Read this manual completely before beginning
installation.
Important: These instructions must be kept with
the furnace for future reference.
IMPROPER INSTALLATION MAY
CREATE A CONDITION WHERE THE
OPERATION OF THE PRODUCT
COULD CAUSE PERSONAL INJURY
OR PROPERTY DAMAGE.
IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY
DAMAGE. REFER TO THIS MANUAL
FOR ASSISTANCE OR ADDITIONAL
INFORMATION, CONSULT A
QUALIFIED INSTALLER, SERVICE
AGENCY OR THE FUEL SUPPLIER.
THIS PRODUCT MUST BE INSTALLED
IN STRICT COMPLIANCE WITH THESE
INSTALLATION INSTRUCTIONS AND
ANY APPLICABLE LOCAL, STATE,
AND NATIONAL CODES INCLUDING
BUT NOT LIMITED TO: BUILDING,
ELECTRICAL AND MECHANICAL
CODES.
The furnace area must not be used as a
broom closet or for any other storage
purposes, as a fire hazard may be
created. Never store items such as the
following on, near or in contact with the
furnace:
1. Spray or aerosol cans, rags,
brooms, dust mops, vacuum
cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or
other cleaning compounds; plastic
items or containers, gasoline,
kerosene, cigarette lighter fluid, dry
cleaning fluids, or other volatile
fluids.
3. Paint thinners or other painting
materials and compounds.
4. Paper bags, boxes, or other paper
or cardboard products.
Never operate the furnace with the
blower door removed. To do so could
result in serious personal injury and/or
equipment damage.
DO NOT USE GASOLINE,
CRANKCASE OIL, OR ANY OTHER
OIL CONTAINING GASOLINE AS A
FUEL FOR THIS FURNACE.
Please read these instructions
completely and carefully before installing
and operating the furnace.
The furnace must be installed and set up
by a qualified contractor.
Model P*LBX16F14501 is a rear-breech
lowboy model with an output range of
130,000 to 143,000 BTUH. Model
P*LBX20F19001 is a rear-breech lowboy
model with an output range of 168,000 to
188,000 BTUH.
All models are listed with the Canadian Standards Association, (CSA), and
comply with the standards of both the
United States and Canada for use with
No. 1 (Stove) and No. 2 (Furnace) Oil.
In the United States, the installation of
the furnace and related equipment shall
be installed in accordance with the
regulations of NFPA No. 31, Installation of Oil Burning Equipment, as well as in
accordance with local codes.
In Canada, the installation of the furnace
and related equipment shall be installed
in accordance with the regulations of
CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in
accordance with local codes.
When installation or application
questions arise, regulations prescribed in
the National Codes and Local
Regulations take precedence over the
general instructions provided with this
installation manual. When in doubt,
please consult your local authorities.
The P*LBX16F14501 model is shipped
assembled, pre-wired, and ready for
lowboy furnace applications. The
P*LBX16F14501 model is air
conditioning ready. The furnace should
be carefully inspected for damage when
being unpacked.
INTRODUCTION
The P*LBX20F19001 is shipped in two
pieces, a furnace section and a blower
section, and must be assembled at the
installation site. Some field wiring is
required. The P*LBX20F19001 is
shipped as a heating only furnace;
however, air conditioning may be added
with the addition of field-installed
controls.
HEAT LOSS
To determine the correct furnace and
firing rate for an application, it is
necessary to calculate the maximum
hourly heat loss of the building based on
local design conditions. In new
construction, the heat loss should be
calculated on a room-by-room basis to
enable proper sizing of the trunk and
branch ductwork. In retrofit applications,
a building shell (overall) heat loss
calculation may be used.
In the United States, Manual J.
"Load Calculation
Conditioning Contractors of America,
(ACCA), describes a suitable procedure
for calculating the maximum hourly heat
loss.
In Canada, the maximum hourly heat
loss may be calculated in accordance
with the procedures described in the
manuals of the Heating, Refrigeration
and Air Conditioning Institute (HRAI), or
by other method prescribed by
authorities having jurisdiction that are
suitable for local conditions.
