Coleman P*HBX12F08001, P*HBX16F10001, P*LBX12F08001, P*LBX16F12001, P*LBX16F14501 Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTION
OIL-FIRED
WARM AIR FURNACES
Supersedes: 035-14289-000-A-300
035-14289-000-A-1101
P*HB (UPFLOW)
P*DH (DOWNFLOW
HORIZONTAL)
NRTL/C
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COM PLIANCE WITH THE ENCLOSED INSTALLATION IN STRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIM ITED TO, BUILDING, ELECTRICAL AND ME CHANICAL CODES.
P*LB LOWBOY
WARNING
-
-
-
-
IMPROPERINSTALLATIONMAYCREATEACONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance
.
WARNING: Improper installation, adjustment, al teration, service or maintenance can cause injury or property damage. Refer to this manual. For as sistance or additional information,consult a quali fied installer , service agency or the oil supplier.
-
-
-
Page 2
035-14289-000 Rev. A(0701)
TABLE OF CONTENTS
Introduction Heat Loss Unit Location/Clearances Air Conditioning Applications Combustion Air
................................................................
..................................................................
..........................................
................................
..........................................................
Downflow/Horizonal Applications Chimney Venting
.......................................................
Unit Dimensions & Physical Data Barometric Damper Fan / Limit Control Electrical Connections Fuel Oil Piping Oil Filter
.....................................................................
Oil Burner Nozzles Oil Burner Adjustment Oil Burner Electrodes Oil Burner Primary Control Air Blower
..................................................................
Maintenance/Service Operating Instructions Oil Burner Air Adjustment Start Up
...................................................................
Sequence of Operation Check Out
...............................................................
...................................................
.....................................................
...............................................
...........................................................
....................................................
...............................................
................................................
........................................
............................................
...............................................
..........................................
...........................................
..............................
.........................
2 2 2
2-3
3 3 3
4 - 5
6 6 7 7 8 8 8 8 8 8
9 - 9
9
9 10 10 10
IMPORTANT: SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INTRODUCTION
Pleaseread these instructions completely and carefully before installingand operating thefurnace. Please referto the dataon pages 4 & 5 for performance and dimensional data.
In the United States the installation of the furnace and related equipmentshall be installedin accordancewith the regulations ofANSINFPANo. 31 (latestedition), Installation Equipment, as well as in accordance with local codes.
In Canada, the installation of the furnace and related equip­ment shall be installed in accordance with the regulations of CAN/CSA -- B139--M91 (latest edition), Installation Oil Burning Equipment, as well as in accordance with local codes.
Regulations prescribed in the National Codes and Local regu lations takeprecedence over the general instructions provided onthis installation manual. When in doubt,please consult your local authorities.
All models are shipped assembled and pre--wired except model P*LBX20F19001 where the blower section is separate. The blower section is shipped together with the burner section, but must be assembled together during installation. The furnace shouldbecarefully inspectedfordamage whenbeingunpacked.
ofOilBurning
Code For
NOMENCLATURE
P * HB X 12 F 080 01
Voltage Code = 120 - 1 - 60
Nominal capacity
(MBH Output)
Heating Fuel
F = Fuel Oil CFM (x100) Cabinet
X = Non-Standard Product Identifier
HB = Upflow, DH = Downflow / Horizontal LB = Lowboy
Product Generation
May be 1, 2, or 3
Product Category
P = Furnace
HEAT LOSS
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the following manuals.
In the United States ACCA Manual “J”. titled, “Load Calcula tion”published by theAir Conditioning Contractors ofAmerica, describes a suitable procedure for calculating the maximum hourly heat loss.
InCanada, usethe Heating,Refrigeration andAir Conditioning Institute of Canada (HRAI), or by any other method which is suitable for local conditions, provided the results obtained are insubstantial agreement with andnot less than thoseobtained using the procedure described in the manual.
LOCATION OF UNIT
The furnace shouldbe located such that the flue connection to the chimney is short, direct and consists of as few elbows as possible.Whenpossible, theunit shouldbe centralizedwith re spect to the supply and return air duct work. A central location minimizes the trunk duct sizing. .
The minimum installation clearances are listed in Table 1.
-
-
-
TABLE 1 - CLEARANCES TO COMBUSTIBLES (INCHES)
CLEARANCE
FROM
TOP 1
FRONT 24
UPFLOW DOWNFLOW / HORIZONTAL
80 MBH 120 MBH
1
24
SIDES 111111
REAR 1
BOTTOM 0
1 0
S. A. PLENUM 1111131
FLUE PIPE 18* 18* 18* 18* 18* 18* 18*
NOTE: Adquate clearance should be provided over and above these clearances, as required for service access.
* May be 9 inches in Canada
** Elevated on 2-1/2 inch bricks
*** Front clearance required for servicing
2 Unitary Products Group
**** With floor base accessory
80 MBH 120 MBH
LOWBOY
DOWNFLOW HORZ. DOWNFLOW HORZ.
06033 6*** 24 16*** 24 24
Side 1 = 6
Side 2 = 18 111124 0**** 1 0**** 1 0**
Page 3
035-14289-000 Rev. A(0701)
AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air conditioning, the furnace shall be installed in parallel with or upstream from the evaporator coil to avoid condensation in the heat exchanger.
In a parallel installation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the damp ersare manually operated, theremust be a meansof control to prevent the operation of either system unless the dampers are in the full heat or full cool position.
The air heated by the furnace shall not pass through a refrig eration unit unless the unit is specifically approved for such service.
The blower speed must be checked and adjusted to compen satefor the pressure drop causedby the evaporator coil. Refer toPage 12 for recommended wiring andelectrical connections of the air conditioning controls.
COMBUSTION AIR
Ifthefurnaceisinstalled ina closetorutility room,two openings must be provided connecting to a well ventilated space (full basement,living room or other room opening thereto,but not a bedroom or bathroom).
