES
All furnace models are certified for multiple firing rates. Choose the firing rate that most closely matches the calculated heat loss of the building. Models, firing rates and nozzles are listed in Table A-1.
BURNER ELECTRODES
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation. The electrode tips should be
adjusted to a gap of 5/32”, 1/16” ahead of the nozzle, 5/16” above the centerline of the nozzle. The “Z” dimension (front edge of the burner head to the front face of the nozzle is 1-1/8 inches.
Electrode positioning should be checked before the first firing of the furnace.
The electrode porcelains should be free of cracks, the electrode tips should be tapered and free of burrs, and the contact rods must be clean and be in firm contact with the ignition transformer contact springs. The electrodes must not come into contact with the burner head.
OIL BURNER SET-UP
The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack of air causes "soft" and "sooty" flames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency.
PREPARATIONS: Drill a 1/4” test port in the venting, ideally
at least 2 flue pipe diameters away from the furnace breeching, if venting horizontally from the furnace, (typically P*LBX) or from the flue pipe elbow if venting vertically before reaching the furnace. (see Figures 4 and 5).
The test port will allow flue gas samples to be taken and stack temperatures to be measured.
Before starting the burner, check the burner alignment with the combustion chamber (fire pot), check that the correct
nozzle is tightened into place, and that the burner electrodes are properly positioned.
The Beckett burner bulk air band should be closed, and the air shutter initial setting should be approximately 7.00.
Note A: Locate hole at least 6 inches on the furnace side of the draft control.
Note B: Ideally, hole should be at least 12 inches from breeching or elbow.
PROCEDURE:
Start the burner and allow it to run at least ten minutes. Set the air shutter to give a good flame visually. The combustion air supply to the burner is controlled by adjusting the air shutter on the left side of the burner, and, if necessary, the bulk air band. To adjust, loosen the bolt on the movable shutter. Move the shutter gradually until a good flame (visually) has been achieved. Re­snug the bolt.
Check the initial draft setting as the furnace warms up. The draft may be measured at the test port. The final breech draft should be - 0.02 inches W.C. to provide adequate over-fire draft.
Check the oil pump pressure. Standard operating pressure is 100 PSIG.
After reaching steady state, take a smoke test. If not indicating a trace, set the combustion air controls to provide a trace.
Typically, the CO
reading will range
2
from 11.5% to 13.5%. After the air adjustments have been
completed, and the air shutter or air
Fig. 4: Horizontal Smoke Test Port Location
8
Fig. 5: Vertical Smoke Test Port Location
adjustment plate has been secured, re­check the breech draft and take another smoke test to ensure that the values have not changed.
SMOKE TEST NOTE: If oily or yellow smoke spots are found
on the smoke test filter paper, it is usually a sign of unburned fuel. This indicates poor combustion. This type of problem may be caused by excess draft, excess air, or contaminated fuel. Do not ignore this indicator.
STACK TEMPERATURE: Stack temperature will vary depending
on fuel input, circulating air blower speed, and burner set up, etc. In general, stack temperature should typically range between 380°F to 550°F , assuming that the combustion air is approximately room temperature (65°F ­70°F). In general, lower stack temperature indicates greater efficiency; however, excessively low stack temperature can lead to condensation forming in the chimney and / or venting. Sulphur and similar contaminants in the fuel oil will mix with condensation to form acids. Acids and resultant chemical salts will cause rapid deterioration of the chimney and venting components, and may attack the furnace.
If the flue gases are below the range, it may be necessary to slow down the blower fan. If the flue gases are above the range, the blower fan may require speeding up. Stack temperature varies directly with the system temperature rise. System temperature rise is the difference between the furnace outlet temperature and furnace inlet temperature as measured in the vicinity of the connection between the plenum take-offs and the trunk ducts. Temperature rise is indicated on the furnace rating plate.