" published by the Air
titled,
LOCATION OF UNIT
The furnace should be located such that
the flue connection to the chimney is
short, direct and consists of as few
elbows as possible. When possible, the
unit should be centralized with respect to
the supply and return air ductwork. A
central location minimizes the trunk duct
sizing.
Minimum installation clearances are
listed in Table 1.
NOTE: The recommended installation
clearances do not necessarily take into
consideration the clearances necessary
to replace the air filter or perform other
routine maintenance.
2
Table 1: Clearance to
Combustibles
Furnace P*LBX
Location Upflow
Top 3 in.
Bottom 0 in.
S/A Plenum 0 in.
Rear 1 in.1
Sides 6 in.2
Front 24 in.
Flue Pipe 9 in.3
Enclosure Standard
1
24” Required for Service
2
18” Required on one Side for
access to rear
3
18” in USA
NON-SUSPENDED INSTALLATION
Maintain clearances to combustibles as
outlined in Table 1. Installation on a
combustible floor requires a clearance of
1 inch. This can be done by using a
noncombustible material such as one
inch thick channel iron or similar
material. The furnace must be supported
in such a way as to not allow twisting or
sagging of the cabinet. Suggestion; as a
measure to prevent fuel oil from
accumulating in locations other than the
fire pot, as could be the case in the event
of nozzle drip, install the furnace with an
approximate 2 degree slope from the oil
burner casing towards the fire pot. Use
shims made of noncombustible material.
SUSPENDED INSTALLATION
Maintain clearances to combustibles as
outlined in Table 1. The furnace may be
suspended by field fabricating a cradle of
angle iron and threaded rod. Secure the
furnace with 2 inch minimum slotted
angle or equivalent. The furnace must be
supported in such a way as to not allow
twisting or sagging of the cabinet.
Position the supports so as to not
interfere with accessing the burner and
blower compartments. Suggestion; as a
measure to prevent fuel oil from
accumulating in locations other than the
fire pot, as could be the case in the event
of nozzle drip, install the furnace with an
approximate 2 degree slope from the oil
burner casing towards the fire pot.
AIR CONDITIONING
If the furnace is used in conjunction with
air conditioning, the furnace shall be
installed in parallel with or upstream from
the evaporator coil to avoid condensation
in the heat exchanger. In a parallel
installation, the dampers or air controlling
means must prevent chilled air from
entering the furnace. If the dampers are
manually operated, there must be a
means of control to prevent the operation
of either system unless the dampers are
in the full heat or full cool position. The
air heated by the furnace shall not pass
through a refrigeration unit unless the
unit is specifically approved for such
service.
Generally, a six-inch clearance between
the air conditioning evaporator coil and
the heat exchanger will provide adequate
airflow through the evaporator coil.
The blower speed must be checked and
adjusted to compensate for the pressure
drop caused by the evaporator coil.
Refer to Appendix B for recommended
wiring and electrical connections of the
air conditioning controls.
COMBUSTION AIR
When a furnace is installed in the full
basement of a typical frame or brick
house, infiltration is normally adequate to
provide air for combustion and draft
operation. If the furnace is installed in a
closet or utility room, two (2) ventilation
openings must be provided connecting to
a well ventilated space (full basement,
living room or other room opening
thereto, but not a bedroom or bathroom).
One opening shall be located 6" from the
top and bottom of the enclosure at the
front of the furnace. For furnaces located
in buildings of unusually tight
construction, such as those with high
quality weather stripping, caulking,
windows and doors, or storm sashed
windows, or where basement windows
are well sealed, a permanent opening
communicating with a well ventilated
attic or with the outdoors shall be
provided, using a duct if necessary. Size
all of the openings and associated
ductwork by the standards provided in
the latest Oil Installation Code editions;
NFPA 31 in the United States, CAN/CSA
B139 in Canada. Take all fuel burning
appliances in the area into consideration
when calculating combustion and
ventilation air requirements.
CHIMNEY VENTING
The chimney must be sized correctly and
be in good repair. If the chimney is
oversized, there is a high risk of the flue
gases condensing resulting in damage to
the chimney and other venting parts.
This problem may be corrected by the
use of an appropriately sized chimney
liner.