One openingshall be located above the level of the upper vent opening and one opening below the combustion airinletopen ing in the front of the furnace. Each opening shall have a mini mum free area of 1
1
square inches per 1,000 Btu/h of total
2
input rating of all appliances installed in the room. For furnaces located in buildings of unusually tight construc-
tion, such as those with high quality weather stripping, caulk­ing, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary.
1
The duct opening shall have a free area of 1
square inches
2
per 1,000 Btu/h of total input rating of all appliances to be in­stalled. When a furnace is installed in a full basement, infiltra tion is normally adequate to provide air for combustion and draftoperation.Furnace roomsunder 700sq. ft.(65m
3
automatically be treated as confined space.
DOWNFLOW/HORIZONTAL FURNACES
Downflow/horizontal models (P*DHX12F08001 & P* DHX16F12001) are factory shipped for downflow installation.
Downflow
Ifthe furnaceisto beinstalled ina downflowapplication,a com bustible floor base must be used (either 1CB0312, or 1CB0316). Refer to Figure 1.
DOWNFLOW
FURNACE
SUB BASE
ASSEMBLY
COMBUSTIBLE
FLOOR
DUCT
CONNECTION
20-½ X 20-½
1 IN. 1 IN.
FRONT VIEW
FIGURE 1 - DOWNFLOW APPLICATION
COMBUSTIBLE FLOOR BASE
Unitary Products Group 3
1 IN.
SIDE VIEW
) should
1 IN.
-
2" MIN.
SIDE VIEW
-
THREADED ROD 3/8'
NUT
-
END VIEW
WASHER
FURNACE
SLOTTED ANGLE
WASHER
NUT
JAM NUT.
FIGURE 2 - HORIZONTAL SUSPENDED APPLICATION
-
HANGER ARRANGEMENT
-
Horizontal
For applying the furnace in a horizontal left or horizontal right application follow these steps.
1. Rotate the furnace 90 degrees to the desired position.
2. Remove three nuts and washers fastening the oil burner assemblyto thefurnace. Rotatethe oilburner assemblyto an upright position (ignition transformer and/or protector relay control should be on top).
3. Realign the oil burner assembly to the combustion cham-
-
ber(firepot) andthensecure withthreenuts andwashers.
4. Remove the cover from the flue collar.
5. Remove the screws securing the flue collar to the furnace and then rotate the flue collar 90 degrees, such that the venting attaches to the top.
6. Secure the flue collar to the furnace, then reinstall the flue
­collar cover.
7. Horizontal-right applications using model P*DHX12F080
-
alsorequirerelocating thelimit controlto thealternative lo cation near the top of the unit (refer to Figure 2).
For non-suspended horizontal applications, maintain clear ances as shown on Table 1. Installation on a combustible floor requires a clearance of 1". This can be done by using non-­combustibles such as 1" channel iron or similar material. The furnacemust be supported in such a wayto prevent twisting or sagging of the cabinet.
For suspended horizontal applications maintain clearance as shown in Table 3. Remove the four circular knockouts on the top panel and the four knockouts on the bottom panel.
The removedknockoutsallow 3/8" threaded rod to be inserted through the interior of the furnace. Refer to Figure 2.
Use care when inserting rods since the foil backed insulation can be easily ripped and torn. Secure the furnace with 2" mini mum slotted angle or equilavent. The furnace must be sup ported in such a way to prevent sagging or twisting of the cabinet.
-
-
-
-
Page 4
035-14289-000 Rev. A(0701)
TABLE 2 - UNIT DIMENSIONS
MODEL
A
HEIGHTBWIDTH
C
DEPTH
WIDTH DEPTH WIDTH DEPTH HEIGHT DEPTH
DIMENSIONS - INCHES
DEFG
J
SUPPLYAIR BOTTOM RETURN SIDE RETURN
KH
FLUE
CONNECT .
UPFLOW
P*HBX12F08001 49-5/8 22 31 20-1/2 20 14 22 14 22 5 P*HBX16F10001 58-1/4 22 30-3/4 20-1/2 20 14 22 14 22 6
DOWNFLOW / HORIZONTAL SUPPLY AIR RETURN AIR
P*DHX12F08001 51 22 31-1/4 19 19 18 18 5 P*DHX16F12001 62 22-1/4 22-1/4 20-1/2 20-1/2 18 18 6
LOWBOY SUPPLYAIR RETURN AIR
P*LBX12F08001 31 22 43 20-1/2 18-5/8 20-1/2 18-5/8 5 (REAR) P*LBX16F12001 41 22 52-1/2 20-1/2 18-5/8 20-1/2 18-5/8 6 (REAR) P*LBX16F14501 41 22 52-1/2 20-1/2 18-5/8 20-1/2 18-5/8 6 (REAR) P*LBX20F19001 56 26 49 24 22 24 22 7 (REAR)
UPFLOW - MODELS P*HB
* 
, 
C
E
H
)
DOWNFLOW/HORIZONTAL - MODEL P*DH16F12001 (Exposed burner)
* 
, 
0
)
+ 
- 
, 
G
J
K
BOTTOM VIEW
F
DOWNFLOW/HORIZONTAL- MODEL P*DH12F08001
* 
, 
-
0
)
+ 
- 
-
, 
/ 
4 Unitary Products Group
. 
/ 
. 
Page 5
035-14289-000 Rev. A(0701)
PHYSICAL & ELECTRICAL DATA
PUT
1
OIL
RATE
GPH
-
AFUE
%
2
CFM @
.5 IWG
E.S.P.
3
UNIT
AMPS
MAX.
OVER­CURRENT PROTECT.
WIRE
SIZE AWG
BLOWER
SIZE HP TONS NOM.