If the venting from the furnace to the chimney is long, or exposed to cold ambient temperatures, it may be necessary to use L-Vent as the vent connector to reduce stack temperature loss to prevent condensation. The venting should be inspected annually to ensure that it is intact.
FURNACE INSTALLATION SET-UP
The furnace must be set up as the final step in the installation.
A) The oil burner must be set up following the procedures outlined above.
B) To determine the temperature rise, measure the supply air and return air temperatures when the furnace has
reached steady state conditions. This is the point at which the supply air temperature stops increasing relative to the return air temperature. The furnace may have to run 10 to 15 minutes to reach steady state conditions. The measurements may be made with duct thermometers or thermocouples used in conjunction with multi-meters with temperature measurement capabilities.
The return air should be measured at a point where the thermometer will be well within the air stream near the furnace return air inlet. Actual location is not particularly critical; however, avoid locations where the temperature readings could be affected by humidifier bypass ducts, the inside radius of elbows, etc.
The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet. Usually, the side mid-point of the supply air plenum take-off is ideal, providing it is out of the line of sight to the heat exchanger. If the thermometer is within the line of sight of the heat exchanger, the supply air readings may be skewed by radiant heat from the heat exchanger. If the plenum take-off is unsuitable, the supply air temperature may be measured within the first 18 inches of the first segment of supply air trunk duct.
If the temperature rise is outside the recommended range, it may be adjusted on direct drive equipped units by selecting alternate circulation fan motor speeds, on belt drive equipped units by adjusting the variable speed motor pulley. If the temperature rise is too high, speed the fan up. If the temperature rise is too low, slow the fan down.
C) Keep in mind that the stack temperature varies directly with the temperature rise. The higher the temperature rise, the higher the stack temperature will be, resulting in lower efficiency. The lower the temperature rise, the lower the stack temperature will be, which, in some cases, may allow condensation to form in the chimney and other vent parts.
D) Test the high l imit control to ensure that it is operating correctly. For direct drive equipped units, this may be done by temporarily removing the circulator fan heating wire or neutral wire. For belt drive equipped units, temporarily remove the fan belt. Turn of electrical power to the furnace before working with the motor wires or fan belt. Be sure to protect any removed wires from shorting
out on metal furnace parts. If the high limit test is successful, shut off the electrical power to the furnace, restore the proper motor wiring. Finally, restore power to the furnace.
E) Adjust the “Fan Off” setting on the L6064A or L4064W fan limit controller. In most cases, the “Fan Off” temperature should be 90° to 100°F as indicated on the thermometer used to measure the supply air temperature. Once the “Fan Off” setting has been established, set the “Fan On” setting. In most cases, the “Fan On” setting should be approximately 30°F higher than the Fan Off” setting.
F) Operate the furnace through a minimum of three full heating cycles. During this time, check for fuel oil leaks, gross air leakage from the supply air ductwork, unusual noises originating anywhere within the heating system which may cause some concern or annoyance to the home owner, etc.
G) Be sure that the homeowner is familiar with the furnace. The homeowner should be aware of the location of electrical circuit breaker or fuse, the location of any electrical switches controlling the furnace, the location of the oil tank shut-off valve and how to operate the valve. The homeowner should be informed where the oil tank gauge is located and how to read it.
It would be beneficial to review safety issues with the home owner, such as the danger of storing combustibles too close to the furnace, hanging anything on the furnace vent pipe, and especially the dangers of indiscriminately pressing the burner reset button.
IMPORTANT: Be sure that the home owner knows where the burner reset switch is located, and is aware that the reset switch is not to be activated more than once without a thorough look for the cause of the problem, (lack of fuel, etc.). Be sure that the homeowner knows when to quit trying to start the furnace during these conditions and who to call for emergency service.
MAINTENANCE AND SERVICE
A: Routine Maintenance By Home Owner
Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation contractor, the most important routine service performed by the homeowner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat,
9
Loading...
+ 19 hidden pages