If the chimney serves the
P*LBX16F14501 furnace only, the vent
should be sized at 4-inch minimum, 6inch maximum. If the chimney serves the
P*LBX20F19001 furnace only, the vent
should be sized at 5-inch minimum, 7inch maximum. The data provided in
Table 3 is based on dedicated venting. If
the furnace is to be co-vented with other
appliances, refer to NFPA 211, Standard
for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances, NFPA 31, Standard for the Installation of Oil
Burning Equipment orCAN/CSA B139,
Installation Code For Oil Burning
Equipment for correct sizing information.
NOTE: This furnace is approved for
use with L-Vent.
NOTE: Maximum temperature for LVent is 575°F (300°C).
IMPORTANT: The chimney must be
capable of providing sufficient draft at all
times for the safe removal of the
products of combustion.
The chimney should be tested under
“winter” conditions; doors and windows
closed, all other fossil fuel burning
appliances on, clothes dryer on,
bathroom fans on, etc. If the chimney
cannot overcome the competition for air,
it will be necessary to access the reason
for it, and take corrective action. If the
chimney is found to be sized correctly
and in good repair, it will probably be
necessary to re-evaluate the availability
of combustion and ventilation air, and
take corrective action.
3
The flue pipe should be as short as
possible with horizontal pipes sloping
upward toward the chimney at a rate of
one-quarter inch to the foot. The flue
pipe should not be smaller in cross
sectional area than the flue collar on the
furnace. The flue pipe may be reduced in
size to fit a smaller diameter chimney
with the use of a tapered reducer fitting
at the chimney inlet. The flue pipe should
connect to the chimney such that the flue
pipe extends into, and terminates flush
with the inside surface of the chimney
liner. Seal the joint between the pipe and
the lining. The chimney outlet should be
at least two feet above the highest point
of a peaked roof. All unused chimney
openings should be closed. Chimneys
must conform to local, provincial or state
codes, or in the absence of local
regulations, to the requirements of the
National Building Code.
See Figure 2 and Table 2 for common
chimney problems and their remedies.
THE FURNACE MUST BE
CONNECTED TO A FLUE HAVING
SUFFICIENT DRAFT AT ALL TIMES TO
ENSURE SAFE AND PROPER
OPERATION OF THE APPLIANCE.
The flue pipe must not be routed through
concealed space, because it must be
visually checked for signs of
deterioration during the annual
inspection and servicing. The flue pipe
must not pass through any floor or
ceiling, but may pass through a wall
where suitable fire protection provisions
have been installed. In the United States,
refer to the latest edition of NFPA 31 for
regulations governing the installation of
oil burning equipment. In Canada, refer
to the latest edition of CAN/CSA B139
for rules governing the installation of oil
burning equipment.
DRAFT REGULATOR CONTROL
This device is used in conjunction with
conventional chimney venting. This
control (or draft regulator) automatically
maintains a constant negative pressure
in the furnace to obtain maximum
efficiency. It ensures that proper
pressures are not exceeded. If the
chimney does not develop sufficient
draft, the draft control cannot function
properly. The draft regulator, must be
installed within the same room or
enclosure as the furnace, and should not
interfere with the combustion air supplied
to the burner. The control should be
located a minimum of 3 flue pipe
diameters from the furnace breeching
and installed in accordance to the
instructions supplied with the regulator.
4
Fig. 2: Common Chimney Problems
Table 2: Common Chimney Problems
Refer to Figure 2
Key Trouble Diagnostic Remedy
Top of chimney
lower than
A
surrounding
objects
Chimney Cap
B
or ventilator.
Coping restricts
C
opening.
Observation
Observation Remove
Observation
Extend chimney
above all
surrounding
objects within
30 feet.
Make opening
as large as
inside of
chimney.
D
E
F
G
H Offset
I
J
K
L
M
Obstruction in
chimney
Joist protruding
into chimney.
Break in
chimney lining.
Collection of
soot at narrow
space in flue
opening.
Two or more
openings to the
same chimney.
Loose-seated
pipe in flue
opening.
Smoke pipe
extends into
chimney.
Failure to
extend the
length of flue
partition to the
floor.