FILTERS
QTY. &
SIZE
MODEL
HEATINGMBH
INPUT * OUT
UPFLOW
P*HBX12F08001 91 80 .65 82.0 1291 12.0 15 14 10 x 10 1/2 (1) 16 x 25 2, 2­P*HBX16F10001 119 100 .85 82.7 1445 12.0 15 14 10 x 10 1/2 (1) 16 x 25 3, 3-
DOWNFLOW / HORIZONTAL
P*DHX12F08001 91 80 .65 82.0 1291 12.0 15 14 11x 10 1/2 (1) 120x 20 2, 2­P*DHX16F12001 140 120 1.0 80.1 1593 12.0 15 14 11 x 10 1/2 (1) 20 x 20 3, 3-
LOWBOY
P*LBX12F08001 91 80 .65 85.1 1717 12.0 15 14 12 x 9 1/2 (1) 20 x 20 2, 2­P*LBX16F12001 140 120 1.0 83.4 1585 12.0 15 14 12 x12 1/2 (1) 20 x 25 3, 3­P*LBX16F14501 168 145 1.20 83.5 1585 12.0 15 14 12 x 12 1/2 (1) 20 x 25 3, 3­P*LBX20F19001
* Standard input as shipped. See Table 3, Page 8 for alternate firing rates.
1
For Altitudes above 2000 feet, reduce ratings 4% for each 1000 feet above sea level.
2
AFUE (Annual Fuel Utilization Efficiency) determined using DOE test procedure, isolated combustion.
3
Available external static pressure is at furnace outlet and ahead of cooling unit.
231 190 1.65 78.0 2135 12.0 15 14 12 x 12 3/4 (2) 20 x 25
LOWBOY - MODELS P*LBX16F12001, P*LBX16F14501, P*LBX16F19001
ADD-ON
COOLING
1
, 3 1200
2
1
, 4 1600
2
1
, 3 1200
2
1
, 4 1600
2
1
,3, 3-
2
1
, 4 1600
2
1
, 4 1600
2
1
3-
, 4, 5
2
1
,4 1200
2
CFM
2000
* 
, 
)
LOWBOY - MODEL P*LBX12F08001 (Exposed Burner)
B
D
E
2-½
F
H
A
Unitary Products Group 5
8-1/2
C
Page 6
035-14289-000 Rev. A(0701)
W
FAN & LIMIT LOCATION
LEFT HORIZONTAL APPLICATION
FAN & LIMIT LOCATION
AIR FLO
BAROMETRIC DAMPER CONTROL
Thisdevice mustbe usedwith allchimney andTypeLvent sys tems.This control(or draftregulator) automaticallymaintains a constant negative pressure in the furnace to obtain maximum efficiency.Itensuresthatproper pressuresarenot exceeded.
If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, when installed should be in the same room or enclosure as the furnace and should not interfere with the combustion air supplied to the burner.
The control should also be located near the furnace flue outlet and installed according to the instructions supplied with the regulator.The flue outletpressure (measured between the fur nace and draft regulator) should be set to --0.02 in. w.c.
-
-
AIR FLOW
FAN AND LIMIT CONTROL
Upflow & Lowboy Models
The L6064A temperature sensitive fan switch is actuated by a helical bi--metal sensing element enclosed in a metal guard, and controls the circulating air blower. This provides a delay betweenthe burnerignition andblowerstartupto eliminateex
FIGURE 3 - HORIZONTAL APPLICATION
RIGHT HORIZONTAL APPLICATION
FAN/LIMITLOCATION
CAUTION: Fan/limit control location is critical in the P*DHX12F08001 horizontal positions. Tooperate ef­fectively as a high limit control, the fan / limit control mustbeinstalled intheupper position.SeeFigure 3.
CHIMNEY VENTING
The flue pipe should be as short as possible with horizontal pipessloping upward towardthe chimney ata rate of onequar­ter inchtothe foot. The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace.
The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface ofthe chimney liner.Sealthe joint betweenthe pipe andthe lin ing.
The chimney outlet should be at least two feet above the high estpointofapeaked roof.All unusedchimney openingsshould be closed.
Chimneysmust conformtolocal, provincialor statecodes, orin the absence of local regulations, to the requirements of NFPA
2.11(latest edition) Chimney,Fireplaces, Ventsand Solid Fuel Burning Appliances (in Canada CSA B139)..
NOTE: All furnace models are approved for use with Type Lvent or equivalent.
CAUTION: The furnace must be connected to a flue having sufficient draft at all times to ensure safe and proper operation of the appliance.
NOTE: The recommended flue draft pressure is --
0.02in. W.C. (asmeasured upstream of the baromet ric draft regulator).
The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provi sions have been installed. Refer to the latest edition of ANSI NFPA31(in theUnited States,or CAN/CSAB--139 in Canada) for regulations governing the installation of oil burning equip ment.
See Table 4 for burner set-up.
cessive flow of cold air when the blower comes on. Blower shutdownis also delayed toremove any residual heatfrom the heat exchanger and improve the annual efficiency of the fur nace. Fan settings of 120° Fto130°F (50° Cto55° C) and fan settingsof 90° F to 100°F (32° Cto37°C) will usually be satis- factory.
Downflow /Horizontal Models
The L4064W temperature sensitive fan switch contains a heater--wrapped bi--metal to actuate the fan switch independ­entof the temperature atthe helical sensing element.The time fromignition, tothe bloweron functionis approximately30 sec­onds. If after 1 minute, the blower has not come on, replace­mentof the control may be necessary.The blowershutdown is the same as noted for the L6064A control.
Thelimit switchperforms asafety functionandbreaks powerto the oil burner primary control, which shuts off the burner if the
­furnaceover--heats.The limitcontrol isthermally operatedand
automatically resets. The limit control is factory installed, pre--
-
set and is not adjustable. The limit control and fan control are incorporated in the same
housing and are operated by the same thermal element. The downflow furnace utilizes an additional auxiliary limit con
trol which is an automatic reset type.
ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards Association under the NRTL (North American) Standard. It is factory wired and requires minimal field wiring. All field wiring should con form to the following standards or by local codes, where they prevail and by In the United States, refer to the National Fire Protection Association NFPA--70, National Electrical Code
-
(latestedition), or in Canada, CAN/CSAC22.1Canadian Elec trical Code, Part 1, and with local codes and regulations.
The furnace should be wired to a separate and dedicated cir cuit in the main electrical panel; however, accessory equip
­ment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located cir cuit breaker can be used as a service switch, a separate serv
­ice switch is advisable. The service switch is necessary if reachingthe circuit breakerinvolves becoming closeto the fur nace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room.
6 Unitary Products Group
-
-
-
-
-
-
-
-
-
-
Page 7
035-14289-000 Rev. A(0701)
The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and
TABLE 3 - OIL PIPING LENGTHS (FEET)
furnaceroom entry,and be located in sucha manner to reduce thelikelihood that it wouldbe mistaken asa light switch orsimi lar device.
Accessories requiring 120 VAC power sources such as elec tronic air cleaners and humidifier transformers may be pow ered from the furnace circuit, but should have their own controls
Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto--generating wind ings of the direct drive motor.
Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring diagrams on Page 12. Some micro--electronic thermostats require addi tional controls and wiring. Refer to the thermostat manufac turer's instructions.
CAUTION: A room thermostat with independent heat/cool circuit is required.
The thermostat should be located approximately 5 feet above thefloor, onan inside wall where there isgood natural air circu lation,and where thethermostat will beexposed to averageroom temperatures. Avoid locations where the thermostat will be ex posed to cold drafts,heat from nearby lamps and appliances, ex posure to sunlight, heat from inside wall stacks, etc.
NOTE: Some electronic thermostats do not have ad­justable heat anticipators. They may have other type cycle rate adjustments. Follow the thermostat manu­facturer's instructions.
-
-
-
LIFT
1 53 100 68 100
SINGLE STAGE 2-STAGE
3/8" O.D.
TUBING
1/2" O.D.
TUBING
3/8" O.D.
TUBING
2 49 100 65 100 3 45 100 63 100 4 41 100 60 100 5 37 100 58 100
-
6 33 100 55 100 7 29 100 53 100 8 259950100 9 218348100
-
-
10 17 68 45 100 12 13 52 42 100 12 37 100 14 32 100
16 18
27 100 — 22 88
­component in the line. In general, keep single line systems
-
short as possible. If the furnace is to be installed in a sus
-
pendedposition,a twopipesystem maybea betteralternative. Two--stage oil pumps may be used with both single line and
two line systems. Two--stage pumps are available from your HVACwholesaler.Table 3lists allowable line lengths (horizon­tal plus vertical) for single and two stage oil pumps.
1/2" O.D.
TUBING
In retrofit applications where an existing oil line system is in
Set the heat anticipator in the room thermostat to .4 amps. for models P*HBX12F080, P*DHX12F080 & P*DHX16F120; for other models set heat anticipator at .2 amps. Setting it lower will cause short cycles. Setting it higher will cause the room temperature to exceed the setpoint.
place, a vacuum check will help determine if a two--stage oil pump is necessary. The vacuum in a system using a single stageoil pump should not exceed 6" Hg. The vacuum in a sys­temusing a two--stageoil pumpshould not exceed15" Hg. For additionalinformation,refertothe instructioninformation sheet affixed to the oil burner.
Installthe oilfilter asclose tothe burneras possible.For further
HUMIDIFIER
A humidifier is an optional accessory available through most heating supplies outlets. Installation should be carried out in accordance with the humidifier manufacturer's installation in structions. Water or water droplets from the humidifier should not be allowed to come into contact with the furnace heat ex changer.Donotuse direct drivemotor connectionsas asource ofpowerfor 120VAChumidifiersandhumidifier transformers.
details of the oil supply tank and piping requirements, please referto the instructions and illustrationsin the oil burnerand oil pump instructions shipped with the furnace.
-
OIL FILTER
All fuel systems should include an oil filter between the fuel oil
­storage tank and the oil burner.When using an oil burner noz zle smaller than 0.65 U.S. Gallons Per Hour, install an addi tional7to 10micronfilter ascloseas possibleto theoilburner.
PIPING INSTALLATION
The entire fuel system should be installed in accordance with the requirements of ANSI NFPANo. 31 in the United States or CAN/CSA B--139 in Canada, and local regulations. Use only an approved fuel oil tanks piping, fittings and oil filter.
Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do
not use compression fittings.
Pressurized or gravity feed installations must not exceed 10 PSIG ontheinlet line or the return line at the pump. Apressure greater then 10 PSIG may cause damage to the shaft seal.
The furnace may be installed with a one pipe system or gravity feedorlift. Themaximumallowable liftona singlelinesystem is 8ft. Liftshouldbe measuredfromthe bottom(outlet) ofthe tank to the inlet of the burner.
Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting, bend and
Unitary Products Group 7
OIL BURNER NOZZLES
These furnaces are certified for multiple firing rates, ranging from60,000to 181,000Btu/h dependingon model.Bymanipu lating the oil burner nozzle, flame retention head, static plate and temperature rise, the furnace may be fired at an ideal rate fora widerange of structures.Refer toTable4,and thefurnace rating plate to determine the proper combinations.
CAUTION: Before operating the furnace check burner alignment with the combustion chamber. The end cone of the air tube must be centered to the ac commodating ring provided in the design of the com bustion chamber. Adjust as necessary.