Loose-fitted
clean-out door.
Can be found
by light and
mirror reflecting
conditions in
chimney.
Lowering a light
on an extension
cord.
Smoke test build smudge
fire blocking off
other opening,
watching for
smoke to
escape.
Lower light on
extension cord.
Lower light on
extension cord.
Found by
inspection from
basement.
Smoke test.
Measurement
of pipe from
within or
observation of
pipe by means
of a lowered
light.
By inspection or
smoke test.
Smoke test.
Use weight to
break and
dislodge.
Must be
handled by
competent
masonry
contractor.
Must be
handled by
competent
masonry
contractor.
Clean out with
weighted brush
or bag of loose
gravel on end
of line.
Change to
straight or to
long offset.
The least
important
opening must
be closed,
using some
other chimney
flue.
Cementing all
pipe openings
should
eliminate leaks.
Length of pipe
must be
reduced to
allow end of
pipe to be flush
with inside of
tile.
Extend partition
to floor level.
Close all leaks
with cement.
5
Table 3: Minimum Chimney Base
Temperatures (°F)
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance < R6
0.50 300 400 535 725
0.65 275 340 430 535
0.75 260 320 380 475
0.85 250 300 355 430
1.00 245 300 355 430
1.10 245 290 345 400
1.20 240 275 320 365
1.50 240 275 320 365
1.65 235 270 300 345
Nozzle
Chimney Height (ft.)
11 20 28 36
Chimney Thermal Resistance > R6
0.50 185 200 220 250
0.65 175 185 205 220
0.75 175 185 195 210
0.85 165 185 195 205
1.00 165 185 195 205
1.10 165 185 195 205
1.20 165 180 190 200
1.50 165 175 185 195
1.65 165 175 180 190
< - less than, > - greater than
OIL TANK
Oil storage tanks must be selected and
installed in compliance with applicable
codes; in the United States, NFPA 31,
Standard for the Installation of Oil
Burning Equipment, Chapter 2. and in Canada, CAN/CSA-B139, Installation
Code for Oil Burning Equipment, Section
6. Observe all local codes and by-laws.
In general, the oil tank must be properly
supported and remain stable in both
empty and full condition. The oil tank
must be fitted with vent and supply pipes
to the outdoors. Refer to the abovementioned codes for sizing. The vent
pipe must be no less than 1¼ inches
I.P.S., and terminate with an appropriate
vent cap in a location where it will not be
blocked. The fill pipe must be no less
than 2 inches I.P.S., and terminate with
an appropriate cap in a location where
debris will not enter the fill pipe during oil
delivery.
If located indoors, the tank should
normally be in the lowest level, (cellar,
basement, etc.). It must be equipped
with a shut-off valve at the tank outlet
used for the oil supply. The oil tank must
be located as to not block the furnace /
room exit pathway. Observe all
clearances specified in the abovementioned codes.
PIPING INSTALLATION
In the United States, NFPA 31, Standard
for the Installation of Oil Burning
Equipment, Chapter 2.
In Canada, the entire fuel system should
be installed in accordance with the
requirements of CAN/CSA B139, and
local regulations. Use only approved fuel
oil tanks piping, fittings and oil filters.
Ensure that all fittings used in a copper
oil line system are high quality flare
fittings. Do not use compression fittings.
Do not use Teflon tape on any fittings.
Pressurized or gravity feed installations
must not exceed 3 PSIG. Pressures
greater than 10 PSIG may cause
damage to the shaft seal. If the height of
the oil stored in a tank above the oil
burner exceeds 11½ feet, it may be
necessary to use a pressure-regulating
device approved for this purpose.
The furnace may be installed with a onepipe system with gravity feed or lift. The
maximum allowable lift on a single line
system is 8 feet. Lift should be measured
from the bottom (outlet) of the tank, to
the inlet of the burner. Sizing a single
line system is complex because of the
difficulty estimating the pressure drop
through each fitting, bend and
component in the line. In general, keep
single line systems short as possible. 2stage oil pumps are not available for
P*LBX furnaces. The following chart
shows the allowable line lengths
(horizontal + vertical) for single and twoline oil piping systems. All distances are
in feet.