-
-
-
-
-
-
Page 8
035-14289-000 Rev. A(0701)
TABLE 4 - BECKETT AF OIL BURNER SET-UP
MODEL
P*HBX12F08001
P*HBX16F10001
P*LBX12F08001
P*LBX16F12001
P*LBX16F14501
P*LBX20F19001
P*DHX12F0801
OUTPUT
(BTU/H)
BURNER
MODEL
NOZZLE
PUMP
PRESSURE
FLOW RATE HEAD
STATIC
PLATE
UPFLOW
60,000 AF76BO 78,000 AF76BO 90,000 AF76XN
0.50 / 60° A
0.65 / 60° A
0.75 / 60° A
100 PSIG 0.50 GPH F0 3-3/8" 100 PSIG 0.65 GPH F0 3-3/8" 100 PSIG 0.75 GPH F3 2-3/4"
100,000 AF76XN 0.85 / 60° A 100 PSIG 0.85 GPH F3 2-3/4"
79,000 AF65XN 90,000 AF65XN
101,000 AF65XN
119,000 AF65XN
0.65 / 80° A
0.75 / 80° A
0.85 / 80° A
1.00 / 80° A
100 PSIG 0.65 GPH F3 2-3/4" 100 PSIG 0.75 GPH F3 2-3/4" 100 PSIG 0.85 GPH F3 2-3/4" 100 PSIG 1.00 GPH F3 2-3/4"
LOWBOY
60,000 AF63B0PWHS
78,000- AF63B0PWHS
90,000
AF63XNPWH
S 79,000 AF76XN 90,000 AF76XN
101,000 AF76XN
117,000 AF76XN 130,000 AF76YB 143,000 AF76YB 168,000 AF65XO 181,000 AF65XO
0.50 / 60° A
0.50 / 60° A
0.75 / 60° A
0.65 / 80° A
0.75 / 80° A
0.85 / 80° A
1.00 / 80° A
1.10 / 70° A
1.20 / 60° A
1.50 / 70° B
1.65 / 70° B
100 PSIG 0.50 GPH F0 3-3/8" 100 PSIG 0.65 GPH F0 3-3/8"
100 PSIG 0.75 GPH F3 2-3/4" 100 PSIG 0.65 GPH F3 2-3/4"
100 PSIG 0.75 GPH F3 2-3/4" 100 PSIG 0.85 GPH F3 2-3/4" 100 PSIG 1.00 GPH F3 2-3/4" 100 PSIG 1.10 GPH F6 2-3/4" 100 PSIG 1.20 GPH F6 2-3/4" 100 PSIG 1.50 GPH F12 2-3/4" 100 PSIG 1.65 GPH F12 2-3/4"
DOWNFLOW/HORIZONTAL
60,000 AF76BO 78,000 AF76BO 90,000 AF76XN
0.50 / 60° A
0.65 / 60° A
0.75 / 60° A
100 PSIG 0.50 GPH F0 3-3/8" 100 PSIG 0.65 GPH F0 3-3/8" 100 PSIG 0.75 GPH F3 2-3/4"
BURNER PRIMARY (SAFETY) CONTROL
The furnace is equipped with a primary combustion control, sometimes referred to as the burner relay or burner protector relay,whichuses alight sensing device(cad cell) locatedin the burner housing, to monitor and control combustion.
Over time, dust or combustion residuals can build up on the lens of the cad cell impairing its response to the flame. The cad cell should be checked for cleanliness and proper align ment if the primary control frequently shuts down combus tion.
CIRCULATING AIR BLOWER
These furnaces (with the exception of model P*LBX20F190 which is belt drive) are equipped with direct drive blower sys tems. Direct drive blower speed adjustments are not normally requiredin properly sized extended plenumduct systems. The motor RPM and air CFM delivery will vary automatically to ac commodateconditions within the usual rangeof external static pressures typical of residential duct systems.
-
-
Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure.
COMBUSTION CHAMBER
This furnace is equipped with a high quality cerafelt combus tion chamber. It is held in place by a retaining bracket.
CHECK THE ALIGNMENT OF THE COMBUSTION CHAM BER AND OIL BURNER BEFORE FIRING. IT IS POSSIBLE FOR THE COMBUSTION CHAMBER TO SHIFT IF SUB JECTED TO ROUGH HANDLING DURING TRANSIT.
The combustion chamber should be inspected for damage or carbon build up whenever the oil burner is removed for repairs or routine maintenance.
WARNING:Do not start the burner unless the blower access door is secured in place.
They typically feature special reducing fittings at each branch run and lack block ends on the trunk ducts.
­These systems may require modification to provide some re sistance to the airflow to prevent over-- amping of the direct
-
drive blower motor. Selecting a lower blower speed may cor rect this problem.
­Direct drive blower speeds are adjusted by changing the “hot” wires to the motor winding connections. Please refer to wiring diagram on Page 12, or the wiring diagram label affixed to the furnace. THE NEUTRAL WIRE (normally the white wire) IS NEVER MOVED TO ADJUST THE BLOWER SPEED.
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to con nect the wiring from both modes is to use a “piggy--back con nector” accommodating both wires on a single motor tap.
8 Unitary Products Group
-
-
-
-
-
-
Page 9
035-14289-000 Rev. A(0701)
Itis alsoacceptable toconnect the selectedmotor speedwith a pig tail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnec tion of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape.
CAUTION:Do not connectpower leads between mo tor speeds. The neutral wire must always be con nected to the motor's designated neutral terminal.
WARNING: Disconnect the power supply to the fur nace before opening the blower access door to serv ice the air filter,fan or motor. Failure to shut off power could allow the blower to start unexpectedly,creating a risk of death or personal injury.
If the joining of the blower speed wiring is done in the furnace junction box, tape off both ends of the unused wire.
Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformersunless will be used. The unused motor taps auto--generate suffi
ciently high voltages to damage accessory equipment.
itis certainthatonly one motor speed
MAINTENANCE AND SERVICE Routine Maintenance By Home Owner
Otherthan rememberingto arrangefor theannual professional servicingof thefurnace bythe serviceor installationcontractor, the most important routine service performed by the home owneris tomaintain theair filteror filters.Adirty filtercan cause the furnace to over--heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or replaced monthly. The furnace is factory equipped with a semi-­permanenttype filter.Ifthe filteris damaged,replace withfilters of the same size and type. (See Page 5 for listing).
During the routine service, inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advice your service or installa tion contractor.
Annual Service By Contractor
CAUTION: The combustion chamber (firepot)is frag ile.Usecare wheninspectingand cleaningthisarea.
The heat exchanger should be inspected periodically and cleaned if necessary. if cleaning is necessary, SHUT OFF POWER TO THE FURNACE and remove the burner. Using a stiff brush with a wire handle, brush off scale and soot from in side the drum and flue pipe. Toclean the radiator, remove the round covers on the inner front panel to gain access to the cleaning ports.