In retrofit applications, where an existing
oil line system is in place, a vacuum
check will help determine the efficacy of
the existing oil line system The vacuum
in a system should not exceed 6” Hg. for
a single pipe system, nor 12” Hg. for a
two-pipe system.
NOTE: The oil burner requires the use of
a bypass plug when converting from
single-pipe to two-pipe oil piping
systems. See burner manufacturer’s
instructions.
All fuel systems should include an oil
filter between the fuel oil storage tank
and the oil burner. For best results,
install the oil filter as close to the burner
as possible. When using an indoor oil
tank, the oil filter may be installed at the
tank downstream from the shut-off valve.
If firing the furnace under the 0.65 gph
rate, a 7 to 10 micron line filter should be
installed as close to the oil burner as
possible.
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian
Standards Association (CSA). All models
except for the P*LBX20F19001 are
factory wired and require minimal field
wiring. The P*LBX20F19001 model is
pre-wired except for the wiring
connections to the blower motor. The
wires from the furnace section are routed
through the grommet in the blower
section blower division panel, and then
connected to the blower motor. In the
United States, the wiring must be in
6
accordance with the National Fire
Protection Association NFPA-70,
National Electrical Code, and with local
codes and regulations. In Canada, all
field wiring should conform to CAN/CSA
C22.1 Canadian Electrical Code, Part 1,
and by local codes, where they prevail.
The furnace should be wired to a
separate and dedicated circuit in the
main electrical panel; however,
accessory equipment such as electronic
air cleaners and humidifiers may be
included on the furnace circuit. Although
a suitably located circuit breaker can be
used as a service switch, a separate
service switch is advisable. The service
switch is necessary if reaching the circuit
breaker involves becoming close to the
furnace, or if the furnace is located
between the circuit breaker and the
means of entry to the furnace room. The
furnace switch (service switch) should be
clearly marked, installed in an easily
accessible area between the furnace and
furnace room entry, and be located in
such a manner to reduce the likelihood
that it would be mistaken as a light
switch or similar device.
The power requirements for all models:
120 VAC, 1 ∅, 60 Hz.
Maximum fuse size for the
P*LBX16F14501 model: 15 amps.
Maximum fuse size for the
P*LBX20F19001 model: 20 amps.
Accessories requiring 120 VAC power
sources such as electronic air cleaners
and humidifier transformers may be
powered from the furnace circuit. Do not
use the direct drive motor connections as
a power source, since there is a high risk
of damaging the accessories by
exposure to high voltage from the autogenerating windings of the direct drive
motor.
Thermostat wiring connections and air
conditioning contactor low voltage
connections are shown in the wiring
diagrams. Some micro-electronic
thermostats require additional controls
and wiring. Refer to the thermostat
manufacturer's instructions.
The thermostat should be located
approximately 5 feet above the floor, on
an inside wall where there is good
natural air circulation, and where the
thermostat will be exposed to average
room temperatures. Avoid locations
where the thermostat will be exposed to
cold drafts, heat from nearby lamps and
appliances, exposure to sunlight, heat
from inside wall stacks, etc.
Normal heat anticipator setting for the
P*LBX models is 0.1 A. For more precise
adjustment, the heat anticipator may be
adjusted to the amperage draw of the
heating control circuit as measured
between the "R" and "W" terminals of the
thermostat. To reduce the risk of
damaging the heat anticipator, do not
measure circuit without first removing
one of the two wires first. To determine
the heating circuit amperage draw:
1. Disconnect one of the “R” or “W”
wires from the thermostat terminal.
2. Connect an ammeter between the
wire and the thermostat terminal to
which it was attached.
3. Note the amperage reading when
the heating contacts are closed.
(System switch must be on “
HEAT” if
so equipped.
4. Re-connect the thermostat wire. If
the thermostat is serving a
combination heating and air
conditioning system, pay particular
attention to polarity.
5. When the thermostat is reconnected
and re-plumbed, adjust the heat
anticipator setting to match the
observed amperage reading.
CIRCULATING AIR BLOWER
The P*LBX16F14501 furnace models
are equipped with a direct drive blower
system. Direct drive blower speed
adjustments are not normally required in
properly sized extended plenum duct
systems. The motor RPM and air CFM
delivery will vary automatically to
accommodate conditions within the usual
range of external static pressures typical
of residential duct systems. Under-sized
duct systems may require a higher
blower speed to obtain a reasonable
system temperature rise. Some older
duct systems were not designed to
provide static pressure. They typically
feature special reducing fittings at each
branch run and lack block ends on the
trunk ducts. These systems may require
modification to provide some resistance
to the airflow to prevent over- amping of
the direct drive blower motor. Selecting a
lower blower speed may correct this
problem.
Direct drive blower speeds are adjusted
by changing the "hot" wires to the motor
winding connections. Please refer to
wiring diagram in Appendix B or the
wiring diagram label affixed to the
furnace. THE NEUTRAL WIRE
(normally the white wire) IS NEVER
MOVED TO ADJUST THE BLOWER
SPEED.
DO NOT CONNECT POWER LEADS
BETWEEN MOTOR SPEEDS. THE
NEUTRAL WIRE MUST ALWAYS BE
CONNECTED TO THE MOTOR'S
DESIGNATED NEUTRAL TERMINAL.
It is possible and acceptable to use a
single blower speed for both heating and
cooling modes. The simplest method to
connect the wiring from both modes is to
use a "piggy-back connector"
accommodating both wires on a single
motor tap. It is also acceptable to
connect the selected motor speed with a
pigtail joined to both heating and cooling
speed wires with a wire nut. As a safety
precaution against accidental
disconnection of the wires by vibration, it
is advisable to secure the wire nut and
wires with a few wraps of electricians
tape.
If the joining of the blower speed wiring
is done in the furnace junction box, tape
off both ends of the unused wire.
The P*LBX20F19001 furnace model is
equipped with a belt drive blower
system. The blower speed (RPM) and
resultant airflow can be varied by
adjusting the variable speed motor
pulley.
DISCONNECT THE POWER SUPPLY
TO THE FURNACE BEFORE
OPENING THE BLOWER ACCESS
DOOR TO SERVICE THE AIR FILTER,
FAN AND MOTOR. FAILURE TO
SHUT OFF POWER COULD ALLOW
THE BLOWER TO START
UNEXPECTEDLY, CREATING A RISK
OF DEATH OR PERSONAL INJURY.
Do not use the blower speed wires as
a source of power to accessories as
electronic air cleaners and humidifier
transformers. The unused motor taps
auto-generate sufficiently high
voltages to damage accessory
equipment.
Do not start the burner or blower fan
unless the blower access door is
securely in place.
7
OIL BURNER
P*LBX furnaces are equipped with
Beckett AF Series oil burners with the
Beckett CleanCut pump and R7184B oil
primary control. The oil burner must align
properly with combustion chamber
(firepot). The combustion chamber is
initially quite soft, but hardens and
becomes quite brittle after the first firing.
The firepot is held in place by a retaining
bracket; however, it is possible for the
firepot to shift if subjected to rough
handling during transit.
BEFORE OPERATING THE
FURNACE CHECK BURNER
ALIGNMENT WITH COMBUSTION
CHAMBER. THE END CONE OF THE
AIR TUBE MUST BE CENTRED TO
THE ACCOMODATING RING
PROVIDED IN THE DESIGN OF THE
COMBUSTION CHAMBER. ADJUST
ALIGNMENT AS NECESSARY
BEFORE THE FIRST FIRING.
OIL BURNER NOZZLES
All furnace models are certified for
multiple firing rates. Choose the firing
rate that most closely matches the
calculated heat loss of the building.
Models, firing rates and nozzles are
listed in Table A-1.
BURNER ELECTRODES
Correct positioning of the electrode tips
with respect to each other, to the fuel oil
nozzle, and to the rest of the burners is
essential for smooth light ups and proper
operation. The electrode tips should be
adjusted to a gap of 5/32”, 1/16” ahead
of the nozzle, 5/16” above the centerline
of the nozzle. The “Z” dimension (front
edge of the burner head to the front face
of the nozzle is 1-1/8 inches.