When this procedure is done for the first time, carefully cut away the insulation covering the opening with a sharp knife. Loosen the nuts on the radiator clean--outs. DO NOT RE MOVE THE NUTS. Remove the covers carefully to avoid tear ing the gaskets. A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator.
Cleanout all accumulated dirt, sootanddebris with a wire han dled brush and an industrial vacuum cleaner.Before replacing the clean--out covers, inspect the gaskets. If the gaskets are broken, remove the remnants and replace with new gaskets. Snug the cleanout covers. DO NOT OVER--TORQUE THE
Unitary Products Group 9
CLEAN--OUT NUTS. Replace the inner front panel clean--out covers.
-
NOTE: A radiator clean--out assembly inadvertently droppedinto the interior of thefurnace can usually be
-
-
Thedirect driveblower motoris factoryoiled. Undernormal op
-
erating conditions it does not require oiling for the first two
-
years. Oil sparingly (a few drops) in each oil port with SAE 20 non--detergent oil. Oiling is most easily done with a “tele-­spout” oilier. This oiler has a long flexible plastic spout. DO NOT OVER--LUBRICATE.Excess oil causes premature elec tric motor failure.
Inspect the blower fan. Clean if necessary. Oil Burner Maintenance: Follow the instructions of the oil
burner manufacturer. (See oil burner manufacturer's instruc
-
tions supplied with furnace). It is advisable to change the oil burner nozzle and oil filter on an annual basis.
Theventing systemshould becleaned and inspectedfor signs of deterioration. Replace pitted or perforated vent pipe and fit tings. The barometric damper should open and close freely.
All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan control should be checked to ensure that the “fan off” function continues to stop the blower fan at temperatures between 90° F to 100° F.
easily retrieved with a magnet on a wire handle or stout string.
OPERATING INSTRUCTIONS
Before Lighting
1. Open all supply and return air registers and grilles.
2. Open all valves in oil pipes.
3. Turn on electric power supply
To Light Unit
1. Set the thermostat above room temperature to call for
-
-
-
-
-
-
heat.The burner should start.NOTE: It maybe necessary to press the RESET button on the primary combustion control relay.
2. After ashort period of time, as thefurnace becomes warm enoughthe act uponthe fan control(L6064A), or preheats the bi--metallic element (L4064W), the blower should start.
3. Set the thermostat below room temperature. The oil burner should stop.
4. Theair circulationblowerwill continueto runaslong asthe temperature in the furnace is higher than the “FAN OFF” setting on the fan control. Typical “fan on” values range from120° Fto 130° F.Typical“fan off”temperatures range between 90° F and 100° F. The fan control adjustments may be altered if the air at the room registers is uncom fortably high upon blower start up or shutdown, the fan control settings can be lowered.
5. The adjustments to the fan control settings should be made by measuring the temperature of the air in the sup ply air take--off, or within the first few inches of the supply air trunk. The side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the “line of sight” wherein false readings from radiant heat could be observed. The system temperature rise, the dif ference in temperature between the supply air and return air, will typically range between 65° F and 70° F.
-
-
-
-
-
-
-
Page 10
035-14289-000 Rev. A(0701)
Tocheck the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor.Restore the electrical power to the furnace and set the thermostatabove room temperature. After three or four minutes of burner operation, the limit control should turn the burner off.
The progress towards a high limit shut down can be monitored by watching the dial on the fan / limit control. When the limit function test is complete, shut off electrical power to the fur nace, replace the neutral wire to the blower fan motor,then re storepower. Theblower fan will start upimmediately.Once the temperature has dropped, the oil burner will resume and con tinue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.
To Shut Down Unit
1. Set the thermostat to the lowest possible setting.
2. Set the manual switch (if installed) in the Electrical Power Supply Line to “OFF”.
NOTE: If the furnace is to be shut down for an ex tendedperiod of time, close theoil supply valve to the burner.
OIL BURNER AIR ADJUSTMENT
For complete details, consult the oil burner instruction manual provided in the furnace documents envelope.
Beckett AF Burner Adjustthe airshutter by looseningthe lockingscrews and mov-
ing the air shutter, and if necessary, the bulk air band.
Procedure
Startthe burner and allow it to run at least ten minutes. Set the air shutter to give a good flame visually. The air supply to the burner is controlled by the air shutter on the left side of the burner,and the bulk air band. To adjust, loosen the bolt on the movableshutter. Move theshutter gradually until a good flame (visually) has been achieved. Re--snug the bolt.
Check the initial draft setting as the furnace warms up. The draftmaybe measuredat thetest port.In mostcases, thepres
-
sure dropbetween the test port and the oil burner is negligible.
-
The test port draft reading may be interpreted as the “over fire draft” reading. The draft should be set to -- 0.02 inches w.c.
­Check the oil pump pressure. All furnaces are designed to be
operated at 100 psig. After reaching steady state,take a smoke test. If not indicating
a trace, set the combustion air controls to provide a trace. In
-
-
BURNER ELECTRODES
Adjustment of the electrode tipswith respect to each other, the nozzle,andto the rest of the burner is very importantto ensure smooth start ups and to permit efficient combustion.
Beckett AF Burner Settings
Electrode gap: 5/32 inch.
Distance above horizontal centerline: 7/16 inch.
Distance ahead of nozzle: 1/16 inch.
Thedistancefrom thefront ofthe endcone (head)to theface of the nozzle should be 1--1/8 inches. If a ceramic head is used, the distance from the end cone to the nozzle face is increased to 1--3/8 inches.
OIL BURNER SET UP
Theburner air supply is adjustedto maintain the fuelto air ratio toobtainideal combustionconditions. Alackofair causes“soft” and “sooty” flames, resulting in soot build--up throughout the heat exchanger passages. Excess combustion air causes a brightroaring fire andhigh stacktemperatures resulting inpoor fuel efficiency.
Preparations
Drill a 1/4" test port in the venting, ideally at least 2 diameters (12") away from the furnace breaching. If venting horizontally fromthe furnace,or fromthe flue pipeelbow ifventing vertically before reaching the furnace (refer to Figure 4).