Electrode positioning should be checked
before the first firing of the furnace.
The electrode porcelains should be free
of cracks, the electrode tips should be
tapered and free of burrs, and the
contact rods must be clean and be in
firm contact with the ignition transformer
contact springs. The electrodes must not
come into contact with the burner head.
OIL BURNER SET-UP
The burner air supply is adjusted to
maintain the fuel to airratio to obtain
ideal combustion conditions. A lack of air
causes "soft" and "sooty" flames,
resulting in soot build-up throughout the
heat exchanger passages. Excess
combustion air causes a bright roaring
fire and high stack temperatures
resulting in poor fuel efficiency.
PREPARATIONS:
Drill a 1/4” test port in the venting, ideally
at least 2 flue pipe diameters away from
the furnace breeching, if venting
horizontally from the furnace, (typically
P*LBX) or from the flue pipe elbow if
venting vertically before reaching the
furnace. (see Figures 4 and 5).
The test port will allow flue gas samples
to be taken and stack temperatures to be
measured.
Before starting the burner, check the
burner alignment with the combustion
chamber (fire pot), check that the correct
nozzle is tightened into place, and that
the burner electrodes are properly
positioned.
The Beckett burner bulk air band should
be closed, and the air shutter initial
setting should be approximately 7.00.
Note A: Locate hole at least 6 inches on
the furnace side of the draft control.
Note B: Ideally, hole should be at least
12 inches from breeching or elbow.
PROCEDURE:
Start the burner and allow it to run at
least ten minutes. Set the air shutter to
give a good flame visually. The
combustion air supply to the burner is
controlled by adjusting the air shutter on
the left side of the burner, and, if
necessary, the bulk air band. To adjust,
loosen the bolt on the movable shutter.
Move the shutter gradually until a good
flame (visually) has been achieved. Resnug the bolt.
Check the initial draft setting as the
furnace warms up. The draft may be
measured at the test port. The final
breech draft should be - 0.02 inches
W.C. to provide adequate over-fire draft.
Check the oil pump pressure. Standard
operating pressure is 100 PSIG.
After reaching steady state, take a
smoke test. If not indicating a trace, set
the combustion air controls to provide a
trace.
Typically, the CO
reading will range
2
from 11.5% to 13.5%.
After the air adjustments have been
completed, and the air shutter or air
Fig. 4: Horizontal Smoke Test Port Location
8
Fig. 5: Vertical Smoke Test Port Location
adjustment plate has been secured, recheck the breech draft and take another
smoke test to ensure that the values
have not changed.
SMOKE TEST NOTE:
If oily or yellow smoke spots are found
on the smoke test filter paper, it is
usually a sign of unburned fuel. This
indicates poor combustion. This type of
problem may be caused by excess draft,
excess air, or contaminated fuel. Do not
ignore this indicator.
STACK TEMPERATURE:
Stack temperature will vary depending
on fuel input, circulating air blower
speed, and burner set up, etc. In
general, stack temperature should
typically range between 380°F to 550°F ,
assuming that the combustion air is
approximately room temperature (65°F 70°F). In general, lower stack
temperature indicates greater efficiency;
however, excessively low stack
temperature can lead to condensation
forming in the chimney and / or venting.
Sulphur and similar contaminants in the
fuel oil will mix with condensation to form
acids. Acids and resultant chemical salts
will cause rapid deterioration of the
chimney and venting components, and
may attack the furnace.
If the flue gases are below the range, it
may be necessary to slow down the
blower fan. If the flue gases are above
the range, the blower fan may require
speeding up. Stack temperature varies
directly with the system temperature rise.
System temperature rise is the difference
between the furnace outlet temperature
and furnace inlet temperature as
measured in the vicinity of the
connection between the plenum take-offs
and the trunk ducts. Temperature rise is
indicated on the furnace rating plate.
If the venting from the furnace to the
chimney is long, or exposed to cold
ambient temperatures, it may be
necessary to use L-Vent as the vent
connector to reduce stack temperature
loss to prevent condensation. The
venting should be inspected annually to
ensure that it is intact.
FURNACE INSTALLATION SET-UP
The furnace must be set up as the final
step in the installation.
A) The oil burner must be set up
following the procedures outlined above.
B) To determine the temperature rise,
measure the supply air and return air
temperatures when the furnace has
reached steady state conditions. This is
the point at which the supply air
temperature stops increasing relative to
the return air temperature. The furnace
may have to run 10 to 15 minutes to
reach steady state conditions. The
measurements may be made with duct
thermometers or thermocouples used in
conjunction with multi-meters with
temperature measurement capabilities.
The return air should be measured at a
point where the thermometer will be well
within the air stream near the furnace
return air inlet. Actual location is not
particularly critical; however, avoid
locations where the temperature
readings could be affected by humidifier
bypass ducts, the inside radius of
elbows, etc.
The supply air temperature should be
measured at a point where the
thermometer will be well within the air
stream near the furnace supply air outlet.
Usually, the side mid-point of the supply
air plenum take-off is ideal, providing it is
out of the line of sight to the heat
exchanger. If the thermometer is within
the line of sight of the heat exchanger,
the supply air readings may be skewed
by radiant heat from the heat exchanger.
If the plenum take-off is unsuitable, the
supply air temperature may be measured
within the first 18 inches of the first
segment of supply air trunk duct.
If the temperature rise is outside the
recommended range, it may be adjusted
on direct drive equipped units by
selecting alternate circulation fan motor
speeds, on belt drive equipped units by
adjusting the variable speed motor
pulley. If the temperature rise is too high,
speed the fan up. If the temperature rise
is too low, slow the fan down.
C) Keep in mind that the stack
temperature varies directly with the
temperature rise. The higher the
temperature rise, the higher the stack
temperature will be, resulting in lower
efficiency. The lower the temperature
rise, the lower the stack temperature will
be, which, in some cases, may allow
condensation to form in the chimney and
other vent parts.
D) Test the high l imit control to ensure
that it is operating correctly. For direct
drive equipped units, this may be done
by temporarily removing the circulator
fan heating wire or neutral wire. For belt
drive equipped units, temporarily remove
the fan belt. Turn of electrical power to
the furnace before working with the
motor wires or fan belt. Be sure to
protect any removed wires from shorting
out on metal furnace parts. If the high
limit test is successful, shut off the
electrical power to the furnace, restore
the proper motor wiring. Finally, restore
power to the furnace.
E) Adjust the “Fan Off” setting on the
L6064A or L4064W fan limit controller. In
most cases, the “Fan Off” temperature
should be 90° to 100°F as indicated on
the thermometer used to measure the
supply air temperature. Once the “Fan
Off” setting has been established, set the
“Fan On” setting. In most cases, the “Fan
On” setting should be approximately
30°F higher than the Fan Off” setting.
F) Operate the furnace through a
minimum of three full heating cycles.
During this time, check for fuel oil leaks,
gross air leakage from the supply air
ductwork, unusual noises originating
anywhere within the heating system
which may cause some concern or
annoyance to the home owner, etc.
G) Be sure that the homeowner is
familiar with the furnace. The
homeowner should be aware of the
location of electrical circuit breaker or
fuse, the location of any electrical
switches controlling the furnace, the
location of the oil tank shut-off valve and
how to operate the valve. The
homeowner should be informed where
the oil tank gauge is located and how to
read it.
It would be beneficial to review safety
issues with the home owner, such as the
danger of storing combustibles too close
to the furnace, hanging anything on the
furnace vent pipe, and especially the
dangers of indiscriminately pressing the
burner reset button.
IMPORTANT: Be sure that the home
owner knows where the burner reset
switch is located, and is aware that the
reset switch is not to be activated more
than once without a thorough look for the
cause of the problem, (lack of fuel, etc.).
Be sure that the homeowner knows
when to quit trying to start the furnace
during these conditions and who to call
for emergency service.
MAINTENANCE AND SERVICE
A: Routine Maintenance By Home
Owner
Other than remembering to arrange for
the annual professional servicing of the
furnace by the service or installation
contractor, the most important routine
service performed by the homeowner is
to maintain the air filter or filters. A dirty
filter can cause the furnace to over-heat,
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.