Before startingthe burner, checkthe burner alignment with the combustion chamber (firepot), check that the correct nozzle is tightened into place, and that the burner electrodes are prop erly positioned.
10 Unitary Products Group
FIGURE 4 - TEST LOCATIONS FOR SMOKE TEST
(TOP - HORIZONTALINSTALLATION) (BOTTOM - VERTICAL INSTALLATION)
NOTEA:Locateholeatleast6inchesonthe furnace side of the draftcontrol.
-
NOTE B: Ideally, hole should be at least 12 inches from breeching or elbow. The test port will allow flue gas samples to be taken and stack temperature to be measured.
Page 11
most cases, adjustment of the end air shutter will be all that is necessary.
035-14289-000 Rev. A(0701)
ducts. Typical temperature rise values range between 65° F and 90° F.
When the trace smoke has been established, measure the
orO2inthe flue gas. Typically,the CO2readingwill be ap
CO
2
proximately 13% or the O
reading approximately 3.3%.
2
Open the end air shutter (or open the bulk air band if neces sary)until the CO measuring O
readingdrops 1or 2 percentagepoints, or,if
2
content, until the O2reading increases 2 or 3
2
percentage points. Take another smoke test; it should now be zero smoke. If the
smoke test reads zero, tighten up the end air shutter, and the bulk air band.
Re--test the draft and the CO
or O2to be certain that the set
2
tings have not shifted.
NOTE: If oily or yellow smoke sports arefound on the smoketest filter paper,it is usuallya sign of unburned fuel. This indicates poor combustion. This type of problem may be caused by excess draft, excess air, or contaminated fuel. Do not ignore this indicator.
Stack Temperature
Stacktemperaturewill vary depending onfuel input, circulating air blower speed and burner set up, etc. In general, stack tem perature should range between 350° Fto450° F,but could be as high as 550° F, assuming that the combustion air approxi mately room temperature (65° F--70° F). In general, lower stack temperature indicates greater efficiency; however, ex­cessive low stack temperature can lead to condensation form­ing in the chimney and/or venting. Sulfur and similar contaminants in the fuel oil will mix with condensation to form acids. Acids andresultant chemical salts will cause rapid dete­rioration of the chimney and venting components, and may at­tack the furnace.
If the flue gases are below the range, it may be necessary to slowdownthe blowerfan. Iftheflue gasesareabove therange, the blower may require speeding up. Stacktemperature varies directly with the system temperature rise. System temperature rise is the difference between the furnace outlet temperature andthe furnace inlettemperature as measuredin the vicinityof the connection between the plenum take--offs and the trunk
If the venting from the furnace to the chimney is long or ex
-
posed to cold ambient temperatures, it is advisable to insulate theventing with aremovable, non--combustible, wrap--around type insulation to reduce stack temperature loss. The vent
­should be inspected annually to ensure that it is intact.
FINAL CHECK OUT
Before the final test cycle, carefully examine the complete heatingsystem forleaks. The hotvent canbe checkedwith a lit taper for signs of air movement around joints or seams.
­Ensure that all safety devices and electrical components have
been set for normal operation. Ensure that all electrical con nections are tight and that the wiring is secure.
IMPORTANT:
Please review the following items with the homeowner:
where the circuit breaker or fuse is located in the main
electrical panel.
-
-
where the furnace switch is located, and the switch “on”
and “off” positions if not obvious. where the oil shut--off valve from the oil storage tank is
located.
how to operate the thermostat, and other related acces­sories.
how to operate the manual reset button on the primary control,andespecially whennotto pushthereset button.
how and where to visuallyinspect the venting system for leaks or other problems.
how to inspect, clean and replace the air filter, and other homeowner maintenance procedures.
who to call for emergency service and routine annual service.
the terms and conditions of the manufacturer's warranty and the contractor's warranty.
-
-
Unitary Products Group 11
Page 12
035-14289-000 Rev. A(0701)
BLOWER PERFORMANCE
MODEL SPEED
P*HBX12F08001 P*DHX12F08001
P*HBX16F10001
P*DHX16F12001
P*LBX12F08001
P*LBX16F12001 P*LBX16F14501
P*LBX20F19001
TAP
HIGH 1505 1444 1359 1291 1195 MED HIGH 1423 1381 1291 1220 1144 MED LOW 1170 1144 1118 1063 1005
LOW 813 813 797 763 690
HIGH 1645 1575 1510 1445 1337 MED HIGH 1540 1500 1420 1350 1266 MED LOW 1145 1135 1115 1095 1035
LOW 745 745 725 715 646
HIGH 1752 1691 1659 1593 1525 MED HIGH 1454 1454 1417 1379 1300 MED LOW 975 944 912 879 844
LOW 631 593 552 515 486
HIGH 1917 1885 1820 1717 1608 MED HIGH 1590 1608 1590 1532 1430 MED LOW 1096 1096 1096 1068 1039
LOW 696 647 692 647 598
HIGH 1810 1740 1675 1585 1480 MED HIGH 1570 1540 1495 1445 1348 MED LOW 1090 1080 1070 1065 1036
LOW 710 700 690 665 614
TURNS OPEN
0 2707 2503 2303 2135 1898 1 2372 2233 2085 1870 1594 2 2257 2085 1841 1594 1216 3 2161 1926 1627 1259 795
0.20 0.30 0.40 0.50 0.60
NOTES:
Airlfow is expressed in standard cubic feet per minute. Motor voltage at 115V
EXTERNAL STATIC PRESSURE, INCHES W.C.
12 Unitary Products Group
Page 13
WIRING DIAGRAM - ALL MODELS
035-14289-000 Rev. A(0701)
Unitary Products Group 13
Page 14
035-14289-000 Rev. A(0701)
SYSTEM TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE REMEDY
Furnace will not start
Furnace will not start without first pushing protector relay reset button (Happens on a frequent basis)
Furnace starts, but cuts out requiring manually resetting the oil protector reset but ton
Thermostat not calling for heat
No power to furnace
Thermostat faulty
Protector relay faulty
Photo cell wiring shorted or room light leaking into photo cell compartment
Open safety switch
No fuel oil
Clogged nozzle Clogged oil pump filter Replace oil tank filter or in-line filter if used.
low oil pump pressure
Air getting into fuel oil lines, or fuel oil line dirty, clogged or in some manner defective
Defective burner motor
Photo Cell (Cad Cell) defective
No fuel oil
Clogged nozzle Clogged oil filter Replace oil tank filter or in-line filter if used.
Low oil pump pressure
­Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective
Defective burner motor Water or contaminants
in oil. Frozen oil line
Check thermostat and adjust. Also, check thermostat for accuracy; if it is a mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit breaker. Also look for any other hand operated switch, such as an old poorly located furnace switch which was not removed during furnace replacement.
Check reset button on protector relay. Remove thermostat wires from pro tector relay terminals TT. Place a jumper across TT. If furnace starts, replace thermostat, thermostat sub-base (if equipped), or both.
Check reset button on protector relay. Remove thermostat wires from pro tector relay terminals TT. Check for 24v across T.T. If no voltage is present, check for 115v to protector relay. If 115v is present, replace protector relay.
Check photo cell (cad cell) wiring for short circuits. Also check for room light leaking in to cad cell compartment. Repair light leak if necessary.
Check for open limit or auxiliary limit, open door switch (if equipped). Also, check internal wiring connections, loose connectors, etc.
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or table in this manual as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil lines.
Check oil lines, Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. An oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, determine why. Replace, if necessary
If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If cad cell is poorly aimed, realign it. NOTE: The photo cell should have a resistance of 100 K ohms in absence of light; a maximum of 1500 ohms in the presence of light. Ensure that room light is not leaking into the cad cell compartment.
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or table in this manual as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.
Check fuel lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. any oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, determine whey. Replace if necessary.
Drain fuel oil storage tank, replace fuel oil. (Consult with fuel oil supplier). Gently warm oil line. Insulate oil line. (Outdoor piping size may require in
creased diameter.
-
-
-
14 Unitary Products Group
Page 15
PROBLEM POSSIBLE CAUSE REMEDY
Oil burner sputtering at nozzle
Excessive fuel oil con
-
sumption
Too much smoke
Furnace will not warm home to desired tempera ture
Home does not heat evenly
Supply air temperature too hot
Supply air temperature too cool
035-14289-000 Rev. A(0701)
SYSTEM TROUBLESHOOTING - CONT'D
Electrodes out of adjustment or defective
Poor transformer high voltage connections or defective transformer
Fuel oil filter clogged Replace fuel oil storage tank filter and/or fuel oil in-line filter Defective oil pump Fuel oil line partially clogged
or contains air System temperature rise too
high
Blower fan control out of ad justment, (fan stops too soon)
Fuel oil leak Check fuel oil line for leaks. Repair or replace if necessary. Stack temperature too high.
Thermostat improperly ad­justed or in poor location.
Insufficient combustion air adjustment at oil burner, or improper draft pressure
Heat exchanger partially clogged
Air flow blocked by dirty air filter
Thermostat adjustments or location
Insufficient air flow
­Defective high limit control
Under-sized nozzle. Blower fan motor stopping in
termittently on overload Burner motor stopping inter
mittently on overload Improper distribution of heat This is not likely to be furnace problem. Balance duct system. Air flow blocked or dirty air fil
ter Insufficient air flow Fan control “fan on” setting
too low Excessive duct losses
Check electrode settings. Check electrodes for dirt build-up or cracks in porcelain.
Check contacts between transformer and electrodes. If OK, replace transformer.
Check burner motor/fuel oil pump coupling. Check oil pump pres sure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line. System temperature rise should not exceed 85° F. Check for
clogged air filters. Check blower fan for excess dirt build-up or de bris. Speed up blower fan if necessary.
Check fan control settings. The fan control is adjusted with a duct thermometer in the supply air plenum take-off or first few inches of
-
the supply air trunk duct. The “fan off” setting should be 90° - 100° F. Once set, the “fan on” setting is normally adjusted 25° -30° F higher than the “fan off” setting.
Check stack temperature. Stack temperature will normally range from 350° to 450° F. Check draft regulator. Draft should be set to
0.02" WC. Check thermostat heat anticipator setting against measured amper age draw. Increase heat anticipator setting if necessary. If the ther­mostat is being influenced by drafts, sunlight, duct work, etc, relocate to a more suitable location.
Adjust the oil burner combustion air band and draft regulator to gain the highest CO
possible with a Bacharach No.1 smoke.
2
Check for soot build-up in heat exchanger flue passages, especially in the outer radiator.
Clean or replace air filter Check thermostat heat anticipator setting against measured amper-
age draw. Increase heat anticipator setting if necessary. If the ther mostat is being influenced by drafts, sunlight, duck work, etc, relocate to more suitable location.
Check all dampers. Open closed dampers including registers in un used rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.
Test high limit function of all limit switches. Use a duct thermometer to assess accuracy of limit control. Check for obstructions to air flow around limit switch bi-metal elements. Replace control if necessary.
Check nozzle. If problem is not caused by air flow problems, use larger nozzle, if permitted by rating plate.
-
Check blower fan motor amperage draw. Check motor ventilation ports, clean if necessary. Replace motor if necessary.
-
Check burner motor. Replace if necessary.
-
Clean or replace air filter. Check all dampers. Open closed dampers including registers in un
used rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.
Check system temperature rise. Slow down blower fan if necessary. Check supply air duct work. Seal leaky joints and seams. Insulate
ductwork if necessary.
-
-
-
-
-
-
Unitary Products Group 15
Page 16
Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 1999. All rights reserved.
Unitary Products Group
5005 York Drive
Norman OK 73069
Code: EBY, L, FSupersedes: 035-14289-A-000-300
035-14289-000-A-1101
Loading...